Muhammad Ayaz’s Post

View profile for Muhammad Ayaz

at Global Projects Service AG with SAIPEM

Power Transformer Turns Ratio (TTR) Test 🎯 Purpose To verify that the actual winding ratio (HV:LV turns) matches the design/nameplate ratio. To ensure correct vector group and polarity. To confirm tap-changer correctness across all tap positions. This test is critical before energization — a wrong ratio or vector group can cause severe circulating currents or parallel operation failure. Test Connections Equipment: Turns Ratio Tester (TTR) (e.g., Megger TTR, DV Power TRT, Omicron CPC100 with TTR module). Wiring Setup: 1. Connect the H terminal of TTR kit to HV bushing terminals of the transformer. 2. Connect the X terminal of the kit to LV bushing terminals. 3. If a tertiary (Δ) winding is present, connect accordingly to verify vector group. 4. Ensure transformer is isolated and discharged before connection. Principle: TTR kit applies a low AC voltage (~80–100 V) to one winding (usually HV) and measures the induced voltage on LV. Ratio = (Applied Voltage / Induced Voltage). Procedure 1. Select the tap position (start from first tap). 2. Apply test voltage through TTR. 3. Record: Ratio (HV/LV) Phase angle error Deviation from nameplate 4. Repeat for middle tap and last tap (plus all in between for OLTC). 5. Compare readings with nameplate ratio and factory test report. Acceptable Readings (IEC / IEEE Standards) Ratio Error Tolerance: ±0.5% (IEC 60076 / IEEE C57). Phase Angle Error: should be < 40 minutes. Vector Group: must match nameplate (e.g., Dyn11, YNd1). If deviation exceeds limits → OLTC problem, wrong winding connection, or shorted turns. Results on Tap Positions 1️⃣ First Tap (Max Tap / Highest Voltage Tap) HV turns are maximum → ratio is highest. Induced LV voltage is lowest for a given applied HV. Ratio error should still be within ±0.5%. 2️⃣ Middle Tap (Nominal Tap) This is the reference point. Ratio must closely match nameplate ratio. Used for base comparison across taps. 3️⃣ Last Tap (Min Tap / Lowest Voltage Tap) HV turns are minimum → ratio is lowest. LV induced voltage is highest. Current in LV winding will be slightly higher at this tap when energized, but for TTR test (low voltage applied), only the ratio matters. ⚡ Important Field Notes Symmetry: All three phases must show nearly identical ratio values; large deviation in one phase suggests winding deformation or OLTC issue. OLTC Jumps: If the ratio suddenly shifts at a particular tap, the OLTC diverter switch is faulty. Vector Group Check: TTR kits can automatically detect vector group; mismatches are often due to wrong bushing labeling or internal misconnection. ✅ Summary Connect TTR kit → HV side (H terminals), LV side (X terminals). Measure ratio at 1st, middle, and last taps. International standard: ratio error ≤ ±0.5%. Expect: Highest ratio at first tap Nominal ratio at middle tap Lowest ratio at last tap Abnormal readings → suspect OLTC, winding, or vector group issues.

  • No alternative text description for this image

To view or add a comment, sign in

Explore content categories