Electrical Engineering Best Practices

Explore top LinkedIn content from expert professionals.

  • View profile for Andreas Bach

    C-Executive │ Advisor │ PV & BESS Delivery │ EPC & CAPEX Strategy

    12,106 followers

    The biggest lie in PV construction: approvals slow you down. In reality, skipping them is how you end up replacing 100 trackers. I once saw a crew assembling trackers with the wrong type of bolts. Nobody noticed at first. By the time the mistake came up, more than 100 trackers were already installed. Result: all bolts had to be replaced. A huge mess. Delays, costs, and finger-pointing in every direction. The real problem: the construction company had skipped the initial inspection. Instead of waiting for approval, they simply went ahead. 𝗧𝗵𝗮𝘁’𝘀 𝘄𝗵𝘆 𝘄𝗲 𝗻𝗲𝗲𝗱 𝗮 𝗚𝗼𝗹𝗱𝗲𝗻 𝗧𝗮𝗯𝗹𝗲 (or Mock-up Table). Before starting serial works, one unit is built and signed off by the site manager, construction manager, or supervising engineer. And it’s not only for trackers or mounting structures. It applies to all repeatable tasks: • DC cable routing between modules • Cable trenches (sand quality, backfilling) • Roads, fences, transformer stations Yes, it might feel like you “lose” half a day for an approval. But that’s nothing compared to the weeks lost when the same error is repeated hundreds of times. → A mistake at the mock-up table is a problem. → A mistake after 1,000 repetitions is a disaster. How do you handle this on your projects? Is the Golden Table mandatory, or do you often see companies rushing straight into serial work? #SolarConstruction #EPC #UtilityScaleSolar #ProjectManagement #QualityControl #RenewableEnergy #BestPractices

  • View profile for Nadia MAHDI, BEng, M.Sc., EnMS 🇵🇸

    Sustainability & Energy Storage Researcher 🌱 | Battery EoL Management, Recycling ♻️ | BESS Technology Screening & Evaluation 🔋 | Sustainability Content Creator ⚡

    5,171 followers

    🌍 Harnessing the Power of Renewables: New Guidelines for Wind & Solar Integration Studies 🌞 The International Energy Agency's (IEA) Technology Collaboration Programmes for Wind Energy Systems (IEA Wind) and Photovoltaic Power Systems (IEA PVPS) have released the third edition of the “Recommended Practices for Wind/PV Integration Studies” – a must-read for anyone involved in renewable energy and power systems design! This updated guide builds on 15+ years of expertise and international collaboration, providing actionable methodologies and best practices for conducting integration studies in systems dominated by wind and solar. 💡 What’s Inside? ✅ Comprehensive Methodologies: Detailed recommendations for system impact studies tailored to power grids with high shares of wind and solar energy. ✅ Core Challenges Addressed: 1️⃣ Managing variability in renewable energy generation. 2️⃣ Ensuring grid stability with inverter-based, non-synchronous energy sources. ✅ Future-Proof Insights: As wind and solar become mainstream, integration studies will evolve into holistic power system design studies, tackling operational, adequacy, and dynamic challenges. ✅ Standardizing Practices: Recognizing the diversity in current methodologies, this edition emphasizes the need for evolving and unifying approaches to support grids with a higher share of renewables. ⚡ Why It Matters This resource is pivotal for defining renewable energy targets and crafting decarbonization pathways, ensuring that the global energy transition is stable, reliable, and economically sound. 🌐 A Collaborative Global Effort With input from experts across 20+ countries – including research institutes, universities, system operators, and industry leaders – this edition reflects a globally relevant, practical, and robust framework for renewable integration. 📘 Download the full report to explore how you can contribute to a greener, more sustainable energy future 🚀 #RenewableEnergy #Sustainability #WindEnergy #SolarEnergy #EnergyTransition #Decarbonization #CleanEnergy

  • View profile for Michael A.

    Instrumentation||Automation||Engineer||Technical Trainer||Leader

    18,247 followers

    Instrument Earth vs Electrical Earth It looks like a small thing. But many signal problems come from mixing these two: Electrical Earth (for power systems and safety) Instrument Earth (for signal cables and shielding) But, what is “earth” or “ground”? It’s a reference point for electrical circuits. It helps carry unwanted current safely during faults and keeps voltages stable. But not all “earths” are created equal. They are not the same. When you connect both grounds without caution, it can cause: ▪️ Ground loops ▪️ Noisy signals ▪️ Unstable transmitter readings ▪️ Even damage during faults Instrument signals are weak. They need a clean, stable reference. That’s what instrument earth gives. Power equipment needs a strong path to ground for safety. That’s what electrical earth is for. Keep them separate; especially in control panels and field junction boxes. It’s basic, but it saves a lot of troubleshooting later. If you want to learn more, see these Standards. IEC 61000-5-2 and IEEE Std 1100 (Emerald Book) will give you a solid guidance on grounding for signal integrity and system performance. #Instrumentation #SignalGrounding #ProcessControl #FieldWiring #ControlSystems

  • View profile for Doug Millner P.E.

    -Expert Power Engineer-

    26,763 followers

    How is grid voltage regulated? Your utility or independent system operator (ISO) does a series of studies to determines how the system should be setup so that the voltage at every connecting point in the system is within a healthy range, typically the range will be something around 0.95 to 1.05 per-unit under non-contingency situations,This usually takes the form of a voltage schedule, that dictates what the voltages should be a various points in the system so that a healthy voltage can be maintained across the grid. This schedule can change seasonally or even nightly. There are several methods that can be used to maintain this schedule. The most common and cheapest form of grid voltage regulation is shunt capacitor banks and reactors.  When capacitor banks are switched into the grid,  the capacitive current or vars offsets the voltage drops across the grid due to reactive current flowing through reactive elements on the grid like transmission and transformers.  These capacitor banks can be programmed to switch in automatically, adjusted seasonally, or put in and out of service as needed by operators. The more capacitance that is switched in, the higher the local voltage will rise.  Shunt reactors do the exact opposite and reduce the system voltage locally by increasing the voltage drops across lines and transformers in the grid. Another form of voltage regulation is with generators importing or exporting vars to raise or lower the system voltage.  A generator when its rotor is over-excited, tries to raise the system voltage by exporting vars, which is when it is "lagging".  When a generator rotor is under-excited, it consumes vars and tries to lower the grid's voltage and is said to be "leading".  This performs the same sort of regulation as capacitor banks or shunt reactors but it is not the preferred method due to it being an expensive means of providing or consuming vars and the rotor and stator thermal limits can limit the real power output of a power plant at lower power factors.  With inverter-based resources like renewables and battery storage, vars can be imported and exported similarly since they usually can operate in all four quadrants. A third method of how voltage is regulated is with transformer taps.  Transformers can have offset taps that try to pull the voltage of one side high or low. For example, a 138:69 kV transformer tapped to 138:69.1 will try to pull the 69 kV side up to 69.1 kV at the expense of pulling down on the 138 kV side. When one side is pushed up, the other side is pushed down. The higher the voltage, the usually the stronger the grid so that side is usually less affected.  These taps can be adjusted seasonally or be in Automatic Voltage Regulation (AVR) mode with transformers with Load Tap Changers (LTC) that can adjust the taps automatically. That is how the voltage is regulated across thousands of miles of lines and cables. #utilities #renewables #energystorage #electricalengineering

  • View profile for OZIZI ELIJAH OPISA.

    Instrumentation and Control Systems Engineer, Dangote Petroleum Refinery and Petrochemicals FZE, BPCS&SIS(Functional Safety&OT/ICS Cyber Security)

    14,961 followers

    PLANT EARTH Vs INSTRUMENT EARTH. In industrial settings, particularly in process control and automation, the terms "Plant Earth" and "Instrument Earth" are often used. While they may seem similar, they serve distinct purposes and are not interchangeable. Plant Earth Plant Earth, also known as "plant ground" or "earth," refers to the physical connection of electrical equipment to the earth's surface. This connection is typically made through a grounding system, which provides a safe path for electrical currents to flow to the earth in case of a fault or short circuit. The primary purpose of Plant Earth is to ensure the safety of personnel and equipment by preventing electrical shocks and equipment damage. Instrument Earth Instrument Earth, also known as "instrument ground" or "signal ground," is a separate grounding system specifically designed for instrumentation and control systems. This system provides a low-noise, stable reference point for instrument signals, ensuring accurate and reliable measurements. Instrument Earth is typically isolated from Plant Earth to prevent electrical noise and interference from affecting instrument signals. Key Differences 1. Purpose: Plant Earth is primarily for safety and equipment protection, while Instrument Earth is for signal integrity and measurement accuracy. 2. Connection: Plant Earth is connected to the physical earth, while Instrument Earth is a separate grounding system. 3. Isolation: Instrument Earth is typically isolated from Plant Earth to prevent electrical noise and interference. Best Practices 1. Use separate grounding systems: Keep Plant Earth and Instrument Earth separate to prevent electrical noise and interference. 2. Ensure proper isolation: Use isolation transformers, optocouplers, or other isolation devices to separate Instrument Earth from Plant Earth. 3. Follow industry standards: Adhere to industry standards and regulations, such as those provided by the International Electrotechnical Commission (IEC) and the National Electric Code (NEC). In conclusion, understanding the difference between Plant Earth and Instrument Earth is crucial for ensuring the safety and reliability of industrial processes. By following best practices and maintaining separate grounding systems, you can prevent electrical noise and interference, ensuring accurate and reliable measurements. Follow🔁 for more Instrumentation and Control Systems Engineering content.

  • View profile for Pavel Purgat

    Innovation | Energy Transition | Electrification | Electric Energy Storage | Solar | LVDC

    26,898 followers

    🔋 Typically, the grid-connected inverters are split into two types: Grid-Following (GFL) inverters and Grid-Forming (GFM) inverters. GFL inverters are conventionally controlled as current sources, relying on a Phase-Locked Loop (PLL) to achieve synchronisation to the external grid voltage. This configuration means GFL inherently lacks both voltage-forming (VFM) and frequency-supporting capabilities. Conversely, GFM inverters operate as voltage sources, achieving self-synchronisation through their active power output, and can form both grid frequency and voltage. A recently investigated extension of GFM control, the Frequency-Following Voltage-Forming (FFL-VFM) inverter, strategically decouples these capabilities. The FFL-VFM inverter forms the voltage but sacrifices frequency support, instead enabling the inverter to stably and quickly follow outer grid frequency variations (FFL) while enhancing grid voltage stiffness (VFM). This structure achieves a faster frequency response than conventional GFM and still supports the voltage control in the grid. 🔦 The FFL-VFM controller is based on GFM matching control, with a virtual amortisseur (red R) and virtual pole-pair number (red N) managing grid synchronisation and dc-link voltage regulation. The structure, integrated with the dc-link capacitor, achieves stable and quick responses to grid frequency changes. The synchronisation loop uses fast PI control, rather than the slower Low-Pass Filter (LPF) in GFM. This control damps the slip frequency between the inverter and grid via the power-angle relationship, ensuring the inverter tracks the grid frequency until synchronisation. 💡 VFM capability appears in the inverter's port admittance. Near the fundamental frequency, FFL-VFM's port admittance is 10x that of GFL. High FFL-VFM admittance lets it provide voltage support, unlike GFL inverters. #gridforming #battery #energystorage #gridmodernization #powerelectronics #renewables #cleanenergy

  • View profile for Khalid Ahmed(B.Sc, PMP®, PMOCP™, CQM, QMS Lead Auditor)

    Construction & Commissioning Specialist | EPC | FEED | Certified Quality Manager | QMS Lead Auditor | PMOCP | Technical Writer | Aramco Approved CBT-EIT | T-BOSIET | OSHA | IOSH

    11,385 followers

    🔧 TYPES OF GENERATOR TESTING🔧 1. Pre-Installation Checks Physical Inspection: Check for mechanical damage, oil leaks, or loose components. Nameplate Verification: Confirm that the generator specifications match the design requirement (Voltage, kVA, Frequency, RPM, etc.). 2. Insulation Resistance Testing (Megger Test) Purpose: To check the condition of winding insulation. Tool: Megger (typically 500V or 1000V DC). Test Points: Between each phase and ground. Between phases. Acceptance Criteria: Usually >1 MΩ depending on manufacturer specs. 3. Winding Resistance Test Purpose: To verify uniformity and continuity of stator windings. Tool: Micro-ohmmeter or Ductor. Acceptance: Balanced readings across all windings. 4. Phase Sequence and Rotation Test Purpose: Confirm correct phase sequence. Tool: Phase sequence indicator. Importance: Ensures compatibility with connected loads. 5. No-Load Test (Open Circuit Test) Purpose: Verify voltage output without any load. Parameters Checked: Voltage, frequency, waveform (if required). Acceptance Criteria: Voltage and frequency should be within ±5% of rated. 6. Load Test (Full Load/Resistive Load Test) Purpose: Verify performance under rated load. Load Bank Used: Resistive or reactive depending on requirement. Duration: Typically 1–4 hours. Parameters Checked: Voltage and frequency stability Load sharing (for multiple sets) Engine temperature Oil pressure Battery charging 7. Voltage Regulation Test Purpose: Assess the Automatic Voltage Regulator (AVR) response. Procedure: Apply varying loads and observe voltage change. Acceptance: Voltage should remain within design tolerance. 8. Frequency Stability Test Purpose: Check frequency response with load changes. Acceptance: ±2–5% frequency variation from rated. 9. Protection System Tests Tests: Over-voltage Under-voltage Over-frequency Over-current Earth fault simulation Purpose: Ensure protective relays and breakers trip correctly. 10. Synchronization Test (For paralleled generators) Purpose: Ensure correct sync with grid or other generators. Checked Parameters: Voltage match Frequency match Phase angle match 11. Functional Test of Control System Check alarms, shutdowns, fuel level indicators, auto/manual modes, and remote start/stop functions. 12. Emission and Noise Level Test (If applicable) As per local environmental and HSE regulations. 📋 DOCUMENTATION & REPORTING Test Report Includes: Equipment details Test methods and tools used Measured values Accept/reject criteria Calibration certificates Signatures (Testing engineer and witness/inspector) #EngineeringLife #TechnicalKnowledge #EngineeringCommunity #ProfessionalEngineer #FieldEngineer #ElectricalProfessionals #EngineeringWorld #QAQC #ElectricalEngineering #InspectionAndTesting #ElectricalInspection #QualityAssurance #SiteTesting #TestAndCommissioning #FieldTesting #SystemValidation #ElectricalSafety #OilAndGas #EnergyIndustry #IndustrialMaintenance #UtilitiesAndPower

  • View profile for Prakash Yvms

    Dy General Manager, Central Transmission Utility of India Limited, wholly owned subsidiary of Power Grid Corporation of India Limited

    3,973 followers

    🌍 Renewable Energy Plant Modeling & Grid Compliance: A Global Perspective ⚡ With increasing renewable energy (RE) integration, accurate modeling and validation have become critical for ensuring grid stability and regulatory compliance. But how do different countries approach this? Let’s explore the best practices from global power markets! 👇 🔹 Why RE Plant Modeling is Essential? ✅ Ensures Grid Code Compliance – RE plants must meet network operator requirements ✅ Enhances System Stability – Simulations predict system behavior under different conditions ✅ Supports Grid Integration – Helps in planning reactive power support and fault ride-through (FRT) 📊 Types of RE Simulation Models 1️⃣ Steady-State Models – Used for power flow studies and voltage stability 2️⃣ RMS (Root Mean Square) Models – For dynamic system stability within a small frequency range 3️⃣ EMT (Electromagnetic Transient) Models – Essential for analyzing fast transients, inverter interactions, and weak grids 🌏 Global Practices in Grid Code Compliance & Model Validation 📌 Australia (AEMO) 🔹 Generators must submit: RMS & EMT models (site-specific) Control block diagrams & source code Pre-commissioning & post-commissioning model validation reports 🔹 Model Stability Requirements: Must work across a wide range of system strength (SCR ≥ 3) Handle voltage & frequency variations dynamically 📌 Denmark (Energinet) 🔹 Generation Facilities are Categorized: Type A/B (≤ 1.5 MW) – No modeling required Type C (1.5 MW – 25 MW) – RMS model needed Type D (> 25 MW or connected at 100+ kV) – Both RMS & EMT models mandatory 🔹 Expects Models to Cover: Control strategies (Voltage, Frequency, PF control) Ride-through behavior for faults Harmonics & transient studies 📌 European Union (EU - NC RfG Standards) 🔹 Grid Code Compliance Methods Across the EU: Equipment Certification – Required in Spain & Germany Simulation Reports – Mandatory for Poland, Romania & Ireland On-Site Testing – Required in Ireland, Northern Ireland, and Sweden 🔹 Simulation Model Requirements: Must be validated against real-world fault recorder data Black-box EMT models are accepted to protect vendor confidentiality Generators must demonstrate Fault Ride-Through (FRT) capability before connection 📌 California (CAISO) 🔹 EMT Model Requirements: Detailed power electronic control representation (no approximations!) Ability to simulate switching dynamics of inverters Must reflect plant-wide response across all MW/MVAr levels 🔹 Validation Criteria: Self-initialization within 5 seconds Time-step accuracy from 10-20 µs Plant response must match real-world measurement data 📌 Common Industry Standards 🔹 WECC, NERC, and IEC guidelines standardize RE modeling for large-scale grid studies 🔹 Harmonic, transient, and long-term stability studies ensure secure integration

  • View profile for NAFEESA TAHIR

    Project Engineer at INTECH Process Automation | Design & Application Engineer | E&I Planning & Execution | FAT/SAT & Commissioning | Industrial Automation & Control Systems (SCADA, PLC, DCS, HMI) | Oil & Gas

    2,831 followers

    Did you know that 70% of control panel failures trace back to improper earthing and wiring practices - not faulty components? When it comes to industrial automation, panel reliability isn’t just about selecting premium devices - it’s built on the invisible foundation of how you wire, segregate, and ground your system. 1. Wiring Segregation – IS vs Non-IS Circuits Follow IEC 60079-14 & ISA RP12.6: Intrinsically Safe (IS) and Non-IS circuits must be segregated physically or by metallic barriers to avoid energy coupling. Maintain ≥50 mm spacing or use earthed metal partitions in marshalling panels. Always separate analog, digital, and power wiring to reduce electromagnetic interference (EMI) and signal noise. Common pitfall: Routing IS and Non-IS in the same conduit — a direct violation that can invalidate IECEx/ATEX certification. 2. Earthing – The Heartbeat of Reliability Follow IEC 60364, IEC 61000, and Shell DEP 33.46.00.31-Gen for control panel grounding. Maintain < 1 Ω earth resistance for control systems and equipotential bonding between instrument earth and main earth bar. Use star-point earthing to prevent ground loops in sensitive analog systems. Ensure individual clean earth for signal reference separate from dirty earth (power/EMI sources). 🧠 Remember: Even a few millivolts of ground potential difference can cause analog drift or false trip signals. 3. Cable Selection & Labeling Select cables per IEC 60228 (conductor sizing) and IEC 60332 (flame retardancy). Voltage drop should stay below 2% for control circuits and below 5% for power feeders. Use tinned copper shields and 100% coverage foil + braid for analog signal cables. Implement IEC 81346-1 / ISA 5.1 for consistent tagging and labeling across panels. Labels must be heat-resistant, UV-stable, and machine-printed for long-term traceability. 4. Common Mistakes & Their Impact Shared earth bars between power & signal → ground loops and EMI noise. Mixed IS/Non-IS wiring → safety certification failure. Undersized neutral or earth conductor → voltage imbalance or equipment damage. Missing ferrules or poor cable termination → intermittent faults and difficult troubleshooting. ✅ Takeaway Panel reliability is not built in the factory — it’s wired into every detail. Good wiring and earthing practices ensure safety, signal integrity, and long-term system stability. 🔍 What’s your approach to ensuring proper segregation and grounding in your panels? Share your experience or key lessons from the field 👇 #IndustrialAutomation #ControlSystems #ElectricalEngineering #PanelDesign #Instrumentation #IECStandards #AutomationEngineering #Earthing #WiringPractices #ProcessSafety #ReliabilityEngineering #EngineeringDesign

  • View profile for Omar Tarek Zayed

    Managing Security Consultant at IBM - Security Intelligence & Operations Consulting (SIOC) | Founder & Instructor at Cyber Dojo | Cyber Threat Hunter & DFIR Analyst | Cybersecurity Instructor & Mentor

    12,845 followers

    In any Security Operations Center, adding new tools or capabilities is a high-stakes decision. Skipping a structured evaluation risks budget overruns, unmet vendor expectations, and hidden operational costs. We can adapt a leaner Analysis of Alternatives (AoA) process to our environments and avoid costly missteps. 1. Identify the Opportunity Begin by defining the core problem: What gap in your detection, investigation, or response workflows drives this investment? Whether it’s reducing alert fatigue, improving threat hunting precision, or streamlining incident enrichment, a clear problem statement focuses the entire evaluation. 2. Define Analysis Criteria Translate that problem into measurable criteria. Examples include mean time to detect (MTTD) improvements, false-positive reduction percentages, integration depth with existing SIEM/SOAR platforms, or total cost of ownership (TCO) thresholds. Your criteria become the yardstick against which every alternative is judged. 3. Identify Alternatives Survey the market and internal options. This might include commercial SIEM add-ons, open-source analytics engines, custom development projects, or even process-only solutions (e.g., enhanced playbooks). Ensure each candidate has the potential to meet your defined criteria at a conceptual level. 4. Compare Features & Functionality Perform a side-by-side comparison, weighting each criterion against cost. Create a simple matrix to score alternatives on capability fit, deployment complexity, vendor support SLAs, and scaling potential. For example, does Platform A’s native UEBA module deliver equivalent detection accuracy to a standalone UEBA tool at half the operational overhead? 5. Report Results Document your methodology and findings in a concise report: - Opportunity summary - Analysis criteria and weighting - Alternatives considered - Feature comparison matrix with scoring - Recommended solution and rationale This transparency not only justifies the decision to stakeholders but also provides an audit trail for future evaluations. Best Practices in AoA Execution - Make a Plan & Pick the Right Team by involving representatives from SOC analysts, threat hunters, engineering, and finance to capture diverse viewpoints. - Be Objective & Avoid Bias by using blind scoring where possible and validate assumptions with small proof-of-concepts. - Articulate Current Shortcomings by precisely documenting why existing tools fall short—every gap you identify reinforces the need for change. - Evaluate Broadly and don’t limit yourself to incumbent vendors; often, niche solutions deliver superior value for specific use cases. - Leverage Overarching Methodologies by integrating AoA into your project management framework to ensure consistent governance and accountability. By adopting a disciplined AoA framework, your SOC can confidently select technologies that deliver on promises, stay within budget, and drive measurable improvements in security posture.

Explore categories