Lesson
23
Condensers &
Evaporators
Version 1 ME, IIT Kharagpur 1
The specific objectives of this lesson are to:
1. Classify refrigerant evaporators as natural convection or forced convection
type, flooded or dry type, refrigerant flow inside the tubes or outside the tubes
(Section 23.1)
2. Discuss salient features of natural convection coils (Section 23.2)
3. Discuss salient features of flooded evaporators (Section 23.3)
4. Discuss salient features of shell-and-tube type evaporators (Section 23.4)
5. Discuss salient features of shell-and-coil evaporator (Section 23.5)
6. Discuss salient features of double pipe evaporators (Section 23.6)
7. Discuss salient features of Baudelot evaporators (Section 23.7)
8. Discuss salient features of direct expansion fin-and-tube type evaporators
(Section 23.8)
9. Discuss salient features of plate surface evaporators (Section 23.9)
10. Discuss salient features of plate type evaporators (Section 23.10)
11. Discuss thermal design aspects of refrigerant evaporators (Section 23.11)
12. Discuss enhancement of boiling heat transfer (Section 23.12)
13. Discuss the concept of Wilson’s plot (Section 23.13)
At the end of the lecture, the student should be able to:
1. Classify refrigerant evaporators and discuss the salient features of different
types of evaporators
2. Perform thermal design calculations on refrigerant evaporators using various
heat transfer correlations presented in the lecture
3. Use Wilson’s plots and determine external and internal heat transfer
coefficients from given experimental data and specifications of evaporators and
condensers
Introduction:
An evaporator, like condenser is also a heat exchanger. In an evaporator,
the refrigerant boils or evaporates and in doing so absorbs heat from the
substance being refrigerated. The name evaporator refers to the evaporation
process occurring in the heat exchanger.
23.1.Classification
There are several ways of classifying the evaporators depending upon the
heat transfer process or refrigerant flow or condition of heat transfer surface.
23.1.1. Natural and Forced Convection Type
The evaporator may be classified as natural convection type or forced
convection type. In forced convection type, a fan or a pump is used to circulate
Version 1 ME, IIT Kharagpur 2
the fluid being refrigerated and make it flow over the heat transfer surface, which
is cooled by evaporation of refrigerant. In natural convection type, the fluid being
cooled flows due to natural convection currents arising out of density difference
caused by temperature difference. The refrigerant boils inside tubes and
evaporator is located at the top. The temperature of fluid, which is cooled by it,
decreases and its density increases. It moves downwards due to its higher
density and the warm fluid rises up to replace it.
23.1.2. Refrigerant Flow Inside or Outside Tubes
The heat transfer phenomenon during boiling inside and outside tubes is
very different; hence, evaporators are classified as those with flow inside and
outside tubes.
In natural convection type evaporators and some other evaporators, the
refrigerant is confined and boils inside the tubes while the fluid being refrigerated
flows over the tubes. The direct expansion coil where the air is directly cooled in
contact with the tubes cooled by refrigerant boiling inside is an example of forced
convection type of evaporator where refrigerant is confined inside the tubes.
In many forced convection type evaporators, the refrigerant is kept in a
shell and the fluid being chilled is carried in tubes, which are immersed in
refrigerant. Shell and tube type brine and water chillers are mainly of this kind.
23.1.3. Flooded and Dry Type
The third classification is flooded type and dry type. Evaporator is said to
be flooded type if liquid refrigerant covers the entire heat transfer surface. This
type of evaporator uses a float type of expansion valve. An evaporator is called
dry type when a portion of the evaporator is used for superheating the refrigerant
vapour after its evaporation.
23.2.Natural Convection type evaporator coils
These are mainly used in domestic refrigerators and cold storages. When
used in cold storages, long lengths of bare or finned pipes are mounted near the
ceiling or along the high sidewalls of the cold storages. The refrigerant from
expansion valve is fed to these tubes. The liquid refrigerant evaporates inside the
tubes and cools the air whose density increases. The high-density air flows
downwards through the product in the cold storage. The air becomes warm by
the time it reaches the floor as heat is transferred from the product to air. Some
free area like a passage is provided for warm air to rise up. The same passage is
used for loading and unloading the product into the cold storage.
The advantages of such natural convection coils are that the coil takes no
floor space and it also requires low maintenance cost. It can operate for long
Version 1 ME, IIT Kharagpur 3
periods without defrosting the ice formed on it and it does not require special skill
to fabricate it. Defrosting can be done easily (e.g. by scraping) even when the
plant is running. These are usually welded at site. However, the disadvantage is
that natural convection heat transfer coefficient is very small hence very long
lengths are required which may cause excessive refrigerant side pressure drops
unless parallel paths are used. The large length requires a larger quantity of
refrigerant than the forced convection coils. The large quantity of refrigerant
increases the time required for defrosting, since before the defrosting can start all
the liquid refrigerant has to be pumped out of the evaporator tubes. The pressure
balancing also takes long time if the system trips or is to be restarted after load
shedding. Natural convection coils are very useful when low air velocities and
minimum dehumidification of the product is required. Household refrigerators,
display cases, walk-in-coolers, reach-in refrigerators and obviously large cold
storages are few of its applications. Sufficient space should be provided between
the evaporator and ceiling to permit the air circulation over the top of the coil.
Baffles are provided to separate the warm air and cold air plumes. Single ceiling
mounted is used for rooms of width less than 2.5 m. For rooms with larger widths
more evaporator coils are used. The refrigerant tubes are made of steel or
copper. Steel tubes are used for ammonia and in large capacity systems.
23.3.Flooded Evaporator
This is typically used in large ammonia systems. The refrigerant enters a
surge drum through a float type expansion valve. The compressor directly draws
the flash vapour formed during expansion. This vapour does not take part in
refrigeration hence its removal makes the evaporator more compact and
pressured drop due to this is also avoided. The liquid refrigerant enters the
evaporator from the bottom of the surge drum. This boils inside the tubes as heat
is absorbed. The mixture of liquid and vapour bubbles rises up along the
evaporator tubes. The vapour is separated as it enters the surge drum. The
remaining unevaporated liquid circulates again in the tubes along with the
constant supply of liquid refrigerant from the expansion valve. The mass flow rate
in the evaporator tubes is m.f where is the mass flow rate through the
expansion valve and to the compressor. The term f is called recirculation factor.
Let x
m
4 be the quality of mixture after the expansion valve and x be the quality of
mixture after boiling in the tubes as shown in Figure 23.1. In steady state mass
flow rate from expansion valve is same as the mass flow rate to the compressor
hence mass conservation gives
..
4 mm.f.xm.x =+ (23.1)
x
)x1(
f 4−
=∴ (23.2)
Version 1 ME, IIT Kharagpur 4
For x4 = x = 0.25, for example, the circulation factor is 3, that is mass flow
rate through the evaporator is three times that through the compressor. Since,
liquid refrigerant is in contact with whole of evaporator surface, the refrigerant
side heat transfer coefficient will be very high. Sometimes a liquid refrigerant
pump may also be used to further increase the heat transfer coefficient. The
lubricating oil tends to accumulate in the flooded evaporator hence an effective
oil separator must be used immediately after the compressor.
Flooded type evaporator
Surge tank
Float valve
To compressor
f.m
m
m
(x4)
(x)
f.m
Fig.23.1. Schematic of a flooded evaporator
Version 1 ME, IIT Kharagpur 5
23.4. Shell-and-Tube Liquid Chillers
The shell-and-tube type evaporators are very efficient and require
minimum floor space and headspace. These are easy to maintain, hence they
are very widely used in medium to large capacity refrigeration systems. The
shell-and-tube evaporators can be either dry type or flooded type. As the name
implies, a shell-and-tube evaporator consists of a shell and a large number of
straight tubes arranged parallel to each other. In dry expansion type, the
refrigerant flows through the tubes while in flooded type the refrigerant is in the
shell. A pump circulates the chilled water or brine. The shell diameters range
from 150 mm to 1.5 m. The number of tubes may be less than 50 to several
thousands and length may be between 1.5 m to 6 m. Steel tubes are used with
ammonia while copper tubes are used with freons. Ammonia has a very high
heat transfer coefficient while freons have rather poor heat transfer coefficient
hence fins are used on the refrigerant side. Dry expansion type uses fins inside
the tubes while flooded type uses fins outside the tube. Dry-expansion type
require less charge of refrigerant and have positive lubricating oil return. These
are used for small and medium capacity refrigeration plants with capacity ranging
from 2 TR to 350 TR. The flooded type evaporators are available in larger
capacities ranging from 10 TR to thousands of TR.
23.4.1 Flooded Type Shell-and-Tube Evaporator
Figure 23.2 shows a flooded type of shell and tube type liquid chiller
where the liquid (usually brine or water) to be chilled flows through the tubes in
double pass just like that in shell and tube condenser. The refrigerant is fed
through a float valve, which maintains a constant level of liquid refrigerant in the
shell. The shell is not filled entirely with tubes as shown in the end view of Fig.
27.2. This is done to maintain liquid refrigerant level below the top of the shell so
that liquid droplets settle down due to gravity and are not carried by the vapour
leaving the shell. If the shell is completely filled with tubes, then a surge drum is
provided after the evaporator to collect the liquid refrigerant.
Shell-and-tube evaporators can be either single pass type or multipass
type. In multipass type, the chilled liquid changes direction in the heads. Shell-
and-tube evaporators are available in vertical design also. Compared to
horizontal type, vertical shell-and-tube type evaporators require less floor area.
The chilled water enters from the top and flows downwards due to gravity and is
then taken to a pump, which circulates it to the refrigeration load. At the inlet to
tubes at the top a special arrangement introduces swirling action to increase the
heat transfer coefficient.
Version 1 ME, IIT Kharagpur 6
Refrigerant in
Refrigerant out
Water
in
Water
out
Fig.23.2: Schematic of a flooded type shell-and-tube evaporator
23.4.2. Direct expansion type, Shell-and-Tube Evaporator
Figure 23.3 shows a liquid chiller with refrigerant flowing through the tubes
and water flowing through the shell. A thermostatic expansion valve feeds the
refrigerant into the tubes through the cover on the left. It may flow in several
passes through the dividers in the covers of the shell on either side. The liquid to
be chilled flows through the shell around the baffles. The presence of baffles
turns the flow around creating some turbulence thereby increasing the heat
transfer coefficient. Baffles also prevent the short-circuiting of the fluid flowing in
the shell. This evaporator is of dry type since some of the tubes superheat the
vapour. To maintain the chilled liquid velocity so as to obtain good heat transfer
coefficient, the length and the spacing of segmental baffles is varied. Widely
spaced baffles are used when the flow rate is high or the liquid viscosity is high.
The number of passes on the refrigerant side are decided by the partitions on the
heads on the two sides of the heat exchanger. Some times more than one circuit
is also provided. Changing the heads can change the number of passes. It
depends upon the chiller load and the refrigerant velocity to be maintained in the
heat exchanger.
23.5.Shell-and-Coil type evaporator
These are of smaller capacity than the shell and tube chillers. These are
made of one or more spiral shaped bare tube coils enclosed in a welded steel
shell. It is usually dry-expansion type with the refrigerant flowing in the tube and
chilled liquid in the shell. In some cases the chiller operates in flooded mode also
with refrigerant in the shell and chilled water flowing thorough the spiral tube. The
water in the shell gives a large amount of thermal storage capacity called hold-up
Version 1 ME, IIT Kharagpur 7
capacity. This type is good for small but highly infrequent peak loads. It is used
for cooling drinking water in stainless steel tanks to maintain sanitary conditions.
It is also used in bakeries and photographic laboratories.
When the refrigerant is in the shell that is in flooded mode it is called
instantaneous liquid chiller. This type does not have thermal storage capacity,
the liquid must be instantaneously chilled whenever required. In the event of
freeze up the water freezes in the tube, which causes bursting of the tubes since
water expands upon freezing. When water is in the shell there is enough space
for expansion of water if the freezing occurs. The flooded types are not
recommended for any application where the temperature of chilled liquid may be
below 3o
C.
Water inlet Water outlet
Refrigerant
inlet
Refrigerant
outlet
Baffles
Fig.23.3: Schematic of a direct expansion type, Shell-and-Tube evaporator
23.6.Double pipe type evaporator
This consists of two concentric tubes, the refrigerant flows through the
annular passage while the liquid being chilled flows through the inner tube in
counter flow. One design is shown in Fig. 23.4 in which the outer horizontal tubes
are welded to vertical header tubes on either side. The inner tubes pass through
the headers and are connected together by 180o
bends. The refrigerant side is
welded hence there is minimum possibility of leakage of refrigerant. These may
Version 1 ME, IIT Kharagpur 8
be used in flooded as well as dry mode. This requires more space than other
designs. Shorter tubes and counter flow gives good heat transfer coefficient. It
has to be insulated from outside since the refrigerant flows in the outer annulus
which may be exposed to surroundings if insulation is not provided.
Refrigerant
outlet
Water
inlet
Water
outlet
Refrigerant
inlet
Fig.23.4: Schematic of a double pipe type evaporator
23.7.Baudelot type evaporators
This type of evaporator consists of a large number of horizontal pipes
stacked one on top of other and connected together to by headers to make single
or multiple circuits. The refrigerant is circulated inside the tubes either in flooded
or dry mode. The liquid to be chilled flows in a thin layer over the outer surface of
the tubes. The liquid flows down by gravity from distributor pipe located on top of
the horizontal tubes as shown in Figure 23.5. The liquid to be chilled is open to
atmosphere, that is, it is at atmospheric pressure and its aeration may take place
during cooling. This is widely used for cooling milk, wine and for chilling water for
carbonation in bottling plants. The liquid can be chilled very close to its freezing
temperature since freezing outside the tubes will not damage the tubes. Another
advantage is that the refrigerant circuit can be split into several parts, which
Version 1 ME, IIT Kharagpur 9
permit a part of the cooling done by cold water and then chilling by the
refrigerant.
Refrigerant
outlet
Refrigerant
inlet
Milk
inlet
Milk
outlet
Distributor
Header
Fig.23.5: Schematic of a Baudelot type evaporator for chilling of milk
23.8. Direct expansion fin-and-tube type
These evaporators are used for cooling and dehumidifying the air directly
by the refrigerant flowing in the tubes. Similar to fin-and-tube type condensers,
these evaporator consists of coils placed in a number of rows with fins mounted
on it to increase the heat transfer area. Various fin arrangements are used.
Tubes with individual spiral straight fins or crimpled fins welded to it are used in
some applications like ammonia. Plate fins accommodating a number of rows are
used in air conditioning applications with ammonia as well as synthetic
refrigerants such as fluorocarbon based refrigerants.
The liquid refrigerant enters from top through a thermostatic expansion
valve as shown in Fig. 23.6. This arrangement makes the oil return to
compressor better rather than feeding refrigerant from the bottom of the coil.
When evaporator is close to the compressor, a direct expansion coil is used
Version 1 ME, IIT Kharagpur 10
since the refrigerant lines are short, refrigerant leakage will be less and pressure
drop is small. If the air-cooling is required away from the compressor, it is
preferable to chill water and pump it to air-cooling coil to reduce the possibility of
refrigerant leakage and excessive refrigerant pressure drop, which reduces the
COP.
Refrigerant
inlet
Refrigerant
outlet
Fig.23.6: Schematic of a direct expansion fin-and-tube type
The fin spacing is kept large for larger tubes and small for smaller tubes. 50 to
500 fins per meter length of the tube are used in heat exchangers. In
evaporators, the atmospheric water vapour condenses on the fins and tubes
when the metal temperature is lower than dew point temperature. On the other
hand frost may form on the tubes if the surface temperature is less than 0o
C.
Hence for low temperature coils a wide spacing with about 80 to 200 fins per m is
used to avoid restriction of flow passage due to frost formation. In air-conditioning
applications a typical fin spacing of 1.8 mm is used. Addition of fins beyond a
certain value will not increase the capacity of evaporator by restricting the airflow.
The frost layer has a poor thermal conductivity hence it decreases the overall
heat transfer coefficient apart from restricting the flow. Therefore, for applications
in freezers below 0o
C, frequent defrosting of the evaporator is required.
23.9.Plate Surface Evaporators
These are also called bonded plate or roll-bond type evaporators. Two flat
sheets of metal (usually aluminum) are embossed in such a manner that when
these are welded together, the embossed portion of the two plates makes a
passage for refrigerant to flow. This type is used in household refrigerators.
Figure 23.7 shows the schematic of a roll-bond type evaporator.
Version 1 ME, IIT Kharagpur 11
In another type of plate surface evaporator, a serpentine tube is placed
between two metal plates such that plates press on to the tube. The edges of the
plates are welded together. The space between the plates is either filled with a
eutectic solution or evacuated. The vacuum between the plates and atmospheric
pressure outside, presses the plates on to the refrigerant carrying tubes making a
very good contact between them. If eutectic solution is filled into the void space,
this also makes a good thermal contact between refrigerant carrying tubes and
the plates. Further, it provides an additional thermal storage capacity during off-
cycle and load shedding to maintain a uniform temperature. These evaporators
are commonly used in refrigerated trucks. Figure 23.8 shows an embedded tube,
plate surface evaporator.
A
A
Section A-A
Refrigerant in
Refrigerant out
Fig.23.7: Schematic of a roll-bond type evaporator
AA
Refrigerant in Refrigerant out
Section A-A
Version 1 ME, IIT Kharagpur 12Eutectic
solution
Fig.23.8: Schematic of an embedded tube, plate surface evaporator
23.10. Plate type evaporators:
Plate type evaporators are used when a close temperature approach (0.5
K or less) between the boiling refrigerant and the fluid being chilled is required.
These evaporators are widely used in dairy plants for chilling milk, in breweries
for chilling beer. These evaporators consist of a series of plates (normally made
of stainless steel) between which alternately the milk or beer to be cooled and
refrigerant flow in counterflow direction. The overall heat transfer coefficient of
these plate type evaporators is very high (as high as 4500 W/m2
K in case of
ammonia/water and 3000 W/m2
.K in case of R 22/water). In addition they also
require very less refrigerant inventory for the same capacity (about 10 percent or
even less than that of shell-and-tube type evaporators). Another important
advantage when used in dairy plants and breweries is that, it is very easy to
clean the evaporator and assemble it back as and when required. The capacity
can be increased or decreased very easily by adding or removing plates. Hence
these evaporators are finding widespread use in a variety of applications. Figure
23.9 shows the schematic of a plate type evaporator.
Fig.23.9: Schematic of a plate type evaporator
Version 1 ME, IIT Kharagpur 13
23.11. Thermal design of evaporators:
Compared to the design of refrigerant condensers, the design of
refrigerant evaporators is more complex. The complexity arises due to the
following factors:
a) On the refrigerant side, the heat transfer coefficient varies widely when
evaporation takes place in tubes due to changing flow regimes. Accurate
estimation of heat transfer coefficient is thus difficult
b) On the external fluid side, if the external fluid is air (as in air conditioning
and cold storage applications), in addition to sensible heat transfer, latent
heat transfer also takes place as moisture in air may condense or even
freeze on the evaporator surface. The evaporator surface may be partly
dry and partly wet, depending upon the operating conditions. Hence, mass
transfer has to be considered in the design. If frost formation due to
freezing of moisture takes place, then heat transfer resistance varies
continuously with time.
c) The lubricating oil gets separated in the evaporator tubes due to low
miscibility of oil at evaporator temperature and pressure. The separation of
oil affects both heat transfer and pressure drop characteristics. A minimum
refrigerant velocity must be provided for oil carry over in direct expansion
type evaporators.
d) Compared to condenser, refrigerant pressure drop in evaporator is more
critical as it has significant influence on the performance of the
refrigeration system. Hence, multiple circuits may have to be used in large
systems to reduce pressure drops. Refrigerant velocity has to be
optimized taking pressure drop and oil return characteristics into account.
e) Under part-load applications, there is a possibility of evaporator flooding
and compressor slugging. This aspect has to be considered at the time of
evaporator design.
Estimation of heat transfer area and overall heat transfer coefficients
For plate fin type evaporators, the expressions of various heat transfer
areas are similar to those given for the air-cooled condensers. The expression for
overall heat transfer coefficient is also similar to that of condenser as long as no
phase change (e.g. moisture condensation or freezing) takes place. However, as
mentioned in air-cooled evaporators the possibility of moisture
condensing/freezing on the evaporator surface must be considered unlike in
condensers where the heat transfer on airside is only sensible. This requires
simultaneous solution of heat and mass transfer equations on the airside to
arrive at expressions for overall heat transfer coefficient and mean temperature
difference. The efficiency of the fins will also be affected by the presence of
condensed layer of water or a frozen layer of ice. Expressions have been derived
for overall heat transfer coefficient, mean temperature difference and fin
efficiency of fin-and-tube type evaporators in which air undergoes cooling and
Version 1 ME, IIT Kharagpur 14
dehumidification. The analysis of cooling and dehumidification coils requires
knowledge of psychrometry and is obviously much more complicated compared
to evaporators in which the external fluid does not undergo phase change. In this
lecture, only the evaporators wherein the external fluid does not undergo any
phase change are considered. Readers should refer to advanced books on
refrigeration for the design aspects of cooling and dehumidifying coils.
Estimation of heat transfer coefficients:
a) Air side heat transfer coefficients in fin-and-tube type evaporators:
If air undergoes only sensible cooling as it flows over the evaporator
surface (i.e., dry evaporator), then the correlations presented for air cooled
condensers for heat transfer coefficients on finned (e.g. Kays & London
correlation) and bare tube surface (e.g. Grimson’s correlation) can be used for air
cooled evaporator also. However, if air undergoes cooling and dehumidification,
then analysis will be different and correlations will also be different. These
aspects will be discussed in a later chapter.
b) Liquid side heat transfer coefficients:
Liquid flowing in tubes:
When liquids such as water, brine, milk etc. flow through tubes without
undergoing any phase changes, the correlations presented earlier for
condensers (e.g. Dittus-Boelter, Sieder-Tate) can be used for evaporator also.
Liquid flowing in a shell:
In direct expansion type, shell-and-tube evaporators refrigerant flows
through the tubes, while water or other liquids flow through the shell. Analytical
prediction of single phase heat transfer coefficient on shell side is very complex
due to the complex fluid flow pattern in the presence of tubes and baffles. The
heat transfer coefficient and pressure drop depends not only on the fluid flow rate
and its properties, but also on the arrangement of tubes and baffles in the shell.
Several correlations have been suggested to estimate heat transfer coefficients
and pressure drops on shell side. A typical correlation suggested by Emerson is
given below:
14.0
w
3.06.0
d
f
PrReC
k
hd
Nu ⎟⎟
⎠
⎞
⎜⎜
⎝
⎛
μ
μ
== (23.3)
where constant C depends on the geometry, i.e, on the arrangement of the
tubes, baffles etc.
Version 1 ME, IIT Kharagpur 15
In the above expression the Reynolds number Re s defined as:d i
μ
=
Gd
Red (23.4)
where G is the mass velocity which is equal to the mass flow rate divided by the
characteristic flow area (kg/m2
.s). From the expression for Nusselt number, it can
be seen that the heat transfer coefficient is proportional to the 0.6 power of the
flow rate as compared to 0.8 power for flow through tubes.
The pressure drop of liquid flowing through the shell is also difficult to
predict analytically. Normally the pressure drop on shell side is obtained from
experimental measurements and is provided in the form of tables and charts for a
particular type of shell-and-tube heat exchanger.
c) Boiling Heat Transfer Coefficients:
Pool boiling vs flow boiling:
In evaporators boiling of refrigerant may take place outside tubes or inside
tubes. When boiling takes place outside the tubes it is called as pool boiling. In
pool boiling it is assumed that the tube or the heat transfer surface is immersed
in a pool of liquid, which is at its saturation temperature. Figure 23.10 shows a
typical boiling curve, which shows the variation of surface heat flux with
temperature difference between the surface and the saturation temperature for
different regimes. For a small temperature difference, the heat transfer from the
surface is by free convection (regime 1). As the temperature difference
increases, bubbles start to form at selected nucleation sites. The bubbles grow in
size as heat is transferred and the evaporation of liquid occurs. After achieving a
critical diameter depending upon the surface tension and other factors, the
bubbles get detached from the surface and rise to the free surface where the
vapour inside the bubbles is released. During the detachment process, the
surrounding liquid rushes towards the void created and also during the bubble
motion upwards convection heat transfer increases from its free convection value
at smaller temperature differences. This region is known as individual bubble
regime (regime 2). As the temperature difference increase further, more and
more bubbles are formed and it is the columns of bubbles, which rise up
increasing the heat transfer drastically. This regime is known as column bubble
regime (regime 3).
As the temperature difference increases further, more and more bubbles
are formed, and columns of bubbles rise to the free surface. The heat transfer
rate increases rapidly. As the bubble columns move upwards they entrain some
liquid also that rises upwards to the free surface. The vapour in the bubbles
escapes at the free surface but the liquid returns to the bottom because of its
lower temperature and higher density. A given surface can accommodate only a
few such rising columns of bubbles and descending columns of relatively colder
Version 1 ME, IIT Kharagpur 16
liquid. Hence, the heat transfer rate cannot increase beyond a certain value. It
becomes maximum at some temperature difference. The maximum heat transfer
rate is called critical heat transfer rate.
If temperature difference is increased beyond this value, then a blanket of
film forms around the heat transfer surface. This vapour film offers conduction
thermal resistance; as a result the heat transfer rate decreases. The film however
is unstable and may break at times. This regime is called unstable film regime
(regime 4).
If temperature difference is increased further it becomes so high that
radiation heat transfer becomes very important and heat transfer rate increases
because of radiation component. This regime is called stable film boiling regime
(regime 5). After this, due to the high surface temperature, radiation effects
become important (regime 6).
As the temperature difference is increased, the temperature of the surface
tw continues to increase since conduction thermal resistance of the film becomes
larger as the film thickness increases. All the heat from the surface cannot be
transferred across the film and surface temperature increases. Ultimately the
temperature may approach the melting point of the metal and severe accident
may occur (if these are the tubes of nuclear power plant). This point is referred to
as burnout point.
(Ts-Tf)
q
1 2 3 4 5 6 Critical
heat flux
Fig.23.10: A typical pool boiling curve showing different regimes, 1 to 6
Version 1 ME, IIT Kharagpur 17
Boiling inside tubes is called as flow boiling. Flow boiling consists of nucleate
boiling as well as convective heat transfer. As the liquid evaporates, more vapour
is formed which increases the average velocity and the convective heat transfer
rate. The flow pattern changes continuously as boiling takes place along the
tube. For example in a horizontal tube, the flow can be stratified flow, wavy flow,
slug flow, annular flow, mist flow etc. The flow pattern will be different if it takes
place in an inclined or vertical tube. The heat transfer coefficient depends upon
fraction of vapour present and parameters of forced convection heat transfer. In
general, prediction of boiling heat transfer coefficients during flow boiling is much
more complex than pool boiling. However, a large number of empirical
correlations have been developed over the years to predict boiling heat transfer
coefficients for both pool as well as flow boiling conditions. The following are
some of the well-known correlations:
Nucleate Pool Boiling
Normally evaporators are designed to operate in nucleate pool boiling
regime as the heat transfer coefficients obtained in this regime are stable and are
very high. Various studies show that in nucleate pool boiling region, the heat
transfer coefficient is proportional to the 2 or 3 power of temperature difference
between the surface and the boiling fluid, i.e.,
3to2
fsnb )TT(Ch −= (23.5)
the value of C depends upon type of the surface etc. The exponent can be as
high as 25 on specially treated surfaces for enhancement of boiling.
Rohsenow’s Correlation for nucleate pool boiling: This correlation is
applicable to clean surfaces and is relatively independent of shape and
orientation of the surface.
s
f
33.0
gffgf
sf
fg
xf
Pr
)(gh
A/Q
C
h
TC
⎥
⎥
⎦
⎤
⎢
⎢
⎣
⎡
ρ−ρ
σ
μ
=
Δ
(23.6)
where:
= Specific heat of liquidCf
ΔTx = Temperature difference between surface and fluid
hfg = Latent heat of vaporization
σ = Surface Tension
Csf = constant which depends on the surface-fluid combination, e.g. 0.013 for
halocarbons boiling on copper surface
Q/A = heat flux
= Viscosity of fluidμf
, ρ = Density of saturated liquid and saturated vapour, respectivelyρf g
Prf = Prandtl number of saturated liquid
s = constant, 1 for water and 1.7 for halocarbons
Version 1 ME, IIT Kharagpur 18
All the fluid properties are calculated at saturation temperature corresponding
to the local pressure.
Forced Convection Boiling inside tubes:
Rohsenow and Griffith suggested that flow boiling in tubes be analyzed as
a combination of pool boiling and forced convection. The total heat flux (qtotal) is
the sum of heat flux due to nucleate pool boiling (q ) and forced convection (qnb fc),
i.e.,
fcnbtotal qqq += (23.7)
Heat flux due to nucleate pool boiling (qnb) is calculated by using nucleate
pool boiling correlations and heat flux due to forced convection (qfc) can be
calculated by using standard forced convection correlations, such as Dittus-
Boelter correlation.
Some of the other correlations suggested for flow boiling are given below:
(a) Bo Pierre’s Correlation : This correlation gives average heat transfer
coefficients and is valid for inlet quality xinlet ≈ 0.1 to 0.16.
( ) 9.0xandnevaporatioincompletefor:KRe0009.0uN exit
2
1
f
2
ff <=
( ) nevaporatiocompletefor:KRe0082.0uN 2
1
f
2
ff = (23.8)
In the above equations, Re and Nuf f are liquid Reynolds and Nusselt
numbers, respectively. K is the load factor, defined as:f
L
hx
K
fg
f
Δ
= (23.9)
where L is the length of the tube.
(b) Chaddock-Brunemann’s Correlation:
[ 6.067.0
tt
4
LTP )X/1(5.110.Boh91.1h += ] (23.10)
)A/m(h
A/Q
NumberBoilingBo
fg
==
ParameterMartinelliLockhart)/()/(
x
x1
X 1.0
gf
5.0
fg
9.0
tt −μμρρ⎟
⎠
⎞
⎜
⎝
⎛ −
=
Version 1 ME, IIT Kharagpur 19
(c) Jung and Radermacher Correlation:
L1sa1TP hFhNh += (23.11)
where hL is the single phase (liquid) heat transfer coefficient as predicted by
Dittus-Boelter equation, and hsa is given by:
85.0
tt1
tt
33.028.0
tt1
tt
13.122.1
tt1
o
5.0
gf
533.0
f
581.0
f
g
745.0
satf
f
sa
)X/129.0(37.2F
5X1for:BoX1.00.2N
1Xfor:BoX4048N
35:
)(g
2
0146.0bd
Pr
T
bd
.
k
q
bd
k
207h
+=
≤<−=
≤=
=β
⎥
⎥
⎦
⎤
⎢
⎢
⎣
⎡
ρ−ρ
σ
β=
⎟
⎟
⎠
⎞
⎜
⎜
⎝
⎛
ρ
ρ
⎟⎟
⎠
⎞
⎜⎜
⎝
⎛
=
−−
(23.12)
In nucleate boiling, the heat transfer coefficient is mainly dependent on the
heat flux and is a very weak function of mass flux. However, in flow boiling the
heat transfer coefficient depends mainly on mass flux and is a weak function of
heat flux. Studies show that for boiling inside tubes, initially when the vapour
fraction (quality) is low, then nucleate boiling is dominant and the heat transfer
coefficient depends on heat flux. However, as the fluid flows through the tubes,
the vapour fraction increases progressively due to heat transfer and when it
exceeds a critical vapour fraction, convective boiling becomes dominant. As
mentioned, in this region, the heat transfer coefficient depends mainly on the
mass flux and is almost independent of heat flux. As a whole, the heat transfer
coefficient due to boiling increases initially reaches a peak and then drops
towards the end of the tube. Thus accurate modeling of evaporators requires
estimation of heat transfer coefficient along the length taking into account the
complex physics.
Horizontal vs Vertical tubes: As mentioned before, boiling heat transfer
coefficients in vertical columns will be different from that in a horizontal tube. In a
vertical tube, due to hydrostatic head, the evaporation temperature increases,
which in turn reduces the driving temperature difference, and hence, the heat
transfer rate.
Effect of oil in evaporator: Studies on R 12 evaporators show that the boiling heat
transfer coefficient inside tubes increases initially with oil concentration upto a
value of about 4 percent and then decreases. The initial increase is attributed to
the greater wetting of the tube surface due to the presence of oil. The
subsequent reduction is due to the rapid increase in viscosity of the refrigerant-oil
mixture as oil is more viscous than refrigerant. For the estimation of heat transfer
Version 1 ME, IIT Kharagpur 20
coefficient, the presence of oil may be neglected as long as its concentration is
low (less than 10 percent).
23.12. Enhancement of heat transfer coefficients:
The overall heat transfer coefficient of a heat exchanger depends mainly
on the component having the largest resistance to heat transfer. When air is
used an external fluid, the heat transfer coefficient on air side is small, hence to
obtain high overall heat transfer coefficient, the air side heat transfer is
augmented by adding fins. When liquid water is used as the external fluid, then
the heat transfer coefficient on water side will be high, when the flow is turbulent
(which normally is the case). Hence to further improve overall heat transfer
coefficient, it may become necessary to enhance heat transfer on the refrigerant
side. This is especially the case with synthetic refrigerants. The enhancement of
boiling heat transfer coefficient can be achieved in several ways such as:
increasing the refrigerant velocity by using an external pump in flooded
evaporators, by using integrally finned tubes, by using treated surfaces, by using
turbulence promoters etc. These methods improve the refrigerant side heat
transfer coefficient and hence the overall heat transfer coefficient significantly
leading to compact and lightweight evaporators. However, it should be kept in
mind that normally any heat transfer enhancement technique imposes penalty by
means of increased pressure drop, hence it is essential to optimize the design so
that the total cost is minimized.
23.13. Wilson’s plot:
The concept of Wilson’s plot was introduced way back in 1915 by Wilson
to determine individual heat transfer coefficients from the experimental data on
heat transfer characteristics of heat exchangers. This is sometimes applied to
determine the condensing or boiling heat transfer coefficients of condensers and
evaporators respectively.
For example, in a water-cooled condenser a number of tests are
conducted by varying the flow rate of water and measuring the inlet and outlet
water temperatures. The total heat transfer rate is determined from
)LMTD(AU)tt(CmQ oowiwopww =−= (23.13)
From measured temperatures, LMTD is calculated. From the heat transfer rate
Q, area of the heat exchanger (Ao) and LMTD, the overall heat transfer
coefficient for a given flow rate is calculated using Eqn.(23.13).
Version 1 ME, IIT Kharagpur 21
Then the overall heat transfer coefficient Uo is equated to the following
equation (for clean tubes are clean with negligible scale formation)
ow
ioi
i
o
ii
o
o h
1
k
)d/d(lnr
A
A
Ah
A
U
1
++= (23.14)
If the water temperature does not vary very significantly during these tests,
then properties of water remain nearly constant. Since during these tests no
changes are made on the refrigerant side, it can be assumed that the heat
transfer resistance offered by the wall separating the two fluids and the heat
transfer coefficient on refrigerant side (ho) remains constant for all values of water
flow rates. Hence, the above equation can be written as:
i
2
1
o h
C
C
U
1
+= (23.15)
where C and C1 2 are empirical constants that depend on the specifications of the
heat exchangers and operating conditions, and the expressions for these can be
obtained by equating Eqns.(23.14) and (23.15).
If flow on water side is turbulent and the variation in thermal properties are
negligible, then the waterside heat transfer coefficient can be written as:
8.0
3i V.Ch = (23.16)
Substituting the expression in Eqn.(23.15), we obtain:
8.0
4
1
o V
C
C
U
1
+= (23.17)
vs 1/V0.8
Then a plot of 1/Uo will be a straight line as shown in Fig. 23.11.
This plot is extrapolated to infinitely high velocity, i.e., where 1/V0.8
tends to zero.
When 1/V0.8
tends to zero, from Eqn.(23.16) 1/hi also tends to zero. Hence, the
intercept on the ordinate is C (=1/h + A r ln (d /d)/(A ko o i 0 i i w1 )). The thermal
conduction resistance of the tube can be calculated and then the condensation
heat transfer coefficient ho can be calculated. As shown in the figure the term
A /(Ah) can also be obtained from the figure at any value of velocity.o i i
It should be kept in mind that it is an approximation since drawing a
straight line and extending it to meet y-axis means that condensation heat
transfer remains constant as the velocity tends to infinity. Wilson plot can be
applied to air-cooled condensers also. In this case as the heat transfer coefficient
for air over finned surface varies as V 0.65
, hence in this case 1/Uo will have to be
plotted versus V - 0.65
.
Version 1 ME, IIT Kharagpur 22
1/V0.8
1/Uo
(1/ho)+(do/di)riln(do/di)/kw
(do/di)1/hi
Fig.23.11: Concept of Wilson’s plot
Questions and answers:
1. Which of the following statements are TRUE?
a) In conventional refrigerators, the evaporators are kept at the top as these are
natural convection type
b) Natural convection type coils are useful when the latent loads are very high
c) Defrosting of evaporators has to be done more frequently in natural convection
type coils compared to forced convection evaporator coils
d) Provision of sufficient free space is very important in natural convection type
evaporator coils
Ans.: a) and d)
Version 1 ME, IIT Kharagpur 23
2. Which of the following statements are TRUE?
a) Flooded type evaporators are very efficient as the heat transfer coefficient on
refrigerant side is very large
b) In flooded type evaporators, the refrigerant evaporation rate is equal to the
refrigerant mass flow rate
c) An oil separator is always required in flooded evaporators as refrigerant tends
to get collected in the evaporator
d) All of the above
Ans.: a) and c)
3. Which of the following statements are TRUE?
a) Shell-and-tube evaporators are available in small to very large capacities
b) In dry expansion type evaporator, refrigerant flows through the shell while the
external fluid flows through the tubes
c) Normally float valves are used expansion devices for flooded type evaporators
d) In shell-and-coil type evaporators, thermal storage can be obtained by having
refrigerant on the shell side
Ans.: a) and c)
4. Which of the following statements are TRUE?
a) In direct expansion, fin-and-tube type evaporators, the oil return to compressor
is better if refrigerant enters at the bottom of the evaporator and leaves from the
top
b) For low temperature applications, the fin spacing of evaporator is kept larger to
take care of the frost formation
c) Double pipe type evaporators are used when close temperature approach is
required
d) Plate type evaporators are used when close temperature approach is required
Ans.: b) and d)
5. Thermal design of evaporators is very complex due to:
a) Continuous variation of heat transfer coefficient along the length
b) Possibility of latent heat transfer on the external fluid side also
c) Presence of lubricating oil affects heat transfer and pressure drop
d) All of the above
Ans.: d)
Version 1 ME, IIT Kharagpur 24
6. Which of the following statements are TRUE?
a) In evaporators using air as an external fluid, fins are frequently required on the
refrigerant side
b) In evaporators using water as an external fluid, fins may be required on the
refrigerant side to enhance heat transfer
c) Flooded type evaporators yield higher heat transfer coefficients compared to
direct expansion type evaporators
d) In general heat transfer enhancement techniques yield more compact heat
exchangers, but may also increase pressure drop
Ans.: b), c) and d)
7. Air enters a direct expansion type, fin-and-tube evaporator at a temperature of
17o o
C and leaves the evaporator at 11 C. The evaporator operates at a constant
temperature of 7o 2
C and has total refrigerant side area of 12 m , while the bare
tube and finned areas on airside are 10 m2 2
and 212 m , respectively. Find the
refrigeration capacity of the evaporator assuming only sensible heat transfer on
airside and counterflow type arrangement. Neglect fouling and resistance offered
by the tube wall. The fin effectiveness for airside is 0.75. The average heat
transfer coefficient on refrigerant and airside are 1700 W/m2 2
.K and 34 W/m .K,
respectively.
Ans.: Neglecting fouling and resistance of the tube wall, the value of ‘UA’ of
evaporator is given by:
iiobff Ah
1
)]AA(h[
1
UA
1
+
+η
=
Substituting the values of airside and refrigerant heat transfer coefficients (ho and
h), bare tube (A ), finned surface (Ai b f) and refrigerant side areas and fin efficiency
(ηf = 0.75) in the above expression, we obtain:
UA = 4483 W/K
From the values of airside and evaporator temperatures, the LMTD of the
evaporator is given by:
C55.6
711
717
ln
)1117(
LMTD o
=
⎟
⎠
⎞
⎜
⎝
⎛
−
−
−
=
Hence, refrigeration capacity, Q = UA.LMTD = 29364 W = 29.364 kW (Ans.)e
Version 1 ME, IIT Kharagpur 25
8. The following are the values measured on a shell-and-tube ammonia
condenser:
Velocity of water flowing through the tubes, V (m/s) 1.22 0.61
Overall heat transfer coefficient, U (W/m2
.K) 2300 1570o
Water flowed inside the tubes while refrigerant condensed outside the tubes. The
tubes were 51 mm OD and 46 mm ID and had a conductivity of 60 W/m.K. Using
the concept of Wilson’s plot, determine the condensing heat transfer coefficient.
What is the value of overall heat transfer coefficient when the velocity of water is
0.244 m/s?
Ans.:
From the data given in the table, the following straight line equation can be
obtained:
8.0
4
1
o V
C
C
U
1
+=
The values of C and C for the given data are found to be:1 4
C1 = 1.605 x 10-4
m2 -4
.K/W and C4 = 3.223 x 10 m1.2
.K/W
The constant C is equal to:1
4
ow
ioo
1 10x605.1
h
1
k
)r/r(lnr
C −
=+=
and rSubstituting the values of internal and external radii (ri o) and the value of
thermal conductivity of the tube kW, we obtain the value of external heat transfer
coefficient (condensation heat transfer coefficient, h ) as:o
ho = 8572.9 W/m2
.K (Ans.)
The value of overall heat transfer coefficient Uo when the velocity of water is
0.244 m/s is given by:
3
8.0
4
4
8.0
4
1
o
10x1567.1
244.0
10x223.3
10x605.1
V
C
C
U
1 −
−
−
=+=+=
⇒ Uo = 864.5 W/m2
.K (Ans.)
Version 1 ME, IIT Kharagpur 26

More Related Content

PPTX
Dry expansion evaporators1
PPTX
Eveporation ppt by sachin ;;;;;;;;;;;
PPTX
Evaporator
PPTX
S3 Lec 3 (Evaporator) Note
PPT
Equipment selection (RAC)
PPTX
Evaporators
PPT
15783 components vc_rs
PDF
Components of ref and ac u5
Dry expansion evaporators1
Eveporation ppt by sachin ;;;;;;;;;;;
Evaporator
S3 Lec 3 (Evaporator) Note
Equipment selection (RAC)
Evaporators
15783 components vc_rs
Components of ref and ac u5

What's hot (20)

PPTX
PPT
MET 214 Module 5
PDF
Evaporator by om
PDF
Presentation on mechanical vapor recompressor evaporator (mvre)
PPTX
Condensers,expansiondevices,evaporators types
PPT
Evaporation- Equipment and Design of Evaporators
PPT
Evaporation
PPT
About refrigeration
PDF
Let ref & aircondirtioning
PPTX
Evaporators
DOCX
Chapter1
PPTX
1.steam jacketed kettle
PDF
Steam traps
PPTX
MET 214 Module 6
PPTX
MET 214 Module 7
PPTX
Condenser
PPT
Evaporator
PPTX
Processing of petroleum types of reflux
PPT
Heat Exchanger
MET 214 Module 5
Evaporator by om
Presentation on mechanical vapor recompressor evaporator (mvre)
Condensers,expansiondevices,evaporators types
Evaporation- Equipment and Design of Evaporators
Evaporation
About refrigeration
Let ref & aircondirtioning
Evaporators
Chapter1
1.steam jacketed kettle
Steam traps
MET 214 Module 6
MET 214 Module 7
Condenser
Evaporator
Processing of petroleum types of reflux
Heat Exchanger
Ad

Viewers also liked (16)

PDF
Vipul tatvam e brochure 1
PPTX
Egleidys gonzalez
PDF
Curso: acordos de offset no setor de defesa
PDF
Cani del canile Ca' Lucio di Urbino
PDF
Sistema endocrino pre definitivo
PDF
Mapa conceptual rocio ramirez
PPTX
Mapa conceptual empresa constructora
PPTX
Empresa constructora
PPTX
Pasos y requisitos
PPTX
Shaun Baker - Crown Workplace Relocation
PDF
Managing and Developing Supplier Relationships
PDF
Expériences et apprentissages value analysis, value engineering par Eric Prev...
PPT
Projeto Construindo Com Ciência
PDF
Prestations Prévoyance : 1 an d’amélioration continue, des clients satisfaits...
PPTX
5. irrigación de la retina
PPTX
Anatomía esencial humana: Sistema circulatorio
Vipul tatvam e brochure 1
Egleidys gonzalez
Curso: acordos de offset no setor de defesa
Cani del canile Ca' Lucio di Urbino
Sistema endocrino pre definitivo
Mapa conceptual rocio ramirez
Mapa conceptual empresa constructora
Empresa constructora
Pasos y requisitos
Shaun Baker - Crown Workplace Relocation
Managing and Developing Supplier Relationships
Expériences et apprentissages value analysis, value engineering par Eric Prev...
Projeto Construindo Com Ciência
Prestations Prévoyance : 1 an d’amélioration continue, des clients satisfaits...
5. irrigación de la retina
Anatomía esencial humana: Sistema circulatorio
Ad

Similar to R&amp;ac lecture 23 (20)

PPTX
Presentation on evaporators
PPTX
Evaporators: Types and Numerical Solutions
PPTX
EVAPORATORS AND TYPES
PDF
R&amp;ac lecture 22
PPTX
different typesofrefrigerationcomponents
PDF
Chapter One.pdf
PDF
Evaporator
PPTX
Condensors and evaporators
PPTX
Condensers
PPTX
Condenser Types and Numerical Analysis
PDF
Refrigeration Equipments
PPTX
Food Dehydrators and evaporators
PDF
IRJET- Review on Comparative Analysis of COP of Vapour Compression Refrig...
PDF
Manual evap
DOCX
process design of water chilling plant
PPTX
Refrigeration and air conditioning detailed experimental procedures
PPTX
Intern ppt ..kk [Autosaved].pptx
PDF
Experimental Investigation of Water Cooler Test Rig Using R-22 as Refrigerant
PPTX
Types of evaporators
Presentation on evaporators
Evaporators: Types and Numerical Solutions
EVAPORATORS AND TYPES
R&amp;ac lecture 22
different typesofrefrigerationcomponents
Chapter One.pdf
Evaporator
Condensors and evaporators
Condensers
Condenser Types and Numerical Analysis
Refrigeration Equipments
Food Dehydrators and evaporators
IRJET- Review on Comparative Analysis of COP of Vapour Compression Refrig...
Manual evap
process design of water chilling plant
Refrigeration and air conditioning detailed experimental procedures
Intern ppt ..kk [Autosaved].pptx
Experimental Investigation of Water Cooler Test Rig Using R-22 as Refrigerant
Types of evaporators

More from sayed fathy (18)

PDF
R&amp;ac lecture 25
PDF
R&amp;ac lecture 24
PDF
R&amp;ac lecture 21
PDF
R&amp;ac lecture 20
PDF
R&amp;ac lecture 19
PDF
R&amp;ac lecture 18
PDF
R&amp;ac lecture 16
DOC
refrigeration home
DOC
type of refrigeration
DOC
Vapor copressor
PDF
Turbine base drawings
PDF
Turbine assem drawings
PDF
Turbine mast drawings
PDF
Turbine hub drawings
PDF
Wind turbine doc
PPTX
Sayed hashim
PDF
Interview
PPTX
Kaizen 130610225436-phpapp01
R&amp;ac lecture 25
R&amp;ac lecture 24
R&amp;ac lecture 21
R&amp;ac lecture 20
R&amp;ac lecture 19
R&amp;ac lecture 18
R&amp;ac lecture 16
refrigeration home
type of refrigeration
Vapor copressor
Turbine base drawings
Turbine assem drawings
Turbine mast drawings
Turbine hub drawings
Wind turbine doc
Sayed hashim
Interview
Kaizen 130610225436-phpapp01

Recently uploaded (20)

PPTX
IOT PPTs Week 10 Lecture Material.pptx of NPTEL Smart Cities contd
PPTX
Recipes for Real Time Voice AI WebRTC, SLMs and Open Source Software.pptx
PDF
TFEC-4-2020-Design-Guide-for-Timber-Roof-Trusses.pdf
PPTX
M Tech Sem 1 Civil Engineering Environmental Sciences.pptx
PDF
R24 SURVEYING LAB MANUAL for civil enggi
PDF
Digital Logic Computer Design lecture notes
PPTX
Engineering Ethics, Safety and Environment [Autosaved] (1).pptx
PDF
Automation-in-Manufacturing-Chapter-Introduction.pdf
PDF
Mohammad Mahdi Farshadian CV - Prospective PhD Student 2026
PPTX
MCN 401 KTU-2019-PPE KITS-MODULE 2.pptx
PPTX
bas. eng. economics group 4 presentation 1.pptx
PPTX
UNIT 4 Total Quality Management .pptx
PDF
The CXO Playbook 2025 – Future-Ready Strategies for C-Suite Leaders Cerebrai...
PDF
Model Code of Practice - Construction Work - 21102022 .pdf
PDF
BMEC211 - INTRODUCTION TO MECHATRONICS-1.pdf
PPTX
Geodesy 1.pptx...............................................
PPTX
FINAL REVIEW FOR COPD DIANOSIS FOR PULMONARY DISEASE.pptx
PPTX
OOP with Java - Java Introduction (Basics)
PDF
Well-logging-methods_new................
PPTX
Internet of Things (IOT) - A guide to understanding
IOT PPTs Week 10 Lecture Material.pptx of NPTEL Smart Cities contd
Recipes for Real Time Voice AI WebRTC, SLMs and Open Source Software.pptx
TFEC-4-2020-Design-Guide-for-Timber-Roof-Trusses.pdf
M Tech Sem 1 Civil Engineering Environmental Sciences.pptx
R24 SURVEYING LAB MANUAL for civil enggi
Digital Logic Computer Design lecture notes
Engineering Ethics, Safety and Environment [Autosaved] (1).pptx
Automation-in-Manufacturing-Chapter-Introduction.pdf
Mohammad Mahdi Farshadian CV - Prospective PhD Student 2026
MCN 401 KTU-2019-PPE KITS-MODULE 2.pptx
bas. eng. economics group 4 presentation 1.pptx
UNIT 4 Total Quality Management .pptx
The CXO Playbook 2025 – Future-Ready Strategies for C-Suite Leaders Cerebrai...
Model Code of Practice - Construction Work - 21102022 .pdf
BMEC211 - INTRODUCTION TO MECHATRONICS-1.pdf
Geodesy 1.pptx...............................................
FINAL REVIEW FOR COPD DIANOSIS FOR PULMONARY DISEASE.pptx
OOP with Java - Java Introduction (Basics)
Well-logging-methods_new................
Internet of Things (IOT) - A guide to understanding

R&amp;ac lecture 23

  • 2. The specific objectives of this lesson are to: 1. Classify refrigerant evaporators as natural convection or forced convection type, flooded or dry type, refrigerant flow inside the tubes or outside the tubes (Section 23.1) 2. Discuss salient features of natural convection coils (Section 23.2) 3. Discuss salient features of flooded evaporators (Section 23.3) 4. Discuss salient features of shell-and-tube type evaporators (Section 23.4) 5. Discuss salient features of shell-and-coil evaporator (Section 23.5) 6. Discuss salient features of double pipe evaporators (Section 23.6) 7. Discuss salient features of Baudelot evaporators (Section 23.7) 8. Discuss salient features of direct expansion fin-and-tube type evaporators (Section 23.8) 9. Discuss salient features of plate surface evaporators (Section 23.9) 10. Discuss salient features of plate type evaporators (Section 23.10) 11. Discuss thermal design aspects of refrigerant evaporators (Section 23.11) 12. Discuss enhancement of boiling heat transfer (Section 23.12) 13. Discuss the concept of Wilson’s plot (Section 23.13) At the end of the lecture, the student should be able to: 1. Classify refrigerant evaporators and discuss the salient features of different types of evaporators 2. Perform thermal design calculations on refrigerant evaporators using various heat transfer correlations presented in the lecture 3. Use Wilson’s plots and determine external and internal heat transfer coefficients from given experimental data and specifications of evaporators and condensers Introduction: An evaporator, like condenser is also a heat exchanger. In an evaporator, the refrigerant boils or evaporates and in doing so absorbs heat from the substance being refrigerated. The name evaporator refers to the evaporation process occurring in the heat exchanger. 23.1.Classification There are several ways of classifying the evaporators depending upon the heat transfer process or refrigerant flow or condition of heat transfer surface. 23.1.1. Natural and Forced Convection Type The evaporator may be classified as natural convection type or forced convection type. In forced convection type, a fan or a pump is used to circulate Version 1 ME, IIT Kharagpur 2
  • 3. the fluid being refrigerated and make it flow over the heat transfer surface, which is cooled by evaporation of refrigerant. In natural convection type, the fluid being cooled flows due to natural convection currents arising out of density difference caused by temperature difference. The refrigerant boils inside tubes and evaporator is located at the top. The temperature of fluid, which is cooled by it, decreases and its density increases. It moves downwards due to its higher density and the warm fluid rises up to replace it. 23.1.2. Refrigerant Flow Inside or Outside Tubes The heat transfer phenomenon during boiling inside and outside tubes is very different; hence, evaporators are classified as those with flow inside and outside tubes. In natural convection type evaporators and some other evaporators, the refrigerant is confined and boils inside the tubes while the fluid being refrigerated flows over the tubes. The direct expansion coil where the air is directly cooled in contact with the tubes cooled by refrigerant boiling inside is an example of forced convection type of evaporator where refrigerant is confined inside the tubes. In many forced convection type evaporators, the refrigerant is kept in a shell and the fluid being chilled is carried in tubes, which are immersed in refrigerant. Shell and tube type brine and water chillers are mainly of this kind. 23.1.3. Flooded and Dry Type The third classification is flooded type and dry type. Evaporator is said to be flooded type if liquid refrigerant covers the entire heat transfer surface. This type of evaporator uses a float type of expansion valve. An evaporator is called dry type when a portion of the evaporator is used for superheating the refrigerant vapour after its evaporation. 23.2.Natural Convection type evaporator coils These are mainly used in domestic refrigerators and cold storages. When used in cold storages, long lengths of bare or finned pipes are mounted near the ceiling or along the high sidewalls of the cold storages. The refrigerant from expansion valve is fed to these tubes. The liquid refrigerant evaporates inside the tubes and cools the air whose density increases. The high-density air flows downwards through the product in the cold storage. The air becomes warm by the time it reaches the floor as heat is transferred from the product to air. Some free area like a passage is provided for warm air to rise up. The same passage is used for loading and unloading the product into the cold storage. The advantages of such natural convection coils are that the coil takes no floor space and it also requires low maintenance cost. It can operate for long Version 1 ME, IIT Kharagpur 3
  • 4. periods without defrosting the ice formed on it and it does not require special skill to fabricate it. Defrosting can be done easily (e.g. by scraping) even when the plant is running. These are usually welded at site. However, the disadvantage is that natural convection heat transfer coefficient is very small hence very long lengths are required which may cause excessive refrigerant side pressure drops unless parallel paths are used. The large length requires a larger quantity of refrigerant than the forced convection coils. The large quantity of refrigerant increases the time required for defrosting, since before the defrosting can start all the liquid refrigerant has to be pumped out of the evaporator tubes. The pressure balancing also takes long time if the system trips or is to be restarted after load shedding. Natural convection coils are very useful when low air velocities and minimum dehumidification of the product is required. Household refrigerators, display cases, walk-in-coolers, reach-in refrigerators and obviously large cold storages are few of its applications. Sufficient space should be provided between the evaporator and ceiling to permit the air circulation over the top of the coil. Baffles are provided to separate the warm air and cold air plumes. Single ceiling mounted is used for rooms of width less than 2.5 m. For rooms with larger widths more evaporator coils are used. The refrigerant tubes are made of steel or copper. Steel tubes are used for ammonia and in large capacity systems. 23.3.Flooded Evaporator This is typically used in large ammonia systems. The refrigerant enters a surge drum through a float type expansion valve. The compressor directly draws the flash vapour formed during expansion. This vapour does not take part in refrigeration hence its removal makes the evaporator more compact and pressured drop due to this is also avoided. The liquid refrigerant enters the evaporator from the bottom of the surge drum. This boils inside the tubes as heat is absorbed. The mixture of liquid and vapour bubbles rises up along the evaporator tubes. The vapour is separated as it enters the surge drum. The remaining unevaporated liquid circulates again in the tubes along with the constant supply of liquid refrigerant from the expansion valve. The mass flow rate in the evaporator tubes is m.f where is the mass flow rate through the expansion valve and to the compressor. The term f is called recirculation factor. Let x m 4 be the quality of mixture after the expansion valve and x be the quality of mixture after boiling in the tubes as shown in Figure 23.1. In steady state mass flow rate from expansion valve is same as the mass flow rate to the compressor hence mass conservation gives .. 4 mm.f.xm.x =+ (23.1) x )x1( f 4− =∴ (23.2) Version 1 ME, IIT Kharagpur 4
  • 5. For x4 = x = 0.25, for example, the circulation factor is 3, that is mass flow rate through the evaporator is three times that through the compressor. Since, liquid refrigerant is in contact with whole of evaporator surface, the refrigerant side heat transfer coefficient will be very high. Sometimes a liquid refrigerant pump may also be used to further increase the heat transfer coefficient. The lubricating oil tends to accumulate in the flooded evaporator hence an effective oil separator must be used immediately after the compressor. Flooded type evaporator Surge tank Float valve To compressor f.m m m (x4) (x) f.m Fig.23.1. Schematic of a flooded evaporator Version 1 ME, IIT Kharagpur 5
  • 6. 23.4. Shell-and-Tube Liquid Chillers The shell-and-tube type evaporators are very efficient and require minimum floor space and headspace. These are easy to maintain, hence they are very widely used in medium to large capacity refrigeration systems. The shell-and-tube evaporators can be either dry type or flooded type. As the name implies, a shell-and-tube evaporator consists of a shell and a large number of straight tubes arranged parallel to each other. In dry expansion type, the refrigerant flows through the tubes while in flooded type the refrigerant is in the shell. A pump circulates the chilled water or brine. The shell diameters range from 150 mm to 1.5 m. The number of tubes may be less than 50 to several thousands and length may be between 1.5 m to 6 m. Steel tubes are used with ammonia while copper tubes are used with freons. Ammonia has a very high heat transfer coefficient while freons have rather poor heat transfer coefficient hence fins are used on the refrigerant side. Dry expansion type uses fins inside the tubes while flooded type uses fins outside the tube. Dry-expansion type require less charge of refrigerant and have positive lubricating oil return. These are used for small and medium capacity refrigeration plants with capacity ranging from 2 TR to 350 TR. The flooded type evaporators are available in larger capacities ranging from 10 TR to thousands of TR. 23.4.1 Flooded Type Shell-and-Tube Evaporator Figure 23.2 shows a flooded type of shell and tube type liquid chiller where the liquid (usually brine or water) to be chilled flows through the tubes in double pass just like that in shell and tube condenser. The refrigerant is fed through a float valve, which maintains a constant level of liquid refrigerant in the shell. The shell is not filled entirely with tubes as shown in the end view of Fig. 27.2. This is done to maintain liquid refrigerant level below the top of the shell so that liquid droplets settle down due to gravity and are not carried by the vapour leaving the shell. If the shell is completely filled with tubes, then a surge drum is provided after the evaporator to collect the liquid refrigerant. Shell-and-tube evaporators can be either single pass type or multipass type. In multipass type, the chilled liquid changes direction in the heads. Shell- and-tube evaporators are available in vertical design also. Compared to horizontal type, vertical shell-and-tube type evaporators require less floor area. The chilled water enters from the top and flows downwards due to gravity and is then taken to a pump, which circulates it to the refrigeration load. At the inlet to tubes at the top a special arrangement introduces swirling action to increase the heat transfer coefficient. Version 1 ME, IIT Kharagpur 6
  • 7. Refrigerant in Refrigerant out Water in Water out Fig.23.2: Schematic of a flooded type shell-and-tube evaporator 23.4.2. Direct expansion type, Shell-and-Tube Evaporator Figure 23.3 shows a liquid chiller with refrigerant flowing through the tubes and water flowing through the shell. A thermostatic expansion valve feeds the refrigerant into the tubes through the cover on the left. It may flow in several passes through the dividers in the covers of the shell on either side. The liquid to be chilled flows through the shell around the baffles. The presence of baffles turns the flow around creating some turbulence thereby increasing the heat transfer coefficient. Baffles also prevent the short-circuiting of the fluid flowing in the shell. This evaporator is of dry type since some of the tubes superheat the vapour. To maintain the chilled liquid velocity so as to obtain good heat transfer coefficient, the length and the spacing of segmental baffles is varied. Widely spaced baffles are used when the flow rate is high or the liquid viscosity is high. The number of passes on the refrigerant side are decided by the partitions on the heads on the two sides of the heat exchanger. Some times more than one circuit is also provided. Changing the heads can change the number of passes. It depends upon the chiller load and the refrigerant velocity to be maintained in the heat exchanger. 23.5.Shell-and-Coil type evaporator These are of smaller capacity than the shell and tube chillers. These are made of one or more spiral shaped bare tube coils enclosed in a welded steel shell. It is usually dry-expansion type with the refrigerant flowing in the tube and chilled liquid in the shell. In some cases the chiller operates in flooded mode also with refrigerant in the shell and chilled water flowing thorough the spiral tube. The water in the shell gives a large amount of thermal storage capacity called hold-up Version 1 ME, IIT Kharagpur 7
  • 8. capacity. This type is good for small but highly infrequent peak loads. It is used for cooling drinking water in stainless steel tanks to maintain sanitary conditions. It is also used in bakeries and photographic laboratories. When the refrigerant is in the shell that is in flooded mode it is called instantaneous liquid chiller. This type does not have thermal storage capacity, the liquid must be instantaneously chilled whenever required. In the event of freeze up the water freezes in the tube, which causes bursting of the tubes since water expands upon freezing. When water is in the shell there is enough space for expansion of water if the freezing occurs. The flooded types are not recommended for any application where the temperature of chilled liquid may be below 3o C. Water inlet Water outlet Refrigerant inlet Refrigerant outlet Baffles Fig.23.3: Schematic of a direct expansion type, Shell-and-Tube evaporator 23.6.Double pipe type evaporator This consists of two concentric tubes, the refrigerant flows through the annular passage while the liquid being chilled flows through the inner tube in counter flow. One design is shown in Fig. 23.4 in which the outer horizontal tubes are welded to vertical header tubes on either side. The inner tubes pass through the headers and are connected together by 180o bends. The refrigerant side is welded hence there is minimum possibility of leakage of refrigerant. These may Version 1 ME, IIT Kharagpur 8
  • 9. be used in flooded as well as dry mode. This requires more space than other designs. Shorter tubes and counter flow gives good heat transfer coefficient. It has to be insulated from outside since the refrigerant flows in the outer annulus which may be exposed to surroundings if insulation is not provided. Refrigerant outlet Water inlet Water outlet Refrigerant inlet Fig.23.4: Schematic of a double pipe type evaporator 23.7.Baudelot type evaporators This type of evaporator consists of a large number of horizontal pipes stacked one on top of other and connected together to by headers to make single or multiple circuits. The refrigerant is circulated inside the tubes either in flooded or dry mode. The liquid to be chilled flows in a thin layer over the outer surface of the tubes. The liquid flows down by gravity from distributor pipe located on top of the horizontal tubes as shown in Figure 23.5. The liquid to be chilled is open to atmosphere, that is, it is at atmospheric pressure and its aeration may take place during cooling. This is widely used for cooling milk, wine and for chilling water for carbonation in bottling plants. The liquid can be chilled very close to its freezing temperature since freezing outside the tubes will not damage the tubes. Another advantage is that the refrigerant circuit can be split into several parts, which Version 1 ME, IIT Kharagpur 9
  • 10. permit a part of the cooling done by cold water and then chilling by the refrigerant. Refrigerant outlet Refrigerant inlet Milk inlet Milk outlet Distributor Header Fig.23.5: Schematic of a Baudelot type evaporator for chilling of milk 23.8. Direct expansion fin-and-tube type These evaporators are used for cooling and dehumidifying the air directly by the refrigerant flowing in the tubes. Similar to fin-and-tube type condensers, these evaporator consists of coils placed in a number of rows with fins mounted on it to increase the heat transfer area. Various fin arrangements are used. Tubes with individual spiral straight fins or crimpled fins welded to it are used in some applications like ammonia. Plate fins accommodating a number of rows are used in air conditioning applications with ammonia as well as synthetic refrigerants such as fluorocarbon based refrigerants. The liquid refrigerant enters from top through a thermostatic expansion valve as shown in Fig. 23.6. This arrangement makes the oil return to compressor better rather than feeding refrigerant from the bottom of the coil. When evaporator is close to the compressor, a direct expansion coil is used Version 1 ME, IIT Kharagpur 10
  • 11. since the refrigerant lines are short, refrigerant leakage will be less and pressure drop is small. If the air-cooling is required away from the compressor, it is preferable to chill water and pump it to air-cooling coil to reduce the possibility of refrigerant leakage and excessive refrigerant pressure drop, which reduces the COP. Refrigerant inlet Refrigerant outlet Fig.23.6: Schematic of a direct expansion fin-and-tube type The fin spacing is kept large for larger tubes and small for smaller tubes. 50 to 500 fins per meter length of the tube are used in heat exchangers. In evaporators, the atmospheric water vapour condenses on the fins and tubes when the metal temperature is lower than dew point temperature. On the other hand frost may form on the tubes if the surface temperature is less than 0o C. Hence for low temperature coils a wide spacing with about 80 to 200 fins per m is used to avoid restriction of flow passage due to frost formation. In air-conditioning applications a typical fin spacing of 1.8 mm is used. Addition of fins beyond a certain value will not increase the capacity of evaporator by restricting the airflow. The frost layer has a poor thermal conductivity hence it decreases the overall heat transfer coefficient apart from restricting the flow. Therefore, for applications in freezers below 0o C, frequent defrosting of the evaporator is required. 23.9.Plate Surface Evaporators These are also called bonded plate or roll-bond type evaporators. Two flat sheets of metal (usually aluminum) are embossed in such a manner that when these are welded together, the embossed portion of the two plates makes a passage for refrigerant to flow. This type is used in household refrigerators. Figure 23.7 shows the schematic of a roll-bond type evaporator. Version 1 ME, IIT Kharagpur 11
  • 12. In another type of plate surface evaporator, a serpentine tube is placed between two metal plates such that plates press on to the tube. The edges of the plates are welded together. The space between the plates is either filled with a eutectic solution or evacuated. The vacuum between the plates and atmospheric pressure outside, presses the plates on to the refrigerant carrying tubes making a very good contact between them. If eutectic solution is filled into the void space, this also makes a good thermal contact between refrigerant carrying tubes and the plates. Further, it provides an additional thermal storage capacity during off- cycle and load shedding to maintain a uniform temperature. These evaporators are commonly used in refrigerated trucks. Figure 23.8 shows an embedded tube, plate surface evaporator. A A Section A-A Refrigerant in Refrigerant out Fig.23.7: Schematic of a roll-bond type evaporator AA Refrigerant in Refrigerant out Section A-A Version 1 ME, IIT Kharagpur 12Eutectic solution Fig.23.8: Schematic of an embedded tube, plate surface evaporator
  • 13. 23.10. Plate type evaporators: Plate type evaporators are used when a close temperature approach (0.5 K or less) between the boiling refrigerant and the fluid being chilled is required. These evaporators are widely used in dairy plants for chilling milk, in breweries for chilling beer. These evaporators consist of a series of plates (normally made of stainless steel) between which alternately the milk or beer to be cooled and refrigerant flow in counterflow direction. The overall heat transfer coefficient of these plate type evaporators is very high (as high as 4500 W/m2 K in case of ammonia/water and 3000 W/m2 .K in case of R 22/water). In addition they also require very less refrigerant inventory for the same capacity (about 10 percent or even less than that of shell-and-tube type evaporators). Another important advantage when used in dairy plants and breweries is that, it is very easy to clean the evaporator and assemble it back as and when required. The capacity can be increased or decreased very easily by adding or removing plates. Hence these evaporators are finding widespread use in a variety of applications. Figure 23.9 shows the schematic of a plate type evaporator. Fig.23.9: Schematic of a plate type evaporator Version 1 ME, IIT Kharagpur 13
  • 14. 23.11. Thermal design of evaporators: Compared to the design of refrigerant condensers, the design of refrigerant evaporators is more complex. The complexity arises due to the following factors: a) On the refrigerant side, the heat transfer coefficient varies widely when evaporation takes place in tubes due to changing flow regimes. Accurate estimation of heat transfer coefficient is thus difficult b) On the external fluid side, if the external fluid is air (as in air conditioning and cold storage applications), in addition to sensible heat transfer, latent heat transfer also takes place as moisture in air may condense or even freeze on the evaporator surface. The evaporator surface may be partly dry and partly wet, depending upon the operating conditions. Hence, mass transfer has to be considered in the design. If frost formation due to freezing of moisture takes place, then heat transfer resistance varies continuously with time. c) The lubricating oil gets separated in the evaporator tubes due to low miscibility of oil at evaporator temperature and pressure. The separation of oil affects both heat transfer and pressure drop characteristics. A minimum refrigerant velocity must be provided for oil carry over in direct expansion type evaporators. d) Compared to condenser, refrigerant pressure drop in evaporator is more critical as it has significant influence on the performance of the refrigeration system. Hence, multiple circuits may have to be used in large systems to reduce pressure drops. Refrigerant velocity has to be optimized taking pressure drop and oil return characteristics into account. e) Under part-load applications, there is a possibility of evaporator flooding and compressor slugging. This aspect has to be considered at the time of evaporator design. Estimation of heat transfer area and overall heat transfer coefficients For plate fin type evaporators, the expressions of various heat transfer areas are similar to those given for the air-cooled condensers. The expression for overall heat transfer coefficient is also similar to that of condenser as long as no phase change (e.g. moisture condensation or freezing) takes place. However, as mentioned in air-cooled evaporators the possibility of moisture condensing/freezing on the evaporator surface must be considered unlike in condensers where the heat transfer on airside is only sensible. This requires simultaneous solution of heat and mass transfer equations on the airside to arrive at expressions for overall heat transfer coefficient and mean temperature difference. The efficiency of the fins will also be affected by the presence of condensed layer of water or a frozen layer of ice. Expressions have been derived for overall heat transfer coefficient, mean temperature difference and fin efficiency of fin-and-tube type evaporators in which air undergoes cooling and Version 1 ME, IIT Kharagpur 14
  • 15. dehumidification. The analysis of cooling and dehumidification coils requires knowledge of psychrometry and is obviously much more complicated compared to evaporators in which the external fluid does not undergo phase change. In this lecture, only the evaporators wherein the external fluid does not undergo any phase change are considered. Readers should refer to advanced books on refrigeration for the design aspects of cooling and dehumidifying coils. Estimation of heat transfer coefficients: a) Air side heat transfer coefficients in fin-and-tube type evaporators: If air undergoes only sensible cooling as it flows over the evaporator surface (i.e., dry evaporator), then the correlations presented for air cooled condensers for heat transfer coefficients on finned (e.g. Kays & London correlation) and bare tube surface (e.g. Grimson’s correlation) can be used for air cooled evaporator also. However, if air undergoes cooling and dehumidification, then analysis will be different and correlations will also be different. These aspects will be discussed in a later chapter. b) Liquid side heat transfer coefficients: Liquid flowing in tubes: When liquids such as water, brine, milk etc. flow through tubes without undergoing any phase changes, the correlations presented earlier for condensers (e.g. Dittus-Boelter, Sieder-Tate) can be used for evaporator also. Liquid flowing in a shell: In direct expansion type, shell-and-tube evaporators refrigerant flows through the tubes, while water or other liquids flow through the shell. Analytical prediction of single phase heat transfer coefficient on shell side is very complex due to the complex fluid flow pattern in the presence of tubes and baffles. The heat transfer coefficient and pressure drop depends not only on the fluid flow rate and its properties, but also on the arrangement of tubes and baffles in the shell. Several correlations have been suggested to estimate heat transfer coefficients and pressure drops on shell side. A typical correlation suggested by Emerson is given below: 14.0 w 3.06.0 d f PrReC k hd Nu ⎟⎟ ⎠ ⎞ ⎜⎜ ⎝ ⎛ μ μ == (23.3) where constant C depends on the geometry, i.e, on the arrangement of the tubes, baffles etc. Version 1 ME, IIT Kharagpur 15
  • 16. In the above expression the Reynolds number Re s defined as:d i μ = Gd Red (23.4) where G is the mass velocity which is equal to the mass flow rate divided by the characteristic flow area (kg/m2 .s). From the expression for Nusselt number, it can be seen that the heat transfer coefficient is proportional to the 0.6 power of the flow rate as compared to 0.8 power for flow through tubes. The pressure drop of liquid flowing through the shell is also difficult to predict analytically. Normally the pressure drop on shell side is obtained from experimental measurements and is provided in the form of tables and charts for a particular type of shell-and-tube heat exchanger. c) Boiling Heat Transfer Coefficients: Pool boiling vs flow boiling: In evaporators boiling of refrigerant may take place outside tubes or inside tubes. When boiling takes place outside the tubes it is called as pool boiling. In pool boiling it is assumed that the tube or the heat transfer surface is immersed in a pool of liquid, which is at its saturation temperature. Figure 23.10 shows a typical boiling curve, which shows the variation of surface heat flux with temperature difference between the surface and the saturation temperature for different regimes. For a small temperature difference, the heat transfer from the surface is by free convection (regime 1). As the temperature difference increases, bubbles start to form at selected nucleation sites. The bubbles grow in size as heat is transferred and the evaporation of liquid occurs. After achieving a critical diameter depending upon the surface tension and other factors, the bubbles get detached from the surface and rise to the free surface where the vapour inside the bubbles is released. During the detachment process, the surrounding liquid rushes towards the void created and also during the bubble motion upwards convection heat transfer increases from its free convection value at smaller temperature differences. This region is known as individual bubble regime (regime 2). As the temperature difference increase further, more and more bubbles are formed and it is the columns of bubbles, which rise up increasing the heat transfer drastically. This regime is known as column bubble regime (regime 3). As the temperature difference increases further, more and more bubbles are formed, and columns of bubbles rise to the free surface. The heat transfer rate increases rapidly. As the bubble columns move upwards they entrain some liquid also that rises upwards to the free surface. The vapour in the bubbles escapes at the free surface but the liquid returns to the bottom because of its lower temperature and higher density. A given surface can accommodate only a few such rising columns of bubbles and descending columns of relatively colder Version 1 ME, IIT Kharagpur 16
  • 17. liquid. Hence, the heat transfer rate cannot increase beyond a certain value. It becomes maximum at some temperature difference. The maximum heat transfer rate is called critical heat transfer rate. If temperature difference is increased beyond this value, then a blanket of film forms around the heat transfer surface. This vapour film offers conduction thermal resistance; as a result the heat transfer rate decreases. The film however is unstable and may break at times. This regime is called unstable film regime (regime 4). If temperature difference is increased further it becomes so high that radiation heat transfer becomes very important and heat transfer rate increases because of radiation component. This regime is called stable film boiling regime (regime 5). After this, due to the high surface temperature, radiation effects become important (regime 6). As the temperature difference is increased, the temperature of the surface tw continues to increase since conduction thermal resistance of the film becomes larger as the film thickness increases. All the heat from the surface cannot be transferred across the film and surface temperature increases. Ultimately the temperature may approach the melting point of the metal and severe accident may occur (if these are the tubes of nuclear power plant). This point is referred to as burnout point. (Ts-Tf) q 1 2 3 4 5 6 Critical heat flux Fig.23.10: A typical pool boiling curve showing different regimes, 1 to 6 Version 1 ME, IIT Kharagpur 17
  • 18. Boiling inside tubes is called as flow boiling. Flow boiling consists of nucleate boiling as well as convective heat transfer. As the liquid evaporates, more vapour is formed which increases the average velocity and the convective heat transfer rate. The flow pattern changes continuously as boiling takes place along the tube. For example in a horizontal tube, the flow can be stratified flow, wavy flow, slug flow, annular flow, mist flow etc. The flow pattern will be different if it takes place in an inclined or vertical tube. The heat transfer coefficient depends upon fraction of vapour present and parameters of forced convection heat transfer. In general, prediction of boiling heat transfer coefficients during flow boiling is much more complex than pool boiling. However, a large number of empirical correlations have been developed over the years to predict boiling heat transfer coefficients for both pool as well as flow boiling conditions. The following are some of the well-known correlations: Nucleate Pool Boiling Normally evaporators are designed to operate in nucleate pool boiling regime as the heat transfer coefficients obtained in this regime are stable and are very high. Various studies show that in nucleate pool boiling region, the heat transfer coefficient is proportional to the 2 or 3 power of temperature difference between the surface and the boiling fluid, i.e., 3to2 fsnb )TT(Ch −= (23.5) the value of C depends upon type of the surface etc. The exponent can be as high as 25 on specially treated surfaces for enhancement of boiling. Rohsenow’s Correlation for nucleate pool boiling: This correlation is applicable to clean surfaces and is relatively independent of shape and orientation of the surface. s f 33.0 gffgf sf fg xf Pr )(gh A/Q C h TC ⎥ ⎥ ⎦ ⎤ ⎢ ⎢ ⎣ ⎡ ρ−ρ σ μ = Δ (23.6) where: = Specific heat of liquidCf ΔTx = Temperature difference between surface and fluid hfg = Latent heat of vaporization σ = Surface Tension Csf = constant which depends on the surface-fluid combination, e.g. 0.013 for halocarbons boiling on copper surface Q/A = heat flux = Viscosity of fluidμf , ρ = Density of saturated liquid and saturated vapour, respectivelyρf g Prf = Prandtl number of saturated liquid s = constant, 1 for water and 1.7 for halocarbons Version 1 ME, IIT Kharagpur 18
  • 19. All the fluid properties are calculated at saturation temperature corresponding to the local pressure. Forced Convection Boiling inside tubes: Rohsenow and Griffith suggested that flow boiling in tubes be analyzed as a combination of pool boiling and forced convection. The total heat flux (qtotal) is the sum of heat flux due to nucleate pool boiling (q ) and forced convection (qnb fc), i.e., fcnbtotal qqq += (23.7) Heat flux due to nucleate pool boiling (qnb) is calculated by using nucleate pool boiling correlations and heat flux due to forced convection (qfc) can be calculated by using standard forced convection correlations, such as Dittus- Boelter correlation. Some of the other correlations suggested for flow boiling are given below: (a) Bo Pierre’s Correlation : This correlation gives average heat transfer coefficients and is valid for inlet quality xinlet ≈ 0.1 to 0.16. ( ) 9.0xandnevaporatioincompletefor:KRe0009.0uN exit 2 1 f 2 ff <= ( ) nevaporatiocompletefor:KRe0082.0uN 2 1 f 2 ff = (23.8) In the above equations, Re and Nuf f are liquid Reynolds and Nusselt numbers, respectively. K is the load factor, defined as:f L hx K fg f Δ = (23.9) where L is the length of the tube. (b) Chaddock-Brunemann’s Correlation: [ 6.067.0 tt 4 LTP )X/1(5.110.Boh91.1h += ] (23.10) )A/m(h A/Q NumberBoilingBo fg == ParameterMartinelliLockhart)/()/( x x1 X 1.0 gf 5.0 fg 9.0 tt −μμρρ⎟ ⎠ ⎞ ⎜ ⎝ ⎛ − = Version 1 ME, IIT Kharagpur 19
  • 20. (c) Jung and Radermacher Correlation: L1sa1TP hFhNh += (23.11) where hL is the single phase (liquid) heat transfer coefficient as predicted by Dittus-Boelter equation, and hsa is given by: 85.0 tt1 tt 33.028.0 tt1 tt 13.122.1 tt1 o 5.0 gf 533.0 f 581.0 f g 745.0 satf f sa )X/129.0(37.2F 5X1for:BoX1.00.2N 1Xfor:BoX4048N 35: )(g 2 0146.0bd Pr T bd . k q bd k 207h += ≤<−= ≤= =β ⎥ ⎥ ⎦ ⎤ ⎢ ⎢ ⎣ ⎡ ρ−ρ σ β= ⎟ ⎟ ⎠ ⎞ ⎜ ⎜ ⎝ ⎛ ρ ρ ⎟⎟ ⎠ ⎞ ⎜⎜ ⎝ ⎛ = −− (23.12) In nucleate boiling, the heat transfer coefficient is mainly dependent on the heat flux and is a very weak function of mass flux. However, in flow boiling the heat transfer coefficient depends mainly on mass flux and is a weak function of heat flux. Studies show that for boiling inside tubes, initially when the vapour fraction (quality) is low, then nucleate boiling is dominant and the heat transfer coefficient depends on heat flux. However, as the fluid flows through the tubes, the vapour fraction increases progressively due to heat transfer and when it exceeds a critical vapour fraction, convective boiling becomes dominant. As mentioned, in this region, the heat transfer coefficient depends mainly on the mass flux and is almost independent of heat flux. As a whole, the heat transfer coefficient due to boiling increases initially reaches a peak and then drops towards the end of the tube. Thus accurate modeling of evaporators requires estimation of heat transfer coefficient along the length taking into account the complex physics. Horizontal vs Vertical tubes: As mentioned before, boiling heat transfer coefficients in vertical columns will be different from that in a horizontal tube. In a vertical tube, due to hydrostatic head, the evaporation temperature increases, which in turn reduces the driving temperature difference, and hence, the heat transfer rate. Effect of oil in evaporator: Studies on R 12 evaporators show that the boiling heat transfer coefficient inside tubes increases initially with oil concentration upto a value of about 4 percent and then decreases. The initial increase is attributed to the greater wetting of the tube surface due to the presence of oil. The subsequent reduction is due to the rapid increase in viscosity of the refrigerant-oil mixture as oil is more viscous than refrigerant. For the estimation of heat transfer Version 1 ME, IIT Kharagpur 20
  • 21. coefficient, the presence of oil may be neglected as long as its concentration is low (less than 10 percent). 23.12. Enhancement of heat transfer coefficients: The overall heat transfer coefficient of a heat exchanger depends mainly on the component having the largest resistance to heat transfer. When air is used an external fluid, the heat transfer coefficient on air side is small, hence to obtain high overall heat transfer coefficient, the air side heat transfer is augmented by adding fins. When liquid water is used as the external fluid, then the heat transfer coefficient on water side will be high, when the flow is turbulent (which normally is the case). Hence to further improve overall heat transfer coefficient, it may become necessary to enhance heat transfer on the refrigerant side. This is especially the case with synthetic refrigerants. The enhancement of boiling heat transfer coefficient can be achieved in several ways such as: increasing the refrigerant velocity by using an external pump in flooded evaporators, by using integrally finned tubes, by using treated surfaces, by using turbulence promoters etc. These methods improve the refrigerant side heat transfer coefficient and hence the overall heat transfer coefficient significantly leading to compact and lightweight evaporators. However, it should be kept in mind that normally any heat transfer enhancement technique imposes penalty by means of increased pressure drop, hence it is essential to optimize the design so that the total cost is minimized. 23.13. Wilson’s plot: The concept of Wilson’s plot was introduced way back in 1915 by Wilson to determine individual heat transfer coefficients from the experimental data on heat transfer characteristics of heat exchangers. This is sometimes applied to determine the condensing or boiling heat transfer coefficients of condensers and evaporators respectively. For example, in a water-cooled condenser a number of tests are conducted by varying the flow rate of water and measuring the inlet and outlet water temperatures. The total heat transfer rate is determined from )LMTD(AU)tt(CmQ oowiwopww =−= (23.13) From measured temperatures, LMTD is calculated. From the heat transfer rate Q, area of the heat exchanger (Ao) and LMTD, the overall heat transfer coefficient for a given flow rate is calculated using Eqn.(23.13). Version 1 ME, IIT Kharagpur 21
  • 22. Then the overall heat transfer coefficient Uo is equated to the following equation (for clean tubes are clean with negligible scale formation) ow ioi i o ii o o h 1 k )d/d(lnr A A Ah A U 1 ++= (23.14) If the water temperature does not vary very significantly during these tests, then properties of water remain nearly constant. Since during these tests no changes are made on the refrigerant side, it can be assumed that the heat transfer resistance offered by the wall separating the two fluids and the heat transfer coefficient on refrigerant side (ho) remains constant for all values of water flow rates. Hence, the above equation can be written as: i 2 1 o h C C U 1 += (23.15) where C and C1 2 are empirical constants that depend on the specifications of the heat exchangers and operating conditions, and the expressions for these can be obtained by equating Eqns.(23.14) and (23.15). If flow on water side is turbulent and the variation in thermal properties are negligible, then the waterside heat transfer coefficient can be written as: 8.0 3i V.Ch = (23.16) Substituting the expression in Eqn.(23.15), we obtain: 8.0 4 1 o V C C U 1 += (23.17) vs 1/V0.8 Then a plot of 1/Uo will be a straight line as shown in Fig. 23.11. This plot is extrapolated to infinitely high velocity, i.e., where 1/V0.8 tends to zero. When 1/V0.8 tends to zero, from Eqn.(23.16) 1/hi also tends to zero. Hence, the intercept on the ordinate is C (=1/h + A r ln (d /d)/(A ko o i 0 i i w1 )). The thermal conduction resistance of the tube can be calculated and then the condensation heat transfer coefficient ho can be calculated. As shown in the figure the term A /(Ah) can also be obtained from the figure at any value of velocity.o i i It should be kept in mind that it is an approximation since drawing a straight line and extending it to meet y-axis means that condensation heat transfer remains constant as the velocity tends to infinity. Wilson plot can be applied to air-cooled condensers also. In this case as the heat transfer coefficient for air over finned surface varies as V 0.65 , hence in this case 1/Uo will have to be plotted versus V - 0.65 . Version 1 ME, IIT Kharagpur 22
  • 23. 1/V0.8 1/Uo (1/ho)+(do/di)riln(do/di)/kw (do/di)1/hi Fig.23.11: Concept of Wilson’s plot Questions and answers: 1. Which of the following statements are TRUE? a) In conventional refrigerators, the evaporators are kept at the top as these are natural convection type b) Natural convection type coils are useful when the latent loads are very high c) Defrosting of evaporators has to be done more frequently in natural convection type coils compared to forced convection evaporator coils d) Provision of sufficient free space is very important in natural convection type evaporator coils Ans.: a) and d) Version 1 ME, IIT Kharagpur 23
  • 24. 2. Which of the following statements are TRUE? a) Flooded type evaporators are very efficient as the heat transfer coefficient on refrigerant side is very large b) In flooded type evaporators, the refrigerant evaporation rate is equal to the refrigerant mass flow rate c) An oil separator is always required in flooded evaporators as refrigerant tends to get collected in the evaporator d) All of the above Ans.: a) and c) 3. Which of the following statements are TRUE? a) Shell-and-tube evaporators are available in small to very large capacities b) In dry expansion type evaporator, refrigerant flows through the shell while the external fluid flows through the tubes c) Normally float valves are used expansion devices for flooded type evaporators d) In shell-and-coil type evaporators, thermal storage can be obtained by having refrigerant on the shell side Ans.: a) and c) 4. Which of the following statements are TRUE? a) In direct expansion, fin-and-tube type evaporators, the oil return to compressor is better if refrigerant enters at the bottom of the evaporator and leaves from the top b) For low temperature applications, the fin spacing of evaporator is kept larger to take care of the frost formation c) Double pipe type evaporators are used when close temperature approach is required d) Plate type evaporators are used when close temperature approach is required Ans.: b) and d) 5. Thermal design of evaporators is very complex due to: a) Continuous variation of heat transfer coefficient along the length b) Possibility of latent heat transfer on the external fluid side also c) Presence of lubricating oil affects heat transfer and pressure drop d) All of the above Ans.: d) Version 1 ME, IIT Kharagpur 24
  • 25. 6. Which of the following statements are TRUE? a) In evaporators using air as an external fluid, fins are frequently required on the refrigerant side b) In evaporators using water as an external fluid, fins may be required on the refrigerant side to enhance heat transfer c) Flooded type evaporators yield higher heat transfer coefficients compared to direct expansion type evaporators d) In general heat transfer enhancement techniques yield more compact heat exchangers, but may also increase pressure drop Ans.: b), c) and d) 7. Air enters a direct expansion type, fin-and-tube evaporator at a temperature of 17o o C and leaves the evaporator at 11 C. The evaporator operates at a constant temperature of 7o 2 C and has total refrigerant side area of 12 m , while the bare tube and finned areas on airside are 10 m2 2 and 212 m , respectively. Find the refrigeration capacity of the evaporator assuming only sensible heat transfer on airside and counterflow type arrangement. Neglect fouling and resistance offered by the tube wall. The fin effectiveness for airside is 0.75. The average heat transfer coefficient on refrigerant and airside are 1700 W/m2 2 .K and 34 W/m .K, respectively. Ans.: Neglecting fouling and resistance of the tube wall, the value of ‘UA’ of evaporator is given by: iiobff Ah 1 )]AA(h[ 1 UA 1 + +η = Substituting the values of airside and refrigerant heat transfer coefficients (ho and h), bare tube (A ), finned surface (Ai b f) and refrigerant side areas and fin efficiency (ηf = 0.75) in the above expression, we obtain: UA = 4483 W/K From the values of airside and evaporator temperatures, the LMTD of the evaporator is given by: C55.6 711 717 ln )1117( LMTD o = ⎟ ⎠ ⎞ ⎜ ⎝ ⎛ − − − = Hence, refrigeration capacity, Q = UA.LMTD = 29364 W = 29.364 kW (Ans.)e Version 1 ME, IIT Kharagpur 25
  • 26. 8. The following are the values measured on a shell-and-tube ammonia condenser: Velocity of water flowing through the tubes, V (m/s) 1.22 0.61 Overall heat transfer coefficient, U (W/m2 .K) 2300 1570o Water flowed inside the tubes while refrigerant condensed outside the tubes. The tubes were 51 mm OD and 46 mm ID and had a conductivity of 60 W/m.K. Using the concept of Wilson’s plot, determine the condensing heat transfer coefficient. What is the value of overall heat transfer coefficient when the velocity of water is 0.244 m/s? Ans.: From the data given in the table, the following straight line equation can be obtained: 8.0 4 1 o V C C U 1 += The values of C and C for the given data are found to be:1 4 C1 = 1.605 x 10-4 m2 -4 .K/W and C4 = 3.223 x 10 m1.2 .K/W The constant C is equal to:1 4 ow ioo 1 10x605.1 h 1 k )r/r(lnr C − =+= and rSubstituting the values of internal and external radii (ri o) and the value of thermal conductivity of the tube kW, we obtain the value of external heat transfer coefficient (condensation heat transfer coefficient, h ) as:o ho = 8572.9 W/m2 .K (Ans.) The value of overall heat transfer coefficient Uo when the velocity of water is 0.244 m/s is given by: 3 8.0 4 4 8.0 4 1 o 10x1567.1 244.0 10x223.3 10x605.1 V C C U 1 − − − =+=+= ⇒ Uo = 864.5 W/m2 .K (Ans.) Version 1 ME, IIT Kharagpur 26