DTU Compute, Technical University of Denmark 07 August 2015
ARX MODELS FOR BUILDING ENERGY
PERFORMANCE ASSESSMENT BASED ON
IN-SITU MEASUREMENTS
IEA EBC Annex 71
Common Exercise 1, Subtask 3
Physical Parameter Identification
Christoffer Rasmussen (chrras@dtu.dk), Peder Bacher, Henrik Madsen
DTU Compute, Technical University of Denmark 07 August 2015
MODEL
ARX model as used in Annex 58, Subtask 3, Part 2
• Output: Indoor temperature
• Input: Heating power
Outdoor temperature
Solar radiation
Annex 71, CE1 ST3 – October 23-25, 20172
𝜙 𝐵 𝑇$
%
= 𝜔( 𝐵 Φ$
(
+ 𝜔+ 𝐵 𝑇$
+
+ 𝜔,-. 𝐵 𝑄$
,-.
+ 𝜖$
DTU Compute, Technical University of Denmark 07 August 2015
DATA REQUIREMENTS FOR THE GOOD FIT
High signal-to-noise ratio
– Daily mean outdoor temperature below 5 ºC
Minimal disturbances in data from occupants
– Out-of-the-house vacation:
• No disturbances
• Limited periods throughout the year.
– Out-of-the-house weekdays:
• No disturbances
• Only applicable if occupants actually leave the house regularly for several hours
– Night-time:
• Few disturbances
• New data accessible every night (normally)
Annex 71, CE1 ST3 – October 23-25, 20173
DTU Compute, Technical University of Denmark 07 August 2015
MODEL
ARX model as used in Annex 58, Subtask 3, Part 2
ARX model as used in Annex 71, Common Exercise 1, Subtask 3
• Output: Indoor temperature
• Input: Heating power
Outdoor temperature
• Data: Only night-time
• Time resolution: 10 minutes
Annex 71, CE1 ST3 – October 23-25, 20174
𝜙 𝐵 𝑇$
%
= 𝜔( 𝐵 Φ$
(
+ 𝜔+ 𝐵 𝑇$
+
+ 𝜔,-. 𝐵 𝑄$
,-.
+ 𝜖$
𝜙 𝐵 𝑇$
%
= 𝜔( 𝐵 Φ$
(
+ 𝜔+ 𝐵 𝑇$
+
+ 𝜖$
DTU Compute, Technical University of Denmark 07 August 2015
DOWN-WEIGHTING DAY-TIME DATA
Annex 71, CE1 ST3 – October 23-25, 20175
051015
Heat consumption, day and night
Energy[kW]
18:00 00:00 06:00 12:00 18:00 00:00 06:00
Day (weight = 0)
Night (weight = 1)
DTU Compute, Technical University of Denmark 07 August 2015
ACF AND CCF ISSUES
N Time Residual
⋮ ⋮ ⋮
35 2014/01/01 06:50 +0.05
36 2014/01/01 07:00 –0.02
37 2014/01/01 19:30 –0.01
38 2014/01/01 19:40 +0.04
⋮ ⋮ ⋮
Annex 71, CE1 ST3 – October 23-25, 20176
𝛾33 𝜏 = Cov 𝑋 𝑡 , 𝑋 𝑡 + 𝜏
𝜌33 𝜏 =
𝛾33 𝜏
𝜎3
=
DTU Compute, Technical University of Denmark 07 August 2015
SEPARATING SPACE HEATING & DHW
0.00 0.01 0.02 0.03 0.04 0.05 0.06 0.07
Summer data
Water consumption [m3
]
Heat[kW]
Hot water and space heating
Hot water
Space heating
0510152025
0.00 0.01 0.02 0.03 0.04 0.05 0.06 0.07
All data
Water consumption [m3
]
0510152025 Annex 71, CE1 ST3 – October 23-25, 20177
DTU Compute, Technical University of Denmark 07 August 2015
SEPARATING SPACE HEATING & DHW
Annex 71, CE1 ST3 – October 23-25, 20178
0515
Energy[kW]
00:00 03:00 06:00 09:00 12:00 15:00 18:00 21:00 24:00
Hot water production
Space heating
0.000.020.04
Waterconsump.[m3
]
00:00 03:00 06:00 09:00 12:00 15:00 18:00 21:00 24:00
20.021.5
Indoortemp.[°C]
00:00 03:00 06:00 09:00 12:00 15:00 18:00 21:00 24:00
DTU Compute, Technical University of Denmark 07 August 2015
CASE
DIFFERENT OCCUPATION PERIODS
Annex 71, CE1 ST3 – October 23-25, 201712
Different occupation periods
Sample period [nights]
HLC[W/K]
335075100125150
1 3 5 7 9 11 13 15 17
Estimate (occupation period 2)
95 % CI
Assumed 83.4 (±16.3) W/K
DTU Compute, Technical University of Denmark 07 August 2015
CASE
DIFFERENT OCCUPATION PERIODS
Annex 71, CE1 ST3 – October 23-25, 201713
Different occupation periods
Sample period [nights]
HLC[W/K]
335075100125150
1 3 5 7 9 11 13 15 17
Estimate (occupation period 1)
Estimate (occupation period 2)
95 % CI
Assumed 83.4 (±16.3) W/K
63.2 (±5.1) W/K
DTU Compute, Technical University of Denmark 07 August 2015
RESIDUAL ANALYSIS
Annex 71, CE1 ST3 – October 23-25, 201714
0 10 20 30 40
−0.050.05
ACF (Residuals)
ACF
0 10 20 30 40
−0.060.04
CCF (Residuals & Outdoor temperature)
CCF
0 10 20 30 40
−0.060.04
CCF (Residuals & Heating power)
Lags
CCF
DTU Compute, Technical University of Denmark 07 August 2015
RESIDUAL ANALYSIS
Annex 71, CE1 ST3 – October 23-25, 201715
20.521.522.523.5
One−step predictions
Indoortemp.(°C)
Measured
Predicted
−0.050.000.05
Residuals
ε
Night 1 Night 2 Night 3 Night 4 Night 5 Night 6 Night 7 Night 8 Night 9 Night 10 Night 11 Night 12 Night 13 Night 14 Night 15 Night 16
DTU Compute, Technical University of Denmark 07 August 2015
RESIDUAL ANALYSIS
Annex 71, CE1 ST3 – October 23-25, 201716
0.0 0.1 0.2 0.3 0.4 0.5
0.00.20.40.60.81.0
Frequency
Cumulative periodogram
−3 −2 −1 0 1 2 3
−0.050.000.05
Q−Q plot
Theoretical quantiles
Samplequantiles
Histogram
Sample quantiles
Density
−0.10 −0.05 0.00 0.05 0.10
051015
DTU Compute, Technical University of Denmark 07 August 2015
CONCLUSIONS
Data
– Obtain good time series where input and output is well-exercised.
– Prober filtering of domestic hot water consumption.
– Get representative indoor temperatures.
– Model internal heat gains from occupants. E.g. through CO₂ measurements.
Assumed and estimated HLC
– Air leakages.
– Thermal bridges.
– All heat is assumed to be transferred to the air.
– Heat capacity of building not taken into account
Annex 71, CE1 ST3 – October 23-25, 201717
DTU Compute, Technical University of Denmark 07 August 2015
PERSPECTIVE
Evaluation of building performance and occupants effect on energy consumption
1. Apply occupant models to estimate if apartment is empty or not.
2. Use periods where apartment is un-occupied and of occupants are sleeping, instead of
night-time only, to include solar radiation in model.
3. Use fitted model on all data and estimate the effect of the occupants on the energy
consumption.
Annex 71, CE1 ST3 – October 23-25, 201718
DTU Compute, Technical University of Denmark 07 August 2015
MODEL MATRIX
Annex 71, CE1 ST3 – October 23-25, 201719
HLC estimate and
standard deviation
obtained from best
model:
63.2 (±5.1) W/K
10 min data of:
Indoor temperature
Outdoor temperature
Heating power
DTU Compute, Technical University of Denmark 07 August 2015
MODEL MATRIX
Annex 71, CE1 ST3 – October 23-25, 201720
HLC estimate and
standard deviation
obtained from best
model:
63.2 (±5.1) W/K
10 min data of:
Indoor temperature
Outdoor temperature
Heating power

More Related Content

PDF
Technology-based Approach for the Impacts of Global Warming on the Energy Use...
PDF
Semester Project 4: Projection of Expansion: Assens to Ejby
PPTX
Energy analysis using computer aided design
PPT
1.3 notes
PPTX
Building Science-Heat exchange analysis of residential building
PDF
dissertationpresentation
PDF
Paper id 71201998
PPTX
Electricity Net Generation
Technology-based Approach for the Impacts of Global Warming on the Energy Use...
Semester Project 4: Projection of Expansion: Assens to Ejby
Energy analysis using computer aided design
1.3 notes
Building Science-Heat exchange analysis of residential building
dissertationpresentation
Paper id 71201998
Electricity Net Generation

What's hot (20)

PDF
Interference effects for inline chmineys
PDF
Semester Project 2: Combined Heat & Power Plants - Fynsværket, Block 7
PPTX
Lakeshore Center Heat Pump Study
PDF
Habitat for Humanity HVAC System Analysis
PDF
MEFM: An R package for long-term probabilistic forecasting of electricity demand
PDF
Short-term uncertainty in long-term energy models
PDF
Probabilistic forecasting of long-term peak electricity demand
PDF
Optimal integration of net Zero Energy Buildings in the Scandinavian energy s...
PDF
Opportunity of Analysis and Assessment of CDM Potential in Residential Area
PPTX
02 sandia pv modeling conference 9 may2017
PPTX
Ads final report - Team 8
PPTX
ZEPHIR @PassiEXPO 2013
PDF
Electrical Drives and Control Heating and Cooling Curves
PPT
The Calculation Method of Heating and Cooling Energy Saving Potential in Urba...
PPT
ASABE 2014 Presentation(Final Version)
PPSX
Presentation1
PPTX
2017 ams
PDF
What does wind really cost? Modeling Wind Resources In AURORAxmp.
PDF
Determination of wind energy potential of campus area of siirt university
PDF
A study on wind speed distributions
Interference effects for inline chmineys
Semester Project 2: Combined Heat & Power Plants - Fynsværket, Block 7
Lakeshore Center Heat Pump Study
Habitat for Humanity HVAC System Analysis
MEFM: An R package for long-term probabilistic forecasting of electricity demand
Short-term uncertainty in long-term energy models
Probabilistic forecasting of long-term peak electricity demand
Optimal integration of net Zero Energy Buildings in the Scandinavian energy s...
Opportunity of Analysis and Assessment of CDM Potential in Residential Area
02 sandia pv modeling conference 9 may2017
Ads final report - Team 8
ZEPHIR @PassiEXPO 2013
Electrical Drives and Control Heating and Cooling Curves
The Calculation Method of Heating and Cooling Energy Saving Potential in Urba...
ASABE 2014 Presentation(Final Version)
Presentation1
2017 ams
What does wind really cost? Modeling Wind Resources In AURORAxmp.
Determination of wind energy potential of campus area of siirt university
A study on wind speed distributions
Ad

Similar to ARX models for Building Energy Performance Assessment Based on In-situ Measurements (20)

PDF
Methodology to estimate energy savings in buildings within ETSAP-TIAM
PPTX
2015 NWA poster
PDF
Survadapt-Webinar_2014_SLIDES
PDF
Selecting representative days
PDF
Michel Reygaerts CV
PPTX
IEA EBC Annex 62 Ventilative cooling
PDF
Documentation of window energy performance
PDF
A case study on heat exchnage network
PDF
PDF
Anand2020
PDF
Smart Grids, Energy Efficiency and Renewable Energy Sources in urban areas: t...
PDF
Low cost solar steam generation
PPTX
Business statistics final
PDF
The effect of microscale spatial variability of wind on estimation of technic...
PDF
Jarek Kurnitski - Työpaja "Aidot hankkeet nZEB:iin"
PPTX
002 160718 ntnu and smart zero emission buildings, districts and cities_sc
PDF
CREATION OF A POSTGRADUATE COURSE FOR WIND ENERGY AT THE INTERNATIONAL HELLEN...
PPTX
Pollution Prevention at CST Storage...
PPT
060728_KK_IMPI
PDF
TIMES Course for Master Students in DTU: Reflections and Way Forward
Methodology to estimate energy savings in buildings within ETSAP-TIAM
2015 NWA poster
Survadapt-Webinar_2014_SLIDES
Selecting representative days
Michel Reygaerts CV
IEA EBC Annex 62 Ventilative cooling
Documentation of window energy performance
A case study on heat exchnage network
Anand2020
Smart Grids, Energy Efficiency and Renewable Energy Sources in urban areas: t...
Low cost solar steam generation
Business statistics final
The effect of microscale spatial variability of wind on estimation of technic...
Jarek Kurnitski - Työpaja "Aidot hankkeet nZEB:iin"
002 160718 ntnu and smart zero emission buildings, districts and cities_sc
CREATION OF A POSTGRADUATE COURSE FOR WIND ENERGY AT THE INTERNATIONAL HELLEN...
Pollution Prevention at CST Storage...
060728_KK_IMPI
TIMES Course for Master Students in DTU: Reflections and Way Forward
Ad

Recently uploaded (20)

PPTX
BIOMOLECULES PPT........................
PDF
Looking into the jet cone of the neutrino-associated very high-energy blazar ...
PPT
Presentation of a Romanian Institutee 2.
PPT
veterinary parasitology ````````````.ppt
PDF
S2 SOIL BY TR. OKION.pdf based on the new lower secondary curriculum
PDF
lecture 2026 of Sjogren's syndrome l .pdf
PPT
Heredity-grade-9 Heredity-grade-9. Heredity-grade-9.
PDF
Worlds Next Door: A Candidate Giant Planet Imaged in the Habitable Zone of ↵ ...
PPTX
Lesson-1-Introduction-to-the-Study-of-Chemistry.pptx
PDF
Warm, water-depleted rocky exoplanets with surfaceionic liquids: A proposed c...
PPTX
TORCH INFECTIONS in pregnancy with toxoplasma
PPTX
Biomechanics of the Hip - Basic Science.pptx
PDF
Worlds Next Door: A Candidate Giant Planet Imaged in the Habitable Zone of ↵ ...
PPTX
Understanding the Circulatory System……..
PPTX
endocrine - management of adrenal incidentaloma.pptx
PDF
Cosmic Outliers: Low-spin Halos Explain the Abundance, Compactness, and Redsh...
PPTX
A powerpoint on colorectal cancer with brief background
PPTX
BODY FLUIDS AND CIRCULATION class 11 .pptx
PPTX
INTRODUCTION TO PAEDIATRICS AND PAEDIATRIC HISTORY TAKING-1.pptx
PPTX
ap-psych-ch-1-introduction-to-psychology-presentation.pptx
BIOMOLECULES PPT........................
Looking into the jet cone of the neutrino-associated very high-energy blazar ...
Presentation of a Romanian Institutee 2.
veterinary parasitology ````````````.ppt
S2 SOIL BY TR. OKION.pdf based on the new lower secondary curriculum
lecture 2026 of Sjogren's syndrome l .pdf
Heredity-grade-9 Heredity-grade-9. Heredity-grade-9.
Worlds Next Door: A Candidate Giant Planet Imaged in the Habitable Zone of ↵ ...
Lesson-1-Introduction-to-the-Study-of-Chemistry.pptx
Warm, water-depleted rocky exoplanets with surfaceionic liquids: A proposed c...
TORCH INFECTIONS in pregnancy with toxoplasma
Biomechanics of the Hip - Basic Science.pptx
Worlds Next Door: A Candidate Giant Planet Imaged in the Habitable Zone of ↵ ...
Understanding the Circulatory System……..
endocrine - management of adrenal incidentaloma.pptx
Cosmic Outliers: Low-spin Halos Explain the Abundance, Compactness, and Redsh...
A powerpoint on colorectal cancer with brief background
BODY FLUIDS AND CIRCULATION class 11 .pptx
INTRODUCTION TO PAEDIATRICS AND PAEDIATRIC HISTORY TAKING-1.pptx
ap-psych-ch-1-introduction-to-psychology-presentation.pptx

ARX models for Building Energy Performance Assessment Based on In-situ Measurements

  • 1. DTU Compute, Technical University of Denmark 07 August 2015 ARX MODELS FOR BUILDING ENERGY PERFORMANCE ASSESSMENT BASED ON IN-SITU MEASUREMENTS IEA EBC Annex 71 Common Exercise 1, Subtask 3 Physical Parameter Identification Christoffer Rasmussen (chrras@dtu.dk), Peder Bacher, Henrik Madsen
  • 2. DTU Compute, Technical University of Denmark 07 August 2015 MODEL ARX model as used in Annex 58, Subtask 3, Part 2 • Output: Indoor temperature • Input: Heating power Outdoor temperature Solar radiation Annex 71, CE1 ST3 – October 23-25, 20172 𝜙 𝐵 𝑇$ % = 𝜔( 𝐵 Φ$ ( + 𝜔+ 𝐵 𝑇$ + + 𝜔,-. 𝐵 𝑄$ ,-. + 𝜖$
  • 3. DTU Compute, Technical University of Denmark 07 August 2015 DATA REQUIREMENTS FOR THE GOOD FIT High signal-to-noise ratio – Daily mean outdoor temperature below 5 ºC Minimal disturbances in data from occupants – Out-of-the-house vacation: • No disturbances • Limited periods throughout the year. – Out-of-the-house weekdays: • No disturbances • Only applicable if occupants actually leave the house regularly for several hours – Night-time: • Few disturbances • New data accessible every night (normally) Annex 71, CE1 ST3 – October 23-25, 20173
  • 4. DTU Compute, Technical University of Denmark 07 August 2015 MODEL ARX model as used in Annex 58, Subtask 3, Part 2 ARX model as used in Annex 71, Common Exercise 1, Subtask 3 • Output: Indoor temperature • Input: Heating power Outdoor temperature • Data: Only night-time • Time resolution: 10 minutes Annex 71, CE1 ST3 – October 23-25, 20174 𝜙 𝐵 𝑇$ % = 𝜔( 𝐵 Φ$ ( + 𝜔+ 𝐵 𝑇$ + + 𝜔,-. 𝐵 𝑄$ ,-. + 𝜖$ 𝜙 𝐵 𝑇$ % = 𝜔( 𝐵 Φ$ ( + 𝜔+ 𝐵 𝑇$ + + 𝜖$
  • 5. DTU Compute, Technical University of Denmark 07 August 2015 DOWN-WEIGHTING DAY-TIME DATA Annex 71, CE1 ST3 – October 23-25, 20175 051015 Heat consumption, day and night Energy[kW] 18:00 00:00 06:00 12:00 18:00 00:00 06:00 Day (weight = 0) Night (weight = 1)
  • 6. DTU Compute, Technical University of Denmark 07 August 2015 ACF AND CCF ISSUES N Time Residual ⋮ ⋮ ⋮ 35 2014/01/01 06:50 +0.05 36 2014/01/01 07:00 –0.02 37 2014/01/01 19:30 –0.01 38 2014/01/01 19:40 +0.04 ⋮ ⋮ ⋮ Annex 71, CE1 ST3 – October 23-25, 20176 𝛾33 𝜏 = Cov 𝑋 𝑡 , 𝑋 𝑡 + 𝜏 𝜌33 𝜏 = 𝛾33 𝜏 𝜎3 =
  • 7. DTU Compute, Technical University of Denmark 07 August 2015 SEPARATING SPACE HEATING & DHW 0.00 0.01 0.02 0.03 0.04 0.05 0.06 0.07 Summer data Water consumption [m3 ] Heat[kW] Hot water and space heating Hot water Space heating 0510152025 0.00 0.01 0.02 0.03 0.04 0.05 0.06 0.07 All data Water consumption [m3 ] 0510152025 Annex 71, CE1 ST3 – October 23-25, 20177
  • 8. DTU Compute, Technical University of Denmark 07 August 2015 SEPARATING SPACE HEATING & DHW Annex 71, CE1 ST3 – October 23-25, 20178 0515 Energy[kW] 00:00 03:00 06:00 09:00 12:00 15:00 18:00 21:00 24:00 Hot water production Space heating 0.000.020.04 Waterconsump.[m3 ] 00:00 03:00 06:00 09:00 12:00 15:00 18:00 21:00 24:00 20.021.5 Indoortemp.[°C] 00:00 03:00 06:00 09:00 12:00 15:00 18:00 21:00 24:00
  • 9. DTU Compute, Technical University of Denmark 07 August 2015 CASE DIFFERENT OCCUPATION PERIODS Annex 71, CE1 ST3 – October 23-25, 201712 Different occupation periods Sample period [nights] HLC[W/K] 335075100125150 1 3 5 7 9 11 13 15 17 Estimate (occupation period 2) 95 % CI Assumed 83.4 (±16.3) W/K
  • 10. DTU Compute, Technical University of Denmark 07 August 2015 CASE DIFFERENT OCCUPATION PERIODS Annex 71, CE1 ST3 – October 23-25, 201713 Different occupation periods Sample period [nights] HLC[W/K] 335075100125150 1 3 5 7 9 11 13 15 17 Estimate (occupation period 1) Estimate (occupation period 2) 95 % CI Assumed 83.4 (±16.3) W/K 63.2 (±5.1) W/K
  • 11. DTU Compute, Technical University of Denmark 07 August 2015 RESIDUAL ANALYSIS Annex 71, CE1 ST3 – October 23-25, 201714 0 10 20 30 40 −0.050.05 ACF (Residuals) ACF 0 10 20 30 40 −0.060.04 CCF (Residuals & Outdoor temperature) CCF 0 10 20 30 40 −0.060.04 CCF (Residuals & Heating power) Lags CCF
  • 12. DTU Compute, Technical University of Denmark 07 August 2015 RESIDUAL ANALYSIS Annex 71, CE1 ST3 – October 23-25, 201715 20.521.522.523.5 One−step predictions Indoortemp.(°C) Measured Predicted −0.050.000.05 Residuals ε Night 1 Night 2 Night 3 Night 4 Night 5 Night 6 Night 7 Night 8 Night 9 Night 10 Night 11 Night 12 Night 13 Night 14 Night 15 Night 16
  • 13. DTU Compute, Technical University of Denmark 07 August 2015 RESIDUAL ANALYSIS Annex 71, CE1 ST3 – October 23-25, 201716 0.0 0.1 0.2 0.3 0.4 0.5 0.00.20.40.60.81.0 Frequency Cumulative periodogram −3 −2 −1 0 1 2 3 −0.050.000.05 Q−Q plot Theoretical quantiles Samplequantiles Histogram Sample quantiles Density −0.10 −0.05 0.00 0.05 0.10 051015
  • 14. DTU Compute, Technical University of Denmark 07 August 2015 CONCLUSIONS Data – Obtain good time series where input and output is well-exercised. – Prober filtering of domestic hot water consumption. – Get representative indoor temperatures. – Model internal heat gains from occupants. E.g. through CO₂ measurements. Assumed and estimated HLC – Air leakages. – Thermal bridges. – All heat is assumed to be transferred to the air. – Heat capacity of building not taken into account Annex 71, CE1 ST3 – October 23-25, 201717
  • 15. DTU Compute, Technical University of Denmark 07 August 2015 PERSPECTIVE Evaluation of building performance and occupants effect on energy consumption 1. Apply occupant models to estimate if apartment is empty or not. 2. Use periods where apartment is un-occupied and of occupants are sleeping, instead of night-time only, to include solar radiation in model. 3. Use fitted model on all data and estimate the effect of the occupants on the energy consumption. Annex 71, CE1 ST3 – October 23-25, 201718
  • 16. DTU Compute, Technical University of Denmark 07 August 2015 MODEL MATRIX Annex 71, CE1 ST3 – October 23-25, 201719 HLC estimate and standard deviation obtained from best model: 63.2 (±5.1) W/K 10 min data of: Indoor temperature Outdoor temperature Heating power
  • 17. DTU Compute, Technical University of Denmark 07 August 2015 MODEL MATRIX Annex 71, CE1 ST3 – October 23-25, 201720 HLC estimate and standard deviation obtained from best model: 63.2 (±5.1) W/K 10 min data of: Indoor temperature Outdoor temperature Heating power