SlideShare a Scribd company logo
Session 13 – Wiring Methods & Cable Standards
Multicore cables on racks or trays may be bunched in a maximum of two layers.
HV and LV single core cables shall be laid in trefoil groups with 150 mm clear spacing
between trefoils.
On trays or racks HV cables shall be segregated from the LV cables. Individual cables emerging from
floors or soil shall be protected against mechanical damage by means of galvanized steel pipes or
rigid PVC pipes. Single core cables emerging from floors or soil shall be protected by rigid PVC pipes.
These pipes shall extend at least 100 mm above ground or floor level.
Grouped cables emerging from floors or soil shall be protected collectively by a properly designed
metal shield or duct in such a way that heat dissipation of the sustained load carrying cables is not
hampered. The propagation of fire from one space to the other shall be prevented by proper sealing
of openings around cables.
Cables or cable supports shall not be fixed directly or indirectly to plant, equipment or process piping
which may require removal or replacement. Cables shall be laid on racks or trays strictly in
accordance with the laying patterns stated on the layout drawings. Metal parts of the cable racks and
trays shall be bonded and connected to the common earthing grid.
Typical IEC Wiring Specification
Typical IEC Wiring Specification
Bends and corners in the cable racks, trays or ladders shall take account of the minimum
cable bending radii. Cable racks and trays shall be closed by removable top covers,
allowing adequate ventilation, in situations where:
‐ mechanical damage of the cables is likely to occur during plant maintenance activities,
‐ oil or chemical spillages on the trays can be expected,
‐sun shielding is required against direct solar radiation.
Vertical cable rack risers shall not be installed in front of, or over, pipe risers.
Flexible cabling
The application of flexible cables in industrial plants and installations shall be limited to:
‐ welding cables;
‐ trailing cables, e.g. for movable equipment, hand tools, hand lamps;
‐ winches, hoists, soot blowers, and electric motors, if connected by means of a nearby
intermediate junction box.
An earth continuity conductor, equal in cross‐sectional area to the largest phase
conductor, shall be provided. This requirement applies even when the cable is armored.
Typical IEC Wiring Specification
Cable marking/numbering
Cable numbers shall be marked on the cables along their routes and at both termination
points. For underground cabling, the spacing between cable numbers along the route should
not exceed 5 m, and for above ground cabling, 25 m. Cables shall also be numbered where
they branch off from a main route.
For underground cable marking purposes non‐corroding strips shall be used, each having
ample length to be wrapped twice around the cable and in which the cable number has been
imprinted by means of letter/cipher punches. For above ground cabling, plastic markers
resistant to the site conditions shall be strapped round the cables.
For underground cabling, above ground route markers shall also be provided at every change
of direction in the routing and at both sides of road or pipeline crossings, except when cable
routing is already indicated by colored concrete pavement.
EX Installation Methods
Conduit or Cable Glands...
Indirect Entry via EEx ‘e’
gland & enclosure
Direct Entry via EEx
‘d’ conduit
Direct Entry via EEx ‘d’
gland
Typical Wiring Methods
Rigid Conduit
Unarmored
Cable
Armored
Cable
IEC Cable Types and Construction
Unarmored Cable similar to US TC type cables but with fully extruded fillers. Armored
Cable similar in concept to IEEE45 Type P marine shipboard cable and continuous
corrugated aluminum armor cable.
Type SWA – Steel Wire Armor
Type STA – Steel Tape Armor
Type SWB – Steel Wire Braid
The following main requirements are listed in the EN60079 standard for cables and conductors:
‐ use only insulated cables and conductors (test voltage ≥ 500 VAC),
‐ in special cases earth the required screening only once at the end of the non‐explosive
environment,
‐ protect intrinsically safe circuits against external electrical or magnetic fields through the
maintenance of adequate distances, screening and/or core twisting, isolate intrinsically safe
cables and conductors from non‐intrinsically safe cables and conductors or, protect against
mechanical damage or, protect through metal housing, or screening of the cables and conductors
do not combine conductors of intrinsically safe and non‐intrinsically
safe circuits
‐ prevent the fraying of fine wired conductors through the use of cable sleeves, for example:
‐ isolate intrinsically safe and non‐intrinsically safe circuits in cable bundles or ducts via insulation
spacer or an earthed metal spacer (not required with screening or sheathing),
‐ identify (i.e. light blue) the cables and conductors of intrinsically safe circuits (not required with
shielding or metal sheathing)
Cable/Conductor Requirements in Zone
applications
When selecting cables and conductors, only use those which can withstand the
expected mechanical, chemical and thermal influences. Cables and conductors with
thermoplastic sheath, duroplastic sheath, elastomer sheath or mineral insulation with
metal sheath may be used for fixed routing. Cable branch lines must comply with the
requirements for hazardous areas.
The cables and conductors must be connected to the electrical equipment in line with
the directives for the associated type of protection. Unused openings on devices and
equipment must be closed. When cables and conductors are installed through openings
into non‐hazardous areas, care must be taken to provide an adequate seal at the
openings (e.g. sand filling, mortar) to prevent carrying‐over of the zone. At particularly
hazardous points, cables and conductors must be protected against thermal, mechanical
or chemical stress by, for example, conduits, tubing or covers. The flame retardance of
cables and conductors for fixed routing must be proven in accordance with IEC 60332‐1.
Cable/Conductor Requirements in Zone
applications
IEC Cable Types and Construction
In general, SWA cable has been the cable of choice in the UK
for onshore installations. It is somewhat flexible, readily
available and has good bending capabilities.
SWB cable has become the choice for installations offshore
with various armor materials including tinned copper, bronze
and other materials. Very flexible yet durable under very
demanding conditions. Many different jacket types available.
STA is more of an onshore type cable and is widely used in
onshore applications in continental Europe, especially for
power applications. Clients have started to shy away from STA
as it is generally regarded as slightly more difficult to terminate
than either SWA or SWB.
One variation commonly used for direct bury applications is a
Lead sheathed armor cable. Lead provides a very good
insulation due to corrosive elements and is particularly
resistant to rodents and ants. Cable glands for lead sheathed
cable typically need an additional component to seat the lead
portion of the cable.
Designations on glands is to mark a XZ for braid and tape, with
a W for wire armor for field installation.
BFOU & RFOU instrumentation cables are manufactured with either overall or individual
screens, the cores are either laid up as pairs or triples. Ideal for signal and
instrumentation circuits where the fire performance and Low Smoke Zero Halogen
properties are increasingly being required within public buildings and power stations, as
well as traditional Petro/Chem industries. The cable is designed to carry on working for a
period of 3 hours when exposed to fire, according to IEC 60331 test procedure. BFOU
also offers good screening properties, reducing Electro Magnetic Interference (EMI).
Construction
Tinned stranded copper conductor, MICA tape, EPR insulation, overall screen of Copper
backed Polyester tape with a stranded copper drain wire 0.75mm², inner sheath of
Halogen Free Thermoset Elastomer, tinned copper wire braid and an outer sheath of
Halogen Free Thermoset Elastomer. The individually screened version has a Copper
backed Polyester tape with a stranded copper drain wire 0.75mm² around each pair or
triple.
Core colors
Pairs ‐ Light blue, black
Triples ‐ Light blue, black and brown
Each pair or triple is identified by a numbered tape.
IEC Cable Types and Construction
The most common sheath material for data cabling in use in the UK is PVC. For many
environments, PVC is the ideal material, having superior mechanical characteristics and
high reliability. However, in a fire, PVC emits heavy black smoke mixed with
hydrochloric acid, thus reducing vision, immediately impairing breathing, and
additionally initiating corrosion of all equipment exposed to the fumes. For improved
fire performance, it is common for LSZH Low Smoke Zero Halogen (usually meeting
IEC61034, IEC60754‐2 and IEC60332‐3) cable sheaths to be used within Europe.
The major Standards in common use are shown in the table.
IEC Cable Types and Construction
IEC Cable Tests for Fire Applications
Typical IEC Cable Tests
Fire Resistant Test – IEC60331‐21 Under
long fire exposure, the cable must
maintain the power supply for vital safety
equipment (emergency lighting, alarm,
systems & fire pumps, etc.)
Smoke Density Test – IEC61034‐1/2
The smoke density test evaluates
the smoke emissions of the cable
and the jacket construction.
Test under fire condition –
IEC60332‐3 Flame retardant test
simulating cables installed in bunch
on a vertical ladder under fire
conditions.
IEC60332‐1‐2 Single wire or cable
• A test on a single length of cable
600mm long held between 2
clamps.
• The flame is applied for a
predetermined amount of time
based on the weight of the
cable.
• To pass the test there should not
be any visible damage or
charring within 50mm of the
lower edge of the top clamp
(Equal to 425mm higher than the
flame source) once all
combustion has stopped.
• This test replaces IEC60332‐1,
BS4066 pt 1 & BS EN 50265‐2‐1.
IEC60332‐3 “The ladder test”
• The IEC60332‐3 ranges of tests are conducted
on bunches of cables and are much closer to a
real life installation. 3.5m Lengths of cables
are bunched onto a cable ladder in a chimney
simulating a building riser.
• The volume of cable on the ladder is
determined in litres of combustible material to
offer a balanced view of performance across a
cable range.
• A flame is applied 500mm from the base of the
ladder for a predetermined time. When the
burner has extinguished a one hour after‐burn
period is allowed then the cables are checked
for performance.
• To pass the tests the cables should not be
affected by the flame 2.5m above the flame
source.
IEC60332‐3 categories
Test Qty of material Flame application Supersedes
60332‐3‐22 Cat A 7.0 litres 40 minutes IEC60332‐3A
BS4066 pt 3A
60332‐3‐23 Cat B 3.5 litres 40 minutes IEC60332‐3B
BS4066 pt 3B
IEC60332‐3‐24 Cat C 1.5 litres 20 minutes IEC60332‐3C
BS4066 pt 3C
IEC60332‐3‐25 Cat D 0.5 litres 20 minutes
60332‐3‐21 Cat A F/R Used for large O.D cables instead of “3‐22 Cat A”. The cables are
mounted on the front and back of the ladder
• All these tests are to be conducted on complete cables.
• Compounds alone cannot be tested to IEC60332
Fire Resistant Testing
• A cables ability to continue operating safely during a fire. Also referred to as circuit integrity.
• Widely used in commercial/public buildings & MOG applications to control fire
alarm/monitoring systems, emergency lighting, fire shutters and emergency evacuation
equipment.
European Fire Standards
• Standard Ref. Performance requirement
• IEC60331 Cables ≤ 0.6/1kV. 3 hours at 750°C (1970 edition)
• IEC60331‐21 Cables ≤ 0.6/1kV 90 minutes @ 750°C (unless alt. stated in the cable
spec)
• IEC60331‐23 Data cables 90 minutes @ 750°C
• IEC60331‐25 Optical fibre 90 minutes @ 750°C
• IEC60331‐31 Cables ≤ 0.6/1kV 120 minutes @ 830°C with vibration
• VDE0472 FE180 This test is equal to IEC60331 (1970 edition)
• DIN 4102 E30 Complete system integrity for 30 minutes
• DIN 4102 E90 Complete system integrity for 90 minutes
Smoke Emission & Toxic Gas
• Obscuration of vision and toxic gas are the main threat to people during a fire leading to
disorientation and chocking from fumes. Death is normally caused by . choking rather than
flames. Reducing smoke & fume emissions is vital to enable safe evacuation.
• Equipment damage is caused by HCl gases mixing with moisture from the sprinkler systems
and creates acid rain leading to long term component failure even if the equipment does not
look damaged.
• Not all materials that are low smoke are halogen free, examples :
• LS‐PVC (Limited Smoke PVC to UL1685)
• Fluorocarbons (PTFE, FEP etc.)
• “Type B” CSP to BS6883 (1991)
European Smoke Testing
• IEC 61034‐2: A one meter sample of cable (or a
bundle of cables depending on the outer diameter) is
placed in a 3m cube and subjected to combustion by
an alcohol produced flame for 20 minutes. The light
transmission through the cube should not fall below
60% during the test (at peak or total)
• Measurement method :
• 100W halogen light source sensed by a photoelectric
cell positioned on the opposite side of the smoke
cube.
• IEC61034‐2 is the most popular test used for cable in
Europe.
• IEC61034‐1 covers the apparatus required and test
procedure.
Toxic Gas Evolution IEC60754
• IEC60754‐1 (BS EN 50267 pt1) measures the amount of hydrochloric acid (HCl)
evolved during burning. The result is normally expressed as a percentage of the
sample weight. There is no pass/fail criteria.
• This method is not suitable for testing cables classed as “Zero Halogen“ and
compounds containing less than 5mg/g (5%)
• IEC60754‐2 (BS EN 50267 pt2) measures the corrosiveness of the evolved gas in
terms of acidity (pH) and conductivity. IEC 60754‐2 recommended values are :
• pH > 4.3. & Conductivity of combustion gases < 10 mS/mm
Panel Wiring to IEC requirements
Most of Europe abides by IEC (International Electrotechnical Commission) wiring color
codes for AC branch circuits. The older color codes in the table reflect the previous style
which did not account for proper phase rotation. The protective ground wire (listed as
green‐yellow) is green with yellow stripe.
Function Label Current Color IEC Old Color IEC
Protective Earth PE Green‐Yellow Green‐Yellow
Neutral N Blue Blue
Line, single Phase L Brown Brown or Black
Line, 3 phase L1 Brown Brown or Black
Line, 3 phase L2 Black Brown or Black
Line, 3 phase L3 Grey Brown or Black
The United Kingdom now follows the IEC AC wiring color codes. The table below lists these
along with the obsolete domestic color codes.
Function Label Current Color UK Old Color UK
Protective Earth PE Green‐Yellow Green‐Yellow
Neutral N Blue Black
Line, single Phase L Brown Red
Line, 3 phase L1 Brown Red
Line, 3 phase L2 Black Yellow
Line, 3 phase L3 Grey Blue
Example of old UK wiring colors
The use of color coded ferrules or sleeves is typically left up to the client/user
preference. Either practice is acceptable to relevant IEC standards.
Cable Gland Selection Criteria
Cable glands used in enclosures intended for use in
a hazardous area must meet with the
same criteria as the enclosure to which they are
connected. For example, cable glands used on
an EEx‘e’ enclosure must meet the requirements
for the enclosures of the EEx‘e’
standard i.e. must be capable of withstanding a
7Nm impact and capable of maintaining an
ingress protection of at least IP54.
Testing Procedures for Cable
Glands
IP 66 Testing – 100 liters of water for 3 minutes
from 2.5 to 3 meters
Continuity Testing of Armor – Gland is heated and
cooled over time and resistivity should not change
more than 10%
Tork Test – Multiple spanners to prescribed
tension with no damage on disassembly
Impact Test – I kg falling from 70cm or 7 joules. No
damage to gland
Pressure Test – Minimum of 450 psi without
leakage for Ex ‘d’, 2000 psi for UL2225
requirements
Load Test – Unarmored cable gland with
mandrel to not slip more than 6 mm over 6 hrs.
Testing Procedures for Cable
Glands
Wiring Methods
Wiring concepts Offshore follow the established & prevailing Marine
standards, e.g. IEC 60092‐352
Metallic parts (including armour) shall be earthed effectively to
prevent them from becoming live.
Cable Armour/Braid provides a means of good earth continuity as well
as mechanical protection.
Normal practice has been to use external grounding as the most direct
route to earth.
This is easily achieved with metallic cable glands in non metallic
enclosures by the use of an earth tag
Shrouds have been found to be an ineffective means of keeping water
out of enclosures and glands are typically not used for North Sea
applications any more
Wiring Methods – Shielding EMI
Protection
A Screened Cable entering shielded enclosure
• Assists in protection against Radiated Emissions
360o Cable shielding provides optimum
performance
for EMC as opposed to ‘pig tail’ techniques.
Metallic glands are an essential part of the
system design in respect of
Electromagnet protection.
Non metallic glands create the weak link in the
system between shielded cable and enclosure.
Two forms of EMI/RFI to consider
• Conducted Emissions (Generated & Susceptibility)
• Radiated Emissions (Generated &
Susceptibility)
Typical Ex d & e armored
cable gland
Components of Typical Ex e & d cable gland….
Front End
Deluge Seal
Armor Cone Clamping Ring Back End
Inner Seal
Outer Seal
Ex d & Ex e
Requirement for Ex d cable glands for equipment
< 2 litres
• Screwed entry threads must maintain flame
path
• Inner seal must be explosion proof and gas tight
• Trend is to use dual certified Ex d & Ex e
Inner & Outer Seals
Installation of Ex ‘ed’ gland
Locknut
Not unusual to use the identical gland for both Ex d and Ex e applications
for less confusion in installation in the field….
Installation of Ex ‘d’ barrier
gland
Seal required to
withstand
a pressure of 450 PSI
(31 bar)
for 2 minutes
Pressure Flame
Hot Gases
Epoxy Resin
Compound
Flame Path
Direct Entry into Zone 1, Ex ‘d’ enclosure over 2 liters volume
With Arcing Sparking Devices and Zone 1 or 2, IIC applications…
Flame Path
Exhaust
Routes
Cable A
Cable D
Cable B Cable C
Cable E
Which type is suitable for use with Flameproof Ex d equipment
using a gland with an ELASTOMERIC seal?
Incorrect Shape,
Cables Should
be Round
No Inner Sheath,
Extruded Bedding
or Suitable Fillers
Correct Cable,
e.g. has an
extruded
inner bedding
û
û
û û
ü
Sample of Cable Types
IEC60079‐15 Cable Gland Selection
Chart
In general, about 90% of the application for hazardous location cable glands can be
fulfilled with the use of a non‐barrier compound gland…
Wiring Methods – Typical Norwegian
Installation Practice
Wiring Methods – Typical Norwegian
Installation Practice
Direct Entry, Gland Type
EEx d Barrier Type if
volume > 2 litres
Indirect Entry, Gland Type
EEx e or Dual Certified EEx
e/EEx d gland
Ignition Source
Direct and Indirect Entry Ex e & Ex d
Enclosures
Gland Type Ex D Barrier Type
providing gas tight Bi‐Directional
seal. Gland must be certified Ex
nR
Gland Type Ex d/Ex e incorporating internal seal
that provides Bi‐Directional Gas‐tight seal.
Direct Entry Ex nR Equipment
Wiring Methods – Cable Gland usage UK
Equipment
Market Sector
Cable
Cable Glands
Ex e 95%
Ex d 5%
Brass "Armored"
Exd / Ex e
Cable Gland
99%
Brass "Armored"
Ex d Compound
Barrier Gland
1%
Braid Armor
98%
Brass "Unarmored"
Ex d / Ex e
Cable Gland
99%
"Unarmored"
Plastic Ex e
Cable Gland
1%
Unarmored
2%
UK Offshore
Hazardous Areas
Thread Information and
Accessories
The standardization of thread type in the IEC world is typically
around the Metric straight thread. However, other thread types do
exist in the IEC world and if not Metric or a variation of, are a PG,
BSP or BST thread type.
Accessories that are commonly used are:
Cable Shrouds – Becoming increasingly less used as they have a
tendency to hold water in and cover up potential corrosion with
glands.
Earth Tags – Otherwise known as “Banjos” or “Frying Pans”. Used
to provide a means to ground the cable gland typically when used in
non‐metallic enclosures.
Locknuts – Typically used to secure the cable gland to the enclosure.
Thread Information and
Accessories (Cont.)
With the various threads used, thread adaptors and
reducers are a common accessory widely used. One
key point is that it is not allowed to reduce a reducer…
Shaker Washers – Typically used between the locknut
and inside of an enclosure, shaker washers are used to
provide a means to keep vibrations from loosening the
cable gland to the enclosure.
IP washers – As the name implies, IP washers help
maintain the IP rating between the cable gland and the
enclosure…
If you have a cable gland in a clearance hole, you have a
metal to metal (or plastic) surface that provides no
better than IP54 protection. IP washers go between
the face of the gland and the outside of the enclosure.
Drains – EEx e drains that allow condensation to drain
from the inside of enclosures due to moisture buildup
during the normal heating and cooling process during
the day and night.
Cable gland spacing on enclosures
Cable glands clearance holes need to be considered when determining number and sizes of
glands installed in enclosures. Always confirm gland cross corner clearance with manufacturer
and template size of enclosure to confirm whether enough space exists for gland entries…
A note on single core cables
entering enclosures
Eddy currents can overheat iron or steel cabinets, locknuts or bushings or any
ferrous metal that completely encircles the single conductor cables. This
presents no problem in multi‐conductor cables, where the magnetic fields tend
to cancel each other out. For single core cables, it is recommended that these
cables enter metal enclosures through a non‐ferrous plate such as aluminum….
Cable gland spacing on enclosures
Traditional use of cable glands entering into an Ex e enclosure need a significant
amount of excess space to allow for the use of a spanner or wrench to tighten the
gland. The use of cabinet seals certified to Ex e can reduce the footprint of the
enclosure required by as much as 50% or allow a doubling of cables to enter in
the same space as traditional cable glands.
Ex ‘d’ Seals and Conduit Systems
Conduit Seals are commonly used with conduit systems
for direct entry into EEx d enclosures. The maximum
allowed distance from enclosure is 450mm. Like the US,
installations also require seal fittings at boundaries. Also,
all Ex d conduit bodies must be sealed when entries are
50mm or larger housing taps, splices, joints or terminals.
Conduit systems have a slightly different requirement in
that countries typically mandate max. fill. In the case of
most of the southern European countries, a max. fill of
60% is allowed. This differs with US regulations of
typically 40% maximum conduit fill. Conduit systems are
usually limited to 3000V or less. Above 3000V, cable
systems are required…
All switching mechanisms should be omni polar where the neutral wire is always cut
‐MINIMUM allowed wire sizes : ‐ Auxiliary Circuits (Controls) 1.5 mm/sq. ‐ Power
Circuits 2.5 mm/sq.
‐ Cables should be 3000V min. and “flame‐retardant” type
Cables MUST protected against insulation damage generally due to :
‐ Impact damage
‐ Heat sources that could damage cables insulation
‐ Chemical substances that could cause insulation cables corrosion
In order to comply with above mentioned requirements, a proper choice of cables and
cable routing is very important.
If “Cables Pass” far away from any place with risk of corrosion or accidental damage (i.e.
cables for ceiling mounted lighting fixtures) a standard PVC insulated cables in proper
cable trays are allowed. When cables come down to working areas, or pass beside to
valves or other equipment that might release heat or corrosive substances that might
damage cables insulation, it is recommended to pass relevant cables inside a galvanized
steel pipes. If cables go to vibrating machines (example: electrical motors) pipes should
be flexible hoses, for the last 500mm approx. connected to special cable glands with
female threaded head which allow for flexible hoses direct connection to the gland nut,
without leaving any part of cables uncovered.
Typical Wiring Practices with Conduit
Typical Wiring Practices with Conduit
Conduit for mechanical
protection
Flexible Conduit for vibration
and mechanical protection
Typical Wiring Practices with Conduit
IEC 61386 is the new European standard governing the performance of
flexible conduit (and rigid) systems in electrical installations.
Superseding the current European flexible conduit systems standards, EN
50086, IEC 61386 covers performance requirements for use of such
products in electrical installation applications. The performance
requirements covered include fatigue life, bend radius, operating
temperature, non‐flame propagation, IP ratings, impact resistance and
pull‐off strength
Tests to be carried out under IEC 61386:
The new IEC 61386 standard requires a number of tests to be carried out
on specimen conduit materials. These include:
The Impact Strength Test ‐ This is carried out on conduits over a range of
different temperatures. The test is made on each specimen using an impact
head with a defined profile. Conventionally, fracture behavior is studied,
but under this test, it is the deformation (buckling) behavior that is also
determined. The specimen passes the test if no fracture occurs after
impact, and there is also no excessive permanent deformation.
Typical Wiring Practices with Conduit
The Peak Load Test ‐ Under the requirements of this test, carried out on conduit specimens
under standard ambient conditions (which is specified as 23°C at 50% relative humidity), the
conduit is deformed by a defined amount between two plates.
The Reverse Bending Test (With Swinging Movements) ‐ This test is based on a cyclic reversed
bending of conduits under various temperatures. Under the requirements for the test, conduits
are dynamically loaded and evaluated over the temperature limits. The number of bending
cycles taken to fracture the conduit determines its strength.
The Self‐Extinguishing Test ‐ Under the requirements for this test, the conduit is exposed to a
flame (from a standard burner). The time to ignition (if any), the flame propagation, and the time
to self‐extinguishing after flame removal are all parameters measured.
Typical Wiring Practices with Cable
A typical method of making final terminations to enclosures is to leave
excess cable in a loop configuration to relieve any potential undue strain on
the cable gland, and allow easier modifications if equipment needs to be
replaced or repaired..
Typical Wiring Practices with Cable

More Related Content

PPT
791697875-1112134515016001-Cables (1).ppt
PPTX
Electrical wiring project
PPTX
cables.pptx
PPTX
Residential wiring PPT.pptx
PPTX
report on electrical wiring
PDF
Iec 62305 for lightning and surge protection follow in india nbc 2016 by bis(...
PDF
Jmv presentation national desaster management authority
PDF
presentation national desaster management and JMV LPS Ltd
791697875-1112134515016001-Cables (1).ppt
Electrical wiring project
cables.pptx
Residential wiring PPT.pptx
report on electrical wiring
Iec 62305 for lightning and surge protection follow in india nbc 2016 by bis(...
Jmv presentation national desaster management authority
presentation national desaster management and JMV LPS Ltd

Similar to Chapter 13 EX Wiring Methods presentation (20)

PDF
Jmv presentation national desaster management authority
PDF
THORNE + DERRICK : LV, MV & HV Cable Installation, Jointing, Substation & Ele...
PPT
T&D GP.ppt
PDF
types of wiring systems used in residentials buildins
PDF
Project sagarmala presentation jmv lps
PDF
THORNE & DERRICK LV MV HV Jointing, Earthing, Substation & Electrical Eqpt
PDF
Power transmission and distribution along with power qualty presentation by j...
PDF
presentation defence and police and JMV LPS LTD
PDF
Jmv presentation smart process plant (fertilizer)
PPTX
Hospital wiring SYSTEM
PPTX
Types of cables
PDF
Jmv presentation smart power transmission projects cea
PPTX
Instrumentation cables rev2
PDF
Xlpe insulated power cable
PDF
Presentation mecon project by jmv lps
PDF
MV Cable Catalogue
PPT
Distribution boards and Protection devices ppt
PPTX
types of cables .pptx
PPT
Safety for wiring methods
Jmv presentation national desaster management authority
THORNE + DERRICK : LV, MV & HV Cable Installation, Jointing, Substation & Ele...
T&D GP.ppt
types of wiring systems used in residentials buildins
Project sagarmala presentation jmv lps
THORNE & DERRICK LV MV HV Jointing, Earthing, Substation & Electrical Eqpt
Power transmission and distribution along with power qualty presentation by j...
presentation defence and police and JMV LPS LTD
Jmv presentation smart process plant (fertilizer)
Hospital wiring SYSTEM
Types of cables
Jmv presentation smart power transmission projects cea
Instrumentation cables rev2
Xlpe insulated power cable
Presentation mecon project by jmv lps
MV Cable Catalogue
Distribution boards and Protection devices ppt
types of cables .pptx
Safety for wiring methods
Ad

Recently uploaded (20)

PPTX
additive manufacturing of ss316l using mig welding
PPTX
M Tech Sem 1 Civil Engineering Environmental Sciences.pptx
PDF
Automation-in-Manufacturing-Chapter-Introduction.pdf
PPTX
Infosys Presentation by1.Riyan Bagwan 2.Samadhan Naiknavare 3.Gaurav Shinde 4...
PDF
Enhancing Cyber Defense Against Zero-Day Attacks using Ensemble Neural Networks
PPTX
Geodesy 1.pptx...............................................
PPTX
MET 305 2019 SCHEME MODULE 2 COMPLETE.pptx
PPTX
FINAL REVIEW FOR COPD DIANOSIS FOR PULMONARY DISEASE.pptx
PDF
Model Code of Practice - Construction Work - 21102022 .pdf
PPT
Project quality management in manufacturing
PPTX
Foundation to blockchain - A guide to Blockchain Tech
PPTX
Artificial Intelligence
PPTX
UNIT 4 Total Quality Management .pptx
PDF
July 2025 - Top 10 Read Articles in International Journal of Software Enginee...
PDF
BMEC211 - INTRODUCTION TO MECHATRONICS-1.pdf
PPTX
CARTOGRAPHY AND GEOINFORMATION VISUALIZATION chapter1 NPTE (2).pptx
PPTX
bas. eng. economics group 4 presentation 1.pptx
DOCX
573137875-Attendance-Management-System-original
PPT
Introduction, IoT Design Methodology, Case Study on IoT System for Weather Mo...
PDF
Unit I ESSENTIAL OF DIGITAL MARKETING.pdf
additive manufacturing of ss316l using mig welding
M Tech Sem 1 Civil Engineering Environmental Sciences.pptx
Automation-in-Manufacturing-Chapter-Introduction.pdf
Infosys Presentation by1.Riyan Bagwan 2.Samadhan Naiknavare 3.Gaurav Shinde 4...
Enhancing Cyber Defense Against Zero-Day Attacks using Ensemble Neural Networks
Geodesy 1.pptx...............................................
MET 305 2019 SCHEME MODULE 2 COMPLETE.pptx
FINAL REVIEW FOR COPD DIANOSIS FOR PULMONARY DISEASE.pptx
Model Code of Practice - Construction Work - 21102022 .pdf
Project quality management in manufacturing
Foundation to blockchain - A guide to Blockchain Tech
Artificial Intelligence
UNIT 4 Total Quality Management .pptx
July 2025 - Top 10 Read Articles in International Journal of Software Enginee...
BMEC211 - INTRODUCTION TO MECHATRONICS-1.pdf
CARTOGRAPHY AND GEOINFORMATION VISUALIZATION chapter1 NPTE (2).pptx
bas. eng. economics group 4 presentation 1.pptx
573137875-Attendance-Management-System-original
Introduction, IoT Design Methodology, Case Study on IoT System for Weather Mo...
Unit I ESSENTIAL OF DIGITAL MARKETING.pdf
Ad

Chapter 13 EX Wiring Methods presentation

  • 1. Session 13 – Wiring Methods & Cable Standards
  • 2. Multicore cables on racks or trays may be bunched in a maximum of two layers. HV and LV single core cables shall be laid in trefoil groups with 150 mm clear spacing between trefoils. On trays or racks HV cables shall be segregated from the LV cables. Individual cables emerging from floors or soil shall be protected against mechanical damage by means of galvanized steel pipes or rigid PVC pipes. Single core cables emerging from floors or soil shall be protected by rigid PVC pipes. These pipes shall extend at least 100 mm above ground or floor level. Grouped cables emerging from floors or soil shall be protected collectively by a properly designed metal shield or duct in such a way that heat dissipation of the sustained load carrying cables is not hampered. The propagation of fire from one space to the other shall be prevented by proper sealing of openings around cables. Cables or cable supports shall not be fixed directly or indirectly to plant, equipment or process piping which may require removal or replacement. Cables shall be laid on racks or trays strictly in accordance with the laying patterns stated on the layout drawings. Metal parts of the cable racks and trays shall be bonded and connected to the common earthing grid. Typical IEC Wiring Specification
  • 3. Typical IEC Wiring Specification Bends and corners in the cable racks, trays or ladders shall take account of the minimum cable bending radii. Cable racks and trays shall be closed by removable top covers, allowing adequate ventilation, in situations where: ‐ mechanical damage of the cables is likely to occur during plant maintenance activities, ‐ oil or chemical spillages on the trays can be expected, ‐sun shielding is required against direct solar radiation. Vertical cable rack risers shall not be installed in front of, or over, pipe risers. Flexible cabling The application of flexible cables in industrial plants and installations shall be limited to: ‐ welding cables; ‐ trailing cables, e.g. for movable equipment, hand tools, hand lamps; ‐ winches, hoists, soot blowers, and electric motors, if connected by means of a nearby intermediate junction box. An earth continuity conductor, equal in cross‐sectional area to the largest phase conductor, shall be provided. This requirement applies even when the cable is armored.
  • 4. Typical IEC Wiring Specification Cable marking/numbering Cable numbers shall be marked on the cables along their routes and at both termination points. For underground cabling, the spacing between cable numbers along the route should not exceed 5 m, and for above ground cabling, 25 m. Cables shall also be numbered where they branch off from a main route. For underground cable marking purposes non‐corroding strips shall be used, each having ample length to be wrapped twice around the cable and in which the cable number has been imprinted by means of letter/cipher punches. For above ground cabling, plastic markers resistant to the site conditions shall be strapped round the cables. For underground cabling, above ground route markers shall also be provided at every change of direction in the routing and at both sides of road or pipeline crossings, except when cable routing is already indicated by colored concrete pavement.
  • 5. EX Installation Methods Conduit or Cable Glands... Indirect Entry via EEx ‘e’ gland & enclosure Direct Entry via EEx ‘d’ conduit Direct Entry via EEx ‘d’ gland
  • 6. Typical Wiring Methods Rigid Conduit Unarmored Cable Armored Cable
  • 7. IEC Cable Types and Construction Unarmored Cable similar to US TC type cables but with fully extruded fillers. Armored Cable similar in concept to IEEE45 Type P marine shipboard cable and continuous corrugated aluminum armor cable. Type SWA – Steel Wire Armor Type STA – Steel Tape Armor Type SWB – Steel Wire Braid
  • 8. The following main requirements are listed in the EN60079 standard for cables and conductors: ‐ use only insulated cables and conductors (test voltage ≥ 500 VAC), ‐ in special cases earth the required screening only once at the end of the non‐explosive environment, ‐ protect intrinsically safe circuits against external electrical or magnetic fields through the maintenance of adequate distances, screening and/or core twisting, isolate intrinsically safe cables and conductors from non‐intrinsically safe cables and conductors or, protect against mechanical damage or, protect through metal housing, or screening of the cables and conductors do not combine conductors of intrinsically safe and non‐intrinsically safe circuits ‐ prevent the fraying of fine wired conductors through the use of cable sleeves, for example: ‐ isolate intrinsically safe and non‐intrinsically safe circuits in cable bundles or ducts via insulation spacer or an earthed metal spacer (not required with screening or sheathing), ‐ identify (i.e. light blue) the cables and conductors of intrinsically safe circuits (not required with shielding or metal sheathing) Cable/Conductor Requirements in Zone applications
  • 9. When selecting cables and conductors, only use those which can withstand the expected mechanical, chemical and thermal influences. Cables and conductors with thermoplastic sheath, duroplastic sheath, elastomer sheath or mineral insulation with metal sheath may be used for fixed routing. Cable branch lines must comply with the requirements for hazardous areas. The cables and conductors must be connected to the electrical equipment in line with the directives for the associated type of protection. Unused openings on devices and equipment must be closed. When cables and conductors are installed through openings into non‐hazardous areas, care must be taken to provide an adequate seal at the openings (e.g. sand filling, mortar) to prevent carrying‐over of the zone. At particularly hazardous points, cables and conductors must be protected against thermal, mechanical or chemical stress by, for example, conduits, tubing or covers. The flame retardance of cables and conductors for fixed routing must be proven in accordance with IEC 60332‐1. Cable/Conductor Requirements in Zone applications
  • 10. IEC Cable Types and Construction In general, SWA cable has been the cable of choice in the UK for onshore installations. It is somewhat flexible, readily available and has good bending capabilities. SWB cable has become the choice for installations offshore with various armor materials including tinned copper, bronze and other materials. Very flexible yet durable under very demanding conditions. Many different jacket types available. STA is more of an onshore type cable and is widely used in onshore applications in continental Europe, especially for power applications. Clients have started to shy away from STA as it is generally regarded as slightly more difficult to terminate than either SWA or SWB. One variation commonly used for direct bury applications is a Lead sheathed armor cable. Lead provides a very good insulation due to corrosive elements and is particularly resistant to rodents and ants. Cable glands for lead sheathed cable typically need an additional component to seat the lead portion of the cable. Designations on glands is to mark a XZ for braid and tape, with a W for wire armor for field installation.
  • 11. BFOU & RFOU instrumentation cables are manufactured with either overall or individual screens, the cores are either laid up as pairs or triples. Ideal for signal and instrumentation circuits where the fire performance and Low Smoke Zero Halogen properties are increasingly being required within public buildings and power stations, as well as traditional Petro/Chem industries. The cable is designed to carry on working for a period of 3 hours when exposed to fire, according to IEC 60331 test procedure. BFOU also offers good screening properties, reducing Electro Magnetic Interference (EMI). Construction Tinned stranded copper conductor, MICA tape, EPR insulation, overall screen of Copper backed Polyester tape with a stranded copper drain wire 0.75mm², inner sheath of Halogen Free Thermoset Elastomer, tinned copper wire braid and an outer sheath of Halogen Free Thermoset Elastomer. The individually screened version has a Copper backed Polyester tape with a stranded copper drain wire 0.75mm² around each pair or triple. Core colors Pairs ‐ Light blue, black Triples ‐ Light blue, black and brown Each pair or triple is identified by a numbered tape. IEC Cable Types and Construction
  • 12. The most common sheath material for data cabling in use in the UK is PVC. For many environments, PVC is the ideal material, having superior mechanical characteristics and high reliability. However, in a fire, PVC emits heavy black smoke mixed with hydrochloric acid, thus reducing vision, immediately impairing breathing, and additionally initiating corrosion of all equipment exposed to the fumes. For improved fire performance, it is common for LSZH Low Smoke Zero Halogen (usually meeting IEC61034, IEC60754‐2 and IEC60332‐3) cable sheaths to be used within Europe. The major Standards in common use are shown in the table. IEC Cable Types and Construction
  • 13. IEC Cable Tests for Fire Applications
  • 14. Typical IEC Cable Tests Fire Resistant Test – IEC60331‐21 Under long fire exposure, the cable must maintain the power supply for vital safety equipment (emergency lighting, alarm, systems & fire pumps, etc.) Smoke Density Test – IEC61034‐1/2 The smoke density test evaluates the smoke emissions of the cable and the jacket construction. Test under fire condition – IEC60332‐3 Flame retardant test simulating cables installed in bunch on a vertical ladder under fire conditions.
  • 15. IEC60332‐1‐2 Single wire or cable • A test on a single length of cable 600mm long held between 2 clamps. • The flame is applied for a predetermined amount of time based on the weight of the cable. • To pass the test there should not be any visible damage or charring within 50mm of the lower edge of the top clamp (Equal to 425mm higher than the flame source) once all combustion has stopped. • This test replaces IEC60332‐1, BS4066 pt 1 & BS EN 50265‐2‐1.
  • 16. IEC60332‐3 “The ladder test” • The IEC60332‐3 ranges of tests are conducted on bunches of cables and are much closer to a real life installation. 3.5m Lengths of cables are bunched onto a cable ladder in a chimney simulating a building riser. • The volume of cable on the ladder is determined in litres of combustible material to offer a balanced view of performance across a cable range. • A flame is applied 500mm from the base of the ladder for a predetermined time. When the burner has extinguished a one hour after‐burn period is allowed then the cables are checked for performance. • To pass the tests the cables should not be affected by the flame 2.5m above the flame source.
  • 17. IEC60332‐3 categories Test Qty of material Flame application Supersedes 60332‐3‐22 Cat A 7.0 litres 40 minutes IEC60332‐3A BS4066 pt 3A 60332‐3‐23 Cat B 3.5 litres 40 minutes IEC60332‐3B BS4066 pt 3B IEC60332‐3‐24 Cat C 1.5 litres 20 minutes IEC60332‐3C BS4066 pt 3C IEC60332‐3‐25 Cat D 0.5 litres 20 minutes 60332‐3‐21 Cat A F/R Used for large O.D cables instead of “3‐22 Cat A”. The cables are mounted on the front and back of the ladder • All these tests are to be conducted on complete cables. • Compounds alone cannot be tested to IEC60332
  • 18. Fire Resistant Testing • A cables ability to continue operating safely during a fire. Also referred to as circuit integrity. • Widely used in commercial/public buildings & MOG applications to control fire alarm/monitoring systems, emergency lighting, fire shutters and emergency evacuation equipment.
  • 19. European Fire Standards • Standard Ref. Performance requirement • IEC60331 Cables ≤ 0.6/1kV. 3 hours at 750°C (1970 edition) • IEC60331‐21 Cables ≤ 0.6/1kV 90 minutes @ 750°C (unless alt. stated in the cable spec) • IEC60331‐23 Data cables 90 minutes @ 750°C • IEC60331‐25 Optical fibre 90 minutes @ 750°C • IEC60331‐31 Cables ≤ 0.6/1kV 120 minutes @ 830°C with vibration • VDE0472 FE180 This test is equal to IEC60331 (1970 edition) • DIN 4102 E30 Complete system integrity for 30 minutes • DIN 4102 E90 Complete system integrity for 90 minutes
  • 20. Smoke Emission & Toxic Gas • Obscuration of vision and toxic gas are the main threat to people during a fire leading to disorientation and chocking from fumes. Death is normally caused by . choking rather than flames. Reducing smoke & fume emissions is vital to enable safe evacuation. • Equipment damage is caused by HCl gases mixing with moisture from the sprinkler systems and creates acid rain leading to long term component failure even if the equipment does not look damaged. • Not all materials that are low smoke are halogen free, examples : • LS‐PVC (Limited Smoke PVC to UL1685) • Fluorocarbons (PTFE, FEP etc.) • “Type B” CSP to BS6883 (1991)
  • 21. European Smoke Testing • IEC 61034‐2: A one meter sample of cable (or a bundle of cables depending on the outer diameter) is placed in a 3m cube and subjected to combustion by an alcohol produced flame for 20 minutes. The light transmission through the cube should not fall below 60% during the test (at peak or total) • Measurement method : • 100W halogen light source sensed by a photoelectric cell positioned on the opposite side of the smoke cube. • IEC61034‐2 is the most popular test used for cable in Europe. • IEC61034‐1 covers the apparatus required and test procedure.
  • 22. Toxic Gas Evolution IEC60754 • IEC60754‐1 (BS EN 50267 pt1) measures the amount of hydrochloric acid (HCl) evolved during burning. The result is normally expressed as a percentage of the sample weight. There is no pass/fail criteria. • This method is not suitable for testing cables classed as “Zero Halogen“ and compounds containing less than 5mg/g (5%) • IEC60754‐2 (BS EN 50267 pt2) measures the corrosiveness of the evolved gas in terms of acidity (pH) and conductivity. IEC 60754‐2 recommended values are : • pH > 4.3. & Conductivity of combustion gases < 10 mS/mm
  • 23. Panel Wiring to IEC requirements Most of Europe abides by IEC (International Electrotechnical Commission) wiring color codes for AC branch circuits. The older color codes in the table reflect the previous style which did not account for proper phase rotation. The protective ground wire (listed as green‐yellow) is green with yellow stripe. Function Label Current Color IEC Old Color IEC Protective Earth PE Green‐Yellow Green‐Yellow Neutral N Blue Blue Line, single Phase L Brown Brown or Black Line, 3 phase L1 Brown Brown or Black Line, 3 phase L2 Black Brown or Black Line, 3 phase L3 Grey Brown or Black The United Kingdom now follows the IEC AC wiring color codes. The table below lists these along with the obsolete domestic color codes. Function Label Current Color UK Old Color UK Protective Earth PE Green‐Yellow Green‐Yellow Neutral N Blue Black Line, single Phase L Brown Red Line, 3 phase L1 Brown Red Line, 3 phase L2 Black Yellow Line, 3 phase L3 Grey Blue
  • 24. Example of old UK wiring colors The use of color coded ferrules or sleeves is typically left up to the client/user preference. Either practice is acceptable to relevant IEC standards.
  • 25. Cable Gland Selection Criteria Cable glands used in enclosures intended for use in a hazardous area must meet with the same criteria as the enclosure to which they are connected. For example, cable glands used on an EEx‘e’ enclosure must meet the requirements for the enclosures of the EEx‘e’ standard i.e. must be capable of withstanding a 7Nm impact and capable of maintaining an ingress protection of at least IP54.
  • 26. Testing Procedures for Cable Glands IP 66 Testing – 100 liters of water for 3 minutes from 2.5 to 3 meters Continuity Testing of Armor – Gland is heated and cooled over time and resistivity should not change more than 10% Tork Test – Multiple spanners to prescribed tension with no damage on disassembly
  • 27. Impact Test – I kg falling from 70cm or 7 joules. No damage to gland Pressure Test – Minimum of 450 psi without leakage for Ex ‘d’, 2000 psi for UL2225 requirements Load Test – Unarmored cable gland with mandrel to not slip more than 6 mm over 6 hrs. Testing Procedures for Cable Glands
  • 28. Wiring Methods Wiring concepts Offshore follow the established & prevailing Marine standards, e.g. IEC 60092‐352 Metallic parts (including armour) shall be earthed effectively to prevent them from becoming live. Cable Armour/Braid provides a means of good earth continuity as well as mechanical protection. Normal practice has been to use external grounding as the most direct route to earth. This is easily achieved with metallic cable glands in non metallic enclosures by the use of an earth tag Shrouds have been found to be an ineffective means of keeping water out of enclosures and glands are typically not used for North Sea applications any more
  • 29. Wiring Methods – Shielding EMI Protection A Screened Cable entering shielded enclosure • Assists in protection against Radiated Emissions 360o Cable shielding provides optimum performance for EMC as opposed to ‘pig tail’ techniques. Metallic glands are an essential part of the system design in respect of Electromagnet protection. Non metallic glands create the weak link in the system between shielded cable and enclosure. Two forms of EMI/RFI to consider • Conducted Emissions (Generated & Susceptibility) • Radiated Emissions (Generated & Susceptibility)
  • 30. Typical Ex d & e armored cable gland Components of Typical Ex e & d cable gland…. Front End Deluge Seal Armor Cone Clamping Ring Back End Inner Seal Outer Seal
  • 31. Ex d & Ex e Requirement for Ex d cable glands for equipment < 2 litres • Screwed entry threads must maintain flame path • Inner seal must be explosion proof and gas tight • Trend is to use dual certified Ex d & Ex e Inner & Outer Seals Installation of Ex ‘ed’ gland Locknut Not unusual to use the identical gland for both Ex d and Ex e applications for less confusion in installation in the field….
  • 32. Installation of Ex ‘d’ barrier gland Seal required to withstand a pressure of 450 PSI (31 bar) for 2 minutes Pressure Flame Hot Gases Epoxy Resin Compound Flame Path Direct Entry into Zone 1, Ex ‘d’ enclosure over 2 liters volume With Arcing Sparking Devices and Zone 1 or 2, IIC applications… Flame Path Exhaust Routes
  • 33. Cable A Cable D Cable B Cable C Cable E Which type is suitable for use with Flameproof Ex d equipment using a gland with an ELASTOMERIC seal? Incorrect Shape, Cables Should be Round No Inner Sheath, Extruded Bedding or Suitable Fillers Correct Cable, e.g. has an extruded inner bedding û û û û ü Sample of Cable Types
  • 34. IEC60079‐15 Cable Gland Selection Chart In general, about 90% of the application for hazardous location cable glands can be fulfilled with the use of a non‐barrier compound gland…
  • 35. Wiring Methods – Typical Norwegian Installation Practice
  • 36. Wiring Methods – Typical Norwegian Installation Practice
  • 37. Direct Entry, Gland Type EEx d Barrier Type if volume > 2 litres Indirect Entry, Gland Type EEx e or Dual Certified EEx e/EEx d gland Ignition Source Direct and Indirect Entry Ex e & Ex d Enclosures
  • 38. Gland Type Ex D Barrier Type providing gas tight Bi‐Directional seal. Gland must be certified Ex nR Gland Type Ex d/Ex e incorporating internal seal that provides Bi‐Directional Gas‐tight seal. Direct Entry Ex nR Equipment
  • 39. Wiring Methods – Cable Gland usage UK Equipment Market Sector Cable Cable Glands Ex e 95% Ex d 5% Brass "Armored" Exd / Ex e Cable Gland 99% Brass "Armored" Ex d Compound Barrier Gland 1% Braid Armor 98% Brass "Unarmored" Ex d / Ex e Cable Gland 99% "Unarmored" Plastic Ex e Cable Gland 1% Unarmored 2% UK Offshore Hazardous Areas
  • 40. Thread Information and Accessories The standardization of thread type in the IEC world is typically around the Metric straight thread. However, other thread types do exist in the IEC world and if not Metric or a variation of, are a PG, BSP or BST thread type. Accessories that are commonly used are: Cable Shrouds – Becoming increasingly less used as they have a tendency to hold water in and cover up potential corrosion with glands. Earth Tags – Otherwise known as “Banjos” or “Frying Pans”. Used to provide a means to ground the cable gland typically when used in non‐metallic enclosures. Locknuts – Typically used to secure the cable gland to the enclosure.
  • 41. Thread Information and Accessories (Cont.) With the various threads used, thread adaptors and reducers are a common accessory widely used. One key point is that it is not allowed to reduce a reducer… Shaker Washers – Typically used between the locknut and inside of an enclosure, shaker washers are used to provide a means to keep vibrations from loosening the cable gland to the enclosure. IP washers – As the name implies, IP washers help maintain the IP rating between the cable gland and the enclosure… If you have a cable gland in a clearance hole, you have a metal to metal (or plastic) surface that provides no better than IP54 protection. IP washers go between the face of the gland and the outside of the enclosure. Drains – EEx e drains that allow condensation to drain from the inside of enclosures due to moisture buildup during the normal heating and cooling process during the day and night.
  • 42. Cable gland spacing on enclosures Cable glands clearance holes need to be considered when determining number and sizes of glands installed in enclosures. Always confirm gland cross corner clearance with manufacturer and template size of enclosure to confirm whether enough space exists for gland entries…
  • 43. A note on single core cables entering enclosures Eddy currents can overheat iron or steel cabinets, locknuts or bushings or any ferrous metal that completely encircles the single conductor cables. This presents no problem in multi‐conductor cables, where the magnetic fields tend to cancel each other out. For single core cables, it is recommended that these cables enter metal enclosures through a non‐ferrous plate such as aluminum….
  • 44. Cable gland spacing on enclosures Traditional use of cable glands entering into an Ex e enclosure need a significant amount of excess space to allow for the use of a spanner or wrench to tighten the gland. The use of cabinet seals certified to Ex e can reduce the footprint of the enclosure required by as much as 50% or allow a doubling of cables to enter in the same space as traditional cable glands.
  • 45. Ex ‘d’ Seals and Conduit Systems Conduit Seals are commonly used with conduit systems for direct entry into EEx d enclosures. The maximum allowed distance from enclosure is 450mm. Like the US, installations also require seal fittings at boundaries. Also, all Ex d conduit bodies must be sealed when entries are 50mm or larger housing taps, splices, joints or terminals. Conduit systems have a slightly different requirement in that countries typically mandate max. fill. In the case of most of the southern European countries, a max. fill of 60% is allowed. This differs with US regulations of typically 40% maximum conduit fill. Conduit systems are usually limited to 3000V or less. Above 3000V, cable systems are required…
  • 46. All switching mechanisms should be omni polar where the neutral wire is always cut ‐MINIMUM allowed wire sizes : ‐ Auxiliary Circuits (Controls) 1.5 mm/sq. ‐ Power Circuits 2.5 mm/sq. ‐ Cables should be 3000V min. and “flame‐retardant” type Cables MUST protected against insulation damage generally due to : ‐ Impact damage ‐ Heat sources that could damage cables insulation ‐ Chemical substances that could cause insulation cables corrosion In order to comply with above mentioned requirements, a proper choice of cables and cable routing is very important. If “Cables Pass” far away from any place with risk of corrosion or accidental damage (i.e. cables for ceiling mounted lighting fixtures) a standard PVC insulated cables in proper cable trays are allowed. When cables come down to working areas, or pass beside to valves or other equipment that might release heat or corrosive substances that might damage cables insulation, it is recommended to pass relevant cables inside a galvanized steel pipes. If cables go to vibrating machines (example: electrical motors) pipes should be flexible hoses, for the last 500mm approx. connected to special cable glands with female threaded head which allow for flexible hoses direct connection to the gland nut, without leaving any part of cables uncovered. Typical Wiring Practices with Conduit
  • 47. Typical Wiring Practices with Conduit Conduit for mechanical protection Flexible Conduit for vibration and mechanical protection
  • 48. Typical Wiring Practices with Conduit IEC 61386 is the new European standard governing the performance of flexible conduit (and rigid) systems in electrical installations. Superseding the current European flexible conduit systems standards, EN 50086, IEC 61386 covers performance requirements for use of such products in electrical installation applications. The performance requirements covered include fatigue life, bend radius, operating temperature, non‐flame propagation, IP ratings, impact resistance and pull‐off strength Tests to be carried out under IEC 61386: The new IEC 61386 standard requires a number of tests to be carried out on specimen conduit materials. These include: The Impact Strength Test ‐ This is carried out on conduits over a range of different temperatures. The test is made on each specimen using an impact head with a defined profile. Conventionally, fracture behavior is studied, but under this test, it is the deformation (buckling) behavior that is also determined. The specimen passes the test if no fracture occurs after impact, and there is also no excessive permanent deformation.
  • 49. Typical Wiring Practices with Conduit The Peak Load Test ‐ Under the requirements of this test, carried out on conduit specimens under standard ambient conditions (which is specified as 23°C at 50% relative humidity), the conduit is deformed by a defined amount between two plates. The Reverse Bending Test (With Swinging Movements) ‐ This test is based on a cyclic reversed bending of conduits under various temperatures. Under the requirements for the test, conduits are dynamically loaded and evaluated over the temperature limits. The number of bending cycles taken to fracture the conduit determines its strength. The Self‐Extinguishing Test ‐ Under the requirements for this test, the conduit is exposed to a flame (from a standard burner). The time to ignition (if any), the flame propagation, and the time to self‐extinguishing after flame removal are all parameters measured.
  • 50. Typical Wiring Practices with Cable A typical method of making final terminations to enclosures is to leave excess cable in a loop configuration to relieve any potential undue strain on the cable gland, and allow easier modifications if equipment needs to be replaced or repaired..