Comparative analysis of three phase,
five phase and
six phase symmetrical components
with MATLAB
Presented by,
Shridhar B. Kulkarni
RIT, Islampur
OUTINES
1. Introduction
2. Three phase Symmetrical components
3. Five phase Symmetrical components
4. Six phase Symmetrical components
5. MATLAB coding
6. Conclusion
7. References
1. Introduction
 Multiphase systems are most applicable in case of transmission
lines and many electrical operations.
 The power system generally operates in normal and balanced
state with 3 ph. Sinusoidal waveforms.
 The disturbance occurs in system i.e. faults takes place in the
system ,which may be S.C. faults (viz. LG, LL, LLL, LLG) etc.
 Fortescue Theorem
 For analysis, provision by symmetrical components to solve
system problems is much simpler, due to which resulting equations
is linearly mutual independent if system in balance state.
2.THREE PHASE SYMMETRICAL COMPONENTS
In the power system, three phase symmetrical components refers to +
ve, -ve and zero Sequence.
1. Positive sequence components consist of ‘abc’ phase sequence
which displaces with 120° from each other.
2. Negative sequence components consist of ‘acb’ phase sequence
which displaces with 120° from each other and which is opposite to
original phases.
3. Zero sequence components have three components of same
magnitudes with no angular displacement between all phases.
210 aaa VVVV 
21
2
0 aab yVVyVV 
2
2
10 aaC VyyVVV 
Vabc = [Y]* [V012]











2
2
1
1
111
yy
yyY
Continued..
Fig.2(a)
Positive Sequence
Fig.2(b)
Negative Sequence
Fig. 2(c)
Zero Sequence
Fig 2: Three phase symmetrical components
3. FIVE PHASE SYMMETRICAL COMPONENTS
As per the Fortescue theorem, the set of unbalanced phasor quantity of six-phase
system can be broke up into balanced system of voltages and currents to number of
phases equal to number of components involved in analysis. The phase differences
between every two adjoining vectors are equivalent to 2π/n .
Adjacent Positive-sequence components: The phase sequence of this type of
component has same as the main unbalanced five phase system. The magnitude of
these components is same and they are displaced from each other by 72° apart.
Adjacent Negative-sequence components: This type of component has exactly
opposite phase sequence than that of original five phase system. The magnitude of
these components is same and they are displaced from each other by 72° apart.
Non-adjacent Positive-sequence components : These components are displaced
from each other by 72°with equal magnitude. These phasors rotate as the
nonadjacent original unbalanced five-phase system components rotates .
Continued…
Non-adjacent Negative-sequence components : This type of component has
exactly opposite phase sequence than that of non-adjacent original unbalanced five
phase system. The magnitude of these components is same and they are displaced
from each other by 72° apart.
Zero-sequence components : The magnitude of these components is same and they
are displaced from each other by 0° apart.
Equations are as follows:
.
Where, Vsc= symmetrical components of voltage. In matrix form five phase
symmetrical components can be represented as follows:
Where,
.
Fig. 3(a)
Adjacent Positive-sequence
Fig. 3(b)
Adjacent Negative-sequence
Fig. 3(c)
Zero Sequence
Fig. 3(d)
Non-adjacent Positive sequence
Fig.3(e)
Non-adjacent Negative-sequence
Fig 3: Five phase symmetrical components
4. SIX PHASE SYMMETRICAL COMPONENTS
 As per the Fortescue theorem, the six-phase system can also be broke up into two
set of symmetrical components of voltages and currents which consisting of first
set of sequence components (a, b, c) and second set of sequence components
(a', b', c').
 The first set of components are consisting of first positive, first negative and first
zero sequence components where as the second set of components consist of
second zero, second positive and second negative sequence components.
 First zero sequence component: The first zero sequence components comprise
of three phasors whose magnitudes are equal and displaced from each other by
zero.
 First positive sequence component :The First positive sequence components
consisting three set of phasors in equal magnitude and they are displaced by 120
deg. apart. The phase sequence of these components is same as original phasors.
Continued…
 First negative sequence component :The first negative sequence components
consisting three set of phasors in equal magnitude and they are displaced by
120deg. apart. The phase sequence of these components is exactly
opposite to the original phasors.
 Second zero sequence component :The second zero sequence components
contain three phasors which are equal in magnitude and zero phase displacement
from each other.
 Second positive sequence component :The second positive sequence
components are comprised of three sets of phasors which are equal magnitude
and they are displaced by 120 degrees apart. The phase sequence of these
components is same as original phasors.
 Second negative sequence component :The second negative sequence
components consisting three set of phasors in equal magnitude and they are
displaced by 120 deg. apart. The phase sequence of these components is exactly
opposite to the original phasors.
.
 For consideration of six phase unbalanced voltages of the order [Vabcdef] by
using matrix transformation [Y] to obtain symmetrical components of order [Vsc]
can be represented is as follows:
Vabcdef = [Y]* [Vsc]
Where,
Here, y is the operator causes rotation of 60deg. in anti-clockwise direction.
Fig.4(a)
First Zero Sequence
Fig.4(b)
First Positive Sequence
Fig.4(c)
First Negative Sequence
Fig.4(d)
Second Zero Sequence
Fig.4(e)
Second Positive Sequence
Fig. 4(f)
Second Negative Sequence
Fig 4: Six phase symmetrical components
CONCLUSION
1. The unsymmetrical ‘N’ phasors can be solved in all ‘N’
symmetrical phasors by using linear complex transformation
2. In six phase system it is observed that two three phase
systems are formed in which each three phase system has
three symmetrical components where as in five phase system
one zero sequence component and two adjacent and two non
adjacent components are present.
3. The MATLAB coding is done to obtain three phase, five
phase and six phase symmetrical components
REFERENCES
[1]James E. Brittain, ‘Scanning the Past: Charles L. G. Fortescue and Method of
Symmetrical Components’, Proceedings of IEEE, Vol. 86(5), pp. 1020-1021, May
1998.
[2] Hadi Sadat, Power Systems Analysis, Tata McGraw Hill Edition, India, pp. 400-
406, 2002.
[3] Iranna Korachagaon “Five-Phase Unbalanced System and its Symmetrical
Components with MATLAB” IEEE conference on Electronic Systems, Signal
Processing and Computing Technologies (ICESC), pp.174-177, 2014
[4] Saifullah Payami Atif Iqbal “Analytical and Graphical Tool to Analyse Unbalanced
Five-Phase Supply System” International J. of Recent Trends in Engineering and
Technology ,Vol. 3, No. 3, May 2010.
[5] E. H. Badawy, M. K. El-Sherbiny, A. A. Ibrahim, M. S. Farghaly,
“A method of analyzing unsymmetrical faults on six phase power systems” IEEE
Transactions on Power Delivery, Vol. 6, Issue: 3, pp. 1139 – 1145, July 1991.
MATLAB Code: My IEEE paper, Click On link
given below
https://ieeexplore.ieee.org/document/8073507
Contact us:
Shreedhar.kulkarni65@gmail.com

More Related Content

PPTX
Gauss Siedel method of Load Flow
PPTX
Symmertical components
PPTX
Per unit representation
PPTX
Classification Of Power System Stability
PPT
Functions and performance requirements of excitation systems
PPT
Lec # 07 parallel operation of synchronous generators
PPTX
Electrical machines lecture notes
PPT
Lecture 10
Gauss Siedel method of Load Flow
Symmertical components
Per unit representation
Classification Of Power System Stability
Functions and performance requirements of excitation systems
Lec # 07 parallel operation of synchronous generators
Electrical machines lecture notes
Lecture 10

What's hot (20)

PPTX
Three Phase Separately Exited Drives
PPT
Symmetrical components
PPTX
Automatic Generation Control
PPT
Two port networks unit ii
PPTX
Lec 3 desgin via root locus
PPTX
Presentation1
 
PDF
Compare star and delta connection. electrical engineering q a
PPTX
Three phase power measurement using 2 wattmeter
PPTX
symmetrical component of power system
PPTX
Supply systems
PDF
Power system calculations
DOCX
Exp 4 (1)4. Gauss Siedal Load flow analysis using Matlab Software.
PPTX
Induction generator
PDF
Introduction to control system
PDF
Electronics 1 : Chapter # 07 : AC Analysis BJT
PDF
Lab manual psd v sem experiment no 6
PPTX
3-phase circuit
PPTX
Inter Connected Power System (2170901)
PPT
Inverter PPT.ppt
PPT
Two port networks
Three Phase Separately Exited Drives
Symmetrical components
Automatic Generation Control
Two port networks unit ii
Lec 3 desgin via root locus
Presentation1
 
Compare star and delta connection. electrical engineering q a
Three phase power measurement using 2 wattmeter
symmetrical component of power system
Supply systems
Power system calculations
Exp 4 (1)4. Gauss Siedal Load flow analysis using Matlab Software.
Induction generator
Introduction to control system
Electronics 1 : Chapter # 07 : AC Analysis BJT
Lab manual psd v sem experiment no 6
3-phase circuit
Inter Connected Power System (2170901)
Inverter PPT.ppt
Two port networks
Ad

Similar to Comparative analysis of 3 phase, 5 phase and 6 phase symmetrical components with MATLAB (20)

PPT
Topic 4 Symmetrical components LECTURE.ppt
PPTX
Power System -II-1 Unit -1 Lecure -1.pptx
PPT
Synthesis of unsymmetrical phasors from their symmetrical components
PPTX
Routh hurwitz stability criterion
PPTX
SUBHADIP POWER SYSTEM.pptx
PPT
Stabiltiy & R-H Ccriterion
PPTX
Symmetrical component
PPTX
Lec 20.pptx
PPTX
Symmetrical Components in fault analysis.pptx
PPTX
Classical control 2(3)
PPTX
Classical control 2(1)
PPTX
Classical control 2
PPTX
Classical control 2(2)
PDF
Lecture_ 03 ( updated with maths).pdf
PPTX
Oscillation ppt
PPTX
Lecture no 4 power system analysis elc353 et313
PDF
BEF43303_-_201620171_W5 Analysis of fault.pdf
PDF
EEP303: Exp1
PDF
Stability criteria and Analysis_Control Systems Engineering_MEB 4101.pdf
PPT
3 phase ac circuit
Topic 4 Symmetrical components LECTURE.ppt
Power System -II-1 Unit -1 Lecure -1.pptx
Synthesis of unsymmetrical phasors from their symmetrical components
Routh hurwitz stability criterion
SUBHADIP POWER SYSTEM.pptx
Stabiltiy & R-H Ccriterion
Symmetrical component
Lec 20.pptx
Symmetrical Components in fault analysis.pptx
Classical control 2(3)
Classical control 2(1)
Classical control 2
Classical control 2(2)
Lecture_ 03 ( updated with maths).pdf
Oscillation ppt
Lecture no 4 power system analysis elc353 et313
BEF43303_-_201620171_W5 Analysis of fault.pdf
EEP303: Exp1
Stability criteria and Analysis_Control Systems Engineering_MEB 4101.pdf
3 phase ac circuit
Ad

More from Shridhar kulkarni (6)

PPTX
Industrial training in Transformer manufacturing company
PPTX
ABC, an effective tool for selective harmonic elimination in multilevel inve...
PPTX
Simulation of transient skin effect of dc railway by shridhar kulkarni
PPTX
Speed control of dc motor using matlab
PPTX
The protection system for beginners
PPTX
Atc calculation methods by shridhar kulkarni
Industrial training in Transformer manufacturing company
ABC, an effective tool for selective harmonic elimination in multilevel inve...
Simulation of transient skin effect of dc railway by shridhar kulkarni
Speed control of dc motor using matlab
The protection system for beginners
Atc calculation methods by shridhar kulkarni

Recently uploaded (20)

PPTX
Construction Project Organization Group 2.pptx
PDF
PRIZ Academy - 9 Windows Thinking Where to Invest Today to Win Tomorrow.pdf
PPT
Introduction, IoT Design Methodology, Case Study on IoT System for Weather Mo...
PDF
TFEC-4-2020-Design-Guide-for-Timber-Roof-Trusses.pdf
PDF
The CXO Playbook 2025 – Future-Ready Strategies for C-Suite Leaders Cerebrai...
PPTX
Lecture Notes Electrical Wiring System Components
PPT
Project quality management in manufacturing
PPTX
FINAL REVIEW FOR COPD DIANOSIS FOR PULMONARY DISEASE.pptx
DOCX
573137875-Attendance-Management-System-original
PPTX
UNIT-1 - COAL BASED THERMAL POWER PLANTS
PDF
Mitigating Risks through Effective Management for Enhancing Organizational Pe...
PPT
Mechanical Engineering MATERIALS Selection
PDF
composite construction of structures.pdf
PPTX
Sustainable Sites - Green Building Construction
PPTX
Internet of Things (IOT) - A guide to understanding
PDF
Model Code of Practice - Construction Work - 21102022 .pdf
PDF
Mohammad Mahdi Farshadian CV - Prospective PhD Student 2026
PDF
Embodied AI: Ushering in the Next Era of Intelligent Systems
PDF
Well-logging-methods_new................
PDF
Enhancing Cyber Defense Against Zero-Day Attacks using Ensemble Neural Networks
Construction Project Organization Group 2.pptx
PRIZ Academy - 9 Windows Thinking Where to Invest Today to Win Tomorrow.pdf
Introduction, IoT Design Methodology, Case Study on IoT System for Weather Mo...
TFEC-4-2020-Design-Guide-for-Timber-Roof-Trusses.pdf
The CXO Playbook 2025 – Future-Ready Strategies for C-Suite Leaders Cerebrai...
Lecture Notes Electrical Wiring System Components
Project quality management in manufacturing
FINAL REVIEW FOR COPD DIANOSIS FOR PULMONARY DISEASE.pptx
573137875-Attendance-Management-System-original
UNIT-1 - COAL BASED THERMAL POWER PLANTS
Mitigating Risks through Effective Management for Enhancing Organizational Pe...
Mechanical Engineering MATERIALS Selection
composite construction of structures.pdf
Sustainable Sites - Green Building Construction
Internet of Things (IOT) - A guide to understanding
Model Code of Practice - Construction Work - 21102022 .pdf
Mohammad Mahdi Farshadian CV - Prospective PhD Student 2026
Embodied AI: Ushering in the Next Era of Intelligent Systems
Well-logging-methods_new................
Enhancing Cyber Defense Against Zero-Day Attacks using Ensemble Neural Networks

Comparative analysis of 3 phase, 5 phase and 6 phase symmetrical components with MATLAB

  • 1. Comparative analysis of three phase, five phase and six phase symmetrical components with MATLAB Presented by, Shridhar B. Kulkarni RIT, Islampur
  • 2. OUTINES 1. Introduction 2. Three phase Symmetrical components 3. Five phase Symmetrical components 4. Six phase Symmetrical components 5. MATLAB coding 6. Conclusion 7. References
  • 3. 1. Introduction  Multiphase systems are most applicable in case of transmission lines and many electrical operations.  The power system generally operates in normal and balanced state with 3 ph. Sinusoidal waveforms.  The disturbance occurs in system i.e. faults takes place in the system ,which may be S.C. faults (viz. LG, LL, LLL, LLG) etc.  Fortescue Theorem  For analysis, provision by symmetrical components to solve system problems is much simpler, due to which resulting equations is linearly mutual independent if system in balance state.
  • 4. 2.THREE PHASE SYMMETRICAL COMPONENTS In the power system, three phase symmetrical components refers to + ve, -ve and zero Sequence. 1. Positive sequence components consist of ‘abc’ phase sequence which displaces with 120° from each other. 2. Negative sequence components consist of ‘acb’ phase sequence which displaces with 120° from each other and which is opposite to original phases. 3. Zero sequence components have three components of same magnitudes with no angular displacement between all phases. 210 aaa VVVV  21 2 0 aab yVVyVV  2 2 10 aaC VyyVVV  Vabc = [Y]* [V012]            2 2 1 1 111 yy yyY
  • 5. Continued.. Fig.2(a) Positive Sequence Fig.2(b) Negative Sequence Fig. 2(c) Zero Sequence Fig 2: Three phase symmetrical components
  • 6. 3. FIVE PHASE SYMMETRICAL COMPONENTS As per the Fortescue theorem, the set of unbalanced phasor quantity of six-phase system can be broke up into balanced system of voltages and currents to number of phases equal to number of components involved in analysis. The phase differences between every two adjoining vectors are equivalent to 2π/n . Adjacent Positive-sequence components: The phase sequence of this type of component has same as the main unbalanced five phase system. The magnitude of these components is same and they are displaced from each other by 72° apart. Adjacent Negative-sequence components: This type of component has exactly opposite phase sequence than that of original five phase system. The magnitude of these components is same and they are displaced from each other by 72° apart. Non-adjacent Positive-sequence components : These components are displaced from each other by 72°with equal magnitude. These phasors rotate as the nonadjacent original unbalanced five-phase system components rotates .
  • 7. Continued… Non-adjacent Negative-sequence components : This type of component has exactly opposite phase sequence than that of non-adjacent original unbalanced five phase system. The magnitude of these components is same and they are displaced from each other by 72° apart. Zero-sequence components : The magnitude of these components is same and they are displaced from each other by 0° apart. Equations are as follows:
  • 8. . Where, Vsc= symmetrical components of voltage. In matrix form five phase symmetrical components can be represented as follows: Where,
  • 9. . Fig. 3(a) Adjacent Positive-sequence Fig. 3(b) Adjacent Negative-sequence Fig. 3(c) Zero Sequence Fig. 3(d) Non-adjacent Positive sequence Fig.3(e) Non-adjacent Negative-sequence Fig 3: Five phase symmetrical components
  • 10. 4. SIX PHASE SYMMETRICAL COMPONENTS  As per the Fortescue theorem, the six-phase system can also be broke up into two set of symmetrical components of voltages and currents which consisting of first set of sequence components (a, b, c) and second set of sequence components (a', b', c').  The first set of components are consisting of first positive, first negative and first zero sequence components where as the second set of components consist of second zero, second positive and second negative sequence components.  First zero sequence component: The first zero sequence components comprise of three phasors whose magnitudes are equal and displaced from each other by zero.  First positive sequence component :The First positive sequence components consisting three set of phasors in equal magnitude and they are displaced by 120 deg. apart. The phase sequence of these components is same as original phasors.
  • 11. Continued…  First negative sequence component :The first negative sequence components consisting three set of phasors in equal magnitude and they are displaced by 120deg. apart. The phase sequence of these components is exactly opposite to the original phasors.  Second zero sequence component :The second zero sequence components contain three phasors which are equal in magnitude and zero phase displacement from each other.  Second positive sequence component :The second positive sequence components are comprised of three sets of phasors which are equal magnitude and they are displaced by 120 degrees apart. The phase sequence of these components is same as original phasors.  Second negative sequence component :The second negative sequence components consisting three set of phasors in equal magnitude and they are displaced by 120 deg. apart. The phase sequence of these components is exactly opposite to the original phasors.
  • 12. .  For consideration of six phase unbalanced voltages of the order [Vabcdef] by using matrix transformation [Y] to obtain symmetrical components of order [Vsc] can be represented is as follows: Vabcdef = [Y]* [Vsc] Where, Here, y is the operator causes rotation of 60deg. in anti-clockwise direction.
  • 13. Fig.4(a) First Zero Sequence Fig.4(b) First Positive Sequence Fig.4(c) First Negative Sequence Fig.4(d) Second Zero Sequence Fig.4(e) Second Positive Sequence Fig. 4(f) Second Negative Sequence Fig 4: Six phase symmetrical components
  • 14. CONCLUSION 1. The unsymmetrical ‘N’ phasors can be solved in all ‘N’ symmetrical phasors by using linear complex transformation 2. In six phase system it is observed that two three phase systems are formed in which each three phase system has three symmetrical components where as in five phase system one zero sequence component and two adjacent and two non adjacent components are present. 3. The MATLAB coding is done to obtain three phase, five phase and six phase symmetrical components
  • 15. REFERENCES [1]James E. Brittain, ‘Scanning the Past: Charles L. G. Fortescue and Method of Symmetrical Components’, Proceedings of IEEE, Vol. 86(5), pp. 1020-1021, May 1998. [2] Hadi Sadat, Power Systems Analysis, Tata McGraw Hill Edition, India, pp. 400- 406, 2002. [3] Iranna Korachagaon “Five-Phase Unbalanced System and its Symmetrical Components with MATLAB” IEEE conference on Electronic Systems, Signal Processing and Computing Technologies (ICESC), pp.174-177, 2014 [4] Saifullah Payami Atif Iqbal “Analytical and Graphical Tool to Analyse Unbalanced Five-Phase Supply System” International J. of Recent Trends in Engineering and Technology ,Vol. 3, No. 3, May 2010. [5] E. H. Badawy, M. K. El-Sherbiny, A. A. Ibrahim, M. S. Farghaly, “A method of analyzing unsymmetrical faults on six phase power systems” IEEE Transactions on Power Delivery, Vol. 6, Issue: 3, pp. 1139 – 1145, July 1991.
  • 16. MATLAB Code: My IEEE paper, Click On link given below https://ieeexplore.ieee.org/document/8073507 Contact us: Shreedhar.kulkarni65@gmail.com