Introduction to Cabling Standards
and the impact of Data Centres on
the ICT industry
23rd November 2008
Paul Mathews MInstSMM
Global Channel Manager
Structured CablingNeed for Structured Cabling
1985 TR-42 Cabling Standards
– 1836 Telegraph
– 1876 Telephone
– 1911 Automatic switch
– 1948 Transistor
– 1950 PABX
– 1960 IBM S360 Computer
– 1980 PCs (Apple IBM)
– 1980 LANs (Ethernet )
– 1980 Telephone Switches
– 1990 10BASE-T
– 1995 100BASE-T
– 1999 1000BASE-T
– 2000 Video distribution
– 2000 Convergence
– 2006 10GBASE-T
Cabling StandardsCabling Standards
600 MHz600 MHz
• CATEGORY 7
– A NEW STANDARD PUBLISHED IN 2002
16 MHz16 MHz
• CATEGORY 3
– NOW ONLY USED FOR HIGH PAIR COUNT BACKBONE TELEPHONE CABLES
– SOMETIMES CALLED CW1308 IN UK 20 MHz20 MHz
• CATEGORY 4
– NOW RETIRED IN MODERN STANDARDS
100 MHz100 MHz
• CATEGORY 5
– THE MAJOR PRODUCT IN STRUCTURED CABLING
– CAT5 WAS UPGRADED TO “CAT5e” IN 2000 and
revamped again in 2002 250 MHz250 MHz
• CATEGORY 6
– A NEW STANDARD PUBLISHED IN 2002
– CAT 6A WAS RATIFIED 2008
500 MHz500 MHz
1000 MHz1000 MHz
• CATEGORY 7A
– DRAFT STANDARDS BEING REVAMPED FOR CLASS FA
Cabling StandardsCabling Standards
TIA 942TIA 942
DATA CENTRESDATA CENTRES
ISO/IEC 11801
Information Technology – Generic
cabling for customer premises
EN50173
Information technology. Generic cabling systems.
General requirements and office areas
ANSI EIA/TIA 568-B
Commercial Building Telecommunications
Cabling Standard
Cabling StandardsCabling Standards
• ANSI/TIA/EIA-568-A – first ratified in 1991 with the goal to specify a
structured cabling system with a projected usable life on at least 10 years
• 1995: TSB-72 introduced ‘Centralised fibre optic guidelines’
• 2001: TIA-568-B.1 incorporated centralised cabling into the standards
• 2005: TIA-568-B and 568-B.1 Addendum 5 added Telecommunication
Enclosures (TE) that enable optical fibre to be used and connected within
zone cabling
• New addendums added Gigabit Ethernet, Cat 6 and 850nm laser-
optimised 50um fibre
ICT EvolutionICT Evolution
• The need for faster and more bandwidth
(such as video streaming content)
• The need for more space as computer
rooms evolve, caused by larger storage
areas for:
Servers and communications cabling
Routers and switches, fibre channel
SAN equipment, storage devices,
keyboards and monitors
Security, access and CCTV equipment
Racks
• See Connectix Article 6 – Server cabinet installation
• See Connectix Article 21 – Why choose Cat 5e, 6 or 10G
The BAD
old days…
ICT EvolutionICT Evolution
• The average lifetime of cabling systems is
3 years
• Is the end user
maximising their
return on investment?
• Company expansion
• Development of
standards,
education and
best practice
installation
The new ICT age….
The data centre...What is a data centre?
• “A building or portion of a building whose
primary function is to house a computer
room and its support areas,” according to
TIA 942
• Includes redundant or backup power
supplies, redundant data communications
connections, HVAC, fire suppression and
special security devices
• Tier 1 – can be as small as a normal
computer room
• Tier 4 – mission critical computer systems
such as ISP hosting, financial services and
emergency services infrastructures
Drivers for DC'sDrivers for data centres
• Disaster backup
– 9/11, Buncefield Oil depot, Hurricane Katrina
• Data protection legislation
– Sarbanes-Oxley, Basel II
• Growth in online businesses
– Mail-order, internet gambling
• Growth in financial sector
– Share dealing, internet banking, credit card transactions
• Competition amongst universities for
‘distance-learning’ students
• Corporate organisations requiring security,
storage, resilience and back-up
• EU Data Retention Directive (Aug 2007), 2 years of call records
Data Ctr DynamicsData Centre Dynamics
1.0 Physical location of the data centre
2.0 Physical sizing and capabilities
3.0 Electrical systems to and within the data centre
4.0 Fire minimisation, detection, alarm and suppression
5.0 Heating, Ventilation and Air Conditioning (HVAC)
6.0 Communications Cabling within and to the data centre
7.0 Cabling containment within the data centre (including
raised floors)
8.0 Equipment racks and cabinets
9.0 Information Technology equipment
10.0 Security, Access and CCTV
11.0 Project management
12.0 Ongoing maintenance
Tier PerformanceData Centre Tier Performance
Tier Classifications per TIA-942 Standard
RequiredRequiredNot requiredNot requiredOperations Centre
0.41.622.028.8Downtime (hours
per year)
99.995%99.982%99.749%99.671%Site availability
Tier 4Tier 3Tier 2Tier 1
New technologyNew technology and techniques
• Connectix Express range offers
preterminated, pre-tested links that exceed
the performance requirements
– Express preterminated are available for Net 10G,
Net 6 or Net 5E and Fibre including Lightspeed
• Removes on-site termination, massively
reducing the time required to install
• Excellent performance is assured because
all the terminations are carried out by
skilled personnel in the UK
• Full performance testing of every link is
carried out prior to dispatch
• Pre-labelled with the required scheme
Pre terminated
copper and fibre
systems
Starlight MTPStarlight MTP
• Pre terminated MTP high density fibre optic
system for high speed networks
• 80% quicker to install over traditional pre
terminated fibre optics
• Supports future transmissions of 40Gbit
and 100Gbit/second
• Will provide 12 – 96 cores in 1u of rack space
(3mm diameter cables – less cable tray, less
air flow obstruction, easier cabinet entry and
easier fire-stopping)
Quality controlQuality control
• Working within an ISO 9001 quality regime
Connectix controls quality right from the
start
• A unique 100% testing programme
– Only Inferometer measuring equipment in the UK
for Lightspeed
– 12 months developing / training and equipping
– £80k investment in new facility in Braintree
• Connectix controls quality all the way
through the supply chain by only using
trained system integrators approved and
authorised and qualified distribution
partners
outstanding
quality and
performance
warranty…
Future EventsFuture Events
• Data Centre Design Principle Seminars, register at
www.connectixcablingsystems.com/register
• Exclusive to Connectix affiliates only
• Copper and fibre optic training courses – see
www.connectixcablingsystems.com/events
IET Endorsed
Training
provider
CIBSE Continuing
Professional Development BICSI Continuing Education Credits
Thank you

More Related Content

PPTX
IOT Presentation 100
PPT
PDF
5G Core Network - ZTE 5g Cloude ServCore
 
PPTX
Lte, lte a, and lte-a pro migration to 5 g training
PDF
The Zenic8 Story - emea master presentation
PDF
Making 5G NR a reality
PPTX
Next generation wireless networks crash course : Tonex Training
PPTX
Architecture of 5G technology
IOT Presentation 100
5G Core Network - ZTE 5g Cloude ServCore
 
Lte, lte a, and lte-a pro migration to 5 g training
The Zenic8 Story - emea master presentation
Making 5G NR a reality
Next generation wireless networks crash course : Tonex Training
Architecture of 5G technology

What's hot (18)

PDF
Nokia 5G Workshop Taiwan Oct 2016
PDF
Gigabit Passive Optical Network Presentation
PDF
Data Sheet SHDSL EFM Unit SUSE1
PDF
Essential infrastructure: A Siklu Presentation
PDF
The way to 5G
PDF
5G Architecture Viewpoints H2020 5G PPP Infrastructure Association
 
PPTX
5 g network & technology
PPTX
Tech 2 Tech - mobility, 15 October 2020
PDF
5G Technology
PDF
Evolving the network for 5G
PDF
LTE-Advanced Pro from Qualcomm
PDF
5G Vision for Future Networks From Use Cases to Implementation - Dr. Hamid Fa...
PPTX
INTRODUCTION OF 4G
PDF
5G Technology Tutorial
PDF
Materi seminar 5 g ieee comsoc lecture 5g evolution v2
PDF
LTE MTC: Optimizing LTE Advanced for Machine Type Communications
PDF
Ishiriya Wireless Technologies-4G Architecture, Networks and Protocols
Nokia 5G Workshop Taiwan Oct 2016
Gigabit Passive Optical Network Presentation
Data Sheet SHDSL EFM Unit SUSE1
Essential infrastructure: A Siklu Presentation
The way to 5G
5G Architecture Viewpoints H2020 5G PPP Infrastructure Association
 
5 g network & technology
Tech 2 Tech - mobility, 15 October 2020
5G Technology
Evolving the network for 5G
LTE-Advanced Pro from Qualcomm
5G Vision for Future Networks From Use Cases to Implementation - Dr. Hamid Fa...
INTRODUCTION OF 4G
5G Technology Tutorial
Materi seminar 5 g ieee comsoc lecture 5g evolution v2
LTE MTC: Optimizing LTE Advanced for Machine Type Communications
Ishiriya Wireless Technologies-4G Architecture, Networks and Protocols
Ad

Similar to Commercial Overview DC Session 1 Introduction To Cabling Standards And The Impact Of Data Centres On The Ict Industry (20)

PPT
Network Technology Presentation Bvh V01
PPT
BVH Network Technology Presentation
PDF
Commercial Overview DC Session 2 Optical Fibre In The Data Centre
PPT
Fundamentals and Basics
PDF
commscope_2023_Data_Center_Trends_eBook_LR.pdf
PPT
Chapter10
PPT
Structured cabling
PPT
Choosing the Right Cabling System for Health care Environments
PDF
PE Presentation
PPTX
Industrial Ethernet, Part 1: Technologies
PPT
CCS Presentation Company Intro, DC Cabling & Racks, Future Trends
PPT
Amp Future Cabling Systems
PDF
Comparing Copper and Fiber Options Data Center
PPT
CCS Presentation On Lda Oct 2010 (Compressed Pics) Parts 3 5
PPTX
Athens Datacentres And 10 G
PDF
Sumitomo Electric Lightwave_The 8 Fiber Solution for Today's Data Center_Apri...
PDF
Taking Your Network Cabling Infrastructure to 40/100G Ethernet
PPT
Jonathan Jew en Congreso Bicsi México 2015
PDF
Analyst Perspective - Next Generation Storage Networking for Next Generation ...
Network Technology Presentation Bvh V01
BVH Network Technology Presentation
Commercial Overview DC Session 2 Optical Fibre In The Data Centre
Fundamentals and Basics
commscope_2023_Data_Center_Trends_eBook_LR.pdf
Chapter10
Structured cabling
Choosing the Right Cabling System for Health care Environments
PE Presentation
Industrial Ethernet, Part 1: Technologies
CCS Presentation Company Intro, DC Cabling & Racks, Future Trends
Amp Future Cabling Systems
Comparing Copper and Fiber Options Data Center
CCS Presentation On Lda Oct 2010 (Compressed Pics) Parts 3 5
Athens Datacentres And 10 G
Sumitomo Electric Lightwave_The 8 Fiber Solution for Today's Data Center_Apri...
Taking Your Network Cabling Infrastructure to 40/100G Ethernet
Jonathan Jew en Congreso Bicsi México 2015
Analyst Perspective - Next Generation Storage Networking for Next Generation ...
Ad

More from paul_mathews (7)

PPT
Connectix Commercial Overview Dc Session 8 Using The Fear Model To Design...
PPT
CCCS Presentation - On Lda Oct 2010 Parts 1&2
PDF
Connectix Commercial Overview Dc Session 6 The European Code Of Conduct O...
PPT
Connectix Commercial Overview Dc Session 5 The Uk Carbon Reduction Commit...
PDF
Commercial Overview SCS Session 1 Server Rack Strategies
PDF
Commercial Overview DC Session 4 Introduction To Energy In The Data Centre
PDF
Commercial Overview DC Session 3 The Greening Of The Data Centre
Connectix Commercial Overview Dc Session 8 Using The Fear Model To Design...
CCCS Presentation - On Lda Oct 2010 Parts 1&2
Connectix Commercial Overview Dc Session 6 The European Code Of Conduct O...
Connectix Commercial Overview Dc Session 5 The Uk Carbon Reduction Commit...
Commercial Overview SCS Session 1 Server Rack Strategies
Commercial Overview DC Session 4 Introduction To Energy In The Data Centre
Commercial Overview DC Session 3 The Greening Of The Data Centre

Commercial Overview DC Session 1 Introduction To Cabling Standards And The Impact Of Data Centres On The Ict Industry

  • 1. Introduction to Cabling Standards and the impact of Data Centres on the ICT industry 23rd November 2008 Paul Mathews MInstSMM Global Channel Manager
  • 2. Structured CablingNeed for Structured Cabling 1985 TR-42 Cabling Standards – 1836 Telegraph – 1876 Telephone – 1911 Automatic switch – 1948 Transistor – 1950 PABX – 1960 IBM S360 Computer – 1980 PCs (Apple IBM) – 1980 LANs (Ethernet ) – 1980 Telephone Switches – 1990 10BASE-T – 1995 100BASE-T – 1999 1000BASE-T – 2000 Video distribution – 2000 Convergence – 2006 10GBASE-T
  • 3. Cabling StandardsCabling Standards 600 MHz600 MHz • CATEGORY 7 – A NEW STANDARD PUBLISHED IN 2002 16 MHz16 MHz • CATEGORY 3 – NOW ONLY USED FOR HIGH PAIR COUNT BACKBONE TELEPHONE CABLES – SOMETIMES CALLED CW1308 IN UK 20 MHz20 MHz • CATEGORY 4 – NOW RETIRED IN MODERN STANDARDS 100 MHz100 MHz • CATEGORY 5 – THE MAJOR PRODUCT IN STRUCTURED CABLING – CAT5 WAS UPGRADED TO “CAT5e” IN 2000 and revamped again in 2002 250 MHz250 MHz • CATEGORY 6 – A NEW STANDARD PUBLISHED IN 2002 – CAT 6A WAS RATIFIED 2008 500 MHz500 MHz 1000 MHz1000 MHz • CATEGORY 7A – DRAFT STANDARDS BEING REVAMPED FOR CLASS FA
  • 4. Cabling StandardsCabling Standards TIA 942TIA 942 DATA CENTRESDATA CENTRES ISO/IEC 11801 Information Technology – Generic cabling for customer premises EN50173 Information technology. Generic cabling systems. General requirements and office areas ANSI EIA/TIA 568-B Commercial Building Telecommunications Cabling Standard
  • 5. Cabling StandardsCabling Standards • ANSI/TIA/EIA-568-A – first ratified in 1991 with the goal to specify a structured cabling system with a projected usable life on at least 10 years • 1995: TSB-72 introduced ‘Centralised fibre optic guidelines’ • 2001: TIA-568-B.1 incorporated centralised cabling into the standards • 2005: TIA-568-B and 568-B.1 Addendum 5 added Telecommunication Enclosures (TE) that enable optical fibre to be used and connected within zone cabling • New addendums added Gigabit Ethernet, Cat 6 and 850nm laser- optimised 50um fibre
  • 6. ICT EvolutionICT Evolution • The need for faster and more bandwidth (such as video streaming content) • The need for more space as computer rooms evolve, caused by larger storage areas for: Servers and communications cabling Routers and switches, fibre channel SAN equipment, storage devices, keyboards and monitors Security, access and CCTV equipment Racks • See Connectix Article 6 – Server cabinet installation • See Connectix Article 21 – Why choose Cat 5e, 6 or 10G The BAD old days…
  • 7. ICT EvolutionICT Evolution • The average lifetime of cabling systems is 3 years • Is the end user maximising their return on investment? • Company expansion • Development of standards, education and best practice installation The new ICT age….
  • 8. The data centre...What is a data centre? • “A building or portion of a building whose primary function is to house a computer room and its support areas,” according to TIA 942 • Includes redundant or backup power supplies, redundant data communications connections, HVAC, fire suppression and special security devices • Tier 1 – can be as small as a normal computer room • Tier 4 – mission critical computer systems such as ISP hosting, financial services and emergency services infrastructures
  • 9. Drivers for DC'sDrivers for data centres • Disaster backup – 9/11, Buncefield Oil depot, Hurricane Katrina • Data protection legislation – Sarbanes-Oxley, Basel II • Growth in online businesses – Mail-order, internet gambling • Growth in financial sector – Share dealing, internet banking, credit card transactions • Competition amongst universities for ‘distance-learning’ students • Corporate organisations requiring security, storage, resilience and back-up • EU Data Retention Directive (Aug 2007), 2 years of call records
  • 10. Data Ctr DynamicsData Centre Dynamics 1.0 Physical location of the data centre 2.0 Physical sizing and capabilities 3.0 Electrical systems to and within the data centre 4.0 Fire minimisation, detection, alarm and suppression 5.0 Heating, Ventilation and Air Conditioning (HVAC) 6.0 Communications Cabling within and to the data centre 7.0 Cabling containment within the data centre (including raised floors) 8.0 Equipment racks and cabinets 9.0 Information Technology equipment 10.0 Security, Access and CCTV 11.0 Project management 12.0 Ongoing maintenance
  • 11. Tier PerformanceData Centre Tier Performance Tier Classifications per TIA-942 Standard RequiredRequiredNot requiredNot requiredOperations Centre 0.41.622.028.8Downtime (hours per year) 99.995%99.982%99.749%99.671%Site availability Tier 4Tier 3Tier 2Tier 1
  • 12. New technologyNew technology and techniques • Connectix Express range offers preterminated, pre-tested links that exceed the performance requirements – Express preterminated are available for Net 10G, Net 6 or Net 5E and Fibre including Lightspeed • Removes on-site termination, massively reducing the time required to install • Excellent performance is assured because all the terminations are carried out by skilled personnel in the UK • Full performance testing of every link is carried out prior to dispatch • Pre-labelled with the required scheme Pre terminated copper and fibre systems
  • 13. Starlight MTPStarlight MTP • Pre terminated MTP high density fibre optic system for high speed networks • 80% quicker to install over traditional pre terminated fibre optics • Supports future transmissions of 40Gbit and 100Gbit/second • Will provide 12 – 96 cores in 1u of rack space (3mm diameter cables – less cable tray, less air flow obstruction, easier cabinet entry and easier fire-stopping)
  • 14. Quality controlQuality control • Working within an ISO 9001 quality regime Connectix controls quality right from the start • A unique 100% testing programme – Only Inferometer measuring equipment in the UK for Lightspeed – 12 months developing / training and equipping – £80k investment in new facility in Braintree • Connectix controls quality all the way through the supply chain by only using trained system integrators approved and authorised and qualified distribution partners outstanding quality and performance warranty…
  • 15. Future EventsFuture Events • Data Centre Design Principle Seminars, register at www.connectixcablingsystems.com/register • Exclusive to Connectix affiliates only • Copper and fibre optic training courses – see www.connectixcablingsystems.com/events IET Endorsed Training provider CIBSE Continuing Professional Development BICSI Continuing Education Credits