INTRODUCTION
Cyber intrusions into US Critical Infrastructure systems are happening with increased
frequency. For many industrial control systems (ICSs), it’s not a matter of if an intrusion will
take place, but when. In Fiscal Year (FY) 2015, 295 incidents were reported to ICS-CERT, and
many more went unreported or undetected. The capabilities of our adversaries have been
demonstrated and cyber incidents are increasing in frequency and complexity. Simply building a
network with a hardened perimeter is no longer adequate. Securing ICSs against the modern
threat requires well-planned and well-implemented strategies that will provide network defense
teams a chance to quickly and effectively detect, counter, and expel an adversary. This paper
presents seven strategies that can be implemented today to counter common exploitable
weaknesses in “as-built” control systems.
Seven Strategies to Defend ICSs
Figure 1: Percentage of ICS-CERT FY 2014 and FY 2015 Incidents Potentially Mitigated by
Each Strategya
a. Incidents mitigated by more than one strategy are listed under the strategy ICS-CERT judged as more effective.
2
If system owners had implemented the strategies outlined in this paper, 98 percent of incidents
ICS-CERT responded to in FY 2014 and FY 2015 would have been prevented. The remaining
2 percent could have been identified with increased monitoring and a robust incident response.
THE SEVEN STRATEGIES
1. IMPLEMENT APPLICATION WHITELISTING
Application Whitelisting (AWL) can detect and prevent attempted execution of malware
uploaded by adversaries. The static nature of some systems, such as database servers and
human-machine interface (HMI) computers, make these ideal candidates to run AWL.
Operators are encouraged to work with their vendors to baseline and calibrate AWL
deployments.
Example: ICS-CERT recently responded to an incident where the victim had to rebuild the
network from scratch at great expense. A particular malware compromised over 80 percent
of its assets. Antivirus software was ineffective; the malware had a 0 percent detection rate
on VirusTotal. AWL would have provided notification and blocked the malware execution.
2. ENSURE PROPER CONFIGURATION/PATCH MANAGEMENT
Adversaries target unpatched systems. A configuration/patch management program centered on
the safe importation and implementation of trusted patches will help keep control systems more
secure.
Such a program will start with an accurate baseline and asset inventory to track what patches are
needed. It will prioritize patching and configuration management of “PC-architecture” machines
used in HMI, database server, and engineering workstation roles, as current adversaries have
significant cyber capabilities against these. Infected laptops are a significant malware vector.
Such a program will limit connection of external laptops to the control network and preferably
supply vendors with known-good company laptops. The program will also encourage initial
installation of any updates onto a test system that includes malware detection features before the
updates are installed on operational systems.
Example: ICS-CERT responded to a Stuxnet infection at a power generation facility. The
root cause of the infection was a vendor laptop.
Use best practices when downloading software and patches destined for your control network.
Take measures to avoid “watering hole” attacks. Use a web Domain Name System (DNS)
reputation system. Get updates from authenticated vendor sites. Validate the authenticity of
3
downloads. Insist that vendors digitally sign updates, and/or publish hashes via an out-of-bound
communications path, and use these to authenticate. Don’t load updates from unverified
sources.
Example: HAVEX spread by infecting patches. With an out-of-band communication path
for patch hashes, such as a blast email, users could have validated that the patches were not
authentic.
3. REDUCE YOUR ATTACK SURFACE AREA
Isolate ICS networks from any untrusted networks, especially the Internet.b
Lock down all
unused ports. Turn off all unused services. Only allow real-time connectivity to external
networks if there is a defined business requirement or control function. If one-way
communication can accomplish a task, use optical separation (“data diode”). If bidirectional
communication is necessary, then use a single open port over a restricted network path.
Example: As of 2014, ICS-CERT was aware of 82,000 cases of industrial control systems
hardware or software directly accessible from the public Internet. ICS-CERT has
encountered numerous cases where direct or nearly direct Internet access enabled a breach.
Examples include a US Crime Lab, a Dam, The Sochi Olympic stadium, and numerous water
utilities.
4. BUILD A DEFENDABLE ENVIRONMENT
Limit damage from network perimeter breaches. Segment networks into logical enclaves and
restrict host-to-host communications paths. This can stop adversaries from expanding their
access, while letting the normal system communications continue to operate. Enclaving limits
possible damage, as compromised systems cannot be used to reach and contaminate systems in
other enclaves. Containment provided by enclaving also makes incident cleanup significantly
less costly.c
b. ICS-ALERT-14-063-01AP, Multiple Reports of Internet Facing Control Systems, ICS-CERT 2015.
c. Improving Industrial Control Systems Cybersecurity with Defense in Depth, ICS-CERT 2009.
4
Example: In one ICS-CERT case, a nuclear asset owner failed to scan media entering a
Level 3 facility. On exit, the media was scanned, and a virus was detected. Because the asset
owner had implemented logical enclaving, only six systems were put at risk and had to be
remediated. Had enclaving not been implemented, hundreds of hosts would have needed to
be remediated.
If one-way data transfer from a secure zone to a less secure zone is required, consider using
approved removable media instead of a network connection. If real-time data transfer is
required, consider using optical separation technologies. This allows replication of data without
putting the control system at risk.
Example: In one ICS-CERT case, a pipeline operator had directly connected the corporate
network to the control network, because the billing unit had asserted it needed metering
data. After being informed of a breach by ICS-CERT, the asset owner removed the
connection. It took the billing department 4 days to notice the connection had been lost,
clearly demonstrating that real-time data were not needed.
5. MANAGE AUTHENTICATION
Adversaries are increasingly focusing on gaining control of legitimate credentials, especially
those associated with highly privileged accounts. Compromising these credentials allows
adversaries to masquerade as legitimate users, leaving less evidence than exploiting
vulnerabilities or executing malware. Implement multi-factor authentication where possible.
Reduce privileges to only those needed for a user’s duties. If passwords are necessary,
implement secure password policies stressing length over complexity. For all accounts,
including system and non-interactive accounts, ensure credentials are unique, and change all
passwords at least every 90 days.
Require separate credentials for corporate and control network zones and store these in separate
trust stores. Never share Active Directory, RSA ACE servers, or other trust stores between
corporate and control networks.
Example: One US Government agency used the same password across the environment for
local administrator accounts. This allowed an adversary to easily move laterally across all
systems.
5
6. IMPLEMENT SECURE REMOTE ACCESS
Some adversaries are effective at gaining remote access into control systems, finding obscure
access vectors, even “hidden back doors” intentionally created by system operators. Remove
such accesses wherever possible, especially modems as these are fundamentally insecure.
Limit any accesses that remain. Where possible, implement “monitoring only” access enforced
by data diodes, and do not rely on “read only” access enforced by software configurations or
permissions. Do not allow remote persistent vendor connections into the control network.
Require any remote access be operator controlled, time limited, and procedurally similar to
“lock out, tag out.” Use the same remote access paths for vendor and employee connections;
don’t allow double standards. Use two-factor authentication if possible, avoiding schemes
where both tokens are similar types and can be easily stolen (e.g., password and soft certificate).
Example: Following these guidelines would have prevented the BlackEnergy intrusions.
BlackEnergy required communications paths for initial compromise, installation and “plug
in” installation.
7. MONITOR AND RESPOND
Defending a network against modern threats requires actively monitoring for adversarial
penetration and quickly executing a prepared response.
Consider establishing monitoring programs in the following five key places:
1) Watch IP traffic on ICS boundaries for abnormal or suspicious communications.
2) Monitor IP traffic within the control network for malicious connections or content.
3) Use host-based products to detect malicious software and attack attempts.
4) Use login analysis (time and place for example) to detect stolen credential usage or
improper access, verifying all anomalies with quick phone calls.
5) Watch account/user administration actions to detect access control manipulation.
Have a response plan for when adversarial activity is detected. Such a plan may include
disconnecting all Internet connections, running a properly scoped search for malware, disabling
affected user accounts, isolating suspect systems, and an immediate 100 percent password reset.
Such a plan may also define escalation triggers and actions, including incident response,
investigation, and public affairs activities.
Have a restoration plan, including having “gold disks” ready to restore systems to known good
states.
6
Example: Attackers render Windows®d
based devices in a control network inoperative by
wiping hard drive contents. Recent attacks against Saudi Aramco™e
and Sony Pictures
demonstrate that quick restoration of such computers is key to restoring an attacked network
to an operational state.
CONCLUSION
Defense against the modern threat requires applying measures to protect not only the perimeter
but also the interior. While no system is 100 percent secure, implementing the seven key
strategies discussed in this paper can greatly improve the security posture of ICSs.
DISCLAIMER
The information and opinions contained in this document are provided “as is” and without any
warranties or guarantees. Reference herein to any specific commercial products, process, or
service by trade name, trademark, manufacturer, or otherwise, does not constitute or imply its
endorsement, recommendation, or favoring by the United States Government, and this guidance
shall not be used for advertising or product endorsement purposes.
ACKNOWLEDGMENT
This document “Seven Steps to Effectively Defend Industrial Control Systems” was written in
collaboration, with contributions from subject matter experts working at the Department of
Homeland Security (DHS), the Federal Bureau of Investigation (FBI), and the National Security
Agency (NSA).
d. Windows®
is a registered trademark of Microsoft Corp.
e. Saudi Aramco™
is an unregistered trademark of Saudi Arabian Oil Company.
7
CONTACT INFORMATION
POC Phone e-Mail
Department of Homeland Security
ICS-CERT
877-776-7585 ICS-CERT@HQ.DHS.GOV
Federal Bureau of Investigation
Cyber Division - CyWatch
855-292-3937 CyWatch@ic.fbi.gov
National Security Agency (Industry)
Industry Inquiries
410-854-6091 bao@nsa.gov
National Security Agency (Government)
IAD Client Contact Center
410-854-4200 IAD CCC@nsa.gov

More Related Content

PDF
CRASHOVERRIDE Analysis of the Threat to Electric Grid Operations. Cyber-attac...
PDF
Cheatsheet for your cloud project
PDF
20 Security Controls for the Cloud
PDF
TACTiCS_WP Security_Addressing Security in SDN Environment
PPTX
Industrial cyber threat landscape
PDF
Cisco amp everywhere
PDF
The Critical Security Controls and the StealthWatch System
CRASHOVERRIDE Analysis of the Threat to Electric Grid Operations. Cyber-attac...
Cheatsheet for your cloud project
20 Security Controls for the Cloud
TACTiCS_WP Security_Addressing Security in SDN Environment
Industrial cyber threat landscape
Cisco amp everywhere
The Critical Security Controls and the StealthWatch System

What's hot (17)

PDF
A Buyers Guide to Investing in Endpoint Detection and Response for Enterprise...
PDF
The Top 20 Cyberattacks on Industrial Control Systems
PPTX
Vulnerability Assesment
PPTX
Network Intrusion Detection and Countermeasure Selection
PPTX
RSAC 2021 Spelunking Through the Steps of a Control System Hack
PDF
Cisco amp for endpoints
PDF
Cisco amp for networks
PPTX
Six Steps to SIEM Success
PDF
Review of network diagram
PDF
Hands on Security, Disrupting the Kill Chain, SplunkLive! Austin
PDF
Advanced Threat Protection – ultimátní bezpečnostní řešení
PPTX
Extending the 20 critical security controls to gap assessments and security m...
PDF
FireEye Use Cases — FireEye Solution Deployment Experience
PDF
Web-style Wireless IDS attacks, Sergey Gordeychik
PDF
2 20613 qualys_top_10_reports_vm
PPTX
Proatively Engaged: Questions Executives Should Ask Their Security Teams
PDF
Gigamon - Network Visibility Solutions
A Buyers Guide to Investing in Endpoint Detection and Response for Enterprise...
The Top 20 Cyberattacks on Industrial Control Systems
Vulnerability Assesment
Network Intrusion Detection and Countermeasure Selection
RSAC 2021 Spelunking Through the Steps of a Control System Hack
Cisco amp for endpoints
Cisco amp for networks
Six Steps to SIEM Success
Review of network diagram
Hands on Security, Disrupting the Kill Chain, SplunkLive! Austin
Advanced Threat Protection – ultimátní bezpečnostní řešení
Extending the 20 critical security controls to gap assessments and security m...
FireEye Use Cases — FireEye Solution Deployment Experience
Web-style Wireless IDS attacks, Sergey Gordeychik
2 20613 qualys_top_10_reports_vm
Proatively Engaged: Questions Executives Should Ask Their Security Teams
Gigamon - Network Visibility Solutions
Ad

Viewers also liked (18)

PDF
Piping and Pipeline Accessories - Titan Flow Control, Inc.
PDF
Compact Clean Steam Generator
PDF
Titan Flow Controls Series CV-50 Check Valve
PDF
Rotor Insertion Flow Meter Technical Information
PDF
Back pressure valves for industrial process control
PDF
Sliding Gate Valve With Variable Orifice
PDF
Methods of Detecting Water Level in Steam Boilers
PDF
Heat Exchange Fundamentals for Shell and Tube Units
PDF
Super high efficiency coalescing filters for compressed air and gas
PDF
Fluoroseal Sleeved Plug Valves
PDF
Kunkle Safety and Relief Valves Technical Reference
PDF
BTU Metering Device For Process or Commercial Tenant
PDF
Crane FKX 9000 Triple Offset Butterfly Valves
PDF
OMB Valves USA Product Line Overview
PDF
Condensate Pumps for industrial steam systems
PDF
Pressure regulator valves for industrial process control
PDF
Wellhead Valves Technical Data
PPT
3 A Papermachine Steam Systems Part1
Piping and Pipeline Accessories - Titan Flow Control, Inc.
Compact Clean Steam Generator
Titan Flow Controls Series CV-50 Check Valve
Rotor Insertion Flow Meter Technical Information
Back pressure valves for industrial process control
Sliding Gate Valve With Variable Orifice
Methods of Detecting Water Level in Steam Boilers
Heat Exchange Fundamentals for Shell and Tube Units
Super high efficiency coalescing filters for compressed air and gas
Fluoroseal Sleeved Plug Valves
Kunkle Safety and Relief Valves Technical Reference
BTU Metering Device For Process or Commercial Tenant
Crane FKX 9000 Triple Offset Butterfly Valves
OMB Valves USA Product Line Overview
Condensate Pumps for industrial steam systems
Pressure regulator valves for industrial process control
Wellhead Valves Technical Data
3 A Papermachine Steam Systems Part1
Ad

Similar to Defending Industrial Control Systems From Cyberattack (20)

ODP
Cloud Computing
PDF
Cloud Computing Security
PDF
AN ISP BASED NOTIFICATION AND DETECTION SYSTEM TO MAXIMIZE EFFICIENCY OF CLIE...
PDF
Designing a security policy to protect your automation solution
PDF
Operational Technology Security Solution for Utilities
PDF
Welcome to International Journal of Engineering Research and Development (IJERD)
PDF
Marlabs cyber threat management
DOCX
Globally.docx
PDF
Evasion Streamline Intruders Using Graph Based Attacker model Analysis and Co...
PDF
Ijnsa050214
PPTX
Cloud Security_ Unit 4
PDF
Secure intrusion detection and countermeasure selection in virtual system usi...
PDF
INTRUSION DETECTION SYSTEM
DOCX
Include at least 250 words in your posting and at least 250 words in
PDF
Identified Vulnerabilitis And Threats In Cloud Computing
PDF
A017130104
PDF
Firewall buyers-guide
PDF
Toward Continuous Cybersecurity with Network Automation
PDF
Toward Continuous Cybersecurity With Network Automation
PDF
Types of Vulnerability Scanning An in depth investigation.pdf
Cloud Computing
Cloud Computing Security
AN ISP BASED NOTIFICATION AND DETECTION SYSTEM TO MAXIMIZE EFFICIENCY OF CLIE...
Designing a security policy to protect your automation solution
Operational Technology Security Solution for Utilities
Welcome to International Journal of Engineering Research and Development (IJERD)
Marlabs cyber threat management
Globally.docx
Evasion Streamline Intruders Using Graph Based Attacker model Analysis and Co...
Ijnsa050214
Cloud Security_ Unit 4
Secure intrusion detection and countermeasure selection in virtual system usi...
INTRUSION DETECTION SYSTEM
Include at least 250 words in your posting and at least 250 words in
Identified Vulnerabilitis And Threats In Cloud Computing
A017130104
Firewall buyers-guide
Toward Continuous Cybersecurity with Network Automation
Toward Continuous Cybersecurity With Network Automation
Types of Vulnerability Scanning An in depth investigation.pdf

More from Mountain States Engineering and Controls (20)

PDF
Design of Fluid Systems - Steam Utilization
PDF
Valves Used in Mining Operations
PDF
Regenerative Turbine Chemical Process Pumps
PDF
Dual Snap Pressure, Temperature and Flow Switches
PDF
Piston Isolation Valves For Steam and Condensate
PDF
Hydrostatic Pressure Liquid Level Transmitter
PDF
Steam Condensate Return Stations
PDF
Breathing Air Purifiers for Commercial and Industrial Use
PDF
Trunnion Mount Ball Valves For Industrial Pipelines
PDF
Thermodynamic Steam Traps for Condensate Removal
PDF
Steam Thermocompressor Technical Information
PDF
Integrated control valve, sensors, actuator, and controller
PDF
Pneumatic Actuators For Industrial Valves
PDF
Natural Gas Dryer for Fueling Station Operations
PDF
Direct Operated Temperature Regulators
PDF
Pneumatic Rack and Pinion Valve Actuators
PDF
Improved closed loop cooling arrangement
PDF
Three Piece Ball Valves Available With Metal Seats
PDF
Industrial Linear Electric Actuators for Valves
PDF
Trunnion mounted ball valves for industrial applications
Design of Fluid Systems - Steam Utilization
Valves Used in Mining Operations
Regenerative Turbine Chemical Process Pumps
Dual Snap Pressure, Temperature and Flow Switches
Piston Isolation Valves For Steam and Condensate
Hydrostatic Pressure Liquid Level Transmitter
Steam Condensate Return Stations
Breathing Air Purifiers for Commercial and Industrial Use
Trunnion Mount Ball Valves For Industrial Pipelines
Thermodynamic Steam Traps for Condensate Removal
Steam Thermocompressor Technical Information
Integrated control valve, sensors, actuator, and controller
Pneumatic Actuators For Industrial Valves
Natural Gas Dryer for Fueling Station Operations
Direct Operated Temperature Regulators
Pneumatic Rack and Pinion Valve Actuators
Improved closed loop cooling arrangement
Three Piece Ball Valves Available With Metal Seats
Industrial Linear Electric Actuators for Valves
Trunnion mounted ball valves for industrial applications

Recently uploaded (20)

PDF
Peak of Data & AI Encore- AI for Metadata and Smarter Workflows
PPTX
Cloud computing and distributed systems.
PDF
Modernizing your data center with Dell and AMD
PDF
Review of recent advances in non-invasive hemoglobin estimation
PDF
Build a system with the filesystem maintained by OSTree @ COSCUP 2025
PDF
How UI/UX Design Impacts User Retention in Mobile Apps.pdf
PDF
Advanced methodologies resolving dimensionality complications for autism neur...
PDF
Machine learning based COVID-19 study performance prediction
PPTX
Effective Security Operations Center (SOC) A Modern, Strategic, and Threat-In...
PDF
CIFDAQ's Market Insight: SEC Turns Pro Crypto
PDF
Mobile App Security Testing_ A Comprehensive Guide.pdf
PDF
Shreyas Phanse Resume: Experienced Backend Engineer | Java • Spring Boot • Ka...
PDF
Building Integrated photovoltaic BIPV_UPV.pdf
PDF
7 ChatGPT Prompts to Help You Define Your Ideal Customer Profile.pdf
PDF
KodekX | Application Modernization Development
PDF
Diabetes mellitus diagnosis method based random forest with bat algorithm
PPTX
Understanding_Digital_Forensics_Presentation.pptx
PDF
cuic standard and advanced reporting.pdf
PPTX
A Presentation on Artificial Intelligence
PPTX
VMware vSphere Foundation How to Sell Presentation-Ver1.4-2-14-2024.pptx
Peak of Data & AI Encore- AI for Metadata and Smarter Workflows
Cloud computing and distributed systems.
Modernizing your data center with Dell and AMD
Review of recent advances in non-invasive hemoglobin estimation
Build a system with the filesystem maintained by OSTree @ COSCUP 2025
How UI/UX Design Impacts User Retention in Mobile Apps.pdf
Advanced methodologies resolving dimensionality complications for autism neur...
Machine learning based COVID-19 study performance prediction
Effective Security Operations Center (SOC) A Modern, Strategic, and Threat-In...
CIFDAQ's Market Insight: SEC Turns Pro Crypto
Mobile App Security Testing_ A Comprehensive Guide.pdf
Shreyas Phanse Resume: Experienced Backend Engineer | Java • Spring Boot • Ka...
Building Integrated photovoltaic BIPV_UPV.pdf
7 ChatGPT Prompts to Help You Define Your Ideal Customer Profile.pdf
KodekX | Application Modernization Development
Diabetes mellitus diagnosis method based random forest with bat algorithm
Understanding_Digital_Forensics_Presentation.pptx
cuic standard and advanced reporting.pdf
A Presentation on Artificial Intelligence
VMware vSphere Foundation How to Sell Presentation-Ver1.4-2-14-2024.pptx

Defending Industrial Control Systems From Cyberattack

  • 1. 1 INTRODUCTION Cyber intrusions into US Critical Infrastructure systems are happening with increased frequency. For many industrial control systems (ICSs), it’s not a matter of if an intrusion will take place, but when. In Fiscal Year (FY) 2015, 295 incidents were reported to ICS-CERT, and many more went unreported or undetected. The capabilities of our adversaries have been demonstrated and cyber incidents are increasing in frequency and complexity. Simply building a network with a hardened perimeter is no longer adequate. Securing ICSs against the modern threat requires well-planned and well-implemented strategies that will provide network defense teams a chance to quickly and effectively detect, counter, and expel an adversary. This paper presents seven strategies that can be implemented today to counter common exploitable weaknesses in “as-built” control systems. Seven Strategies to Defend ICSs Figure 1: Percentage of ICS-CERT FY 2014 and FY 2015 Incidents Potentially Mitigated by Each Strategya a. Incidents mitigated by more than one strategy are listed under the strategy ICS-CERT judged as more effective.
  • 2. 2 If system owners had implemented the strategies outlined in this paper, 98 percent of incidents ICS-CERT responded to in FY 2014 and FY 2015 would have been prevented. The remaining 2 percent could have been identified with increased monitoring and a robust incident response. THE SEVEN STRATEGIES 1. IMPLEMENT APPLICATION WHITELISTING Application Whitelisting (AWL) can detect and prevent attempted execution of malware uploaded by adversaries. The static nature of some systems, such as database servers and human-machine interface (HMI) computers, make these ideal candidates to run AWL. Operators are encouraged to work with their vendors to baseline and calibrate AWL deployments. Example: ICS-CERT recently responded to an incident where the victim had to rebuild the network from scratch at great expense. A particular malware compromised over 80 percent of its assets. Antivirus software was ineffective; the malware had a 0 percent detection rate on VirusTotal. AWL would have provided notification and blocked the malware execution. 2. ENSURE PROPER CONFIGURATION/PATCH MANAGEMENT Adversaries target unpatched systems. A configuration/patch management program centered on the safe importation and implementation of trusted patches will help keep control systems more secure. Such a program will start with an accurate baseline and asset inventory to track what patches are needed. It will prioritize patching and configuration management of “PC-architecture” machines used in HMI, database server, and engineering workstation roles, as current adversaries have significant cyber capabilities against these. Infected laptops are a significant malware vector. Such a program will limit connection of external laptops to the control network and preferably supply vendors with known-good company laptops. The program will also encourage initial installation of any updates onto a test system that includes malware detection features before the updates are installed on operational systems. Example: ICS-CERT responded to a Stuxnet infection at a power generation facility. The root cause of the infection was a vendor laptop. Use best practices when downloading software and patches destined for your control network. Take measures to avoid “watering hole” attacks. Use a web Domain Name System (DNS) reputation system. Get updates from authenticated vendor sites. Validate the authenticity of
  • 3. 3 downloads. Insist that vendors digitally sign updates, and/or publish hashes via an out-of-bound communications path, and use these to authenticate. Don’t load updates from unverified sources. Example: HAVEX spread by infecting patches. With an out-of-band communication path for patch hashes, such as a blast email, users could have validated that the patches were not authentic. 3. REDUCE YOUR ATTACK SURFACE AREA Isolate ICS networks from any untrusted networks, especially the Internet.b Lock down all unused ports. Turn off all unused services. Only allow real-time connectivity to external networks if there is a defined business requirement or control function. If one-way communication can accomplish a task, use optical separation (“data diode”). If bidirectional communication is necessary, then use a single open port over a restricted network path. Example: As of 2014, ICS-CERT was aware of 82,000 cases of industrial control systems hardware or software directly accessible from the public Internet. ICS-CERT has encountered numerous cases where direct or nearly direct Internet access enabled a breach. Examples include a US Crime Lab, a Dam, The Sochi Olympic stadium, and numerous water utilities. 4. BUILD A DEFENDABLE ENVIRONMENT Limit damage from network perimeter breaches. Segment networks into logical enclaves and restrict host-to-host communications paths. This can stop adversaries from expanding their access, while letting the normal system communications continue to operate. Enclaving limits possible damage, as compromised systems cannot be used to reach and contaminate systems in other enclaves. Containment provided by enclaving also makes incident cleanup significantly less costly.c b. ICS-ALERT-14-063-01AP, Multiple Reports of Internet Facing Control Systems, ICS-CERT 2015. c. Improving Industrial Control Systems Cybersecurity with Defense in Depth, ICS-CERT 2009.
  • 4. 4 Example: In one ICS-CERT case, a nuclear asset owner failed to scan media entering a Level 3 facility. On exit, the media was scanned, and a virus was detected. Because the asset owner had implemented logical enclaving, only six systems were put at risk and had to be remediated. Had enclaving not been implemented, hundreds of hosts would have needed to be remediated. If one-way data transfer from a secure zone to a less secure zone is required, consider using approved removable media instead of a network connection. If real-time data transfer is required, consider using optical separation technologies. This allows replication of data without putting the control system at risk. Example: In one ICS-CERT case, a pipeline operator had directly connected the corporate network to the control network, because the billing unit had asserted it needed metering data. After being informed of a breach by ICS-CERT, the asset owner removed the connection. It took the billing department 4 days to notice the connection had been lost, clearly demonstrating that real-time data were not needed. 5. MANAGE AUTHENTICATION Adversaries are increasingly focusing on gaining control of legitimate credentials, especially those associated with highly privileged accounts. Compromising these credentials allows adversaries to masquerade as legitimate users, leaving less evidence than exploiting vulnerabilities or executing malware. Implement multi-factor authentication where possible. Reduce privileges to only those needed for a user’s duties. If passwords are necessary, implement secure password policies stressing length over complexity. For all accounts, including system and non-interactive accounts, ensure credentials are unique, and change all passwords at least every 90 days. Require separate credentials for corporate and control network zones and store these in separate trust stores. Never share Active Directory, RSA ACE servers, or other trust stores between corporate and control networks. Example: One US Government agency used the same password across the environment for local administrator accounts. This allowed an adversary to easily move laterally across all systems.
  • 5. 5 6. IMPLEMENT SECURE REMOTE ACCESS Some adversaries are effective at gaining remote access into control systems, finding obscure access vectors, even “hidden back doors” intentionally created by system operators. Remove such accesses wherever possible, especially modems as these are fundamentally insecure. Limit any accesses that remain. Where possible, implement “monitoring only” access enforced by data diodes, and do not rely on “read only” access enforced by software configurations or permissions. Do not allow remote persistent vendor connections into the control network. Require any remote access be operator controlled, time limited, and procedurally similar to “lock out, tag out.” Use the same remote access paths for vendor and employee connections; don’t allow double standards. Use two-factor authentication if possible, avoiding schemes where both tokens are similar types and can be easily stolen (e.g., password and soft certificate). Example: Following these guidelines would have prevented the BlackEnergy intrusions. BlackEnergy required communications paths for initial compromise, installation and “plug in” installation. 7. MONITOR AND RESPOND Defending a network against modern threats requires actively monitoring for adversarial penetration and quickly executing a prepared response. Consider establishing monitoring programs in the following five key places: 1) Watch IP traffic on ICS boundaries for abnormal or suspicious communications. 2) Monitor IP traffic within the control network for malicious connections or content. 3) Use host-based products to detect malicious software and attack attempts. 4) Use login analysis (time and place for example) to detect stolen credential usage or improper access, verifying all anomalies with quick phone calls. 5) Watch account/user administration actions to detect access control manipulation. Have a response plan for when adversarial activity is detected. Such a plan may include disconnecting all Internet connections, running a properly scoped search for malware, disabling affected user accounts, isolating suspect systems, and an immediate 100 percent password reset. Such a plan may also define escalation triggers and actions, including incident response, investigation, and public affairs activities. Have a restoration plan, including having “gold disks” ready to restore systems to known good states.
  • 6. 6 Example: Attackers render Windows®d based devices in a control network inoperative by wiping hard drive contents. Recent attacks against Saudi Aramco™e and Sony Pictures demonstrate that quick restoration of such computers is key to restoring an attacked network to an operational state. CONCLUSION Defense against the modern threat requires applying measures to protect not only the perimeter but also the interior. While no system is 100 percent secure, implementing the seven key strategies discussed in this paper can greatly improve the security posture of ICSs. DISCLAIMER The information and opinions contained in this document are provided “as is” and without any warranties or guarantees. Reference herein to any specific commercial products, process, or service by trade name, trademark, manufacturer, or otherwise, does not constitute or imply its endorsement, recommendation, or favoring by the United States Government, and this guidance shall not be used for advertising or product endorsement purposes. ACKNOWLEDGMENT This document “Seven Steps to Effectively Defend Industrial Control Systems” was written in collaboration, with contributions from subject matter experts working at the Department of Homeland Security (DHS), the Federal Bureau of Investigation (FBI), and the National Security Agency (NSA). d. Windows® is a registered trademark of Microsoft Corp. e. Saudi Aramco™ is an unregistered trademark of Saudi Arabian Oil Company.
  • 7. 7 CONTACT INFORMATION POC Phone e-Mail Department of Homeland Security ICS-CERT 877-776-7585 ICS-CERT@HQ.DHS.GOV Federal Bureau of Investigation Cyber Division - CyWatch 855-292-3937 CyWatch@ic.fbi.gov National Security Agency (Industry) Industry Inquiries 410-854-6091 bao@nsa.gov National Security Agency (Government) IAD Client Contact Center 410-854-4200 IAD CCC@nsa.gov