Dynamic Power Quality Compensator with an Adaptive Shunt
Hybrid Filter
Sindhu M R, Manjula G Nair, T N P Nambiar
Department of Electrical and Electronics Engineering, AMRITA VISHWA VIDYAPEETHAM
Article Info ABSTRACT
Article history:
Received May 24, 2014
Revised Oct 7, 2014
Accepted Oct 20, 2014
Major portion of nonlinear loads in industries are contributed by variable
speed drives because of their desirable features such as energy saving,
smooth control, flexible operation and fast response. These electric drives
introduce large amount of current and voltage harmonic distortions at the
point of common coupling. These distortions are propagated throughout the
system and affect all other loads connected in the system. Hence these
distortions are to be mitigated with suitable harmonic filters installed near to
the respective load terminals. This paper presents an effective ANN based
digital controller for shunt hybrid harmonic filter to provide instantaneous
harmonic and reactive compensation. The performance of the adaptive shunt
hybrid filter is verified by simulation and experimental studies under steady
state and dynamic conditions. The results show that it is an effective, flexible
and low rated hybrid filter configuration.
Keyword:
Harmonic Distortion
Harmonic Filter
Power Quality
Reactive power compensation
Active Filter
Copyright © 2014 Institute of Advanced Engineering and Science.
All rights reserved.
Corresponding Author:
Sindhu M R,
Department of Electrical and Electronics Engineering,
Amrita Vishwa Vidya Peetham,
Amrita nagar, Coimbatore – 641112.
Email:
1. INTRODUCTION
Utilities take efforts to maintain good power quality at the point of common coupling (PCC).
Majority of industrial loads are induction motor drives [1, 2]. They are preferred because of saving in energy,
rugged nature, easiness in control and cheapness [1, 2]. Various PWM techniques such as Space Vector pulse
width modulation, sinusoidal PWM etc. are implemented [3]-[5]. These are implemented with digital
controllers and it improved performance of induction motor drives. These equipment resulted in generation
of large amounts of current and voltage harmonics, reduction in source power factor, voltage sag, voltage
swell etc. [6]. The propagation of these power quality issues are prevented by installing harmonic filter of
suitable configuration at point of common coupling. Different power quality improvement schemes such as
passive filters [6] and active filters [7] are developed by various researchers. Passive filters have drawbacks
such as bulky in size, high no load losses, resonance, fixed compensation etc [6]. Active filters provide
effective and dynamic compensation with the help of efficient controllers [7]. But this scheme is expensive.
Hence as an economical solution, hybrid filters were developed. Here, shunt passive filter contributes major
part of reactive power compensation and remaining harmonics are compensated by shunt active filter.
Various research papers on intelligent digital controller based harmonic filters are published [8-12]. This
paper describes an ANN based adaptive shunt hybrid filter for harmonic mitigation and reactive power
compensation of adjustable speed drives.ANN controller helps to provide instantaneous harmonic and
reactive power compensation under steady state and dynamic conditions.
IJPEDS ISSN: 2088-8694 
Dynamic Power Quality Compensator with an Adaptive Shunt Hybrid Filter (Sindhu M R)
509
2. TEST SYSTEM
An industrial system is selected for performance study of the adaptive shunt hybrid filter. A scaled
down laboratory model of industrial drive, three phase 3 HP, 4 pole, induction motor drive is used in this
work. It is operated as an adjustable speed drive using three phase voltage source inverter. The specifications
of the induction motor drive are shown in Table 1.
Table 1. Induction Motor Drive Specifications
Power rating 3 HP
Switching frequency 10kHz
Rotor resistance 1.24
Stator resistance 1.517
Vdc 300V
Base frequency 100Hz
Stator Leakage Reactance 5.12
Rotor Leakage Reactance 120
No. of poles 4
Moment of Inertia 0.2 kgm2
The experimental set up is made as shown in the block diagram in Figure 1.
Figure 1. Schematic Diagram of Three Phase Test System
The VSI is controlled using space vector PWM. The space vector PWM based speed control is
implemented through the following steps:
(a) Measure the motor quantities (speed and phase currents)
(b) Transform them to two phase system (,β) using Clarke transformation
(c) Calculate rotor flux space vector magnitude and angle
(d) The stator current torque and flux components are separately controlled (isd, isq)
(e) The output stator voltage space vector is calculated using decoupling block (vsd, vsq)
(f) The stator voltage space vector is transformed by an inverse park transformation back from d –q
reference frame into two phase system fixed with the stator (vs, vsβ)
(g) Using space vector modulation, output three phase voltages is generated.
The whole process of the speed controller, implemented in the dsPIC30F4011, is explained using
flow chart in Figure 2. Three phase source currents, and source voltages at the point of common coupling are
sensed and harmonic analysis is performed with the help of power quality analyser. The power system
quantities –magnitudes and waveforms of source currents and source voltages for different speed settings are
shown in Figure 3.
 ISSN: 2088-8694
IJPEDS Vol. 4, No. 4, December 2014 : 508 – 516
510
Figure 3. Source voltage and source current at the point of common coupling for variable speed induction
motor drive with speed of (a)135 rad/sec (Case I) (b)320 rad/sec – (Case II)
Figure 2. Flow chart of the speed controller
Table 2 shows large amount of harmonics in currents at the point of common coupling under steady
state conditions. When the load is changed suddenly from 75% rated load to 25% rated load, the source
current, reactive power demand and harmonic components are also changed correspondingly. The
fundamental component of source current, THD in source current, % of current harmonic components,
displacement power factor, distortion power factor, source power factor, real power, reactive power, apparent
power and distortion power in each cycle is shown in Table 3.
Table 2(a). Fundamental component of source current and THD in source current at the point of common
coupling with variable speed induction motor drive – under steady state conditions
Case
Fundamental component of
source current (p.u.)
THD in
Source
Current (%)
% of
5th
harmonic
% of
7th
harmonic
% of
11th
harmonic
% of
13th
harmonic
Phase a Phase b Phase c Phase a
Phase
A
Phase
A
Phase
a
Phase
a
I 0.92 0.92 0.92 34.5 28.2 12.6 4.1 2.1
II 0.51 0.51 0.51 57.13 53.5 19.4 5.2 2.9
Table 2(b). Estimation of Power system parameters for the specified load conditions under steady state
Case
Displacement
power factor
Distortion power
factor
Source power
factor
Real Power
(pu)
Reactive
Power
(pu)
Apparent
Power
(pu)
Distortion
Power (pu)
I 0.98 0.9453 0.9293 0.91 0.16 0.92 0.08
II 0.53 0.87 0.4342 0.46 0.7967 0.92 0.085
IJPEDS ISSN: 2088-8694 
Dynamic Power Quality Compensator with an Adaptive Shunt Hybrid Filter (Sindhu M R)
511
Table 3(a). Fundamental component of source current and THD in source current in each cycle at the point of
common coupling with variable speed induction motor drive – under dynamic conditions
Cycle
Fundamental component of
source current (p.u.)
THD in
Source
current (%)
% of
5th
harmonic
% of
7th
harmonic
% of
11th
harmonic
% of
13th
harmonic
Phase a Phase b Phase c Phase a
Phase
A
Phase
A
Phase
A
Phase
a
I 0.92 0.92 0.92 34.5 28.2 12.6
4.1
2.1
II 0.84 0.84 0.84 39.2
34.6
14.12
4.29
2.25
III 0.78 0.78 0.78 43.8
39.87
15.78
4.47
2.42
IV 0.70 0.70 0.70 47.96
44.3
17.24
4.7
2.63
V 0.62 0.62 0.62 53.2
49.7
18.3
4.95
2.81
VI
0.51 0.51 0.51 57.13
53.5
19.4
5.2
2.9
Table 3(b). Estimation of Power system parameters in each cycle with variable speed induction motor drive -
under dynamic load conditions
Cycle
Displacement
power factor
Distortion power
factor
Source power
factor
Real Power
(pu)
Reactive
Power
(pu)
Apparent Power
(pu)
Distortion
Power (pu)
I 0.98 0.9453 0.9293 0.91 0.16 0.92
0.08
II 0.9397 0.945 0.888 0.7893
0.287
0.84
0.03
III 0.866 0.9289 0.8044 0.6755
0.39
0.78
0.026
IV 0.766 0.9143 0.7004 0.5362
0.45
0.7
0.0036
V 0.6428 0.8955 0.5756 0.3985
0.4749
0.62
0.0082
VI 0.53 0.87 0.4342 0.46
0.7967
0.92
0.085
Results show an effective harmonic filter is necessary to provide variable reactive power and
harmonic compensation to meet IEEE standards of good power quality. Active filters are commonly used for
dynamic power quality compensation. But these active filters are highly expensive. Hence as an economical
solution, hybrid filters were introduced. Here, shunt passive filter contributes major part of reactive
compensation and selected harmonic compensation. Only remaining harmonic compensation is to be met by
the shunt active filter.
3. PROPOSED ADAPTIVE SHUNT HYBRID FILTER FOR POWER QUALITY COMPENSATION
IN INDUCTION MOTOR DRIVES
The adaptive shunt hybrid filter consists of three phase adaptive shunt passive filters and adaptive
shunt active filter. Adaptive shunt passive filters are developed by series combination of thyristor switched
series combination of inductor and capacitor. Their values are designed such as to provide bypass path for
fifth and seventh harmonics. It also provides fundamental frequency reactive power to the system. The
capacitor values are selected as 210F and inductor values are 15mH and 7mH respectively. Remaining
amounts of harmonics and reactive compensation currents are provided by the adaptive shunt active filter.
The shunt active filter is controlled to inject remaining amount of harmonics and reactive compensation
currents such that source need to supply only real part of fundamental component of current. The schematic
diagram of the filtering system is shown in Figure 4. The hybrid filter elements are controlled by ANN based
intelligent digital controller. The responsiveness of filter is improved by hysteresis controller based closed
loop control. PI controller is also used to compensate for inverter losses and regulation of dc link voltage.
 ISSN: 2088-8694
IJPEDS Vol. 4, No. 4, December 2014 : 508 – 516
512
Figure 4. Three phase system feeding variable speed induction motor drive with Adaptive Shunt Hybrid
Filter
3.1. Methodology
The load current in induction motor drive is represented by:
)sin()sin()(
,5,3
1 1 



h
LhLhLL thititi L
 = Real part of fundamental component
of load current +Reactive part of fundamental component of load current +
Harmonic components of load current
(1)
Adaptive shunt passive filter compensates for major part of fundamental frequency reactive power
and harmonics. Adaptive shunt active filter injects remaining small amount of harmonics and helps to obtain
unity power factor sinusoidal current at the point of common coupling.
Three phase instantaneous source voltages, fundamental load currents and filter compensation
currents are selected as input quantities for training adaptive ANN. The reference compensation currents are
developed by analog controller circuit. The actual compensation currents are compared with reference
compensation currents to generate switching pulses to IGBTs of three phase voltage source inverter. The
current transducers and voltage transducers sample instantaneous load currents, compensation currents and
source voltages. Sampled value of instantaneous load current is expressed as:
i.e. iL[k] = )]cos()sin([ 2
,.....3,2,1
1 tnkWtnkW n
N
n
n 

= )]cos()sin([)]sin()cos([ 2
,.....3,2
12111 tnkWtnkWtnkWtnkW n
N
n
n  

= iL1, re[k] + iL1, im[k] + h
[k]ih (2)
where W1n and W2n are amplitudes of sine and cosine components of the measured load current.
The equation is represented in vectorial form as:
iL[k] = [W11 W21 ---------W1N W2N]
































)cos(
)sin(
)2cos(
)2sin(
)cos(
)sin(
tNk
tNk
tk
tk
tk
tk






The adaptive ANN network is implemented using Widrow-Hoff weights updating algorithm [6], [7].
The weights of the connection links are updated using error in the estimated fundamental component and
IJPEDS ISSN: 2088-8694 
Dynamic Power Quality Compensator with an Adaptive Shunt Hybrid Filter (Sindhu M R)
513
actual real part of fundamental component of load current. The back propagation neural network was trained
with MATLAB using 1500 training patterns for 2500 epochs with goal of 0.001.Training method used is
Levenberg – Marquardt algorithm. Trained artificial neural network consists of two layers: input layer (6
neurons), output layer (7 neurons) and hidden layer (6 neurons). The ANN network is shown in Figure 5. The
performance characteristics of neural network training is shown in Figure 6. The ANN is programmed and
implemented using dsPIC30F4011 microcontroller. Two bipolar ADCs are used for conversion of analog
quantities to digital quantities. Sampling frequency of 3kHz is selected considering time for sensing input
samples, digital conversion, program execution and generation of switching signals. The switching pulses are
amplified and given to IGBTs in shunt active filter. The isolation between power circuit and controller circuit
is done using an optocoupler 6N136. The shunt active power filter circuit includes power inverter
(SKM50GB12B) with three phase IGBT bridge and two capacitors of 2200F. The compensating currents
injected by three phase inverter through coupling inductors to the point of common coupling. For
sA
dt
diF
/10
max






, 400V 5A 10mH coupling inductor is used. The experimental results with the
insertion of ANN Controller based shunt hybrid filter are discussed in following section.
Figure 5. Artificial Neural Network for controlling adaptive shunt hybrid filter
Figure 6. Performance plot of training neural network for controlling the adaptive shunt hybrid filter
4. PERFORMANCE OF ANN CONTROLLED SHUNT ACTIVE FILTER UNDER DYNAMIC
CONDITIONS–RESULTS AND DISCUSSION
The operating performance of the adaptive shunt hybrid filter is studied under dynamic conditions –
with the application of 25% load and 75% load at t = 0.5s. Fundamental component of source current, THD
in source current and power system parameters at the point of common coupling with the installation of
adaptive shunt hybrid filter is shown in Table 4 and 5. Figure 7, and 8 show waveforms of source voltage,
load current, filter current and source current with the installation of adaptive shunt hybrid filter under
 ISSN: 2088-8694
IJPEDS Vol. 4, No. 4, December 2014 : 508 – 516
514
dynamic conditions. The performance of adaptive shunt hybrid filter is verified with reduction in source
current harmonics and sinusoidal source currents in phase with source voltages. Waveforms also confirm the
performance of the filter under dynamic conditions.
Table 4(a). Fundamental component of source current and THD in source current at the point of common
coupling with variable speed induction motor drive with Adaptive Shunt Hybrid Filter – Steady state
conditions
Case
Fundamental component of
source current (p.u.)
THD in Source
Current (%)
% of
5th
harmonic
% of
7th
harmonic
% of
11th
harmonic
% of
13th
harmonic
Phase a Phase b Phase c Phase a
Phase
A
Phase
A
Phase
a
Phase
a
I 0.84 0.84 0.84 3.15 2.2 1.6 0.7 0.4
II 0.23 0.23 0.23 3.19 2.5 1.4 1.2 0.9
Table 4(b). Estimate of Power system parameters for the specified load conditions – with Adaptive Shunt
Hybrid Filter – Steady state conditions
Case
Displacement
power factor
Distortion power
factor
Source power
factor
Power Delivered by Source
Real Power
(pu)
Reactive
Power
(pu)
Apparent
Power
(pu)
Distortion
Power (pu)
I 1 0.9991 0.9991 0.84 0 0.84 0
II 1 0.9995 0.9995 0.23 0 0.23 0
.
Figure 7. Source voltage, Load current, Filter current, Source current waveforms for induction motor drive
load at 25% rated load under balanced system with adaptive shunt hybrid filter –dynamic conditions
Figure 8 Experimental results - Source current waveforms for the induction motor drive load under balanced
system with adaptive shunt hybrid filter – dynamic conditions; (a) Without filter, (b) With adaptive shunt
hybrid filter
IJPEDS ISSN: 2088-8694 
Dynamic Power Quality Compensator with an Adaptive Shunt Hybrid Filter (Sindhu M R)
515
Table 5(a). Fundamental component of source current and THD in source current at the point of common
coupling with variable speed induction motor drive after the installation of Adaptive Shunt Hybrid Filter –
Dynamic conditions
Cycle
Fundamental component of
source current (p.u.)
THD in
Source
Current (%)
% of
5th
harmonic
% of
7th
harmonic
% of
11th
harmonic
% of
13th
harmonic
Phase a Phase b Phase c Phase a
Phase
A
Phase
A
Phase
a
Phase
A
I 0.84 0.84 0.84 3.15 2.2 1.6
0.7
0.4
II 0.72 0.72 0.72 3.24
2.31
1.59
0.6
0.31
III 0.60 0.60 0.60 3.56
2.43
1.87
0.78
0.35
IV 0.48 0.48 0.48 3.32
2.36
1.63
0.63
0.32
V 0.36 0.36 0.36 3.26
2.34
1.60
0.58
0.29
VI 0.23 0.23 0.23 3.19
2.5
1.4
1.2
0.9
Table 5(b). Estimate of Power system parameters in each cycle under dynamic load conditions with the
installation of Adaptive Shunt Hybrid Filter
Cycle
Displacement
power factor
Distortion power
factor
Source power
factor
Power Delivered by Source
Real Power
(pu)
Reactive
Power
(pu)
Apparent
Power
(pu)
Distortion
Power (pu)
I 1 0.9991 0.9991 0.84 0 0.84 0
II 1 0.998 0.998 0.72 0 0.72 0
III 1 0.997 0.997 0.60 0 0.60 0
IV 1 0.997 0.997 0.48 0 0.48 0
V 1 0.998 0.998 0.36 0 0.36 0
VI 1 0.999 0.999 0.23 0 0.23 0
The simulation and experimental results related to the adaptive shunt hybrid filter illustrated:
a) A single controller is used for controlling both adaptive shunt passive filter and adaptive shunt
active filter
b) The digital ANN based controller is flexible and easy to implement in large quantities.
c) In the case of adaptive shunt hybrid filter, the kVA delivered by source for the load is much less
compared with shunt adaptive passive filter or ANN controller based shunt active filter.
d) The fundamental reactive power drawn from source is much reduced and hence source power
factor is improved.
e) The performance of the ANN controller is satisfactory with balanced/ unbalanced source and
balanced/unbalanced nonlinear load under steady state and dynamic conditions.
5. CONCLUSION
Adjustable speed induction motor drives cause large amounts of current and voltage harmonic
distortions and reactive power absorption at the point of common coupling. The propagation of distortions
throughout the power system affects lifetime of all other power system equipment. Various power quality
improvement schemes were suggested by different authors. This paper shows an ANN based adaptive shunt
hybrid filter for power quality enhancement in a variable speed drive system. The simulation and
experimental results show effective performance of adaptive shunt hybrid filter under steady state and
transient conditions.
ACKNOWLEDGEMENT
The authors wish to thank Amrita Vishwa Vidyapeetham, Coimbatore and Department of Science
and Technology, New Delhi for their financial support for carrying out this work.
 ISSN: 2088-8694
IJPEDS Vol. 4, No. 4, December 2014 : 508 – 516
516
REFERENCES
[1] Bimal K Bose. Power Electronics and Motor Drives: Advances and Trends. Academic press, 2010, Ch 7. Gopal K
Dubey. Fundamentals of Electric Drives. Narosa Publishing House, 2013; Ch 6.
[2] Gaiceanu M, Rosu E, Paduraru R, Munteanu T. Vector-controlled optimal drive system for the induction motor. 4th
International Symposium on Electrical and Electronics Engineering (ISEEE), 2013; 1 - 6 .
[3] Zakaria L, Barra K. Predictive Direct Torque and Flux Control of an induction motor drive fed by a Direct Matrix
Converter with reactive power minimization. 10th IEEE International Conference on Networking, Sensing and
Control (ICNSC), 2013; 34 - 39.
[4] Rajesh, Tejavathu, Panda AK, Kumar, S Shiva, Bonala, Sathyam. High performance direct torque and flux control
of induction motor drive using fuzzy logic based speed controller Circuits. International Conference on Power and
Computing Technologies (ICCPCT). 2013; 213 - 218.
[5] Ewald Fuchs and Mohammad Masoum. Power Quality in Power Systems and Electrical Machines. Elseveir
Academic Press, 2008; Ch.3.
[6] HL Jou. Performance comparison of the three phase active power filter algorithms. IEEE Proc. Gener. Transm.
Distrib. 1995: 142(6): 646-652.
[7] Ginnes K John, Sindhu MR, Manjula G Nair, “DSP Based digital controller for shunt active filter to improve power
quality. International Journal of Recent Trends in Electrical and Electronics Engineering. 2009; 2(7): 92-94.
[8] SMR Rafiei, Reza Ghazi, Hamid A Toliyat. IEEE-519-Based Real-Time and Optimal Control of Active Filters
Under Non sinusoidal Line Voltages Using Neural Networks,” IEEE Transactions on Power Delivery, Vol. 17, No.
3, July 2002,pp. 815-821.
[9] Patricio Salmeron, Jesus R Vazquez. Practical Design of a Three Phase Active Power Line Conditioner controlled
by Artificial Neural Networks. IEEE Trans. on Power Delivery. 20(2): 2005; 1037-1044.
[10] Zhenfeng Xiao, Yilong Chen, Xiangtian Deng. A Shunt Active Power Filter with enhanced dynamic performance
using Dual-Repititive controller and predictive compensation. International Journal of Power Electronics and Drive
Systems. 2013; 3: 209-217.
[11] Mridula Jha, SP Dubey, Neuro-Fuzzy Based Controller for a Three Phase Four Wire Shunt Active Filter,
International Journal of Power Electronics and Drive Systems. 2011; 7; 11(2):148-155. 

More Related Content

PDF
Load Frequency Control of DFIG-isolated and Grid Connected Mode
PDF
Simulation of three-phase bridge rectifier using MATLAB/ SIMULINK for harmoni...
PDF
A Simulink Model for Damping Power System Oscillations Using Fact Devices
PDF
PSO based Direct Power Control for a Multifunctional Grid Connected Photovolt...
PDF
Optimal Placement of DG for Loss Reduction and Voltage Sag Mitigation in Radi...
PDF
Performance Evaluation of GA optimized Shunt Active Power Filter for Constant...
PDF
Modeling and Simulation for Transformer Ratio Controlled Slip Power Recovery ...
PDF
T04201162168Optimal Allocation of FACTS Device with Multiple Objectives Using...
Load Frequency Control of DFIG-isolated and Grid Connected Mode
Simulation of three-phase bridge rectifier using MATLAB/ SIMULINK for harmoni...
A Simulink Model for Damping Power System Oscillations Using Fact Devices
PSO based Direct Power Control for a Multifunctional Grid Connected Photovolt...
Optimal Placement of DG for Loss Reduction and Voltage Sag Mitigation in Radi...
Performance Evaluation of GA optimized Shunt Active Power Filter for Constant...
Modeling and Simulation for Transformer Ratio Controlled Slip Power Recovery ...
T04201162168Optimal Allocation of FACTS Device with Multiple Objectives Using...

What's hot (20)

PDF
B021201015023
PDF
Direct Power Control of Brushless Doubly-fed Induction Generator Used in Wind...
PDF
Neural Network based p-q-r Theory for Harmonic Reduction and Neutral Current ...
PDF
Solar fed BLDC motor drive for mixer grinder using a buck-boost converter
PDF
Control of PMSG based variable speed wind energy conversion system connected ...
PDF
Two area system
PDF
A Performance Comparison of DFIG using Power Transfer Matrix and Direct Power...
PDF
D027026030
PDF
M347781
PDF
Review of the Most Applicable Regulator Collections to Control the Parallel A...
PDF
Improved Fuzzy Control Strategy for Power Quality in Distributed Generation’s...
PDF
Total Harmonic Distortion Analysis of a Four Switch 3-Phase Inverter Fed Spee...
PDF
Utility current compensation by PV-APF system using fuzzy logic controller
PDF
Evaluation of Synchronization and MPPT Algorithms in a DFIG Wind Turbine Cont...
PDF
Multi-Objective Evolutionary Programming for Static VAR Compensator (SVC) in ...
PDF
Impact of hybrid FACTS devices on the stability of the Kenyan power system
PDF
Indian journal 3
PDF
Predictive Approach for Power Quality Improvement Based Direct Power Control
PDF
Modeling and Nonlinear Control of a Wind Turbine System Based on a Permanent ...
PDF
Load / Frequency balancing Control systems study
 
B021201015023
Direct Power Control of Brushless Doubly-fed Induction Generator Used in Wind...
Neural Network based p-q-r Theory for Harmonic Reduction and Neutral Current ...
Solar fed BLDC motor drive for mixer grinder using a buck-boost converter
Control of PMSG based variable speed wind energy conversion system connected ...
Two area system
A Performance Comparison of DFIG using Power Transfer Matrix and Direct Power...
D027026030
M347781
Review of the Most Applicable Regulator Collections to Control the Parallel A...
Improved Fuzzy Control Strategy for Power Quality in Distributed Generation’s...
Total Harmonic Distortion Analysis of a Four Switch 3-Phase Inverter Fed Spee...
Utility current compensation by PV-APF system using fuzzy logic controller
Evaluation of Synchronization and MPPT Algorithms in a DFIG Wind Turbine Cont...
Multi-Objective Evolutionary Programming for Static VAR Compensator (SVC) in ...
Impact of hybrid FACTS devices on the stability of the Kenyan power system
Indian journal 3
Predictive Approach for Power Quality Improvement Based Direct Power Control
Modeling and Nonlinear Control of a Wind Turbine System Based on a Permanent ...
Load / Frequency balancing Control systems study
 
Ad

Similar to Dynamic Power Quality Compensator with an Adaptive Shunt Hybrid Filter (20)

PDF
International Journal of Engineering Research and Development
PDF
Hysteresis Current Control Based Shunt Active Power Filter for Six Pulse Ac/D...
PDF
Improving Efficiency of Active Power Filter for Renewable Power Generation Sy...
PDF
Solar fed BLDC motor drive for mixer grinder using a boost converter
PDF
Analysis and design of single phase voltage-frequency converter with optimize...
PDF
Enhancement of power quality using microprocessor based shunt active power fi...
PDF
78201910
PDF
Power Quality Improvement by SRF Based Control using D-STATCOM
DOCX
Renewable Energy Based on Current Fed Switched Inverter for Smart Grid Applic...
PDF
Harmonic analysis and Power factor improvement with UPQC under two Novel cont...
PDF
Power Quality Enhancement in Power Distribution System by Using Fuzzy Logic C...
PDF
Interleaved Boost Converter Fed with PV for Induction Motor/Agricultural Appl...
PDF
Comparison of solar based closed loop DC-DC converter using PID and ANN contr...
PDF
Harmonic enhancement in microgrid with applications on sensitive loads
PDF
IRJET- Reduction of So Urce Current Harmonics in an Inverter Fed Induction Mo...
PDF
A review on different control techniques using DSTATCOM for distribution syst...
PDF
Design Of Hybrid Series Active Filters for Harmonic Reduction in Single Phase...
PDF
Comparative of Conventional and Intelligence Controller based Hybrid Generati...
PDF
A fault-tolerant photovoltaic integrated shunt active power filter with a 27-...
PDF
Mitigation of the Harmonics under Reactive Power Compensation by SHPF-TCR Usi...
International Journal of Engineering Research and Development
Hysteresis Current Control Based Shunt Active Power Filter for Six Pulse Ac/D...
Improving Efficiency of Active Power Filter for Renewable Power Generation Sy...
Solar fed BLDC motor drive for mixer grinder using a boost converter
Analysis and design of single phase voltage-frequency converter with optimize...
Enhancement of power quality using microprocessor based shunt active power fi...
78201910
Power Quality Improvement by SRF Based Control using D-STATCOM
Renewable Energy Based on Current Fed Switched Inverter for Smart Grid Applic...
Harmonic analysis and Power factor improvement with UPQC under two Novel cont...
Power Quality Enhancement in Power Distribution System by Using Fuzzy Logic C...
Interleaved Boost Converter Fed with PV for Induction Motor/Agricultural Appl...
Comparison of solar based closed loop DC-DC converter using PID and ANN contr...
Harmonic enhancement in microgrid with applications on sensitive loads
IRJET- Reduction of So Urce Current Harmonics in an Inverter Fed Induction Mo...
A review on different control techniques using DSTATCOM for distribution syst...
Design Of Hybrid Series Active Filters for Harmonic Reduction in Single Phase...
Comparative of Conventional and Intelligence Controller based Hybrid Generati...
A fault-tolerant photovoltaic integrated shunt active power filter with a 27-...
Mitigation of the Harmonics under Reactive Power Compensation by SHPF-TCR Usi...
Ad

More from IAES-IJPEDS (20)

PDF
42 30 nA Comparative Study of Power Semiconductor Devices for Industrial PWM ...
PDF
Modeling and State Feedback Controller Design of Tubular Linear Permanent Mag...
PDF
Analysis of Harmonics and Ripple Current in Multi-Module Converters with Incr...
PDF
Comparative Study of Various Adjustable Speed Drives during Voltage Sag
PDF
Modified Distribution Transformer for Enhancing Power Quality in Distribution...
PDF
Modelling of Virtual Synchronous Converter for Grid-Inverter Synchronization ...
PDF
Enhanced Crowbar Protection for Fault Ride through Capability of Wind Generat...
PDF
An Improved of Multiple Harmonic Sources Identification in Distribution Syste...
PDF
Performance and Energy Saving Analysis of Grid Connected Photovoltaic in West...
PDF
An Improved Constant Voltage Based MPPT Technique for PMDC Motor
PDF
A Discrete PLL Based Load Frequency Control of FLC-Based PV-Wind Hybrid Power...
PDF
An Adaptive Virtual Impedance Based Droop Control Scheme for Parallel Inverte...
PDF
Open-Switch Fault-Tolerant Control of Power Converters in a Grid-Connected Ph...
PDF
Photovoltaic System with SEPIC Converter Controlled by the Fuzzy Logic
PDF
An Approach to Voltage Quality Enhancement by Introduction of CWVM for Distri...
PDF
Electric Power Converter with a Wide Input Voltage Range
PDF
Design and Implementation of Real Time Charging Optimization for Hybrid Elect...
PDF
Performance Analysis of Photovoltaic Induction Motor Drive for Agriculture Pu...
PDF
Comparison of Sine and Space Vector Modulated Embedded Z-Source Inverter fed ...
PDF
Single-Phase Multilevel Inverter with Simpler Basic Unit Cells for Photovolta...
42 30 nA Comparative Study of Power Semiconductor Devices for Industrial PWM ...
Modeling and State Feedback Controller Design of Tubular Linear Permanent Mag...
Analysis of Harmonics and Ripple Current in Multi-Module Converters with Incr...
Comparative Study of Various Adjustable Speed Drives during Voltage Sag
Modified Distribution Transformer for Enhancing Power Quality in Distribution...
Modelling of Virtual Synchronous Converter for Grid-Inverter Synchronization ...
Enhanced Crowbar Protection for Fault Ride through Capability of Wind Generat...
An Improved of Multiple Harmonic Sources Identification in Distribution Syste...
Performance and Energy Saving Analysis of Grid Connected Photovoltaic in West...
An Improved Constant Voltage Based MPPT Technique for PMDC Motor
A Discrete PLL Based Load Frequency Control of FLC-Based PV-Wind Hybrid Power...
An Adaptive Virtual Impedance Based Droop Control Scheme for Parallel Inverte...
Open-Switch Fault-Tolerant Control of Power Converters in a Grid-Connected Ph...
Photovoltaic System with SEPIC Converter Controlled by the Fuzzy Logic
An Approach to Voltage Quality Enhancement by Introduction of CWVM for Distri...
Electric Power Converter with a Wide Input Voltage Range
Design and Implementation of Real Time Charging Optimization for Hybrid Elect...
Performance Analysis of Photovoltaic Induction Motor Drive for Agriculture Pu...
Comparison of Sine and Space Vector Modulated Embedded Z-Source Inverter fed ...
Single-Phase Multilevel Inverter with Simpler Basic Unit Cells for Photovolta...

Recently uploaded (20)

PDF
The CXO Playbook 2025 – Future-Ready Strategies for C-Suite Leaders Cerebrai...
PDF
PRIZ Academy - 9 Windows Thinking Where to Invest Today to Win Tomorrow.pdf
DOCX
573137875-Attendance-Management-System-original
PDF
SM_6th-Sem__Cse_Internet-of-Things.pdf IOT
PDF
Well-logging-methods_new................
DOCX
ASol_English-Language-Literature-Set-1-27-02-2023-converted.docx
PPTX
Internet of Things (IOT) - A guide to understanding
PPTX
UNIT-1 - COAL BASED THERMAL POWER PLANTS
PDF
Structs to JSON How Go Powers REST APIs.pdf
PPTX
Foundation to blockchain - A guide to Blockchain Tech
PDF
BMEC211 - INTRODUCTION TO MECHATRONICS-1.pdf
PDF
Mitigating Risks through Effective Management for Enhancing Organizational Pe...
PPTX
CARTOGRAPHY AND GEOINFORMATION VISUALIZATION chapter1 NPTE (2).pptx
PDF
PPT on Performance Review to get promotions
PDF
keyrequirementskkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkk
PPTX
web development for engineering and engineering
PPTX
KTU 2019 -S7-MCN 401 MODULE 2-VINAY.pptx
PPTX
IOT PPTs Week 10 Lecture Material.pptx of NPTEL Smart Cities contd
PPTX
M Tech Sem 1 Civil Engineering Environmental Sciences.pptx
PPTX
FINAL REVIEW FOR COPD DIANOSIS FOR PULMONARY DISEASE.pptx
The CXO Playbook 2025 – Future-Ready Strategies for C-Suite Leaders Cerebrai...
PRIZ Academy - 9 Windows Thinking Where to Invest Today to Win Tomorrow.pdf
573137875-Attendance-Management-System-original
SM_6th-Sem__Cse_Internet-of-Things.pdf IOT
Well-logging-methods_new................
ASol_English-Language-Literature-Set-1-27-02-2023-converted.docx
Internet of Things (IOT) - A guide to understanding
UNIT-1 - COAL BASED THERMAL POWER PLANTS
Structs to JSON How Go Powers REST APIs.pdf
Foundation to blockchain - A guide to Blockchain Tech
BMEC211 - INTRODUCTION TO MECHATRONICS-1.pdf
Mitigating Risks through Effective Management for Enhancing Organizational Pe...
CARTOGRAPHY AND GEOINFORMATION VISUALIZATION chapter1 NPTE (2).pptx
PPT on Performance Review to get promotions
keyrequirementskkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkk
web development for engineering and engineering
KTU 2019 -S7-MCN 401 MODULE 2-VINAY.pptx
IOT PPTs Week 10 Lecture Material.pptx of NPTEL Smart Cities contd
M Tech Sem 1 Civil Engineering Environmental Sciences.pptx
FINAL REVIEW FOR COPD DIANOSIS FOR PULMONARY DISEASE.pptx

Dynamic Power Quality Compensator with an Adaptive Shunt Hybrid Filter

  • 1. International Journal of Power Electronics and Drive System (IJPEDS) Vol. 4, No. 4, December 2014, pp. 508~516 ISSN: 2088-8694  508 Journal homepage: http://iaesjournal.com/online/index.php/IJPEDS Dynamic Power Quality Compensator with an Adaptive Shunt Hybrid Filter Sindhu M R, Manjula G Nair, T N P Nambiar Department of Electrical and Electronics Engineering, AMRITA VISHWA VIDYAPEETHAM Article Info ABSTRACT Article history: Received May 24, 2014 Revised Oct 7, 2014 Accepted Oct 20, 2014 Major portion of nonlinear loads in industries are contributed by variable speed drives because of their desirable features such as energy saving, smooth control, flexible operation and fast response. These electric drives introduce large amount of current and voltage harmonic distortions at the point of common coupling. These distortions are propagated throughout the system and affect all other loads connected in the system. Hence these distortions are to be mitigated with suitable harmonic filters installed near to the respective load terminals. This paper presents an effective ANN based digital controller for shunt hybrid harmonic filter to provide instantaneous harmonic and reactive compensation. The performance of the adaptive shunt hybrid filter is verified by simulation and experimental studies under steady state and dynamic conditions. The results show that it is an effective, flexible and low rated hybrid filter configuration. Keyword: Harmonic Distortion Harmonic Filter Power Quality Reactive power compensation Active Filter Copyright © 2014 Institute of Advanced Engineering and Science. All rights reserved. Corresponding Author: Sindhu M R, Department of Electrical and Electronics Engineering, Amrita Vishwa Vidya Peetham, Amrita nagar, Coimbatore – 641112. Email: 1. INTRODUCTION Utilities take efforts to maintain good power quality at the point of common coupling (PCC). Majority of industrial loads are induction motor drives [1, 2]. They are preferred because of saving in energy, rugged nature, easiness in control and cheapness [1, 2]. Various PWM techniques such as Space Vector pulse width modulation, sinusoidal PWM etc. are implemented [3]-[5]. These are implemented with digital controllers and it improved performance of induction motor drives. These equipment resulted in generation of large amounts of current and voltage harmonics, reduction in source power factor, voltage sag, voltage swell etc. [6]. The propagation of these power quality issues are prevented by installing harmonic filter of suitable configuration at point of common coupling. Different power quality improvement schemes such as passive filters [6] and active filters [7] are developed by various researchers. Passive filters have drawbacks such as bulky in size, high no load losses, resonance, fixed compensation etc [6]. Active filters provide effective and dynamic compensation with the help of efficient controllers [7]. But this scheme is expensive. Hence as an economical solution, hybrid filters were developed. Here, shunt passive filter contributes major part of reactive power compensation and remaining harmonics are compensated by shunt active filter. Various research papers on intelligent digital controller based harmonic filters are published [8-12]. This paper describes an ANN based adaptive shunt hybrid filter for harmonic mitigation and reactive power compensation of adjustable speed drives.ANN controller helps to provide instantaneous harmonic and reactive power compensation under steady state and dynamic conditions.
  • 2. IJPEDS ISSN: 2088-8694  Dynamic Power Quality Compensator with an Adaptive Shunt Hybrid Filter (Sindhu M R) 509 2. TEST SYSTEM An industrial system is selected for performance study of the adaptive shunt hybrid filter. A scaled down laboratory model of industrial drive, three phase 3 HP, 4 pole, induction motor drive is used in this work. It is operated as an adjustable speed drive using three phase voltage source inverter. The specifications of the induction motor drive are shown in Table 1. Table 1. Induction Motor Drive Specifications Power rating 3 HP Switching frequency 10kHz Rotor resistance 1.24 Stator resistance 1.517 Vdc 300V Base frequency 100Hz Stator Leakage Reactance 5.12 Rotor Leakage Reactance 120 No. of poles 4 Moment of Inertia 0.2 kgm2 The experimental set up is made as shown in the block diagram in Figure 1. Figure 1. Schematic Diagram of Three Phase Test System The VSI is controlled using space vector PWM. The space vector PWM based speed control is implemented through the following steps: (a) Measure the motor quantities (speed and phase currents) (b) Transform them to two phase system (,β) using Clarke transformation (c) Calculate rotor flux space vector magnitude and angle (d) The stator current torque and flux components are separately controlled (isd, isq) (e) The output stator voltage space vector is calculated using decoupling block (vsd, vsq) (f) The stator voltage space vector is transformed by an inverse park transformation back from d –q reference frame into two phase system fixed with the stator (vs, vsβ) (g) Using space vector modulation, output three phase voltages is generated. The whole process of the speed controller, implemented in the dsPIC30F4011, is explained using flow chart in Figure 2. Three phase source currents, and source voltages at the point of common coupling are sensed and harmonic analysis is performed with the help of power quality analyser. The power system quantities –magnitudes and waveforms of source currents and source voltages for different speed settings are shown in Figure 3.
  • 3.  ISSN: 2088-8694 IJPEDS Vol. 4, No. 4, December 2014 : 508 – 516 510 Figure 3. Source voltage and source current at the point of common coupling for variable speed induction motor drive with speed of (a)135 rad/sec (Case I) (b)320 rad/sec – (Case II) Figure 2. Flow chart of the speed controller Table 2 shows large amount of harmonics in currents at the point of common coupling under steady state conditions. When the load is changed suddenly from 75% rated load to 25% rated load, the source current, reactive power demand and harmonic components are also changed correspondingly. The fundamental component of source current, THD in source current, % of current harmonic components, displacement power factor, distortion power factor, source power factor, real power, reactive power, apparent power and distortion power in each cycle is shown in Table 3. Table 2(a). Fundamental component of source current and THD in source current at the point of common coupling with variable speed induction motor drive – under steady state conditions Case Fundamental component of source current (p.u.) THD in Source Current (%) % of 5th harmonic % of 7th harmonic % of 11th harmonic % of 13th harmonic Phase a Phase b Phase c Phase a Phase A Phase A Phase a Phase a I 0.92 0.92 0.92 34.5 28.2 12.6 4.1 2.1 II 0.51 0.51 0.51 57.13 53.5 19.4 5.2 2.9 Table 2(b). Estimation of Power system parameters for the specified load conditions under steady state Case Displacement power factor Distortion power factor Source power factor Real Power (pu) Reactive Power (pu) Apparent Power (pu) Distortion Power (pu) I 0.98 0.9453 0.9293 0.91 0.16 0.92 0.08 II 0.53 0.87 0.4342 0.46 0.7967 0.92 0.085
  • 4. IJPEDS ISSN: 2088-8694  Dynamic Power Quality Compensator with an Adaptive Shunt Hybrid Filter (Sindhu M R) 511 Table 3(a). Fundamental component of source current and THD in source current in each cycle at the point of common coupling with variable speed induction motor drive – under dynamic conditions Cycle Fundamental component of source current (p.u.) THD in Source current (%) % of 5th harmonic % of 7th harmonic % of 11th harmonic % of 13th harmonic Phase a Phase b Phase c Phase a Phase A Phase A Phase A Phase a I 0.92 0.92 0.92 34.5 28.2 12.6 4.1 2.1 II 0.84 0.84 0.84 39.2 34.6 14.12 4.29 2.25 III 0.78 0.78 0.78 43.8 39.87 15.78 4.47 2.42 IV 0.70 0.70 0.70 47.96 44.3 17.24 4.7 2.63 V 0.62 0.62 0.62 53.2 49.7 18.3 4.95 2.81 VI 0.51 0.51 0.51 57.13 53.5 19.4 5.2 2.9 Table 3(b). Estimation of Power system parameters in each cycle with variable speed induction motor drive - under dynamic load conditions Cycle Displacement power factor Distortion power factor Source power factor Real Power (pu) Reactive Power (pu) Apparent Power (pu) Distortion Power (pu) I 0.98 0.9453 0.9293 0.91 0.16 0.92 0.08 II 0.9397 0.945 0.888 0.7893 0.287 0.84 0.03 III 0.866 0.9289 0.8044 0.6755 0.39 0.78 0.026 IV 0.766 0.9143 0.7004 0.5362 0.45 0.7 0.0036 V 0.6428 0.8955 0.5756 0.3985 0.4749 0.62 0.0082 VI 0.53 0.87 0.4342 0.46 0.7967 0.92 0.085 Results show an effective harmonic filter is necessary to provide variable reactive power and harmonic compensation to meet IEEE standards of good power quality. Active filters are commonly used for dynamic power quality compensation. But these active filters are highly expensive. Hence as an economical solution, hybrid filters were introduced. Here, shunt passive filter contributes major part of reactive compensation and selected harmonic compensation. Only remaining harmonic compensation is to be met by the shunt active filter. 3. PROPOSED ADAPTIVE SHUNT HYBRID FILTER FOR POWER QUALITY COMPENSATION IN INDUCTION MOTOR DRIVES The adaptive shunt hybrid filter consists of three phase adaptive shunt passive filters and adaptive shunt active filter. Adaptive shunt passive filters are developed by series combination of thyristor switched series combination of inductor and capacitor. Their values are designed such as to provide bypass path for fifth and seventh harmonics. It also provides fundamental frequency reactive power to the system. The capacitor values are selected as 210F and inductor values are 15mH and 7mH respectively. Remaining amounts of harmonics and reactive compensation currents are provided by the adaptive shunt active filter. The shunt active filter is controlled to inject remaining amount of harmonics and reactive compensation currents such that source need to supply only real part of fundamental component of current. The schematic diagram of the filtering system is shown in Figure 4. The hybrid filter elements are controlled by ANN based intelligent digital controller. The responsiveness of filter is improved by hysteresis controller based closed loop control. PI controller is also used to compensate for inverter losses and regulation of dc link voltage.
  • 5.  ISSN: 2088-8694 IJPEDS Vol. 4, No. 4, December 2014 : 508 – 516 512 Figure 4. Three phase system feeding variable speed induction motor drive with Adaptive Shunt Hybrid Filter 3.1. Methodology The load current in induction motor drive is represented by: )sin()sin()( ,5,3 1 1     h LhLhLL thititi L  = Real part of fundamental component of load current +Reactive part of fundamental component of load current + Harmonic components of load current (1) Adaptive shunt passive filter compensates for major part of fundamental frequency reactive power and harmonics. Adaptive shunt active filter injects remaining small amount of harmonics and helps to obtain unity power factor sinusoidal current at the point of common coupling. Three phase instantaneous source voltages, fundamental load currents and filter compensation currents are selected as input quantities for training adaptive ANN. The reference compensation currents are developed by analog controller circuit. The actual compensation currents are compared with reference compensation currents to generate switching pulses to IGBTs of three phase voltage source inverter. The current transducers and voltage transducers sample instantaneous load currents, compensation currents and source voltages. Sampled value of instantaneous load current is expressed as: i.e. iL[k] = )]cos()sin([ 2 ,.....3,2,1 1 tnkWtnkW n N n n   = )]cos()sin([)]sin()cos([ 2 ,.....3,2 12111 tnkWtnkWtnkWtnkW n N n n    = iL1, re[k] + iL1, im[k] + h [k]ih (2) where W1n and W2n are amplitudes of sine and cosine components of the measured load current. The equation is represented in vectorial form as: iL[k] = [W11 W21 ---------W1N W2N]                                 )cos( )sin( )2cos( )2sin( )cos( )sin( tNk tNk tk tk tk tk       The adaptive ANN network is implemented using Widrow-Hoff weights updating algorithm [6], [7]. The weights of the connection links are updated using error in the estimated fundamental component and
  • 6. IJPEDS ISSN: 2088-8694  Dynamic Power Quality Compensator with an Adaptive Shunt Hybrid Filter (Sindhu M R) 513 actual real part of fundamental component of load current. The back propagation neural network was trained with MATLAB using 1500 training patterns for 2500 epochs with goal of 0.001.Training method used is Levenberg – Marquardt algorithm. Trained artificial neural network consists of two layers: input layer (6 neurons), output layer (7 neurons) and hidden layer (6 neurons). The ANN network is shown in Figure 5. The performance characteristics of neural network training is shown in Figure 6. The ANN is programmed and implemented using dsPIC30F4011 microcontroller. Two bipolar ADCs are used for conversion of analog quantities to digital quantities. Sampling frequency of 3kHz is selected considering time for sensing input samples, digital conversion, program execution and generation of switching signals. The switching pulses are amplified and given to IGBTs in shunt active filter. The isolation between power circuit and controller circuit is done using an optocoupler 6N136. The shunt active power filter circuit includes power inverter (SKM50GB12B) with three phase IGBT bridge and two capacitors of 2200F. The compensating currents injected by three phase inverter through coupling inductors to the point of common coupling. For sA dt diF /10 max       , 400V 5A 10mH coupling inductor is used. The experimental results with the insertion of ANN Controller based shunt hybrid filter are discussed in following section. Figure 5. Artificial Neural Network for controlling adaptive shunt hybrid filter Figure 6. Performance plot of training neural network for controlling the adaptive shunt hybrid filter 4. PERFORMANCE OF ANN CONTROLLED SHUNT ACTIVE FILTER UNDER DYNAMIC CONDITIONS–RESULTS AND DISCUSSION The operating performance of the adaptive shunt hybrid filter is studied under dynamic conditions – with the application of 25% load and 75% load at t = 0.5s. Fundamental component of source current, THD in source current and power system parameters at the point of common coupling with the installation of adaptive shunt hybrid filter is shown in Table 4 and 5. Figure 7, and 8 show waveforms of source voltage, load current, filter current and source current with the installation of adaptive shunt hybrid filter under
  • 7.  ISSN: 2088-8694 IJPEDS Vol. 4, No. 4, December 2014 : 508 – 516 514 dynamic conditions. The performance of adaptive shunt hybrid filter is verified with reduction in source current harmonics and sinusoidal source currents in phase with source voltages. Waveforms also confirm the performance of the filter under dynamic conditions. Table 4(a). Fundamental component of source current and THD in source current at the point of common coupling with variable speed induction motor drive with Adaptive Shunt Hybrid Filter – Steady state conditions Case Fundamental component of source current (p.u.) THD in Source Current (%) % of 5th harmonic % of 7th harmonic % of 11th harmonic % of 13th harmonic Phase a Phase b Phase c Phase a Phase A Phase A Phase a Phase a I 0.84 0.84 0.84 3.15 2.2 1.6 0.7 0.4 II 0.23 0.23 0.23 3.19 2.5 1.4 1.2 0.9 Table 4(b). Estimate of Power system parameters for the specified load conditions – with Adaptive Shunt Hybrid Filter – Steady state conditions Case Displacement power factor Distortion power factor Source power factor Power Delivered by Source Real Power (pu) Reactive Power (pu) Apparent Power (pu) Distortion Power (pu) I 1 0.9991 0.9991 0.84 0 0.84 0 II 1 0.9995 0.9995 0.23 0 0.23 0 . Figure 7. Source voltage, Load current, Filter current, Source current waveforms for induction motor drive load at 25% rated load under balanced system with adaptive shunt hybrid filter –dynamic conditions Figure 8 Experimental results - Source current waveforms for the induction motor drive load under balanced system with adaptive shunt hybrid filter – dynamic conditions; (a) Without filter, (b) With adaptive shunt hybrid filter
  • 8. IJPEDS ISSN: 2088-8694  Dynamic Power Quality Compensator with an Adaptive Shunt Hybrid Filter (Sindhu M R) 515 Table 5(a). Fundamental component of source current and THD in source current at the point of common coupling with variable speed induction motor drive after the installation of Adaptive Shunt Hybrid Filter – Dynamic conditions Cycle Fundamental component of source current (p.u.) THD in Source Current (%) % of 5th harmonic % of 7th harmonic % of 11th harmonic % of 13th harmonic Phase a Phase b Phase c Phase a Phase A Phase A Phase a Phase A I 0.84 0.84 0.84 3.15 2.2 1.6 0.7 0.4 II 0.72 0.72 0.72 3.24 2.31 1.59 0.6 0.31 III 0.60 0.60 0.60 3.56 2.43 1.87 0.78 0.35 IV 0.48 0.48 0.48 3.32 2.36 1.63 0.63 0.32 V 0.36 0.36 0.36 3.26 2.34 1.60 0.58 0.29 VI 0.23 0.23 0.23 3.19 2.5 1.4 1.2 0.9 Table 5(b). Estimate of Power system parameters in each cycle under dynamic load conditions with the installation of Adaptive Shunt Hybrid Filter Cycle Displacement power factor Distortion power factor Source power factor Power Delivered by Source Real Power (pu) Reactive Power (pu) Apparent Power (pu) Distortion Power (pu) I 1 0.9991 0.9991 0.84 0 0.84 0 II 1 0.998 0.998 0.72 0 0.72 0 III 1 0.997 0.997 0.60 0 0.60 0 IV 1 0.997 0.997 0.48 0 0.48 0 V 1 0.998 0.998 0.36 0 0.36 0 VI 1 0.999 0.999 0.23 0 0.23 0 The simulation and experimental results related to the adaptive shunt hybrid filter illustrated: a) A single controller is used for controlling both adaptive shunt passive filter and adaptive shunt active filter b) The digital ANN based controller is flexible and easy to implement in large quantities. c) In the case of adaptive shunt hybrid filter, the kVA delivered by source for the load is much less compared with shunt adaptive passive filter or ANN controller based shunt active filter. d) The fundamental reactive power drawn from source is much reduced and hence source power factor is improved. e) The performance of the ANN controller is satisfactory with balanced/ unbalanced source and balanced/unbalanced nonlinear load under steady state and dynamic conditions. 5. CONCLUSION Adjustable speed induction motor drives cause large amounts of current and voltage harmonic distortions and reactive power absorption at the point of common coupling. The propagation of distortions throughout the power system affects lifetime of all other power system equipment. Various power quality improvement schemes were suggested by different authors. This paper shows an ANN based adaptive shunt hybrid filter for power quality enhancement in a variable speed drive system. The simulation and experimental results show effective performance of adaptive shunt hybrid filter under steady state and transient conditions. ACKNOWLEDGEMENT The authors wish to thank Amrita Vishwa Vidyapeetham, Coimbatore and Department of Science and Technology, New Delhi for their financial support for carrying out this work.
  • 9.  ISSN: 2088-8694 IJPEDS Vol. 4, No. 4, December 2014 : 508 – 516 516 REFERENCES [1] Bimal K Bose. Power Electronics and Motor Drives: Advances and Trends. Academic press, 2010, Ch 7. Gopal K Dubey. Fundamentals of Electric Drives. Narosa Publishing House, 2013; Ch 6. [2] Gaiceanu M, Rosu E, Paduraru R, Munteanu T. Vector-controlled optimal drive system for the induction motor. 4th International Symposium on Electrical and Electronics Engineering (ISEEE), 2013; 1 - 6 . [3] Zakaria L, Barra K. Predictive Direct Torque and Flux Control of an induction motor drive fed by a Direct Matrix Converter with reactive power minimization. 10th IEEE International Conference on Networking, Sensing and Control (ICNSC), 2013; 34 - 39. [4] Rajesh, Tejavathu, Panda AK, Kumar, S Shiva, Bonala, Sathyam. High performance direct torque and flux control of induction motor drive using fuzzy logic based speed controller Circuits. International Conference on Power and Computing Technologies (ICCPCT). 2013; 213 - 218. [5] Ewald Fuchs and Mohammad Masoum. Power Quality in Power Systems and Electrical Machines. Elseveir Academic Press, 2008; Ch.3. [6] HL Jou. Performance comparison of the three phase active power filter algorithms. IEEE Proc. Gener. Transm. Distrib. 1995: 142(6): 646-652. [7] Ginnes K John, Sindhu MR, Manjula G Nair, “DSP Based digital controller for shunt active filter to improve power quality. International Journal of Recent Trends in Electrical and Electronics Engineering. 2009; 2(7): 92-94. [8] SMR Rafiei, Reza Ghazi, Hamid A Toliyat. IEEE-519-Based Real-Time and Optimal Control of Active Filters Under Non sinusoidal Line Voltages Using Neural Networks,” IEEE Transactions on Power Delivery, Vol. 17, No. 3, July 2002,pp. 815-821. [9] Patricio Salmeron, Jesus R Vazquez. Practical Design of a Three Phase Active Power Line Conditioner controlled by Artificial Neural Networks. IEEE Trans. on Power Delivery. 20(2): 2005; 1037-1044. [10] Zhenfeng Xiao, Yilong Chen, Xiangtian Deng. A Shunt Active Power Filter with enhanced dynamic performance using Dual-Repititive controller and predictive compensation. International Journal of Power Electronics and Drive Systems. 2013; 3: 209-217. [11] Mridula Jha, SP Dubey, Neuro-Fuzzy Based Controller for a Three Phase Four Wire Shunt Active Filter, International Journal of Power Electronics and Drive Systems. 2011; 7; 11(2):148-155.