Effect of Wavy (Corrugated) Twisted Tape Inserts on Heat Transfer
in a double Pipe Heat Exchanger
Mr. A. S .Kurhade
Department of Mechanical Engineering, GSMCOE, University of Pune, India
Prof. M. M. Dange
Department of Mechanical Engg. Faculty of Engineering, GSMCOE, University of Pune, India
Prof. D. B. Nalawade
Department of Mechanical Engineering, Faculty of Engineering, VIIT, University of Pune, India
Abstract
In the present work heat transfer and friction factor properties were experimentally investigated by using copper
wavy (corrugated) twisted tape inserts. The turbulent flow was created by inserting the wavy twisted tape inserts
into the inner tube of heat exchanger creating high rate of turbulence in pipe, which results in increasing heat
transfer enhancement and pressure drop. The tape consists of the corrugations and the twisting with various twist
ratios (TR=10.7, 8.5, 7.1). The length and width of insert was 1 meter and 14 mm respectively. The outer tube of
heat exchanger is made up of mild steel with outside diameter 0.0198 m & 0.0142 m inside diameter and the inner
tube is made up of copper with 0.038 m outside diameter and 0.032 m inside diameter. The length of pipe in pipe
heat exchanger is 1.4 m. The bulk mean temperatures at various positions are used for different flow rate of water.
From the obtained results the new Correlations for Nusselt number and friction factor are developed for twisted
tape inserts. The Reynolds number is varied from 5000 to 17000. The results of varying twists in wavy twisted
tape inserts with different pitches have been compared with the values for the smooth tube. It showed that the
highest heat transfer rate was achieved for the wavy twisted tape with twist ration 7.1. The Nusselt number value
increased by 172 % and friction factor value increased by 32.11% as compared to the smooth tube values.
Keywords - Heat transfer, heat exchanger, wavy twisted tape, turbulent, pressure drop, friction factor,
Introduction
In heat exchanger, the enthalpy is transferred between two or more fluids, at different temperatures. The use of
heat exchangers are in various industrial processes for heating and cooling applications such as air conditioning
and refrigeration systems, heat recovery processes, food and dairy processes, chemical process plants etc. The
major challenge in designing a heat exchanger is to make the equipment more compact and achieve a high heat
transfer rate using minimum pumping power. Techniques for heat transfer augmentation are relevant to several
engineering applications. In recent years, the high cost of energy and material has resulted in an increased effort
aimed at producing more efficient heat exchange equipment. Sometimes there is a need for miniaturization of a
heat exchanger in specific applications, such as space application, through an augmentation of heat transfer.
Furthermore, as a heat exchanger becomes older, the resistance to heat transfer increases owing to fouling or
scaling. These problems are more common for heat exchangers used in marine applications and in chemical
industries. In some specific applications, such as heat exchangers dealing with fluids of low thermal conductivity
and desalination plants, there is a need to increase the heat transfer rate. The heat transfer rate can be improved by
introducing a disturbance in the fluid flow thereby breaking the viscous and thermal boundary layer. However, in
the process pumping power may increase significantly and ultimately the pumping cost becomes high. Therefore,
to achieve a desired heat transfer rate in an existing heat exchanger at an economic pumping power, several
techniques have been proposed in recent years and are discussed under the classification section. The heat transfer
enhancement techniques are performed in widespread applications. Those methods are, for instance, the insertion
of twisted strips and tapes, the insertion of coil wire and helical wire coil and the mounting of turbulent decaying
swirl flow devices in several heat exchangers. The results of those studies have been shown that although heat
NOVATEUR PUBLICATIONS
INTERNATIONAL JOURNAL OF INNOVATIONS IN ENGINEERING RESEARCH AND TECHNOLOGY [IJIERT]
ISSN: 2394-3696
VOLUME 2, ISSUE 1 JAN-2015
2 | P a g e
transfer efficiencies are improved, the flow frictions are also considerably increased. In this report the various
wavy twisted tapes are used for heat transfer enhancement having various twist ratios. The strips are expected to
induce a rapid mixing and a high turbulent and longitudinal vortex flow like a delta wing, of course, resulting in an
excellent rate of heat transfer in the tube.
Experimental Set-Up
Fig. 1 The schematic diagram of experimentation
Fig. 2 Actual photograph of experimentation
NOVATEUR PUBLICATIONS
INTERNATIONAL JOURNAL OF INNOVATIONS IN ENGINEERING RESEARCH AND TECHNOLOGY [IJIERT]
ISSN: 2394-3696
VOLUME 2, ISSUE 1 JAN-2015
3 | P a g e
The experimental set up and the various measuring devices were shown in figure. It consisted of tube in tube type
heat exchanger. The material of inside tube was of Copper and outside tube was of Mild Steel. The thermocouples
were used to measure the inlet and outlet temperature of cold and hot water. Here four thermocouples were used;
two at the inlet and two at the outlet of hot and cold water respectively. Rota meters were used to measure
the flow rate at inlet of cold and hot water. Two centrifugal pumps were used to circulate the cold and hot water.
Two tanks were used for storing the hot water and cold water. Electric heater was attached to the hot water tank
having capacity of 1500 watt. Inverted U-tube manometer was used to measure the pressure difference between
inlet and outlet of test section of hot fluid the velocity of flow through inserted tube was measured by using current
meter. The control valves and bypass valves were provided at inlet of both the rota meters.
Procedure
In the experiment, initially the water tank was filled with cold water and maintained its temperature up to 80 0
C by
using water heater. Then, this hot water was flowed through the rota meter by opening the flow control valve with
help of hot water pump and through the inner pipe of heat exchanger. The cold water from the cold water tank was
allowed to enter the heat exchanger through rota meter by flow control valve & cold water pump. Adjust the flow
rate of cold water at 100 LPH and made it constant during whole experiment. The flow rate of hot water was
adjusted at 300 LPH and kept it constant. When the steady state was reached, the temperatures of the inlet and
outlet of the cold and the hot waters were recorded and pressure drop across the test tube was measured for plain
tube without inserts. Thereafter repeat same procedure with wavy twisted tapes having twist ratio (TR=10.7, 8.5,
7.1) for various flow rates of hot water like 400, 500, 600, 700, 800, 850, 900 & 950 LPH. The figure 3 shows the
terminology of wavy twisted tape and figure 4, 5, 6 shows the wavy tape inserts with twist ratio 10.7, 8.5, 7.1
respectively.
Fig. 3 Terminology of twisted tape
Fig. 4 Wavy corrugated twisted tape with TR – 10.7
Fig. 5 Wavy corrugated twisted tape with TR – 8.5
NOVATEUR PUBLICATIONS
INTERNATIONAL JOURNAL OF INNOVATIONS IN ENGINEERING RESEARCH AND TECHNOLOGY [IJIERT]
ISSN: 2394-3696
VOLUME 2, ISSUE 1 JAN-2015
4 | P a g e
Fig. 6 Wavy corrugated twisted tape with TR – 7.1
Specifications of inserts:
1. Material = Copper
2. Width of twisted tape (W) = 14 mm
3. Twist ratio (TR) = 10.7, 8.5, 7.1.
4. Length of insert = 1000 mm
5. Thickness of inserts = 2 mm
6. Wave-width (WW) = 10 mm
7. Depth of wave = 10 mm
Sample Calculations
The Properties of hot water and cold water are calculated at their bulk mean temperature,
Tbh =
2
T+T h2h1
(1)
Tbc =
2
T+T c2c1
(2)
Tbh and Tbc are bulk mean temperature of hot & cold water. Th1 & Th2 and Tc1 & Tc2 are inlet and outlet
temperature of hot & cold water respectively.
Hot water heat transfer rate,
Qh = mh × Cph × (Th1-Th2) (3)
Cold water heat transfer rate,
Qc = mc × Cpc × (Tc2-Tc1) (4)
mh & mc are the mass flow rate of hot and cold waters. Cp is the specific heat coefficient of water. (Th1-Th2) and
(Tc2-Tc1) are the present temperature difference between inlet and outlet cold water and temperature difference of
inlet and outlet hot water, respectively.
An average heat transfer rate between hot and cold waters and the convection heat transfer between copper surface
and hot fluid flow, can be written as,
Qavg. =
2
Ch QQ +
(5)
Qavg. = TmAsU ∆×× (6)
∆Tm =
( )
( )2
1
ln
21
T
T
TT
∆
∆
∆−∆
(7)
∆T1 = Th1 – Tc2
∆T2 = Th2 – Tc1
NOVATEUR PUBLICATIONS
INTERNATIONAL JOURNAL OF INNOVATIONS IN ENGINEERING RESEARCH AND TECHNOLOGY [IJIERT]
ISSN: 2394-3696
VOLUME 2, ISSUE 1 JAN-2015
5 | P a g e
As , U & ∆Tm is the surface area of tube, overall heat transfer coefficient & Logarithmic mean temperature
difference respectively.
Nusselt Number of cold water flowing through the annular space is given by,
Nuo = 0.023(Reo) 0.8
(Pr) 0.3
(8)
Reo =
µ
ρ hoDU
(9)
Dh = Di - do
Continuity equation, mc = ρAoUo
Heat transfer coefficient (h0) of cold water flowing through the annular space is given by,
Nuo =
K
hoDh
(10)
ho =
h
o
D
KNu
Heat transfer coefficient of hot water (hi),
oi hhU
111
+=
(11)
Nusselt Number (Experimental) of hot water flowing through the tube,
Nui =
K
iidh
(12)
Theoretical Nusselt Number of hot water flowing through the tube is given by (Dittus Boelter equation).
Nui = 0.023(Rei) 0.8
(Pr) 0.3
(13)
Experimental Friction Factor is calculated by,
ghP ρ=∆
i
i
d
UfL
P
2
2
ρ
=∆
2
2
i
i
LU
hgd
f =
(14)
Theoretical Friction Factor f can be written as,






















++×=
33.0
6
Re
10
5010055.0
i
f (15)
Result and discussion
After the experimental study, the Nusselt numbers and friction factors were calculated for plain tube and tube with
wavy tape inserts. These results were compared with the correlation of Dittus and Boelter for Nusselt number &
NOVATEUR PUBLICATIONS
INTERNATIONAL JOURNAL OF INNOVATIONS IN ENGINEERING RESEARCH AND TECHNOLOGY [IJIERT]
ISSN: 2394-3696
VOLUME 2, ISSUE 1 JAN-2015
6 | P a g e
John Nikuradse for friction factor. Figure 7a.shows the graph of Nusselt number Vs Reynolds number for plain
tube. It is found that there is linear behavior of Nusselt number along Reynolds number. Nusselt number is a
function of Reynolds number. Figure 7b.shows the graph of friction factor Vs Reynolds number for plain tube. The
friction factor is inversely proportional with Reynolds number.
Fig. 7a Nusselt number Vs Reynolds number Fig. 7b Friction factor Vs Reynolds number
Fig. 8 Nusselt number Vs Reynolds number for TR=10.7, 8.5, 7.1
Figure 8 shows the variation of Nusselt number with Reynolds number at various twist ratios (TR=10.7, 8.5,
7.1). This figure concludes that the Nusselt number increases with increase in Reynolds number. Therefore heat
transfer rate is more with higher Reynolds number. Here Nusselt number is more for the twisted tape with lesser
twist ratio (TR – 7.1) for particular Reynolds number compared with other twisted tapes. So highest heat transfer
rate was obtained for lesser twist ratio.
NOVATEUR PUBLICATIONS
INTERNATIONAL JOURNAL OF INNOVATIONS IN ENGINEERING RESEARCH AND TECHNOLOGY [IJIERT]
ISSN: 2394-3696
VOLUME 2, ISSUE 1 JAN-2015
7 | P a g e
Fig. 9 Friction Factor Vs Reynolds number for TR=10.7, 8.5, 7.1
Figure 9 shows the variation of friction factor with Reynolds number. It was found that the friction factor become
greater as the twist ratio decreased. The value of friction factor is more for the wavy twisted tape insert having
twist ratio 7.1 as compared with other inserts. The friction factors for the case of the insert having twist ratio 7.1,
8.5 & 10.7 were 2.00, 1.47 and 0.147 times over the plain tube respectively.
Conclusions
By using wavy (corrugated) twisted tape inserts the highest heat transfer rate was achieved for twist ration 7.1. In
comparison with plain tube all wavy twisted tape inserts would significantly enhance the heat transfer rate. The
more twist increased the heat transfer and decreased the friction factor. From this experimental study the results
can be concluded as follows,
1) For Reynold number range 5000 to 17000, the Nusselt number for wavy twisted tape insert with twist ratio
10.7, 8.5 and 7.1 was found to be 75.75 %, 157 % and 172 % respectively.
2) The Friction factor is increased approximately by 9.4 %, 22.44 % and 32.11 % with twist ratio 10.7, 8.5
and 7.1 respectively.
Nomenclatures
As Lateral surface area of tube, m2
Re Reynolds number
Cp Specific heat, J/Kg K V Mean velocity of water
f Friction factor L Length of inner tube
h Heat transfer coefficient, W/m2
K ν Kinematic viscosity of water
k Thermal conductivity, W/mK ρ Density of water
Nu Nusselt number Pr Prandle number
∆P Prassure drop
References
[1] Veysel Ozceyhan, Sibel Gunes, Orhan Buyukalaca and Necdet Altuntop, “Heat transfer enhancement in a tube
using circular cross sectional rings separated from wall”, Applied energy 85 (2008) 988 – 1001
[2] Naga Sarada S., Kalyani K. Radha, A.V.S.Raju, “Experimental Investigation in a Circular Tube to Enhance
Turbulance Heat Transfer Using Mesh Inserts”, ARPN Journals of Engineering & Applied Science (2009)
[3] Piroz Zamankhan, “Heat transfer in counterflow heat exchangers with helical turbulators”, Commun Nonlinear
Sci Numer Simulat 15 (2010) 2894–2907
[4] Mr.Kumbhar D.G., Dr. Sane N.K.,”Heat Transfer Behavior In A Tube With Conical Wire Coil Inserts”.
NOVATEUR PUBLICATIONS
INTERNATIONAL JOURNAL OF INNOVATIONS IN ENGINEERING RESEARCH AND TECHNOLOGY [IJIERT]
ISSN: 2394-3696
VOLUME 2, ISSUE 1 JAN-2015
8 | P a g e
[5] Somsak Pethkool, Smith Eiamsa-ard, Artit Ridluan and Pongjet Promvonge, “Effect of Louvered Strips on
Heat Transfer in a Concentric Pipe Heat Exchanger”, The 2nd Joint International Conference on “Sustainable
Energy and Environment (SEE 2006) 21-23 November 2006, Bangkok, Thailand
[6] Paisarn Naphon , Effect of coil-wire insert on heat transfer enhancement and pressure drop of the horizontal
concentric tube,
[7]S.K. Saha, A. Dutta, S.K. Dhal, Friction and heat transfer characteristics of laminar swirl flow through circular
tubes fitted with regularly spaced twisted-tape elements, International Journal of Heat and Mass Transfer 44
(2001) 4211–4223.
[8] R. Sethumadhavan, M.R. Rao, Turbulent flow heat transfer and fluid friction in helical-wire-coil-inserted tubes,
International Journal of Heat and Mass Transfer 26 (1983) 1833–1845.
[9]Sivashanmugam .P and P.K. Nagarajan, 2007. “Studies on heat transfer and friction factor characteristics of
laminar flow through a circular tube fitted with right and left helical screw-tape inserts”, Experimental Thermal
and Fluid Science, Vol. 32, No. 1, pp. 192-197.
[10] Shah, R.K., Joshi, S.D., 1987. Convective heat transfer in curved ducts. In: Kakac, S., Shah, R.K., Aung, W.
(Eds.), Handbook of Singlephase Convective Heat Transfer. Wiley Interscience, New York, pp. 5.1–5.46.Eiamsa-
ard.
[11] Patil A.G, February 2000, “Laminar flow heat transfer and pressure drop characteristics of power-law inside
tubes with varying width twisted width inserts”, ASME Transactions, Vol. 122, pp. 143-149.
[12] L.Wang, B. Sund, “Performance comparison of some tube inserts”, International communication Heat Mass
Transfer 29 (2002) 45–56.
[13] Pongjet Promvonge, “Thermal performance in circular tube fitted with coiled square wires”, 2007 Elsevier
Ltd.
[14] V. Ozceyhan, “Conjugate heat transfer and thermal stress analysis of wire coil inserted tubes that are heated
externally with uniform heat flux”, Energy Conversion and Management 46 (2005) 1543–1559.
[15] M.A. Akhavan-Behabadi, M.R. Salimpour, V.A. Pazouki, “Pressure drop increase of forced convective
condensation inside horizontal coiled wire inserted tube”. International Communications in Heat and Mass
Transfer 35 (2008) 1220e1226.
[16] K.N. Agrawal, A. Kumar, M.A.A. Behabadi, H.K. Varma, “Heat transfer augmentation by coiled wire inserts
during forced convection condensation of R-22 inside horizontal tubes”, International Journal of Multiphase Flow
24 (1998) 635–650.
[17] P.Promvonge, “Thermal performance in circular tube fitted with coiled square wires”. Energy Conversion and
Management49 (2008)980e987.
[18] Naphon P. “Effect of coil-wire insert on heat transfer enhancement and pressure drop of the horizontal
concentric tubes”. Int Commun Heat Mass Transfer 2006; 33(6):753–63.
[19] S. Gunes, V. Ozceyhan, O. Buyukalaca, The experimental investigation of heat transfer and pressure drop in a
tube with coiled wire inserts placed separately from the tube wall, Applied Thermal Engineering 30 (2010) 1719–
1725.

More Related Content

PDF
Irjet v4 i12326Effect of External Threaded Inside Tube on Heat Transfer Rate ...
PDF
IRJET- Effect of Wavy Tube on Heat Transfer in a Concentric Tube Heat Exch...
PDF
E351923
PDF
International Journal of Engineering Research and Development
PDF
Experimental Study of Heat Transfer Enhancement of Pipe-inPipe Helical Coil H...
PDF
Experimental analysis of heat transfer enhancementin circular
PDF
A Review on Enhancement of Heat Transfer Rate by Various Passive Methods
PDF
Experimental Investigation on Heat Transfer Enhancement in Laminar Flow in Ci...
Irjet v4 i12326Effect of External Threaded Inside Tube on Heat Transfer Rate ...
IRJET- Effect of Wavy Tube on Heat Transfer in a Concentric Tube Heat Exch...
E351923
International Journal of Engineering Research and Development
Experimental Study of Heat Transfer Enhancement of Pipe-inPipe Helical Coil H...
Experimental analysis of heat transfer enhancementin circular
A Review on Enhancement of Heat Transfer Rate by Various Passive Methods
Experimental Investigation on Heat Transfer Enhancement in Laminar Flow in Ci...

What's hot (17)

PDF
Team a01 9_lab_2
PDF
Paper id 21201420
PDF
Experimental Investigation of Heat Transfer Enhancement by Using Clockwise an...
PDF
Gd3411261132
PDF
D0532328
PDF
Df4301619624
PDF
Experimental study on heat transfer and friction factor characteristics in la...
PDF
FLUID FLOW ANALYSIS IN AIR DUCT FLOW WITH AND WITHOUT INTERNAL THREADS USING ...
PDF
IRJET-Enhancement of Heat Transfer through Pipe with the Help of Various Type...
PDF
EXPERIMENTAL STUDY ON THE ANALYSIS OF HEAT ENHANCEMENT IN CORRUGATED TWISTED ...
PDF
IRJET- Experimental Analysis of Convective Heat Transfer Augmentation of Bi-M...
PDF
[IJET-V2I3P20] Authors: Pravin S.Nikam , Prof. R.Y.Patil ,Prof. P.R.Patil , P...
PDF
IRJET- Numerical Analysis for Effect of Different Length Combination of Turbu...
PDF
C1303071722
PDF
Optimization of a Shell and Tube Condenser using Numerical Method
PDF
IRJET- Experimental Investigation of Pipe in Pipe Tube Heat Exchanger using S...
PDF
Heat Transfer Enhancement of Shell and Tube Heat Exchanger Using Conical Tapes.
Team a01 9_lab_2
Paper id 21201420
Experimental Investigation of Heat Transfer Enhancement by Using Clockwise an...
Gd3411261132
D0532328
Df4301619624
Experimental study on heat transfer and friction factor characteristics in la...
FLUID FLOW ANALYSIS IN AIR DUCT FLOW WITH AND WITHOUT INTERNAL THREADS USING ...
IRJET-Enhancement of Heat Transfer through Pipe with the Help of Various Type...
EXPERIMENTAL STUDY ON THE ANALYSIS OF HEAT ENHANCEMENT IN CORRUGATED TWISTED ...
IRJET- Experimental Analysis of Convective Heat Transfer Augmentation of Bi-M...
[IJET-V2I3P20] Authors: Pravin S.Nikam , Prof. R.Y.Patil ,Prof. P.R.Patil , P...
IRJET- Numerical Analysis for Effect of Different Length Combination of Turbu...
C1303071722
Optimization of a Shell and Tube Condenser using Numerical Method
IRJET- Experimental Investigation of Pipe in Pipe Tube Heat Exchanger using S...
Heat Transfer Enhancement of Shell and Tube Heat Exchanger Using Conical Tapes.
Ad

Similar to Effect of Wavy (Corrugated) Twisted Tape Inserts on Heat Transfer in a double Pipe Heat Exchanger (20)

PDF
It3314911496
PDF
CFD Analysis of Concentric Tube Heat Exchanger Using Twisted Tapes
PDF
Experimental study of heat transfer enhancement in a pipe using twisted tapes
PDF
30120140506001
PDF
NUMERICAL SIMULATION OF ENHANCEMENT OF HEAT TRANSFER IN A TUBE WITH AND WITHO...
PDF
Enhancement of heat transfer in tube in-tube heat exchangers using twisted in...
PDF
Performance Analysis of Copper Twisted Tape Inserts for Heat Transfer in A Ci...
PDF
EXPERIMENTATION ON COPPER TUBE WITH INTERNAL THREADING FOR A HEAT EXCHANGER P...
PDF
Paper id 25201450
PDF
Review of Heat Transfer Parameters using internal threaded pipe fitted with i...
PDF
IRJET- Convective Heat Transfers Inside Tubes
PDF
Effect of Wavy Tube on Heat Transfer in a Concentric Tube Heat Exchanger: A R...
PDF
[IJET V2I4P7] Authors: Pravin S.Nikam, Prof. R. Y. Patil, Prof. D.A. Patil, P...
PDF
The Effect of insertion of different geometries on heat transfer performance ...
PDF
The Effect of insertion of different geometries on heat transfer performance ...
PDF
A Review on Experimental and CFD Analysis for Heat Transfer Enhancement in He...
PDF
Thermo hydraulics performance of turbulent flow heat transfer through square ...
PDF
Thermo hydraulics performance of turbulent flow heat transfer through square ...
PDF
CONVECTIVE HEAT TRANSFER ENHANCEMENTS IN TUBE USING LOUVERED STRIP INSERT
PDF
CONVECTIVE HEAT TRANSFER ENHANCEMENTS IN TUBE USING INSERT – A REVIEW
It3314911496
CFD Analysis of Concentric Tube Heat Exchanger Using Twisted Tapes
Experimental study of heat transfer enhancement in a pipe using twisted tapes
30120140506001
NUMERICAL SIMULATION OF ENHANCEMENT OF HEAT TRANSFER IN A TUBE WITH AND WITHO...
Enhancement of heat transfer in tube in-tube heat exchangers using twisted in...
Performance Analysis of Copper Twisted Tape Inserts for Heat Transfer in A Ci...
EXPERIMENTATION ON COPPER TUBE WITH INTERNAL THREADING FOR A HEAT EXCHANGER P...
Paper id 25201450
Review of Heat Transfer Parameters using internal threaded pipe fitted with i...
IRJET- Convective Heat Transfers Inside Tubes
Effect of Wavy Tube on Heat Transfer in a Concentric Tube Heat Exchanger: A R...
[IJET V2I4P7] Authors: Pravin S.Nikam, Prof. R. Y. Patil, Prof. D.A. Patil, P...
The Effect of insertion of different geometries on heat transfer performance ...
The Effect of insertion of different geometries on heat transfer performance ...
A Review on Experimental and CFD Analysis for Heat Transfer Enhancement in He...
Thermo hydraulics performance of turbulent flow heat transfer through square ...
Thermo hydraulics performance of turbulent flow heat transfer through square ...
CONVECTIVE HEAT TRANSFER ENHANCEMENTS IN TUBE USING LOUVERED STRIP INSERT
CONVECTIVE HEAT TRANSFER ENHANCEMENTS IN TUBE USING INSERT – A REVIEW
Ad

More from ijiert bestjournal (20)

PDF
CRACKS IN STEEL CASTING FOR VOLUTE CASING OF A PUMP
PDF
A COMPARATIVE STUDY OF DESIGN OF SIMPLE SPUR GEAR TRAIN AND HELICAL GEAR TRAI...
PDF
COMPARATIVE ANALYSIS OF CONVENTIONAL LEAF SPRING AND COMPOSITE LEAF
PDF
POWER GENERATION BY DIFFUSER AUGMENTED WIND TURBINE
PDF
FINITE ELEMENT ANALYSIS OF CONNECTING ROD OF MG-ALLOY
PDF
REVIEW ON CRITICAL SPEED IMPROVEMENT IN SINGLE CYLINDER ENGINE VALVE TRAIN
PDF
ENERGY CONVERSION PHENOMENON IN IMPLEMENTATION OF WATER LIFTING BY USING PEND...
PDF
SCUDERI SPLIT CYCLE ENGINE: REVOLUTIONARY TECHNOLOGY & EVOLUTIONARY DESIGN RE...
PDF
EXPERIMENTAL EVALUATION OF TEMPERATURE DISTRIBUTION IN JOURNAL BEARING OPERAT...
PDF
STUDY OF SOLAR THERMAL CAVITY RECEIVER FOR PARABOLIC CONCENTRATING COLLECTOR
PDF
DESIGN, OPTIMIZATION AND FINITE ELEMENT ANALYSIS OF CRANKSHAFT
PDF
ELECTRO CHEMICAL MACHINING AND ELECTRICAL DISCHARGE MACHINING PROCESSES MICRO...
PDF
HEAT TRANSFER ENHANCEMENT BY USING NANOFLUID JET IMPINGEMENT
PDF
MODIFICATION AND OPTIMIZATION IN STEEL SANDWICH PANELS USING ANSYS WORKBENCH
PDF
IMPACT ANALYSIS OF ALUMINUM HONEYCOMB SANDWICH PANEL BUMPER BEAM: A REVIEW
PDF
DESIGN OF WELDING FIXTURES AND POSITIONERS
PDF
ADVANCED TRANSIENT THERMAL AND STRUCTURAL ANALYSIS OF DISC BRAKE BY USING ANS...
PDF
REVIEW ON MECHANICAL PROPERTIES OF NON-ASBESTOS COMPOSITE MATERIAL USED IN BR...
PDF
PERFORMANCE EVALUATION OF TRIBOLOGICAL PROPERTIES OF COTTON SEED OIL FOR MULT...
PDF
MAGNETIC ABRASIVE FINISHING
CRACKS IN STEEL CASTING FOR VOLUTE CASING OF A PUMP
A COMPARATIVE STUDY OF DESIGN OF SIMPLE SPUR GEAR TRAIN AND HELICAL GEAR TRAI...
COMPARATIVE ANALYSIS OF CONVENTIONAL LEAF SPRING AND COMPOSITE LEAF
POWER GENERATION BY DIFFUSER AUGMENTED WIND TURBINE
FINITE ELEMENT ANALYSIS OF CONNECTING ROD OF MG-ALLOY
REVIEW ON CRITICAL SPEED IMPROVEMENT IN SINGLE CYLINDER ENGINE VALVE TRAIN
ENERGY CONVERSION PHENOMENON IN IMPLEMENTATION OF WATER LIFTING BY USING PEND...
SCUDERI SPLIT CYCLE ENGINE: REVOLUTIONARY TECHNOLOGY & EVOLUTIONARY DESIGN RE...
EXPERIMENTAL EVALUATION OF TEMPERATURE DISTRIBUTION IN JOURNAL BEARING OPERAT...
STUDY OF SOLAR THERMAL CAVITY RECEIVER FOR PARABOLIC CONCENTRATING COLLECTOR
DESIGN, OPTIMIZATION AND FINITE ELEMENT ANALYSIS OF CRANKSHAFT
ELECTRO CHEMICAL MACHINING AND ELECTRICAL DISCHARGE MACHINING PROCESSES MICRO...
HEAT TRANSFER ENHANCEMENT BY USING NANOFLUID JET IMPINGEMENT
MODIFICATION AND OPTIMIZATION IN STEEL SANDWICH PANELS USING ANSYS WORKBENCH
IMPACT ANALYSIS OF ALUMINUM HONEYCOMB SANDWICH PANEL BUMPER BEAM: A REVIEW
DESIGN OF WELDING FIXTURES AND POSITIONERS
ADVANCED TRANSIENT THERMAL AND STRUCTURAL ANALYSIS OF DISC BRAKE BY USING ANS...
REVIEW ON MECHANICAL PROPERTIES OF NON-ASBESTOS COMPOSITE MATERIAL USED IN BR...
PERFORMANCE EVALUATION OF TRIBOLOGICAL PROPERTIES OF COTTON SEED OIL FOR MULT...
MAGNETIC ABRASIVE FINISHING

Recently uploaded (20)

PDF
Structs to JSON How Go Powers REST APIs.pdf
PPTX
Lesson 3_Tessellation.pptx finite Mathematics
PPTX
Lecture Notes Electrical Wiring System Components
PPTX
OOP with Java - Java Introduction (Basics)
PDF
BMEC211 - INTRODUCTION TO MECHATRONICS-1.pdf
PPTX
M Tech Sem 1 Civil Engineering Environmental Sciences.pptx
PPTX
UNIT 4 Total Quality Management .pptx
PPTX
Welding lecture in detail for understanding
PPTX
UNIT-1 - COAL BASED THERMAL POWER PLANTS
DOCX
573137875-Attendance-Management-System-original
PPTX
CYBER-CRIMES AND SECURITY A guide to understanding
PDF
PRIZ Academy - 9 Windows Thinking Where to Invest Today to Win Tomorrow.pdf
PPTX
MCN 401 KTU-2019-PPE KITS-MODULE 2.pptx
PDF
Operating System & Kernel Study Guide-1 - converted.pdf
PPTX
Foundation to blockchain - A guide to Blockchain Tech
PDF
July 2025 - Top 10 Read Articles in International Journal of Software Enginee...
PDF
SM_6th-Sem__Cse_Internet-of-Things.pdf IOT
PPTX
FINAL REVIEW FOR COPD DIANOSIS FOR PULMONARY DISEASE.pptx
DOCX
ASol_English-Language-Literature-Set-1-27-02-2023-converted.docx
PPTX
Infosys Presentation by1.Riyan Bagwan 2.Samadhan Naiknavare 3.Gaurav Shinde 4...
Structs to JSON How Go Powers REST APIs.pdf
Lesson 3_Tessellation.pptx finite Mathematics
Lecture Notes Electrical Wiring System Components
OOP with Java - Java Introduction (Basics)
BMEC211 - INTRODUCTION TO MECHATRONICS-1.pdf
M Tech Sem 1 Civil Engineering Environmental Sciences.pptx
UNIT 4 Total Quality Management .pptx
Welding lecture in detail for understanding
UNIT-1 - COAL BASED THERMAL POWER PLANTS
573137875-Attendance-Management-System-original
CYBER-CRIMES AND SECURITY A guide to understanding
PRIZ Academy - 9 Windows Thinking Where to Invest Today to Win Tomorrow.pdf
MCN 401 KTU-2019-PPE KITS-MODULE 2.pptx
Operating System & Kernel Study Guide-1 - converted.pdf
Foundation to blockchain - A guide to Blockchain Tech
July 2025 - Top 10 Read Articles in International Journal of Software Enginee...
SM_6th-Sem__Cse_Internet-of-Things.pdf IOT
FINAL REVIEW FOR COPD DIANOSIS FOR PULMONARY DISEASE.pptx
ASol_English-Language-Literature-Set-1-27-02-2023-converted.docx
Infosys Presentation by1.Riyan Bagwan 2.Samadhan Naiknavare 3.Gaurav Shinde 4...

Effect of Wavy (Corrugated) Twisted Tape Inserts on Heat Transfer in a double Pipe Heat Exchanger

  • 1. NOVATEUR PUBLICATIONS INTERNATIONAL JOURNAL OF INNOVATIONS IN ENGINEERING RESEARCH AND TECHNOLOGY [IJIERT] ISSN: 2394-3696 VOLUME 2, ISSUE 1 JAN-2015 1 | P a g e Effect of Wavy (Corrugated) Twisted Tape Inserts on Heat Transfer in a double Pipe Heat Exchanger Mr. A. S .Kurhade Department of Mechanical Engineering, GSMCOE, University of Pune, India Prof. M. M. Dange Department of Mechanical Engg. Faculty of Engineering, GSMCOE, University of Pune, India Prof. D. B. Nalawade Department of Mechanical Engineering, Faculty of Engineering, VIIT, University of Pune, India Abstract In the present work heat transfer and friction factor properties were experimentally investigated by using copper wavy (corrugated) twisted tape inserts. The turbulent flow was created by inserting the wavy twisted tape inserts into the inner tube of heat exchanger creating high rate of turbulence in pipe, which results in increasing heat transfer enhancement and pressure drop. The tape consists of the corrugations and the twisting with various twist ratios (TR=10.7, 8.5, 7.1). The length and width of insert was 1 meter and 14 mm respectively. The outer tube of heat exchanger is made up of mild steel with outside diameter 0.0198 m & 0.0142 m inside diameter and the inner tube is made up of copper with 0.038 m outside diameter and 0.032 m inside diameter. The length of pipe in pipe heat exchanger is 1.4 m. The bulk mean temperatures at various positions are used for different flow rate of water. From the obtained results the new Correlations for Nusselt number and friction factor are developed for twisted tape inserts. The Reynolds number is varied from 5000 to 17000. The results of varying twists in wavy twisted tape inserts with different pitches have been compared with the values for the smooth tube. It showed that the highest heat transfer rate was achieved for the wavy twisted tape with twist ration 7.1. The Nusselt number value increased by 172 % and friction factor value increased by 32.11% as compared to the smooth tube values. Keywords - Heat transfer, heat exchanger, wavy twisted tape, turbulent, pressure drop, friction factor, Introduction In heat exchanger, the enthalpy is transferred between two or more fluids, at different temperatures. The use of heat exchangers are in various industrial processes for heating and cooling applications such as air conditioning and refrigeration systems, heat recovery processes, food and dairy processes, chemical process plants etc. The major challenge in designing a heat exchanger is to make the equipment more compact and achieve a high heat transfer rate using minimum pumping power. Techniques for heat transfer augmentation are relevant to several engineering applications. In recent years, the high cost of energy and material has resulted in an increased effort aimed at producing more efficient heat exchange equipment. Sometimes there is a need for miniaturization of a heat exchanger in specific applications, such as space application, through an augmentation of heat transfer. Furthermore, as a heat exchanger becomes older, the resistance to heat transfer increases owing to fouling or scaling. These problems are more common for heat exchangers used in marine applications and in chemical industries. In some specific applications, such as heat exchangers dealing with fluids of low thermal conductivity and desalination plants, there is a need to increase the heat transfer rate. The heat transfer rate can be improved by introducing a disturbance in the fluid flow thereby breaking the viscous and thermal boundary layer. However, in the process pumping power may increase significantly and ultimately the pumping cost becomes high. Therefore, to achieve a desired heat transfer rate in an existing heat exchanger at an economic pumping power, several techniques have been proposed in recent years and are discussed under the classification section. The heat transfer enhancement techniques are performed in widespread applications. Those methods are, for instance, the insertion of twisted strips and tapes, the insertion of coil wire and helical wire coil and the mounting of turbulent decaying swirl flow devices in several heat exchangers. The results of those studies have been shown that although heat
  • 2. NOVATEUR PUBLICATIONS INTERNATIONAL JOURNAL OF INNOVATIONS IN ENGINEERING RESEARCH AND TECHNOLOGY [IJIERT] ISSN: 2394-3696 VOLUME 2, ISSUE 1 JAN-2015 2 | P a g e transfer efficiencies are improved, the flow frictions are also considerably increased. In this report the various wavy twisted tapes are used for heat transfer enhancement having various twist ratios. The strips are expected to induce a rapid mixing and a high turbulent and longitudinal vortex flow like a delta wing, of course, resulting in an excellent rate of heat transfer in the tube. Experimental Set-Up Fig. 1 The schematic diagram of experimentation Fig. 2 Actual photograph of experimentation
  • 3. NOVATEUR PUBLICATIONS INTERNATIONAL JOURNAL OF INNOVATIONS IN ENGINEERING RESEARCH AND TECHNOLOGY [IJIERT] ISSN: 2394-3696 VOLUME 2, ISSUE 1 JAN-2015 3 | P a g e The experimental set up and the various measuring devices were shown in figure. It consisted of tube in tube type heat exchanger. The material of inside tube was of Copper and outside tube was of Mild Steel. The thermocouples were used to measure the inlet and outlet temperature of cold and hot water. Here four thermocouples were used; two at the inlet and two at the outlet of hot and cold water respectively. Rota meters were used to measure the flow rate at inlet of cold and hot water. Two centrifugal pumps were used to circulate the cold and hot water. Two tanks were used for storing the hot water and cold water. Electric heater was attached to the hot water tank having capacity of 1500 watt. Inverted U-tube manometer was used to measure the pressure difference between inlet and outlet of test section of hot fluid the velocity of flow through inserted tube was measured by using current meter. The control valves and bypass valves were provided at inlet of both the rota meters. Procedure In the experiment, initially the water tank was filled with cold water and maintained its temperature up to 80 0 C by using water heater. Then, this hot water was flowed through the rota meter by opening the flow control valve with help of hot water pump and through the inner pipe of heat exchanger. The cold water from the cold water tank was allowed to enter the heat exchanger through rota meter by flow control valve & cold water pump. Adjust the flow rate of cold water at 100 LPH and made it constant during whole experiment. The flow rate of hot water was adjusted at 300 LPH and kept it constant. When the steady state was reached, the temperatures of the inlet and outlet of the cold and the hot waters were recorded and pressure drop across the test tube was measured for plain tube without inserts. Thereafter repeat same procedure with wavy twisted tapes having twist ratio (TR=10.7, 8.5, 7.1) for various flow rates of hot water like 400, 500, 600, 700, 800, 850, 900 & 950 LPH. The figure 3 shows the terminology of wavy twisted tape and figure 4, 5, 6 shows the wavy tape inserts with twist ratio 10.7, 8.5, 7.1 respectively. Fig. 3 Terminology of twisted tape Fig. 4 Wavy corrugated twisted tape with TR – 10.7 Fig. 5 Wavy corrugated twisted tape with TR – 8.5
  • 4. NOVATEUR PUBLICATIONS INTERNATIONAL JOURNAL OF INNOVATIONS IN ENGINEERING RESEARCH AND TECHNOLOGY [IJIERT] ISSN: 2394-3696 VOLUME 2, ISSUE 1 JAN-2015 4 | P a g e Fig. 6 Wavy corrugated twisted tape with TR – 7.1 Specifications of inserts: 1. Material = Copper 2. Width of twisted tape (W) = 14 mm 3. Twist ratio (TR) = 10.7, 8.5, 7.1. 4. Length of insert = 1000 mm 5. Thickness of inserts = 2 mm 6. Wave-width (WW) = 10 mm 7. Depth of wave = 10 mm Sample Calculations The Properties of hot water and cold water are calculated at their bulk mean temperature, Tbh = 2 T+T h2h1 (1) Tbc = 2 T+T c2c1 (2) Tbh and Tbc are bulk mean temperature of hot & cold water. Th1 & Th2 and Tc1 & Tc2 are inlet and outlet temperature of hot & cold water respectively. Hot water heat transfer rate, Qh = mh × Cph × (Th1-Th2) (3) Cold water heat transfer rate, Qc = mc × Cpc × (Tc2-Tc1) (4) mh & mc are the mass flow rate of hot and cold waters. Cp is the specific heat coefficient of water. (Th1-Th2) and (Tc2-Tc1) are the present temperature difference between inlet and outlet cold water and temperature difference of inlet and outlet hot water, respectively. An average heat transfer rate between hot and cold waters and the convection heat transfer between copper surface and hot fluid flow, can be written as, Qavg. = 2 Ch QQ + (5) Qavg. = TmAsU ∆×× (6) ∆Tm = ( ) ( )2 1 ln 21 T T TT ∆ ∆ ∆−∆ (7) ∆T1 = Th1 – Tc2 ∆T2 = Th2 – Tc1
  • 5. NOVATEUR PUBLICATIONS INTERNATIONAL JOURNAL OF INNOVATIONS IN ENGINEERING RESEARCH AND TECHNOLOGY [IJIERT] ISSN: 2394-3696 VOLUME 2, ISSUE 1 JAN-2015 5 | P a g e As , U & ∆Tm is the surface area of tube, overall heat transfer coefficient & Logarithmic mean temperature difference respectively. Nusselt Number of cold water flowing through the annular space is given by, Nuo = 0.023(Reo) 0.8 (Pr) 0.3 (8) Reo = µ ρ hoDU (9) Dh = Di - do Continuity equation, mc = ρAoUo Heat transfer coefficient (h0) of cold water flowing through the annular space is given by, Nuo = K hoDh (10) ho = h o D KNu Heat transfer coefficient of hot water (hi), oi hhU 111 += (11) Nusselt Number (Experimental) of hot water flowing through the tube, Nui = K iidh (12) Theoretical Nusselt Number of hot water flowing through the tube is given by (Dittus Boelter equation). Nui = 0.023(Rei) 0.8 (Pr) 0.3 (13) Experimental Friction Factor is calculated by, ghP ρ=∆ i i d UfL P 2 2 ρ =∆ 2 2 i i LU hgd f = (14) Theoretical Friction Factor f can be written as,                       ++×= 33.0 6 Re 10 5010055.0 i f (15) Result and discussion After the experimental study, the Nusselt numbers and friction factors were calculated for plain tube and tube with wavy tape inserts. These results were compared with the correlation of Dittus and Boelter for Nusselt number &
  • 6. NOVATEUR PUBLICATIONS INTERNATIONAL JOURNAL OF INNOVATIONS IN ENGINEERING RESEARCH AND TECHNOLOGY [IJIERT] ISSN: 2394-3696 VOLUME 2, ISSUE 1 JAN-2015 6 | P a g e John Nikuradse for friction factor. Figure 7a.shows the graph of Nusselt number Vs Reynolds number for plain tube. It is found that there is linear behavior of Nusselt number along Reynolds number. Nusselt number is a function of Reynolds number. Figure 7b.shows the graph of friction factor Vs Reynolds number for plain tube. The friction factor is inversely proportional with Reynolds number. Fig. 7a Nusselt number Vs Reynolds number Fig. 7b Friction factor Vs Reynolds number Fig. 8 Nusselt number Vs Reynolds number for TR=10.7, 8.5, 7.1 Figure 8 shows the variation of Nusselt number with Reynolds number at various twist ratios (TR=10.7, 8.5, 7.1). This figure concludes that the Nusselt number increases with increase in Reynolds number. Therefore heat transfer rate is more with higher Reynolds number. Here Nusselt number is more for the twisted tape with lesser twist ratio (TR – 7.1) for particular Reynolds number compared with other twisted tapes. So highest heat transfer rate was obtained for lesser twist ratio.
  • 7. NOVATEUR PUBLICATIONS INTERNATIONAL JOURNAL OF INNOVATIONS IN ENGINEERING RESEARCH AND TECHNOLOGY [IJIERT] ISSN: 2394-3696 VOLUME 2, ISSUE 1 JAN-2015 7 | P a g e Fig. 9 Friction Factor Vs Reynolds number for TR=10.7, 8.5, 7.1 Figure 9 shows the variation of friction factor with Reynolds number. It was found that the friction factor become greater as the twist ratio decreased. The value of friction factor is more for the wavy twisted tape insert having twist ratio 7.1 as compared with other inserts. The friction factors for the case of the insert having twist ratio 7.1, 8.5 & 10.7 were 2.00, 1.47 and 0.147 times over the plain tube respectively. Conclusions By using wavy (corrugated) twisted tape inserts the highest heat transfer rate was achieved for twist ration 7.1. In comparison with plain tube all wavy twisted tape inserts would significantly enhance the heat transfer rate. The more twist increased the heat transfer and decreased the friction factor. From this experimental study the results can be concluded as follows, 1) For Reynold number range 5000 to 17000, the Nusselt number for wavy twisted tape insert with twist ratio 10.7, 8.5 and 7.1 was found to be 75.75 %, 157 % and 172 % respectively. 2) The Friction factor is increased approximately by 9.4 %, 22.44 % and 32.11 % with twist ratio 10.7, 8.5 and 7.1 respectively. Nomenclatures As Lateral surface area of tube, m2 Re Reynolds number Cp Specific heat, J/Kg K V Mean velocity of water f Friction factor L Length of inner tube h Heat transfer coefficient, W/m2 K ν Kinematic viscosity of water k Thermal conductivity, W/mK ρ Density of water Nu Nusselt number Pr Prandle number ∆P Prassure drop References [1] Veysel Ozceyhan, Sibel Gunes, Orhan Buyukalaca and Necdet Altuntop, “Heat transfer enhancement in a tube using circular cross sectional rings separated from wall”, Applied energy 85 (2008) 988 – 1001 [2] Naga Sarada S., Kalyani K. Radha, A.V.S.Raju, “Experimental Investigation in a Circular Tube to Enhance Turbulance Heat Transfer Using Mesh Inserts”, ARPN Journals of Engineering & Applied Science (2009) [3] Piroz Zamankhan, “Heat transfer in counterflow heat exchangers with helical turbulators”, Commun Nonlinear Sci Numer Simulat 15 (2010) 2894–2907 [4] Mr.Kumbhar D.G., Dr. Sane N.K.,”Heat Transfer Behavior In A Tube With Conical Wire Coil Inserts”.
  • 8. NOVATEUR PUBLICATIONS INTERNATIONAL JOURNAL OF INNOVATIONS IN ENGINEERING RESEARCH AND TECHNOLOGY [IJIERT] ISSN: 2394-3696 VOLUME 2, ISSUE 1 JAN-2015 8 | P a g e [5] Somsak Pethkool, Smith Eiamsa-ard, Artit Ridluan and Pongjet Promvonge, “Effect of Louvered Strips on Heat Transfer in a Concentric Pipe Heat Exchanger”, The 2nd Joint International Conference on “Sustainable Energy and Environment (SEE 2006) 21-23 November 2006, Bangkok, Thailand [6] Paisarn Naphon , Effect of coil-wire insert on heat transfer enhancement and pressure drop of the horizontal concentric tube, [7]S.K. Saha, A. Dutta, S.K. Dhal, Friction and heat transfer characteristics of laminar swirl flow through circular tubes fitted with regularly spaced twisted-tape elements, International Journal of Heat and Mass Transfer 44 (2001) 4211–4223. [8] R. Sethumadhavan, M.R. Rao, Turbulent flow heat transfer and fluid friction in helical-wire-coil-inserted tubes, International Journal of Heat and Mass Transfer 26 (1983) 1833–1845. [9]Sivashanmugam .P and P.K. Nagarajan, 2007. “Studies on heat transfer and friction factor characteristics of laminar flow through a circular tube fitted with right and left helical screw-tape inserts”, Experimental Thermal and Fluid Science, Vol. 32, No. 1, pp. 192-197. [10] Shah, R.K., Joshi, S.D., 1987. Convective heat transfer in curved ducts. In: Kakac, S., Shah, R.K., Aung, W. (Eds.), Handbook of Singlephase Convective Heat Transfer. Wiley Interscience, New York, pp. 5.1–5.46.Eiamsa- ard. [11] Patil A.G, February 2000, “Laminar flow heat transfer and pressure drop characteristics of power-law inside tubes with varying width twisted width inserts”, ASME Transactions, Vol. 122, pp. 143-149. [12] L.Wang, B. Sund, “Performance comparison of some tube inserts”, International communication Heat Mass Transfer 29 (2002) 45–56. [13] Pongjet Promvonge, “Thermal performance in circular tube fitted with coiled square wires”, 2007 Elsevier Ltd. [14] V. Ozceyhan, “Conjugate heat transfer and thermal stress analysis of wire coil inserted tubes that are heated externally with uniform heat flux”, Energy Conversion and Management 46 (2005) 1543–1559. [15] M.A. Akhavan-Behabadi, M.R. Salimpour, V.A. Pazouki, “Pressure drop increase of forced convective condensation inside horizontal coiled wire inserted tube”. International Communications in Heat and Mass Transfer 35 (2008) 1220e1226. [16] K.N. Agrawal, A. Kumar, M.A.A. Behabadi, H.K. Varma, “Heat transfer augmentation by coiled wire inserts during forced convection condensation of R-22 inside horizontal tubes”, International Journal of Multiphase Flow 24 (1998) 635–650. [17] P.Promvonge, “Thermal performance in circular tube fitted with coiled square wires”. Energy Conversion and Management49 (2008)980e987. [18] Naphon P. “Effect of coil-wire insert on heat transfer enhancement and pressure drop of the horizontal concentric tubes”. Int Commun Heat Mass Transfer 2006; 33(6):753–63. [19] S. Gunes, V. Ozceyhan, O. Buyukalaca, The experimental investigation of heat transfer and pressure drop in a tube with coiled wire inserts placed separately from the tube wall, Applied Thermal Engineering 30 (2010) 1719– 1725.