Model T7800 Electro-Pneumatic I/P, E/P Transducer
89
800-334-8422
Features
• The T7800 Series Transducers provide
maximum versatility for precision applications.
• Field Reversible Feature provides output
that is inversely proportional to input signal.
• RFI/EMI Protection eliminates susceptibility
to electromagnetic and radio interference.
• Internal Electronic Feedback and solid
state controlled Piezoelectric Actuator
provide precise control of output pressure
regardless of vibration or position.
• Damping Adjustment for optimum tuning
response.
• Split range operation lets a common signal
source control two or more functions.
• Compact size for use in restricted spaces.
• Various mounting configurations allow
installation flexibility for most applications.
• NEMA 4X, Type 4 Enclosure and IP65
rated for indoor and outdoor installations.
• Canadian Registration Numbers (CRN)
certification for all territories and provinces.
Operating Principles
STANDARD RANGE
The Model T7800 Series converts a DC
input signal to a linear proportional
pneumatic output. It includes the Primary
Converting Section and the pneumatic Relay
Section. The Piezoelectric Ceramic Actuator,
in the Primary Converting Section, functions
as a Flapper. The Flapper and Nozzle work
together to control the signal pressure. The
signal pressure that sets the output pressure
acts on the Upper Control Diaphragm in the
Pneumatic Relay Section. The Lower
Control Diaphragm in the Pneumatic Relay
Section senses the output pressure.
EXTENDED RANGE
In the Extended Range units, an additional
Relay Section amplifies the output pressure.
Model TA7800 Standard Range
B
Model
T7800
BTRANS65 quark 7:B Trans 65-110.qxd 9/1/2006 5:54 PM Page 89
M.S. Jacobs & Associates Pittsburgh, PA USA 800-348-0089 www.msjacobs.com
Model T7800 Electro-Pneumatic I/P, E/P Transducer
90
800-334-8422
Model TA7800 Extended Range
Model TT7800 Extended Range
Model TD7800 Extended Range
Model TR7800 Extended Range
Model TT7800 Standard Range
Model TD7800 Standard Range
Model TR7800 Standard Range
Model TR7800 for use with TR Manifold Rack Kit. TR7800 unit
same as TT7800 except terminal block is located on rear.
Model TR7800 for use with TR Manifold Rack Kit. TR7800 unit
same as TT7800 except terminal block is located on rear.
B
Model
T7800
BTRANS65 quark 7:B Trans 65-110.qxd 9/1/2006 5:54 PM Page 90
Model T7800 Electro-Pneumatic I/P, E/P Transducer
91
800-334-8422
Standard Range Specifications
OUTPUT RANGE
psig
[BAR]
(kPa)
3-15 3-27 6-30
[0.2-1.0] [0.2-1.8] [0.4-2.0]
(20-100) (20-180) (40-200)
Input Range 4-20 mA DC, 0-10 VDC, 1-9 VDC
Supply Pressure1 20-120 32-120 35-120
[1.5-8.0] [2.2-8.0] [2.4-8.0]
(150-800) (220-800) (240-800)
Minimum Span 5 10 10
[0.35] [0.7] [0.7]
(35) (70) (70)
Frequency Response -3 db @ 5 Hz per ISA S26.4.3.1 load configuration A.
Accuracy (ISA S51.1) 0.25% Full Scale Guaranteed
0.15% Full Scale Typical
Hysteresis (ISA S51.1) 0.1% Full Scale
Deadband 0.02% Full Scale
Repeatability (ISA S51.1) 0.1% Full Scale
Position Effect No Measurable Effect
Vibration Effect Less than +1% of Span under the following conditions: 5-15 Hz @ 0.8 inches
constant displacement 15-500 Hz @ 10 Gs.
Reverse Polarity Protection No damage occurs from reversal of normal supply current (4-20 mA) or from
misapplication of up to 60 mA.
RFI/EMI Effect Less than 0.5% of span @ 30 v
/m class 3 Band ABC (20-1000 mHz) per SAMA
PMC 33.1 1978 and less than 0.5% of Span @ 10 v
/m level, to 2 GHz Band per
EN 61000-4-3:1998 +A1 EMC Directive 89/336/EEC European Norms EN 61326
Supply Pressure Effect No Measurable Effect
Temperature Effect [+0.5% +0.04% / o
F Temperature Change] of Span typical
Materials of Construction Body and Housing . . . . . . . . . . . . . . . . . . . . . . . . . .Chromate Treated Aluminum
Orifice . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Nickel Plated Brass & Sapphire
Trim . . . . . . . . . . . . . . . . . . . . . . . . . . .Stainless Steel, Brass & Zinc Plated Steel
Elastomers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Nitrile
Finish . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Epoxy Powder Coating
SET POINT
psig
[BAR]
(kPa)
3 9 15 30
[0.2] [0.6] [1.0] [2.0]
(20) (60) (100) (200)
1
Supply Pressure must be no less than 5 psig, [0.35 BAR], (35 kPa), above maximum output
Maximum Air Consumption All Ranges 3.5 7.0 9.5 13.5
SCFH (.10 m3
/HR) (.20 m3
/HR) (.27 m3
/HR) (.38 m3
/HR)
Flow Rate 2.5 (4.25 m3/
HR) @ 9.0 (15.3 m3
/HR) @
(SCFM) 25 psig, [1.7 BAR], 120 psig, [8.0 BAR],
(170 kPa) supply & OR (800 kPa) supply &
9 psig, [0.6 BAR], 9 psig, [0.6 BAR],
(60 kPa) Output (60 kPa) Output
Temperature Range Operating -40o
F to + 160o
F (-40o
C to + 71.2o
C)
Storage -40o
F to + 180o
F (-40o
C to + 82.2o
C)
Span/Zero Adjustments Screwdriver adjustments located on front of unit
Required Operating Voltages Two Wire Current Input 7.2 VDC @ 20 mA (4-20 mA signal)
Supply Voltages Three Wire Voltage Input 7.2-30 VDC, less than 3 mA
Signal Impedance Three Wire Voltage Input 10 Kilohms
B
Model
T7800
BTRANS65 quark 7:B Trans 65-110.qxd 9/1/2006 5:54 PM Page 91
Model T7800 Electro-Pneumatic I/P, E/P Transducer
92
800-334-8422
Extended Range Specifications
Input Range 4-20 mA DC, 0-10 VDC, 1-9 VDC
Supply Pressure1 35-150 65-150 125-150
[2.4-10] [4.6-10] [8.8-10]
(240-1000) (460-1000) (880-100)
Minimum Span 12.5 25 50
[0.85] [1.5] [3.0]
(85) (150) (300)
Frequency Response -3 db @ 2 Hz per ISA S26.4.3.1 load configuration A.
Accuracy (ISA S51.1) 0.25% Full Scale Guaranteed
0.15% Full Scale Typical
Hysteresis (ISA S51.1) 0.25% Full Scale
Deadband 0.02% Full Scale
Repeatability (ISA S51.1) 0.1% Full Scale
Position Effect 0.125% @ 90 0
& 0.25% @ 180 0
Vibration Effect Less than +1% of Span under the following conditions: 5-15 Hz @ 0.8 inches
constant displacement 15-500 Hz @ 10 Gs.
Reverse Polarity Protection No damage occurs from reversal of normal supply current (4-20 mA) or from
misapplication of up to 60 mA.
RFI/EMI Effect Less than 0.5% of span @ 30 v
/m class 3 Band ABC (20-1000 mHz) per SAMA
PMC 33.1 1978 and less than 0.5% of Span @ 10 v
/m level, to 2 GHz Band per EN
61000-4-3:1998 +A1 EMC Directive 89/336/EEC European Norms EN 61326
Supply Pressure Effect < 0.1 psig change for 10 psig supply change
Temperature Effect [+0.5% +0.06% / o
F Temperature Change] of Span typical
Materials of Construction Body and Housing . . . . . . . . . . . . . . . . . . . . . . . . . .Chromate Treated Aluminum
Orifice . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Nickel Plated Brass & Sapphire
Trim . . . . . . . . . . . . . . . . . . . . . . . . . . .Stainless Steel, Brass & Zinc Plated Steel
Elastomers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Nitrile
Finish . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Epoxy Powder Coating
OUTPUT RANGE
psig
[BAR]
(kPa)
0-30 0-60 0-120
[0-2.0] [0-4.0] [0-8.0]
(0-200) (0-400) (0-800)
SET POINT
psig
[BAR]
(kPa)
0 15 30 60 120
[0] [1.0] [2.0] [4.0] [8.0]
(0) (100) (200) (400) (800)
Maximum Air Consumption 0-30 psig 3.1 7.8 11.8
SCFH (.09 m3
/HR) (.22 m3
/HR) (.33 m3
/HR)
0-60 psig 1.6 4.7 7.8 13.3
SCFH (0.4 m3
/HR) (.13 m3
/HR) (.22 m3
/HR) (.37 m3
/HR)
0-120 psig 0.5 3.8 7.6 15.1
SCFH (.01 m3
/HR) (.11 m3
/HR) (.21 m3
/HR) (.42 m3
/HR)
Flow Rate (SCFM) 11.0 (18.7 m3
/HR) @ 150 psig, [10 BAR], (1000 kPa)
supply & midscale output
Temperature Range Operating -40o
F to + 160o
F, (-40o
C to + 71.2o
C)
Storage -40o
F to + 180o
F, (-40o
C to + 82.2o
C)
Span/Zero Adjustments Screwdriver adjustments located on front of unit
Required Operating Voltages Two Wire Current Input 7.2 VDC @ 20 mA (4-20 mA signal)
Supply Voltages Three Wire Voltage Input 7.2 - 30 VDC, less than 3 mA
Signal Impedance Three Wire Voltage Input 10 Kilohms
1
Supply Pressure must be no less than 5 psig, [0.35 BAR], (35 kPa), above maximum output
B
Model
T7800
BTRANS65 quark 7:B Trans 65-110.qxd 9/1/2006 5:54 PM Page 92
Model T7800 Electro-Pneumatic I/P, E/P Transducer
93
800-334-8422
Hazardous Area Specifications
Intrinsically Safe (4-20 mA Only) Division 2
Factory Mutual TDFI7800, TAFI7800 TDFI7800, TAFI7800,
(FM) Approvals Class I, Division 1, Groups C and D; TDFN7800, TAFN7800
Class II, Division 1, Groups E,F and G; Class I, Division 2, Groups A, B, C and D;
Class III, Division 1, Fibers; Suitable for
NEMA 4X Enclosure; Class II, Division 2, Groups F and G;
Temperature Code T4, Tamb = -20 o
C to 65 o
C Class III, Division 2; NEMA 4X Enclosure;
Non-Incendive 4-20 mA, voltage input
units ; Temperature Code T4.
TTFI7800, TRFI7800 TTFI7800, TRFI7800,
Class I, Division 1, Groups C and D; TTFN7800, TRFN7800
Temperature Code T4, Tamb = -20 o
C to 65 o
C Class I, Division 2, Groups A, B, C and D;
Non-Incendive 4-20 mA, voltage input
units; Temperature Code T4.
Canadian Standards TDCI7800, TACI7800 TDCI7800, TTCI7800, TRCI7800
Association (CSA) Class I, Division 1, Groups C and D; Class I, Division 2, Groups A, B, C and D;
Approvals Class II, Division 1, Groups E, F and G; Rated 4-20 mA, 30 VDC maximum;
Type 4 Enclosure; Temperature Code T6.
Rated 4-20 mA, 30 VDC maximum;
Temperature Code T6. Flame-Proof Intrinsically Safe
TTCI7800, TRCI7800 TACI7800
Class I, Division 1, Groups C and D; Class I, Division 2, Groups A, B, C and D;
Rated 4-20 mA, 30VDC maximum; Class II, Division 2, Groups E, F and G;
Temperature Code T6. Type 4 Enclosure;
Rated 4-20 mA, 30 VDC maximum;
Temperature Code T6.
ATEX Approvals TAEI7800, TDEI7800
EEx ia IIB, T4, Tamb = -20o
C to 72o
C
II 1G (T4), II 1D (T85o
C)
IP65 Enclosure
TTEI7800, TREI7800
EEx ia IIB, T4, Tamb = -20o
C to 72o
C
II 1G (T4)
Transducer Parameters
Umax1= 28 V Pi3 = 0.7 W
Imax2= 100 mA Ci4 = 0
Li5 = 0
1
Umax = Max. Voltage 3
Pi = Max. Power
2
Imax = Max. Current 4
Ci = Capacitance
5
Li = Inductance
Approvals are valid when connected
through a Shunt Zener Diode Safety
Barrier meeting the following
parametric requirements:
System Type 1: Single Channel Polarized
Rated: 28.5V Max. 300
Ohm Min.
System Type 2: Dual Channel Polarized
Rated 28.5V Max. 300
Ohm Min. and 10V
Max. 50 Ohm Min.
System Type 3: Dual Channel Polarized
Rated: 28.5V Max. 300
Ohm Min. and 28V Diode
return per channel
Entity Parameters
Vmax1
= 30 VDC Ci3 = O µ F
Imax2
= 200 mA Li4
= O mH
1Vmax = Max. Voltage 3Ci = Capacitance
2Imax = Max. Current 4Li = Inductance
Non-Incendive Field Wiring Parameters
Vmax1
= 30 VDC Ci3 = O µ F
Li4
= O mH
1Vmax = Max. Voltage 3Ci = Capacitance
4Li = Inductance
B
Model
T7800
BTRANS65 quark 7:B Trans 65-110.qxd 9/1/2006 5:54 PM Page 93
Catalog Information
Installation
For installation instructions, refer to the Fairchild T7800 Standard
Range Electro-Pneumatic Transducer Installation, Operation and
Maintenance Instructions, IS-50T7800S and the Fairchild T7800
Extended Range Electro-Pneumatic Transducer Installation,
Operation and Maintenance Instructions, IS-50T7800E.
Optional manifolds are available to mount 3, 5, 10 or 15 transducers.
An optional rack kit is available to mount 10 transducers in a standard
19” rack. For more information, see the Fairchild Manifold and Rack
Kit, CS-4000MRKT.
Catalog Number T 7800
Electrical Connections
1/2 NPT Conduit . . . . . . . . . . . . A
Fitting with Pigtail
DIN43650 Connection . . . . . . . . D
Rack Mount . . . . . . . . . . . . . . . . R
Terminal Block . . . . . . . . . . . . . . T
Underwriting Group
Canadian Standards . . . . . . . . . . . . . C
ATEX . . . . . . . . . . . . . . . . . . . . . . . . . E
Factory Mutual . . . . . . . . . . . . . . . . . . F
None (leave blank) . . . . . . . . . . . . . . .
Approval Class
Intrinsically Safe1 . . . . . . . . . . . . . . . . . . . . I
Non-Incendive (Division 2)2 . . . . . . . . . . . . N
None (leave blank) . . . . . . . . . . . . . . . . . . .
Input
4-20 mA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1-5 VDC6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
0-5 VDC 6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
1-9 VDC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
0-10 VDC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0
Output
3-15 psig 3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 01
3-27 psig 3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 02
6-30 psig 3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 03
0-30 psig 4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 04
0-60 psig 4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 05
0-120 psig 4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 06
[0.2-1.0 BAR] 3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
[0.2-1.8 BAR] 3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
[0.4-2.0 BAR] 3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
[0-2.0 BAR] 4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
[0-4.0 BAR] 4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
[0-8.0 BAR] 4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
(20-100 kPa) 3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
(20-180 kPa) 3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
(40-200 kPa) 3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
(0-200 kPa) 4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
(0-400 kPa) 4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
(0-800 kPa) 4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Options
BSPT Thread 5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . U
1 Intrinsically Safe Approval includes Non-Incendive (Division 2), available on 4-20 mA
units only.
2
Non-Incendive (Division 2) approval on FM voltage input units only
3
Standard Range
4
Extended Range
5
Available on all units EXCEPT Factory Mutual and Canadian Standards Underwriting
Group units.
6
Limited Availability
Mounting Kits
Mounting Bracket: 16799-1
Mounting Bracket: 16893
Mounting Bracket: 19254-1
Model T7800 Transducer Kits
& Accessories
Mounting Bracket Kits ..........16799-1 (included with unit)
16893 (included with unit)
19254-1 (sold separately)
Model T7800 Electro-Pneumatic I/P, E/P Transducer
94
800-334-8422
BB
Model
T7800
BTRANS65 quark 7:B Trans 65-110.qxd 9/1/2006 5:54 PM Page 94

More Related Content

PDF
Process Differential Pressure Gauge
PDF
Electronic Pressure Switch for Industrial Applications
PDF
Sealed Vacuum and Pressure Feedthrough Fittings
PDF
Pressure-Control-Brochure
PDF
Level limit switch-Soliswitch FTE30
PDF
ASCO Valves - Valve Selection by Alphanumerical Or Numerical System
PDF
Current To Pneumatic Converter for Process Control
PDF
ASCO ATEX Solenoid Valves - 327 Series - Spec Sheet
Process Differential Pressure Gauge
Electronic Pressure Switch for Industrial Applications
Sealed Vacuum and Pressure Feedthrough Fittings
Pressure-Control-Brochure
Level limit switch-Soliswitch FTE30
ASCO Valves - Valve Selection by Alphanumerical Or Numerical System
Current To Pneumatic Converter for Process Control
ASCO ATEX Solenoid Valves - 327 Series - Spec Sheet

What's hot (19)

PDF
Heaters for process air and gases
PDF
Turbimax cus31 endress+hauser datasheet-turbidity sensor
PDF
Temperature, Pressure, Vacuum, and Differential Switches
PDF
ASCO Solenoid Valves Catalog
PDF
Kinetrol Manual Failsafe Handle
PDF
Asco Du Atex Explosion Proof Operator Hazardous Area Solenoid Valve Operator ...
PDF
Asco 8210 Series RedHat Solenoid Valve
PDF
ASCO Solenoid Valves - Process Industry Applications
PDF
Kinetrol Universal Limit Switch
PDF
Htr india-products-current-sense-resistors-current-sense-open-frame-resistor-...
PDF
PDF
Level Limit Switch-Soliswitch FTE31
PDF
44 5800
PDF
Kinetrol Explosion Proof Limit Switch
PDF
Flameproof High Range Pressure Switches FE Series
PDF
Ashcroft Pressure Gauges - Air Conditioning, Heating & Refridgeration Industr...
PDF
Thermon HTSX Heat Tracing Cable - Spec Sheet
PDF
Positive displacement flowmeter gear type for high viscosity liquids
PDF
Sw low pressure
Heaters for process air and gases
Turbimax cus31 endress+hauser datasheet-turbidity sensor
Temperature, Pressure, Vacuum, and Differential Switches
ASCO Solenoid Valves Catalog
Kinetrol Manual Failsafe Handle
Asco Du Atex Explosion Proof Operator Hazardous Area Solenoid Valve Operator ...
Asco 8210 Series RedHat Solenoid Valve
ASCO Solenoid Valves - Process Industry Applications
Kinetrol Universal Limit Switch
Htr india-products-current-sense-resistors-current-sense-open-frame-resistor-...
Level Limit Switch-Soliswitch FTE31
44 5800
Kinetrol Explosion Proof Limit Switch
Flameproof High Range Pressure Switches FE Series
Ashcroft Pressure Gauges - Air Conditioning, Heating & Refridgeration Industr...
Thermon HTSX Heat Tracing Cable - Spec Sheet
Positive displacement flowmeter gear type for high viscosity liquids
Sw low pressure
Ad

Similar to Electro-Pneumatic Transducer for Process Control (20)

PDF
Electro-Pneumatic Pressure Controller and I/P Transducer
PDF
Inverter Ducted Brochure
PDF
Adp9000 lv1.1.8en
PDF
VHIA - WIRE WOUND RESISTORS SILICONE COATED TYPE
PDF
Current to Pneumatic Converter
PDF
Catalog timer idec mới nhất 2019
PDF
3100 3200-cat
PDF
Explosion Proof/Flame Proof (Ex D) Sensors for Hazardous Area Now Available i...
PDF
Idec timers idec
PDF
Idec timers idec
PDF
2600T Series Pressure Transmitter Model 261GS Gauge Model 261AS Absolute stan...
PDF
2600T Series Pressure Transmitter Model 261GS Gauge Model 261AS Absolute stan...
PDF
Hioki 3291 50-clamp-on_hi_tester_datasheet
PDF
HAA - COMPACT WIRE WOUND RESISTORS SILICONE/CEMENT COATED TYPE
PDF
HSE - Low OHM Power Resistors
PDF
Htr india-products-wire-wound-resistors-silicone-coated-resistors-vhia-english
PDF
ZIPP Wireless torque transducer operation manual
PDF
Kollmorgen nema 23 t specsheet
PDF
LS Circuit Breaker Catalogue
Electro-Pneumatic Pressure Controller and I/P Transducer
Inverter Ducted Brochure
Adp9000 lv1.1.8en
VHIA - WIRE WOUND RESISTORS SILICONE COATED TYPE
Current to Pneumatic Converter
Catalog timer idec mới nhất 2019
3100 3200-cat
Explosion Proof/Flame Proof (Ex D) Sensors for Hazardous Area Now Available i...
Idec timers idec
Idec timers idec
2600T Series Pressure Transmitter Model 261GS Gauge Model 261AS Absolute stan...
2600T Series Pressure Transmitter Model 261GS Gauge Model 261AS Absolute stan...
Hioki 3291 50-clamp-on_hi_tester_datasheet
HAA - COMPACT WIRE WOUND RESISTORS SILICONE/CEMENT COATED TYPE
HSE - Low OHM Power Resistors
Htr india-products-wire-wound-resistors-silicone-coated-resistors-vhia-english
ZIPP Wireless torque transducer operation manual
Kollmorgen nema 23 t specsheet
LS Circuit Breaker Catalogue
Ad

Recently uploaded (20)

PPTX
MET 305 2019 SCHEME MODULE 2 COMPLETE.pptx
PDF
Human-AI Collaboration: Balancing Agentic AI and Autonomy in Hybrid Systems
PDF
Well-logging-methods_new................
PDF
PPT on Performance Review to get promotions
PDF
Mitigating Risks through Effective Management for Enhancing Organizational Pe...
PPT
introduction to datamining and warehousing
PDF
Artificial Superintelligence (ASI) Alliance Vision Paper.pdf
PPTX
Engineering Ethics, Safety and Environment [Autosaved] (1).pptx
PDF
A SYSTEMATIC REVIEW OF APPLICATIONS IN FRAUD DETECTION
DOCX
ASol_English-Language-Literature-Set-1-27-02-2023-converted.docx
PDF
R24 SURVEYING LAB MANUAL for civil enggi
PPTX
FINAL REVIEW FOR COPD DIANOSIS FOR PULMONARY DISEASE.pptx
PPT
Mechanical Engineering MATERIALS Selection
PPTX
M Tech Sem 1 Civil Engineering Environmental Sciences.pptx
PDF
BMEC211 - INTRODUCTION TO MECHATRONICS-1.pdf
PPT
Project quality management in manufacturing
PPTX
CARTOGRAPHY AND GEOINFORMATION VISUALIZATION chapter1 NPTE (2).pptx
PDF
The CXO Playbook 2025 – Future-Ready Strategies for C-Suite Leaders Cerebrai...
PDF
keyrequirementskkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkk
PDF
Mohammad Mahdi Farshadian CV - Prospective PhD Student 2026
MET 305 2019 SCHEME MODULE 2 COMPLETE.pptx
Human-AI Collaboration: Balancing Agentic AI and Autonomy in Hybrid Systems
Well-logging-methods_new................
PPT on Performance Review to get promotions
Mitigating Risks through Effective Management for Enhancing Organizational Pe...
introduction to datamining and warehousing
Artificial Superintelligence (ASI) Alliance Vision Paper.pdf
Engineering Ethics, Safety and Environment [Autosaved] (1).pptx
A SYSTEMATIC REVIEW OF APPLICATIONS IN FRAUD DETECTION
ASol_English-Language-Literature-Set-1-27-02-2023-converted.docx
R24 SURVEYING LAB MANUAL for civil enggi
FINAL REVIEW FOR COPD DIANOSIS FOR PULMONARY DISEASE.pptx
Mechanical Engineering MATERIALS Selection
M Tech Sem 1 Civil Engineering Environmental Sciences.pptx
BMEC211 - INTRODUCTION TO MECHATRONICS-1.pdf
Project quality management in manufacturing
CARTOGRAPHY AND GEOINFORMATION VISUALIZATION chapter1 NPTE (2).pptx
The CXO Playbook 2025 – Future-Ready Strategies for C-Suite Leaders Cerebrai...
keyrequirementskkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkk
Mohammad Mahdi Farshadian CV - Prospective PhD Student 2026

Electro-Pneumatic Transducer for Process Control

  • 1. Model T7800 Electro-Pneumatic I/P, E/P Transducer 89 800-334-8422 Features • The T7800 Series Transducers provide maximum versatility for precision applications. • Field Reversible Feature provides output that is inversely proportional to input signal. • RFI/EMI Protection eliminates susceptibility to electromagnetic and radio interference. • Internal Electronic Feedback and solid state controlled Piezoelectric Actuator provide precise control of output pressure regardless of vibration or position. • Damping Adjustment for optimum tuning response. • Split range operation lets a common signal source control two or more functions. • Compact size for use in restricted spaces. • Various mounting configurations allow installation flexibility for most applications. • NEMA 4X, Type 4 Enclosure and IP65 rated for indoor and outdoor installations. • Canadian Registration Numbers (CRN) certification for all territories and provinces. Operating Principles STANDARD RANGE The Model T7800 Series converts a DC input signal to a linear proportional pneumatic output. It includes the Primary Converting Section and the pneumatic Relay Section. The Piezoelectric Ceramic Actuator, in the Primary Converting Section, functions as a Flapper. The Flapper and Nozzle work together to control the signal pressure. The signal pressure that sets the output pressure acts on the Upper Control Diaphragm in the Pneumatic Relay Section. The Lower Control Diaphragm in the Pneumatic Relay Section senses the output pressure. EXTENDED RANGE In the Extended Range units, an additional Relay Section amplifies the output pressure. Model TA7800 Standard Range B Model T7800 BTRANS65 quark 7:B Trans 65-110.qxd 9/1/2006 5:54 PM Page 89 M.S. Jacobs & Associates Pittsburgh, PA USA 800-348-0089 www.msjacobs.com
  • 2. Model T7800 Electro-Pneumatic I/P, E/P Transducer 90 800-334-8422 Model TA7800 Extended Range Model TT7800 Extended Range Model TD7800 Extended Range Model TR7800 Extended Range Model TT7800 Standard Range Model TD7800 Standard Range Model TR7800 Standard Range Model TR7800 for use with TR Manifold Rack Kit. TR7800 unit same as TT7800 except terminal block is located on rear. Model TR7800 for use with TR Manifold Rack Kit. TR7800 unit same as TT7800 except terminal block is located on rear. B Model T7800 BTRANS65 quark 7:B Trans 65-110.qxd 9/1/2006 5:54 PM Page 90
  • 3. Model T7800 Electro-Pneumatic I/P, E/P Transducer 91 800-334-8422 Standard Range Specifications OUTPUT RANGE psig [BAR] (kPa) 3-15 3-27 6-30 [0.2-1.0] [0.2-1.8] [0.4-2.0] (20-100) (20-180) (40-200) Input Range 4-20 mA DC, 0-10 VDC, 1-9 VDC Supply Pressure1 20-120 32-120 35-120 [1.5-8.0] [2.2-8.0] [2.4-8.0] (150-800) (220-800) (240-800) Minimum Span 5 10 10 [0.35] [0.7] [0.7] (35) (70) (70) Frequency Response -3 db @ 5 Hz per ISA S26.4.3.1 load configuration A. Accuracy (ISA S51.1) 0.25% Full Scale Guaranteed 0.15% Full Scale Typical Hysteresis (ISA S51.1) 0.1% Full Scale Deadband 0.02% Full Scale Repeatability (ISA S51.1) 0.1% Full Scale Position Effect No Measurable Effect Vibration Effect Less than +1% of Span under the following conditions: 5-15 Hz @ 0.8 inches constant displacement 15-500 Hz @ 10 Gs. Reverse Polarity Protection No damage occurs from reversal of normal supply current (4-20 mA) or from misapplication of up to 60 mA. RFI/EMI Effect Less than 0.5% of span @ 30 v /m class 3 Band ABC (20-1000 mHz) per SAMA PMC 33.1 1978 and less than 0.5% of Span @ 10 v /m level, to 2 GHz Band per EN 61000-4-3:1998 +A1 EMC Directive 89/336/EEC European Norms EN 61326 Supply Pressure Effect No Measurable Effect Temperature Effect [+0.5% +0.04% / o F Temperature Change] of Span typical Materials of Construction Body and Housing . . . . . . . . . . . . . . . . . . . . . . . . . .Chromate Treated Aluminum Orifice . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Nickel Plated Brass & Sapphire Trim . . . . . . . . . . . . . . . . . . . . . . . . . . .Stainless Steel, Brass & Zinc Plated Steel Elastomers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Nitrile Finish . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Epoxy Powder Coating SET POINT psig [BAR] (kPa) 3 9 15 30 [0.2] [0.6] [1.0] [2.0] (20) (60) (100) (200) 1 Supply Pressure must be no less than 5 psig, [0.35 BAR], (35 kPa), above maximum output Maximum Air Consumption All Ranges 3.5 7.0 9.5 13.5 SCFH (.10 m3 /HR) (.20 m3 /HR) (.27 m3 /HR) (.38 m3 /HR) Flow Rate 2.5 (4.25 m3/ HR) @ 9.0 (15.3 m3 /HR) @ (SCFM) 25 psig, [1.7 BAR], 120 psig, [8.0 BAR], (170 kPa) supply & OR (800 kPa) supply & 9 psig, [0.6 BAR], 9 psig, [0.6 BAR], (60 kPa) Output (60 kPa) Output Temperature Range Operating -40o F to + 160o F (-40o C to + 71.2o C) Storage -40o F to + 180o F (-40o C to + 82.2o C) Span/Zero Adjustments Screwdriver adjustments located on front of unit Required Operating Voltages Two Wire Current Input 7.2 VDC @ 20 mA (4-20 mA signal) Supply Voltages Three Wire Voltage Input 7.2-30 VDC, less than 3 mA Signal Impedance Three Wire Voltage Input 10 Kilohms B Model T7800 BTRANS65 quark 7:B Trans 65-110.qxd 9/1/2006 5:54 PM Page 91
  • 4. Model T7800 Electro-Pneumatic I/P, E/P Transducer 92 800-334-8422 Extended Range Specifications Input Range 4-20 mA DC, 0-10 VDC, 1-9 VDC Supply Pressure1 35-150 65-150 125-150 [2.4-10] [4.6-10] [8.8-10] (240-1000) (460-1000) (880-100) Minimum Span 12.5 25 50 [0.85] [1.5] [3.0] (85) (150) (300) Frequency Response -3 db @ 2 Hz per ISA S26.4.3.1 load configuration A. Accuracy (ISA S51.1) 0.25% Full Scale Guaranteed 0.15% Full Scale Typical Hysteresis (ISA S51.1) 0.25% Full Scale Deadband 0.02% Full Scale Repeatability (ISA S51.1) 0.1% Full Scale Position Effect 0.125% @ 90 0 & 0.25% @ 180 0 Vibration Effect Less than +1% of Span under the following conditions: 5-15 Hz @ 0.8 inches constant displacement 15-500 Hz @ 10 Gs. Reverse Polarity Protection No damage occurs from reversal of normal supply current (4-20 mA) or from misapplication of up to 60 mA. RFI/EMI Effect Less than 0.5% of span @ 30 v /m class 3 Band ABC (20-1000 mHz) per SAMA PMC 33.1 1978 and less than 0.5% of Span @ 10 v /m level, to 2 GHz Band per EN 61000-4-3:1998 +A1 EMC Directive 89/336/EEC European Norms EN 61326 Supply Pressure Effect < 0.1 psig change for 10 psig supply change Temperature Effect [+0.5% +0.06% / o F Temperature Change] of Span typical Materials of Construction Body and Housing . . . . . . . . . . . . . . . . . . . . . . . . . .Chromate Treated Aluminum Orifice . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Nickel Plated Brass & Sapphire Trim . . . . . . . . . . . . . . . . . . . . . . . . . . .Stainless Steel, Brass & Zinc Plated Steel Elastomers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Nitrile Finish . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Epoxy Powder Coating OUTPUT RANGE psig [BAR] (kPa) 0-30 0-60 0-120 [0-2.0] [0-4.0] [0-8.0] (0-200) (0-400) (0-800) SET POINT psig [BAR] (kPa) 0 15 30 60 120 [0] [1.0] [2.0] [4.0] [8.0] (0) (100) (200) (400) (800) Maximum Air Consumption 0-30 psig 3.1 7.8 11.8 SCFH (.09 m3 /HR) (.22 m3 /HR) (.33 m3 /HR) 0-60 psig 1.6 4.7 7.8 13.3 SCFH (0.4 m3 /HR) (.13 m3 /HR) (.22 m3 /HR) (.37 m3 /HR) 0-120 psig 0.5 3.8 7.6 15.1 SCFH (.01 m3 /HR) (.11 m3 /HR) (.21 m3 /HR) (.42 m3 /HR) Flow Rate (SCFM) 11.0 (18.7 m3 /HR) @ 150 psig, [10 BAR], (1000 kPa) supply & midscale output Temperature Range Operating -40o F to + 160o F, (-40o C to + 71.2o C) Storage -40o F to + 180o F, (-40o C to + 82.2o C) Span/Zero Adjustments Screwdriver adjustments located on front of unit Required Operating Voltages Two Wire Current Input 7.2 VDC @ 20 mA (4-20 mA signal) Supply Voltages Three Wire Voltage Input 7.2 - 30 VDC, less than 3 mA Signal Impedance Three Wire Voltage Input 10 Kilohms 1 Supply Pressure must be no less than 5 psig, [0.35 BAR], (35 kPa), above maximum output B Model T7800 BTRANS65 quark 7:B Trans 65-110.qxd 9/1/2006 5:54 PM Page 92
  • 5. Model T7800 Electro-Pneumatic I/P, E/P Transducer 93 800-334-8422 Hazardous Area Specifications Intrinsically Safe (4-20 mA Only) Division 2 Factory Mutual TDFI7800, TAFI7800 TDFI7800, TAFI7800, (FM) Approvals Class I, Division 1, Groups C and D; TDFN7800, TAFN7800 Class II, Division 1, Groups E,F and G; Class I, Division 2, Groups A, B, C and D; Class III, Division 1, Fibers; Suitable for NEMA 4X Enclosure; Class II, Division 2, Groups F and G; Temperature Code T4, Tamb = -20 o C to 65 o C Class III, Division 2; NEMA 4X Enclosure; Non-Incendive 4-20 mA, voltage input units ; Temperature Code T4. TTFI7800, TRFI7800 TTFI7800, TRFI7800, Class I, Division 1, Groups C and D; TTFN7800, TRFN7800 Temperature Code T4, Tamb = -20 o C to 65 o C Class I, Division 2, Groups A, B, C and D; Non-Incendive 4-20 mA, voltage input units; Temperature Code T4. Canadian Standards TDCI7800, TACI7800 TDCI7800, TTCI7800, TRCI7800 Association (CSA) Class I, Division 1, Groups C and D; Class I, Division 2, Groups A, B, C and D; Approvals Class II, Division 1, Groups E, F and G; Rated 4-20 mA, 30 VDC maximum; Type 4 Enclosure; Temperature Code T6. Rated 4-20 mA, 30 VDC maximum; Temperature Code T6. Flame-Proof Intrinsically Safe TTCI7800, TRCI7800 TACI7800 Class I, Division 1, Groups C and D; Class I, Division 2, Groups A, B, C and D; Rated 4-20 mA, 30VDC maximum; Class II, Division 2, Groups E, F and G; Temperature Code T6. Type 4 Enclosure; Rated 4-20 mA, 30 VDC maximum; Temperature Code T6. ATEX Approvals TAEI7800, TDEI7800 EEx ia IIB, T4, Tamb = -20o C to 72o C II 1G (T4), II 1D (T85o C) IP65 Enclosure TTEI7800, TREI7800 EEx ia IIB, T4, Tamb = -20o C to 72o C II 1G (T4) Transducer Parameters Umax1= 28 V Pi3 = 0.7 W Imax2= 100 mA Ci4 = 0 Li5 = 0 1 Umax = Max. Voltage 3 Pi = Max. Power 2 Imax = Max. Current 4 Ci = Capacitance 5 Li = Inductance Approvals are valid when connected through a Shunt Zener Diode Safety Barrier meeting the following parametric requirements: System Type 1: Single Channel Polarized Rated: 28.5V Max. 300 Ohm Min. System Type 2: Dual Channel Polarized Rated 28.5V Max. 300 Ohm Min. and 10V Max. 50 Ohm Min. System Type 3: Dual Channel Polarized Rated: 28.5V Max. 300 Ohm Min. and 28V Diode return per channel Entity Parameters Vmax1 = 30 VDC Ci3 = O µ F Imax2 = 200 mA Li4 = O mH 1Vmax = Max. Voltage 3Ci = Capacitance 2Imax = Max. Current 4Li = Inductance Non-Incendive Field Wiring Parameters Vmax1 = 30 VDC Ci3 = O µ F Li4 = O mH 1Vmax = Max. Voltage 3Ci = Capacitance 4Li = Inductance B Model T7800 BTRANS65 quark 7:B Trans 65-110.qxd 9/1/2006 5:54 PM Page 93
  • 6. Catalog Information Installation For installation instructions, refer to the Fairchild T7800 Standard Range Electro-Pneumatic Transducer Installation, Operation and Maintenance Instructions, IS-50T7800S and the Fairchild T7800 Extended Range Electro-Pneumatic Transducer Installation, Operation and Maintenance Instructions, IS-50T7800E. Optional manifolds are available to mount 3, 5, 10 or 15 transducers. An optional rack kit is available to mount 10 transducers in a standard 19” rack. For more information, see the Fairchild Manifold and Rack Kit, CS-4000MRKT. Catalog Number T 7800 Electrical Connections 1/2 NPT Conduit . . . . . . . . . . . . A Fitting with Pigtail DIN43650 Connection . . . . . . . . D Rack Mount . . . . . . . . . . . . . . . . R Terminal Block . . . . . . . . . . . . . . T Underwriting Group Canadian Standards . . . . . . . . . . . . . C ATEX . . . . . . . . . . . . . . . . . . . . . . . . . E Factory Mutual . . . . . . . . . . . . . . . . . . F None (leave blank) . . . . . . . . . . . . . . . Approval Class Intrinsically Safe1 . . . . . . . . . . . . . . . . . . . . I Non-Incendive (Division 2)2 . . . . . . . . . . . . N None (leave blank) . . . . . . . . . . . . . . . . . . . Input 4-20 mA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 1-5 VDC6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 0-5 VDC 6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 1-9 VDC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 0-10 VDC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0 Output 3-15 psig 3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 01 3-27 psig 3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 02 6-30 psig 3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 03 0-30 psig 4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 04 0-60 psig 4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 05 0-120 psig 4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 06 [0.2-1.0 BAR] 3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 [0.2-1.8 BAR] 3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 [0.4-2.0 BAR] 3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 [0-2.0 BAR] 4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 [0-4.0 BAR] 4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 [0-8.0 BAR] 4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 (20-100 kPa) 3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 (20-180 kPa) 3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 (40-200 kPa) 3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 (0-200 kPa) 4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 (0-400 kPa) 4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25 (0-800 kPa) 4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26 Options BSPT Thread 5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . U 1 Intrinsically Safe Approval includes Non-Incendive (Division 2), available on 4-20 mA units only. 2 Non-Incendive (Division 2) approval on FM voltage input units only 3 Standard Range 4 Extended Range 5 Available on all units EXCEPT Factory Mutual and Canadian Standards Underwriting Group units. 6 Limited Availability Mounting Kits Mounting Bracket: 16799-1 Mounting Bracket: 16893 Mounting Bracket: 19254-1 Model T7800 Transducer Kits & Accessories Mounting Bracket Kits ..........16799-1 (included with unit) 16893 (included with unit) 19254-1 (sold separately) Model T7800 Electro-Pneumatic I/P, E/P Transducer 94 800-334-8422 BB Model T7800 BTRANS65 quark 7:B Trans 65-110.qxd 9/1/2006 5:54 PM Page 94