Enhancement of Power Quality Problem by Using Dynamic
Voltage Restorer
Mr.Shinde Abhijeet G. Mr.Pramod Kumar S.
Electrical Engg. Department Asst. Prof. Electrical Engg.Department
MSS’s CET Jalna MSS’s CET Jalna
Dr. BAMU University Aurangabd. Dr. BAMU University Aurangabd.
Abstract— Dynamic voltage restorers (DVRs) are used to protect sensitive loads from the effects of voltage sags on the
distribution feeder. This paper presents and verifies a novel voltage sag detection technique for use in conjunction
with the main control system of a DVR. In all cases it is necessary for the DVR control system to not only detect the
start and end of a voltage sag but also to determine the sag depth and any associated phase shift. The DVR, which is
placed in series with a sensitive load, must be able to respond quickly to a voltage sag if end users of sensitive
equipment are to experience no voltage sag. The DVR can restore the load voltage within few milliseconds. A control
technique based on a proportional–integral (PI) controller and a selective controller is used. The controller is
designed in a synchronously-rotating reference frame. In fact, three independent controllers have been used to tackle
balanced and unbalanced voltage supplies. Simulation results using ‘MATLAB SIMULINK’ Sim Power System
Toolbox is presented to illustrate the principle and performance of a DVR operation in load voltage compensation.
Keywords— Dynamic Voltage Restorer (DVR), MATLAB SIMULINK, sensitive load, voltage sags, voltage swells.
I. INTRODUCTION
Nowadays, modern industrial devices are mostly based on electronic devices such as programmable logic controllers
and electronic drives. The electronic devices are very sensitive to disturbances and become less tolerant to power quality
problems such as voltage sags, swells and harmonics. Voltage dips are considered to be one of the most severe
disturbances to the industrial equipments.
Voltage support at a load can be achieved by reactive power injection at the load point of common coupling. The
common method for this is to install mechanically switched shunt capacitors in the primary terminal of the distribution
transformer. The mechanical switching may be on a schedule, via signals from a supervisory control and data acquisition
(SCADA) system, with some timing schedule, or with no switching at all. The disadvantage is that, high speed transients
cannot be compensated. Some sags are not corrected within the limited time frame of mechanical switching devices.
Transformer taps may be used, but tap changing under load is costly.
Another power electronic solution to the voltage regulation is the use of a dynamic voltage restorer (DVR). DVRs are
a class of custom power devices for providing reliable distribution power quality. They employ a series of voltage boost
technology using solid state switches for compensating voltage sags/swells. The DVR applications are mainly for
sensitive loads that may be drastically affected by fluctuations in system voltage [1]
.
II. POWER QUALITY PROBLEMS
Power distribution systems, ideally, should provide their customers with an uninterrupted flow of energy at smooth
sinusoidal voltage at the contracted magnitude level and frequency. However, in practice, power systems, especially the
distribution systems, have numerous nonlinear loads, which significantly affect the quality of power supplies. As a result
of the nonlinear loads, the purity of the waveform of supplies is lost. This ends up producing many power quality
problems. While power disturbances occur on all electrical systems, the sensitivity of today’s sophisticated electronic
devices makes them more susceptible to the quality of power supply. For some sensitive devices, a momentary
disturbance can cause scrambled data, interrupted communications, a frozen mouse, system crashes and equipment
failure etc. A power voltage spike can damage valuable components. Power Quality problems encompass a wide range of
disturbances such as voltage sags/swells, flicker, harmonics distortion, impulse transient, and interruptions [2-3]
.
III.SOLUTIONS TO POWER QUALITY PROBLEMS
There are two approaches to the mitigation of power quality problems. The solution to the power quality can be done
from customer side or from utility side First approach is called load conditioning, which ensures that the equipment is
less sensitive to power disturbances, allowing the operation even under significant voltage distortion. The other solution
is to install line conditioning systems that suppress or counteracts the power system disturbances. Dynamic Voltage
Restorer is suitable device for voltage sag reduction [4]
.
IV.DYNAMIC VOLTAGE RESTORER
Among the power quality problems (sags, swells, harmonics…) voltage sags are the most severe disturbances. In
order to overcome these problems the concept of custom power devices is introduced recently. One of those devices is
International Journal of Innovative Research in Advanced Engineering (IJIRAE) ISSN: 2349-2163
Volume 1 Issue 6 (July 2014) http://ijirae.com
_________________________________________________________________________________________________
© 2014, IJIRAE- All Rights Reserved Page -401
the Dynamic Voltage Restorer (DVR), which is the most efficient and effective modern custom power device used in
power distribution networks. DVR is a recently proposed series connected solid state device that injects voltage into the
system in order to regulate the load side voltage. It is normally installed in a distribution system between the supply and
the critical load feeder at the point of common coupling (PCC). Other than voltage sags and swells compensation, DVR
can also added other features like: line voltage harmonics compensation, reduction of transients in voltage and fault
current limitations[5]
.
FIGURE 1: Location of DVR
A. Equations Related to DVR
The system impedance Zth depends on the fault level of the load bus. When the system voltage (VTH) drops,
the DVR injects a series voltage VDVR through the injection transformer so that the desired load voltage magnitude VL
can be maintained. The series injected voltage of the DVR can be written as
Where
VL: The desired load voltage magnitude
ZTH: The load impedance.
IL: The load current
VTH: The system voltage during fault condition
FIGURE 2: Equivalent circuit diagram of DVR
B. Operating Modes of DVR
The basic function of the DVR is to inject a dynamically controlled voltage VDVR generated by a forced
commutated converter in series to the bus voltage by means of a booster transformer. The momentary amplitudes of the
three injected phase voltages are controlled such as to eliminate any detrimental effects of a bus fault to the load voltage
VL. This means that any differential voltages caused by transient disturbances in the ac feeder will be compensated by an
equivalent voltage generated by the converter and injected on the medium voltage level through the booster transformer
[6]
.
The DVR has three modes of operation which are: protection mode, standby mode, injection/boost mode.
1. Protection mode:
If the over current on the load side exceeds a permissible limit due to short circuit on the load or large inrush current,
the DVR will be isolated from the systems by using the bypass switches (S2 and S3 will open) and supplying another
path for current (S1 will be closed).
International Journal of Innovative Research in Advanced Engineering (IJIRAE) ISSN: 2349-2163
Volume 1 Issue 6 (July 2014) http://ijirae.com
_________________________________________________________________________________________________
© 2014, IJIRAE- All Rights Reserved Page -402
FIGURE 3: Protection Mode (creating another path for current)
2. Standby Mode: (VDVR= 0)
FIGURE 4: Standby Mode of DVR
In the standby mode the booster transformer’s low voltage winding is shorted through the converter. No
switching of semiconductors occurs in this mode of operation and the full load current will pass through the primary.
3. Injection/Boost Mode: (VDVR>0)
In the Injection/Boost mode the DVR is injecting a compensating voltage through the booster transformer due
to the detection of a disturbance in the supply voltage.
C. Discrete PWM-Based Control Scheme
In order to mitigate the simulated voltage sags in the test system of each compensation technique, also to
compensate voltage sags in practical application, a discrete PWM-based control scheme is implemented, with reference
to DVR. The aim of the control scheme is to maintain a constant voltage magnitude at the sensitive load point, under the
system disturbance. The control system only measures the rms voltage at load point, for example, no reactive power
measurement is required. Figure 4.1 shows the DVR controller scheme implemented in MATLAB/SIMULINK. The
DVR control system exerts a voltage angle control as follows: an error signal is obtained by comparing the reference
voltage with the rms voltage measured at the load point[7-8]
. The PI controller processes the error signal and generates the
required angle δ to drive the error to zero, for example; the load rms voltage is brought back to the reference voltage.
It should be noted that, an assumption of balanced network and operating conditions are made. The modulating
angle δ or delta is applied to the PWM generators in phase A, whereas the angles for phase B and C are shifted by 240°
or -120° and 120° respectively[9]
.
VA = Sin (ωt +δ)
VB=Sin (ωt+δ-2π/3)
VC = Sin (ωt +δ+2π/3
V. SIMULATION AND RESULTS
Digital simulation is done using the blocks of Matlab simulink and the results are presented here. The first
simulation was done with no DVR and no three phase fault is applied to the system. This system shows the normal
operating power system without DVR and three phase fault.
International Journal of Innovative Research in Advanced Engineering (IJIRAE) ISSN: 2349-2163
Volume 1 Issue 6 (July 2014) http://ijirae.com
_________________________________________________________________________________________________
© 2014, IJIRAE- All Rights Reserved Page -403
Figure 5 shows the SIMULINK model for Normal Operating Power System. Figure 6 and Figure 7 shows the
output waveform for figure 5. The FFT analysis for this model shows total harmonic distortion is 0%, which means the
system, is in healthy condition figure 8 shows the FFT analysis for Normal Operating Power System.
FIGURE 5: Normal Operating Power System
FIGURE 6: 3-Ø Voltage at Load Point, Without DVR
FIGURE 7: P.U Voltage at Load Point Without DVR
The second simulation was done (figure 9) with no DVR and a three phase fault is applied to the system at point
with fault resistance of 0.66 U for a time duration of 200 ms. The third simulation is carried out (figure 10) at the same
scenario as above but a DVR is now introduced at the load side to compensate the voltage sag occurred due to the three
phase fault applied.
International Journal of Innovative Research in Advanced Engineering (IJIRAE) ISSN: 2349-2163
Volume 1 Issue 6 (July 2014) http://ijirae.com
_________________________________________________________________________________________________
© 2014, IJIRAE- All Rights Reserved Page -404
FIGURE 8: FFT Analysis for Normal Operating Power System
Figure 11 shows the pu voltage at load point when the system operates with no DVR and a three phase fault is
applied to the system.
FIGURE 9: SIMULINK for Fault on Power System
FIGURE 10:3-Ø Voltage at Load Point, with 3-Ø fault, without DVR
International Journal of Innovative Research in Advanced Engineering (IJIRAE) ISSN: 2349-2163
Volume 1 Issue 6 (July 2014) http://ijirae.com
_________________________________________________________________________________________________
© 2014, IJIRAE- All Rights Reserved Page -405
FIGURE 11: P.U Voltage at Load Point, with 3-Ø fault, without DVR
FIGURE 12: FFT analysis for fault on Power system
Figure 12 shows the FFT analysis of power system during fault.
FIGURE 13: SIMULINK Model of DVR In Power System
International Journal of Innovative Research in Advanced Engineering (IJIRAE) ISSN: 2349-2163
Volume 1 Issue 6 (July 2014) http://ijirae.com
_________________________________________________________________________________________________
© 2014, IJIRAE- All Rights Reserved Page -406
When the DVR is in operation (Figure13) the voltage interruption is compensated almost completely and the
rms voltage at the sensitive load point is maintained at normal condition. Injected voltage and the voltage across load is
shown in Figure14 & Figure15. FFT analysis for the output voltage is shown in Figure16. THD reduces to 0.39%. Thus
the harmonics are reduced from 1.37% to 0.39%.
FIGURE14: 3-Ø Voltage at Load Point, with 3-Ø fault, with DVR
FIGURE15: P.U Voltage at Load Point, with 3-Ø fault, with DVR
FIGURE16: FFT Analysis for Power System with DVR
International Journal of Innovative Research in Advanced Engineering (IJIRAE) ISSN: 2349-2163
Volume 1 Issue 6 (July 2014) http://ijirae.com
_________________________________________________________________________________________________
© 2014, IJIRAE- All Rights Reserved Page -407
V. CONCLUSION
We are presented here power quality problems such as voltage sag and harmonics. By using the custom power
electronic device (DVR) we have solved the problem of voltage sag and harmonics. The design and applications of DVR
for voltage sags and comprehensive results were presented. The effectiveness of a DVR system mainly depends upon the
rating of DC storage rating and the loads. In the test system it is observed that after a particular amount of load increases
on 11 kV feeders, the voltage levels at the load terminal decreases. The simulation shows that the DVR performance is
satisfactory in mitigating voltage sags. From simulation results also show that the DVR compensates the sags/swells
quickly and provides excellent voltage regulation. The DVR handles both balanced and unbalanced situations without
any difficulties and injects the appropriate voltage component to correct rapidly any anomaly in the supply voltage to
keep the load voltage balanced and constant at the nominal value. A PWM-based control scheme was implemented. As
opposed to fundamental frequency switching schemes already available in the MATLAB/ SIMULINK, this PWM control
scheme only requires voltage measurements. This characteristic makes it ideally suitable for low-voltage custom power
applications.
Acknowledgment
I Mr. Shinde Abhijeet acknowledges that the above study achieved by myself with the aid of
MATLAB/SIMULINK. All the simulation results are performed by the mentioned software.
REFERENCES
[1] A. Kara, P. Dahler, D. Amhof, and H. Gruning, Power supply quality improvement with a dynamic voltage
restorer (DVR), in Proc. IEEE APEC’98, vol. 2, Feb. 15–19, 1998, pp. 986–993.
[2] M. H. J. Bollen, Understanding Power Quality Problems: Voltage Sags and Interruptions. New York: IEEE Press,
1999.
[3] M. F. McGranaghan, D. R. Mueller, and M. J. Samotyj, Voltage sags in industrial systems, IEEE Trans. Ind.
Applicat., vol. 29, pp. 397– 403, Mar./Apr. 1993.
[4] Chris Fitzer, Mike Barnes, Voltage Sag Detection Technique for a Dynamic Voltage Restorer, IEEE Transactions
on Industry Applications, vol. 40, no. 1, pp.203 January/February 2004.
[5] N.G. Hingorani, Introducing Custom Power in IEEE Spectrum, 32p, pp. 4l-48, 1995. IEEE Std. 1159 – 1995,
Recommended Practice for Monitoring Electric Power Quality.
[6] P. Boonchiam and N. Mithulananthan, Understanding of Dynamic Voltage Restorers through MATLAB
Simulation, Thammasat Int. J. Sc. Tech., Vol. 11, No. 3, July-Sept 2006.
[7] R. Buxton, Protection from voltage dips with the dynamic voltage restorer, in IEE Half Day Colloquium on
Dynamic Voltage Restorers – Replacing Those Missing Cycles, 1998, pp. 3/1- 3/6.
[8] C. Zhan, V. K. Ramachandaramurthy, A. Arulampalam, C. Fitzer, S. Kromlidis, M. Barnes, and N. Jenkins,
Dynamic voltage restorer Based on voltage space vector PWM control, IEEE Trans. Ind. Applicat., vol. 37, pp.
1855–1863, Nov./Dec. 2001.
[9] R. Buxton, Protection from voltage dips with the dynamic voltage restorer, in Dynamic Voltage Restorers—
Replacing Those Missing Cycles, IEE Half Day Colloq., Feb. 11, 1998, pp. 3/1–3/6.

More Related Content

PDF
Control of Dvr with Battery Energy Storage System Using Srf Theory
PDF
COMPENSATION OF SAGS AND SWELLS VOLTAGE USING DYNAMIC VOLTAGE RESTORER (DVR) ...
DOCX
Fault Current Interruption by the Dynamic Voltage Restorer
DOCX
Dynamic Voltage Regulator
PPT
Dynamic voltage restorer (dvr)2
PPTX
Control of dvr with a bess
PPTX
Dynamic Voltage Regulator
PPTX
modeling and simulation of a dynamic voltage restorer
Control of Dvr with Battery Energy Storage System Using Srf Theory
COMPENSATION OF SAGS AND SWELLS VOLTAGE USING DYNAMIC VOLTAGE RESTORER (DVR) ...
Fault Current Interruption by the Dynamic Voltage Restorer
Dynamic Voltage Regulator
Dynamic voltage restorer (dvr)2
Control of dvr with a bess
Dynamic Voltage Regulator
modeling and simulation of a dynamic voltage restorer

What's hot (20)

PDF
DESIGN AND SIMULATION OF DYNAMIC VOLTAGE RESTORER (DVR)
PDF
Mitigation of Voltage Sag/Swell using Custom Power Devices with SMES System i...
PPTX
Dynamic voltage restorer
PDF
Mitigation of voltage sag/swell using Dynamic voltage restorer (DVR)
PDF
Power Quality Enhancement through Dynamic Voltage Restorer using SRF Theory f...
DOCX
Power quality improvement using dvr
PPTX
Voltage sag and it’s mitigation
PDF
An enhanced voltage sag compensation scheme for dynamic voltage restorer
PDF
Mitigation of Voltage Sag/Swell with Fuzzy Control Reduced Rating DVR
PPTX
DESIGN OF MATRIX CONVERTER BASED DYNAMIC VOLTAGE RESTORER FOR POWER QUALITY ...
DOCX
Voltage sag mitigationreport
DOCX
the control of DVR with bess
PDF
Power Quality Solutions: Dynamic Voltage Restorer
PDF
VOLTAGE SAG AND SWELL ALLEVIATION IN DISTRIBUTION NETWORK USING CUSTOM POWER...
PPTX
power quality improvement by using DVR
PPT
Voltage harmonic mitigation using DVR
PPTX
Enhancement of power quality in distribution system using d statcom
PPTX
VSC based DSTATCOM
PDF
Effect of Voltage Sag on an Induction Motor
DESIGN AND SIMULATION OF DYNAMIC VOLTAGE RESTORER (DVR)
Mitigation of Voltage Sag/Swell using Custom Power Devices with SMES System i...
Dynamic voltage restorer
Mitigation of voltage sag/swell using Dynamic voltage restorer (DVR)
Power Quality Enhancement through Dynamic Voltage Restorer using SRF Theory f...
Power quality improvement using dvr
Voltage sag and it’s mitigation
An enhanced voltage sag compensation scheme for dynamic voltage restorer
Mitigation of Voltage Sag/Swell with Fuzzy Control Reduced Rating DVR
DESIGN OF MATRIX CONVERTER BASED DYNAMIC VOLTAGE RESTORER FOR POWER QUALITY ...
Voltage sag mitigationreport
the control of DVR with bess
Power Quality Solutions: Dynamic Voltage Restorer
VOLTAGE SAG AND SWELL ALLEVIATION IN DISTRIBUTION NETWORK USING CUSTOM POWER...
power quality improvement by using DVR
Voltage harmonic mitigation using DVR
Enhancement of power quality in distribution system using d statcom
VSC based DSTATCOM
Effect of Voltage Sag on an Induction Motor
Ad

Viewers also liked (9)

PPTX
enhancement of power quality using integrated power quality controller
PDF
Enhancement of power quality in distribution system by using D-STATCOM
PPTX
power quality improvement in distrution system using D statcom
PPT
FACTS Technology
PPT
Basic types of facts controllers
PPT
FACTS
PPTX
POWER QUALITY IMPROVEMENT IN A PV DISTRIBUTION SYSTEM BY USING D-STATCOM
PPTX
POWER QUALITY IMPROVEMENT
PPT
Dstatcom
enhancement of power quality using integrated power quality controller
Enhancement of power quality in distribution system by using D-STATCOM
power quality improvement in distrution system using D statcom
FACTS Technology
Basic types of facts controllers
FACTS
POWER QUALITY IMPROVEMENT IN A PV DISTRIBUTION SYSTEM BY USING D-STATCOM
POWER QUALITY IMPROVEMENT
Dstatcom
Ad

Similar to Enhancement of Power Quality Problem by Using Dynamic Voltage Restorer (20)

PDF
Ht3414361441
PDF
IRJET-Simulation and Modeling of Dynamic Voltage Restorer for Compensation Of...
PDF
Simulation and Modeling of Dynamic Voltage Restorer for Compensation Of Volta...
PDF
Sag/Swell Compensation by using BES DVR in Industrial Drives Applications
PDF
Sag mitigation in distribution system by using Dynamic voltage Restorer (DVR)
PDF
IRJET- Mollification Parameter Control by Dynamic Voltage Restorer (DVR)
PDF
H011125457
PDF
Ad03101770183.
PDF
Compensation of Single-Phase and Three-Phase Voltage Sag and Swell Using Dyna...
PDF
Mitigation of Voltage Sags & Swells in LV Distribution System Using Dynamic V...
PDF
Iaetsd minimization of voltage sags and swells using dvr
PDF
IRJET- Power Quality Improvement using Dynamic Voltage Restorer (DVR)
PDF
Voltage Dip Mitigation Using Static Var Compensator
PDF
A New Structure of Dynamic Voltage Restorer Based on Asymmetrical ī-source In...
PDF
F010344049
PDF
International Refereed Journal of Engineering and Science (IRJES)
PDF
STATE OF THE ART: DYNAMIC VOLTAGE RESTORER FOR POWER QUALITY IMPROVEMENT
PDF
Bc4101312317
PDF
A Fuzzy Logic controller based Multifunctional Dynamic Voltage restorer in Di...
PDF
DVR with Artificial Intelligent Controller for Voltage Sag Mitigation
Ht3414361441
IRJET-Simulation and Modeling of Dynamic Voltage Restorer for Compensation Of...
Simulation and Modeling of Dynamic Voltage Restorer for Compensation Of Volta...
Sag/Swell Compensation by using BES DVR in Industrial Drives Applications
Sag mitigation in distribution system by using Dynamic voltage Restorer (DVR)
IRJET- Mollification Parameter Control by Dynamic Voltage Restorer (DVR)
H011125457
Ad03101770183.
Compensation of Single-Phase and Three-Phase Voltage Sag and Swell Using Dyna...
Mitigation of Voltage Sags & Swells in LV Distribution System Using Dynamic V...
Iaetsd minimization of voltage sags and swells using dvr
IRJET- Power Quality Improvement using Dynamic Voltage Restorer (DVR)
Voltage Dip Mitigation Using Static Var Compensator
A New Structure of Dynamic Voltage Restorer Based on Asymmetrical ī-source In...
F010344049
International Refereed Journal of Engineering and Science (IRJES)
STATE OF THE ART: DYNAMIC VOLTAGE RESTORER FOR POWER QUALITY IMPROVEMENT
Bc4101312317
A Fuzzy Logic controller based Multifunctional Dynamic Voltage restorer in Di...
DVR with Artificial Intelligent Controller for Voltage Sag Mitigation

More from AM Publications (20)

PDF
DEVELOPMENT OF TODDLER FAMILY CADRE TRAINING BASED ON ANDROID APPLICATIONS IN...
PDF
TESTING OF COMPOSITE ON DROP-WEIGHT IMPACT TESTING AND DAMAGE IDENTIFICATION ...
PDF
THE USE OF FRACTAL GEOMETRY IN TILING MOTIF DESIGN
PDF
TWO-DIMENSIONAL INVERSION FINITE ELEMENT MODELING OF MAGNETOTELLURIC DATA: CA...
PDF
USING THE GENETIC ALGORITHM TO OPTIMIZE LASER WELDING PARAMETERS FOR MARTENSI...
PDF
ANALYSIS AND DESIGN E-MARKETPLACE FOR MICRO, SMALL AND MEDIUM ENTERPRISES
PDF
REMOTE SENSING AND GEOGRAPHIC INFORMATION SYSTEMS
PDF
EVALUATE THE STRAIN ENERGY ERROR FOR THE LASER WELD BY THE H-REFINEMENT OF TH...
PDF
HMM APPLICATION IN ISOLATED WORD SPEECH RECOGNITION
PDF
PEDESTRIAN DETECTION IN LOW RESOLUTION VIDEOS USING A MULTI-FRAME HOG-BASED D...
PDF
INTELLIGENT BLIND STICK
PDF
EFFECT OF SILICON - RUBBER (SR) SHEETS AS AN ALTERNATIVE FILTER ON HIGH AND L...
PDF
UTILIZATION OF IMMUNIZATION SERVICES AMONG CHILDREN UNDER FIVE YEARS OF AGE I...
PDF
REPRESENTATION OF THE BLOCK DATA ENCRYPTION ALGORITHM IN AN ANALYTICAL FORM F...
PDF
OPTICAL CHARACTER RECOGNITION USING RBFNN
PDF
DETECTION OF MOVING OBJECT
PDF
SIMULATION OF ATMOSPHERIC POLLUTANTS DISPERSION IN AN URBAN ENVIRONMENT
PDF
PREPARATION AND EVALUATION OF WOOL KERATIN BASED CHITOSAN NANOFIBERS FOR AIR ...
PDF
ANALYSIS ON LOAD BALANCING ALGORITHMS IMPLEMENTATION ON CLOUD COMPUTING ENVIR...
PDF
A MODEL BASED APPROACH FOR IMPLEMENTING WLAN SECURITY
DEVELOPMENT OF TODDLER FAMILY CADRE TRAINING BASED ON ANDROID APPLICATIONS IN...
TESTING OF COMPOSITE ON DROP-WEIGHT IMPACT TESTING AND DAMAGE IDENTIFICATION ...
THE USE OF FRACTAL GEOMETRY IN TILING MOTIF DESIGN
TWO-DIMENSIONAL INVERSION FINITE ELEMENT MODELING OF MAGNETOTELLURIC DATA: CA...
USING THE GENETIC ALGORITHM TO OPTIMIZE LASER WELDING PARAMETERS FOR MARTENSI...
ANALYSIS AND DESIGN E-MARKETPLACE FOR MICRO, SMALL AND MEDIUM ENTERPRISES
REMOTE SENSING AND GEOGRAPHIC INFORMATION SYSTEMS
EVALUATE THE STRAIN ENERGY ERROR FOR THE LASER WELD BY THE H-REFINEMENT OF TH...
HMM APPLICATION IN ISOLATED WORD SPEECH RECOGNITION
PEDESTRIAN DETECTION IN LOW RESOLUTION VIDEOS USING A MULTI-FRAME HOG-BASED D...
INTELLIGENT BLIND STICK
EFFECT OF SILICON - RUBBER (SR) SHEETS AS AN ALTERNATIVE FILTER ON HIGH AND L...
UTILIZATION OF IMMUNIZATION SERVICES AMONG CHILDREN UNDER FIVE YEARS OF AGE I...
REPRESENTATION OF THE BLOCK DATA ENCRYPTION ALGORITHM IN AN ANALYTICAL FORM F...
OPTICAL CHARACTER RECOGNITION USING RBFNN
DETECTION OF MOVING OBJECT
SIMULATION OF ATMOSPHERIC POLLUTANTS DISPERSION IN AN URBAN ENVIRONMENT
PREPARATION AND EVALUATION OF WOOL KERATIN BASED CHITOSAN NANOFIBERS FOR AIR ...
ANALYSIS ON LOAD BALANCING ALGORITHMS IMPLEMENTATION ON CLOUD COMPUTING ENVIR...
A MODEL BASED APPROACH FOR IMPLEMENTING WLAN SECURITY

Recently uploaded (20)

PPTX
IOT PPTs Week 10 Lecture Material.pptx of NPTEL Smart Cities contd
PDF
Well-logging-methods_new................
PPTX
Sustainable Sites - Green Building Construction
DOCX
573137875-Attendance-Management-System-original
PPTX
UNIT 4 Total Quality Management .pptx
PDF
The CXO Playbook 2025 – Future-Ready Strategies for C-Suite Leaders Cerebrai...
PPTX
M Tech Sem 1 Civil Engineering Environmental Sciences.pptx
PPT
Mechanical Engineering MATERIALS Selection
PPTX
FINAL REVIEW FOR COPD DIANOSIS FOR PULMONARY DISEASE.pptx
PPTX
Internet of Things (IOT) - A guide to understanding
PDF
PRIZ Academy - 9 Windows Thinking Where to Invest Today to Win Tomorrow.pdf
PDF
Mohammad Mahdi Farshadian CV - Prospective PhD Student 2026
PPTX
Geodesy 1.pptx...............................................
PPTX
Lecture Notes Electrical Wiring System Components
PPTX
Infosys Presentation by1.Riyan Bagwan 2.Samadhan Naiknavare 3.Gaurav Shinde 4...
PPT
Project quality management in manufacturing
PPTX
Strings in CPP - Strings in C++ are sequences of characters used to store and...
PDF
keyrequirementskkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkk
PPTX
Recipes for Real Time Voice AI WebRTC, SLMs and Open Source Software.pptx
PPTX
Welding lecture in detail for understanding
IOT PPTs Week 10 Lecture Material.pptx of NPTEL Smart Cities contd
Well-logging-methods_new................
Sustainable Sites - Green Building Construction
573137875-Attendance-Management-System-original
UNIT 4 Total Quality Management .pptx
The CXO Playbook 2025 – Future-Ready Strategies for C-Suite Leaders Cerebrai...
M Tech Sem 1 Civil Engineering Environmental Sciences.pptx
Mechanical Engineering MATERIALS Selection
FINAL REVIEW FOR COPD DIANOSIS FOR PULMONARY DISEASE.pptx
Internet of Things (IOT) - A guide to understanding
PRIZ Academy - 9 Windows Thinking Where to Invest Today to Win Tomorrow.pdf
Mohammad Mahdi Farshadian CV - Prospective PhD Student 2026
Geodesy 1.pptx...............................................
Lecture Notes Electrical Wiring System Components
Infosys Presentation by1.Riyan Bagwan 2.Samadhan Naiknavare 3.Gaurav Shinde 4...
Project quality management in manufacturing
Strings in CPP - Strings in C++ are sequences of characters used to store and...
keyrequirementskkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkk
Recipes for Real Time Voice AI WebRTC, SLMs and Open Source Software.pptx
Welding lecture in detail for understanding

Enhancement of Power Quality Problem by Using Dynamic Voltage Restorer

  • 1. International Journal of Innovative Research in Advanced Engineering (IJIRAE) ISSN: 2349-2163 Volume 1 Issue 6 (July 2014) http://ijirae.com _________________________________________________________________________________________________ © 2014, IJIRAE- All Rights Reserved Page - 400 Enhancement of Power Quality Problem by Using Dynamic Voltage Restorer Mr.Shinde Abhijeet G. Mr.Pramod Kumar S. Electrical Engg. Department Asst. Prof. Electrical Engg.Department MSS’s CET Jalna MSS’s CET Jalna Dr. BAMU University Aurangabd. Dr. BAMU University Aurangabd. Abstract— Dynamic voltage restorers (DVRs) are used to protect sensitive loads from the effects of voltage sags on the distribution feeder. This paper presents and verifies a novel voltage sag detection technique for use in conjunction with the main control system of a DVR. In all cases it is necessary for the DVR control system to not only detect the start and end of a voltage sag but also to determine the sag depth and any associated phase shift. The DVR, which is placed in series with a sensitive load, must be able to respond quickly to a voltage sag if end users of sensitive equipment are to experience no voltage sag. The DVR can restore the load voltage within few milliseconds. A control technique based on a proportional–integral (PI) controller and a selective controller is used. The controller is designed in a synchronously-rotating reference frame. In fact, three independent controllers have been used to tackle balanced and unbalanced voltage supplies. Simulation results using ‘MATLAB SIMULINK’ Sim Power System Toolbox is presented to illustrate the principle and performance of a DVR operation in load voltage compensation. Keywords— Dynamic Voltage Restorer (DVR), MATLAB SIMULINK, sensitive load, voltage sags, voltage swells. I. INTRODUCTION Nowadays, modern industrial devices are mostly based on electronic devices such as programmable logic controllers and electronic drives. The electronic devices are very sensitive to disturbances and become less tolerant to power quality problems such as voltage sags, swells and harmonics. Voltage dips are considered to be one of the most severe disturbances to the industrial equipments. Voltage support at a load can be achieved by reactive power injection at the load point of common coupling. The common method for this is to install mechanically switched shunt capacitors in the primary terminal of the distribution transformer. The mechanical switching may be on a schedule, via signals from a supervisory control and data acquisition (SCADA) system, with some timing schedule, or with no switching at all. The disadvantage is that, high speed transients cannot be compensated. Some sags are not corrected within the limited time frame of mechanical switching devices. Transformer taps may be used, but tap changing under load is costly. Another power electronic solution to the voltage regulation is the use of a dynamic voltage restorer (DVR). DVRs are a class of custom power devices for providing reliable distribution power quality. They employ a series of voltage boost technology using solid state switches for compensating voltage sags/swells. The DVR applications are mainly for sensitive loads that may be drastically affected by fluctuations in system voltage [1] . II. POWER QUALITY PROBLEMS Power distribution systems, ideally, should provide their customers with an uninterrupted flow of energy at smooth sinusoidal voltage at the contracted magnitude level and frequency. However, in practice, power systems, especially the distribution systems, have numerous nonlinear loads, which significantly affect the quality of power supplies. As a result of the nonlinear loads, the purity of the waveform of supplies is lost. This ends up producing many power quality problems. While power disturbances occur on all electrical systems, the sensitivity of today’s sophisticated electronic devices makes them more susceptible to the quality of power supply. For some sensitive devices, a momentary disturbance can cause scrambled data, interrupted communications, a frozen mouse, system crashes and equipment failure etc. A power voltage spike can damage valuable components. Power Quality problems encompass a wide range of disturbances such as voltage sags/swells, flicker, harmonics distortion, impulse transient, and interruptions [2-3] . III.SOLUTIONS TO POWER QUALITY PROBLEMS There are two approaches to the mitigation of power quality problems. The solution to the power quality can be done from customer side or from utility side First approach is called load conditioning, which ensures that the equipment is less sensitive to power disturbances, allowing the operation even under significant voltage distortion. The other solution is to install line conditioning systems that suppress or counteracts the power system disturbances. Dynamic Voltage Restorer is suitable device for voltage sag reduction [4] . IV.DYNAMIC VOLTAGE RESTORER Among the power quality problems (sags, swells, harmonics…) voltage sags are the most severe disturbances. In order to overcome these problems the concept of custom power devices is introduced recently. One of those devices is
  • 2. International Journal of Innovative Research in Advanced Engineering (IJIRAE) ISSN: 2349-2163 Volume 1 Issue 6 (July 2014) http://ijirae.com _________________________________________________________________________________________________ © 2014, IJIRAE- All Rights Reserved Page -401 the Dynamic Voltage Restorer (DVR), which is the most efficient and effective modern custom power device used in power distribution networks. DVR is a recently proposed series connected solid state device that injects voltage into the system in order to regulate the load side voltage. It is normally installed in a distribution system between the supply and the critical load feeder at the point of common coupling (PCC). Other than voltage sags and swells compensation, DVR can also added other features like: line voltage harmonics compensation, reduction of transients in voltage and fault current limitations[5] . FIGURE 1: Location of DVR A. Equations Related to DVR The system impedance Zth depends on the fault level of the load bus. When the system voltage (VTH) drops, the DVR injects a series voltage VDVR through the injection transformer so that the desired load voltage magnitude VL can be maintained. The series injected voltage of the DVR can be written as Where VL: The desired load voltage magnitude ZTH: The load impedance. IL: The load current VTH: The system voltage during fault condition FIGURE 2: Equivalent circuit diagram of DVR B. Operating Modes of DVR The basic function of the DVR is to inject a dynamically controlled voltage VDVR generated by a forced commutated converter in series to the bus voltage by means of a booster transformer. The momentary amplitudes of the three injected phase voltages are controlled such as to eliminate any detrimental effects of a bus fault to the load voltage VL. This means that any differential voltages caused by transient disturbances in the ac feeder will be compensated by an equivalent voltage generated by the converter and injected on the medium voltage level through the booster transformer [6] . The DVR has three modes of operation which are: protection mode, standby mode, injection/boost mode. 1. Protection mode: If the over current on the load side exceeds a permissible limit due to short circuit on the load or large inrush current, the DVR will be isolated from the systems by using the bypass switches (S2 and S3 will open) and supplying another path for current (S1 will be closed).
  • 3. International Journal of Innovative Research in Advanced Engineering (IJIRAE) ISSN: 2349-2163 Volume 1 Issue 6 (July 2014) http://ijirae.com _________________________________________________________________________________________________ © 2014, IJIRAE- All Rights Reserved Page -402 FIGURE 3: Protection Mode (creating another path for current) 2. Standby Mode: (VDVR= 0) FIGURE 4: Standby Mode of DVR In the standby mode the booster transformer’s low voltage winding is shorted through the converter. No switching of semiconductors occurs in this mode of operation and the full load current will pass through the primary. 3. Injection/Boost Mode: (VDVR>0) In the Injection/Boost mode the DVR is injecting a compensating voltage through the booster transformer due to the detection of a disturbance in the supply voltage. C. Discrete PWM-Based Control Scheme In order to mitigate the simulated voltage sags in the test system of each compensation technique, also to compensate voltage sags in practical application, a discrete PWM-based control scheme is implemented, with reference to DVR. The aim of the control scheme is to maintain a constant voltage magnitude at the sensitive load point, under the system disturbance. The control system only measures the rms voltage at load point, for example, no reactive power measurement is required. Figure 4.1 shows the DVR controller scheme implemented in MATLAB/SIMULINK. The DVR control system exerts a voltage angle control as follows: an error signal is obtained by comparing the reference voltage with the rms voltage measured at the load point[7-8] . The PI controller processes the error signal and generates the required angle δ to drive the error to zero, for example; the load rms voltage is brought back to the reference voltage. It should be noted that, an assumption of balanced network and operating conditions are made. The modulating angle δ or delta is applied to the PWM generators in phase A, whereas the angles for phase B and C are shifted by 240° or -120° and 120° respectively[9] . VA = Sin (ωt +δ) VB=Sin (ωt+δ-2π/3) VC = Sin (ωt +δ+2π/3 V. SIMULATION AND RESULTS Digital simulation is done using the blocks of Matlab simulink and the results are presented here. The first simulation was done with no DVR and no three phase fault is applied to the system. This system shows the normal operating power system without DVR and three phase fault.
  • 4. International Journal of Innovative Research in Advanced Engineering (IJIRAE) ISSN: 2349-2163 Volume 1 Issue 6 (July 2014) http://ijirae.com _________________________________________________________________________________________________ © 2014, IJIRAE- All Rights Reserved Page -403 Figure 5 shows the SIMULINK model for Normal Operating Power System. Figure 6 and Figure 7 shows the output waveform for figure 5. The FFT analysis for this model shows total harmonic distortion is 0%, which means the system, is in healthy condition figure 8 shows the FFT analysis for Normal Operating Power System. FIGURE 5: Normal Operating Power System FIGURE 6: 3-Ø Voltage at Load Point, Without DVR FIGURE 7: P.U Voltage at Load Point Without DVR The second simulation was done (figure 9) with no DVR and a three phase fault is applied to the system at point with fault resistance of 0.66 U for a time duration of 200 ms. The third simulation is carried out (figure 10) at the same scenario as above but a DVR is now introduced at the load side to compensate the voltage sag occurred due to the three phase fault applied.
  • 5. International Journal of Innovative Research in Advanced Engineering (IJIRAE) ISSN: 2349-2163 Volume 1 Issue 6 (July 2014) http://ijirae.com _________________________________________________________________________________________________ © 2014, IJIRAE- All Rights Reserved Page -404 FIGURE 8: FFT Analysis for Normal Operating Power System Figure 11 shows the pu voltage at load point when the system operates with no DVR and a three phase fault is applied to the system. FIGURE 9: SIMULINK for Fault on Power System FIGURE 10:3-Ø Voltage at Load Point, with 3-Ø fault, without DVR
  • 6. International Journal of Innovative Research in Advanced Engineering (IJIRAE) ISSN: 2349-2163 Volume 1 Issue 6 (July 2014) http://ijirae.com _________________________________________________________________________________________________ © 2014, IJIRAE- All Rights Reserved Page -405 FIGURE 11: P.U Voltage at Load Point, with 3-Ø fault, without DVR FIGURE 12: FFT analysis for fault on Power system Figure 12 shows the FFT analysis of power system during fault. FIGURE 13: SIMULINK Model of DVR In Power System
  • 7. International Journal of Innovative Research in Advanced Engineering (IJIRAE) ISSN: 2349-2163 Volume 1 Issue 6 (July 2014) http://ijirae.com _________________________________________________________________________________________________ © 2014, IJIRAE- All Rights Reserved Page -406 When the DVR is in operation (Figure13) the voltage interruption is compensated almost completely and the rms voltage at the sensitive load point is maintained at normal condition. Injected voltage and the voltage across load is shown in Figure14 & Figure15. FFT analysis for the output voltage is shown in Figure16. THD reduces to 0.39%. Thus the harmonics are reduced from 1.37% to 0.39%. FIGURE14: 3-Ø Voltage at Load Point, with 3-Ø fault, with DVR FIGURE15: P.U Voltage at Load Point, with 3-Ø fault, with DVR FIGURE16: FFT Analysis for Power System with DVR
  • 8. International Journal of Innovative Research in Advanced Engineering (IJIRAE) ISSN: 2349-2163 Volume 1 Issue 6 (July 2014) http://ijirae.com _________________________________________________________________________________________________ © 2014, IJIRAE- All Rights Reserved Page -407 V. CONCLUSION We are presented here power quality problems such as voltage sag and harmonics. By using the custom power electronic device (DVR) we have solved the problem of voltage sag and harmonics. The design and applications of DVR for voltage sags and comprehensive results were presented. The effectiveness of a DVR system mainly depends upon the rating of DC storage rating and the loads. In the test system it is observed that after a particular amount of load increases on 11 kV feeders, the voltage levels at the load terminal decreases. The simulation shows that the DVR performance is satisfactory in mitigating voltage sags. From simulation results also show that the DVR compensates the sags/swells quickly and provides excellent voltage regulation. The DVR handles both balanced and unbalanced situations without any difficulties and injects the appropriate voltage component to correct rapidly any anomaly in the supply voltage to keep the load voltage balanced and constant at the nominal value. A PWM-based control scheme was implemented. As opposed to fundamental frequency switching schemes already available in the MATLAB/ SIMULINK, this PWM control scheme only requires voltage measurements. This characteristic makes it ideally suitable for low-voltage custom power applications. Acknowledgment I Mr. Shinde Abhijeet acknowledges that the above study achieved by myself with the aid of MATLAB/SIMULINK. All the simulation results are performed by the mentioned software. REFERENCES [1] A. Kara, P. Dahler, D. Amhof, and H. Gruning, Power supply quality improvement with a dynamic voltage restorer (DVR), in Proc. IEEE APEC’98, vol. 2, Feb. 15–19, 1998, pp. 986–993. [2] M. H. J. Bollen, Understanding Power Quality Problems: Voltage Sags and Interruptions. New York: IEEE Press, 1999. [3] M. F. McGranaghan, D. R. Mueller, and M. J. Samotyj, Voltage sags in industrial systems, IEEE Trans. Ind. Applicat., vol. 29, pp. 397– 403, Mar./Apr. 1993. [4] Chris Fitzer, Mike Barnes, Voltage Sag Detection Technique for a Dynamic Voltage Restorer, IEEE Transactions on Industry Applications, vol. 40, no. 1, pp.203 January/February 2004. [5] N.G. Hingorani, Introducing Custom Power in IEEE Spectrum, 32p, pp. 4l-48, 1995. IEEE Std. 1159 – 1995, Recommended Practice for Monitoring Electric Power Quality. [6] P. Boonchiam and N. Mithulananthan, Understanding of Dynamic Voltage Restorers through MATLAB Simulation, Thammasat Int. J. Sc. Tech., Vol. 11, No. 3, July-Sept 2006. [7] R. Buxton, Protection from voltage dips with the dynamic voltage restorer, in IEE Half Day Colloquium on Dynamic Voltage Restorers – Replacing Those Missing Cycles, 1998, pp. 3/1- 3/6. [8] C. Zhan, V. K. Ramachandaramurthy, A. Arulampalam, C. Fitzer, S. Kromlidis, M. Barnes, and N. Jenkins, Dynamic voltage restorer Based on voltage space vector PWM control, IEEE Trans. Ind. Applicat., vol. 37, pp. 1855–1863, Nov./Dec. 2001. [9] R. Buxton, Protection from voltage dips with the dynamic voltage restorer, in Dynamic Voltage Restorers— Replacing Those Missing Cycles, IEE Half Day Colloq., Feb. 11, 1998, pp. 3/1–3/6.