t’s difficult to imagine a business to which backup
power is more critical than Profitability.net, a
Cincinnati, OH-based provider of private data center
space, hosted applications, cloud computing capacity,
and network storage. Redundant security is a major
element of how the firm defines itself, both in terms of clients’
data and equipment, and the power supply to the equipment.
Any unauthorized personnel attempting to access an infra-
structure cabinet would run into five layers of security; the
cabinets themselves are electronically secure and provide 24/7
notification of unauthorized attempts at access. The company,
which was founded in 2002, also uses a redundant flywheel
UPS system to prevent outages from compromising data cen-
ter cooling infrastructure and, thus, data security.
Aaron Larkins, Profitability.net’s president and CEO, says
that UPS redundancy has always been considered mandatory
at the company’s 23,000-square-foot facility, which can be
expanded by 12,000 additional square feet. Until late 2008, two
separate battery-based systems had been used as a redundant
UPS for the company’s single generator.
“We have public company clients, medical groups, and
large manufacturing multi-site companies that rely on our data
center to access their business applications,” says Larkins.“So
we made a decision that we would have a primary and redun-
dant power source from the UPS forward to ensure that no
matter what happens in that primary line, whether it’s a fatal
problem with the UPS, or the power distribution unit [PDU],
or the circuit breakers that are feeding individual branch cir-
cuits, the customer has a secondary source of power.”
In late 2008, the company had a CleanSource UPS from
Active Power installed for the redundant system, and then
added a second unit for the primary system a little less than
a year later, replacing battery UPS systems that had reached
the end of their service lives. Profitability.net’s experience
demonstrates the choices in equipment that managers at
companies in a wide variety of industries have in protecting
Business owners explore a wide
variety of electrical equipment options
and renewable energy alternatives for
their backup power operations.
BY DON TALEND
Equipped for
ActivePower
Continuity
their power supply.
The CleanSource UPS uses a flywheel that normally spins
at 7,700 rpm and stores kinetic energy. In event of a power
outage, discharge energy from the flywheel provides about
15 seconds of “ride-through” power, typically a sufficient
length of time for standby generators to kick in. According to
the manufacturer, the system is 98% efficient. The flywheel
is located between top and bottom mechanical bearings and
the entire unit is enclosed in a cast-iron housing. Rather than
turning on a vertical shaft, magnetic pulses turn the flywheel.
The UPS steadies the kinetic energy produced by the flywheel
to a 480-V, 60-Hertz output, and an automatic transfer switch
transfers power from the flywheel to the standby system.
Each client’s cabinet has a primary and redundant power
source from the UPS forward. Each UPS feeds its own PDU
that feeds the individual cabinets.
January/February 2011 • 23
“The flywheel systems are designed to give us sufficient
run time until our generators start up, which in our case, is
a little less than 10 seconds in the event of a power outage or
voltage drop in the grid,” says Larkins. Each system never has
more than a 50% load, allowing a “bridge” of longer than 15
seconds should a power outage or voltage drop occur.
“In this business, power infrastructure invest-
ments are pretty substantial, and you have to
take the long view on what your costs of
operation are going to be over time,”
points out Larkins. “Our analysis in
2008 showed that energy costs were
already starting to pop up, and our
thought was that energy isn’t going to
get any cheaper over the next 10 or 15
years, so whatever we deploy needs to
be the highest-efficiency available.”
Larkins adds that the new system
also offers continual monitoring ca-
pability. “Stored kinetic energy doesn’t
lie—if you’ve got a wheel rotating at a
certain rpm [revolutions per minute], you
know you have a certain amount of power,”
he says.
The system performed as intended dur-
ing a brief power outage along the down-
town Cincinnati corridor shortly before
1 a.m. on July 24, 2009. The company’s
monitoring systems immediately identi-
fied the power issue from Duke Energy
and signaled the generator power system
to start. The transition occurred in less
than 10 seconds.
“Before [the outage], we had a
confidence level that they would work,
because we saw them in operation every
day and we saw the consistency in how
they performed,” says Larkins. He adds that
the company has realized financial benefits
from the new installation as well. It was possible
to shut down one of two 10-ton air conditioners that were
dedicated to the UPS room. Additionally, the company saves
about $18,000 in the form of lower maintenance costs every
year since the installation, according to Larkins.
Growth Meets Modularity
When Atlantic.net, an Orlando, FL-based provider of busi-
ness data services such as server colocation, dedicated serv-
ers, data backup, security, and private networks looked at the
impact of future growth on its 25,000-square foot facility, it
was clear that growth, reliable power, and sustainability did
not have to be mutually exclusive.
In 2003, the company built the facility—which is fully
steel reinforced and meets Category 5 hurricane require-
ments—and had two Eaton 9315 battery-powered UPS
units rated at 225–750 kVA installed. By 2007, the 9315s had
reached capacity and the company began looking to expand
its UPS capacity. Minimizing energy consumption and costs
were a major consideration, however.
“We have global customers, so just because we’re in the
Eastern time zone, that doesn’t mean that when we go home,
Client demands,
infrastructure
adjustments, and
an overall desire
to minimize energy
consumption led
Atlantic.net to
expand its UPS
capacity.
Photosthispage:Eaton
24 • www.distributedenergy.com
our clients stop working,” points out Brett
Haines, operations manager for Atlantic.net,
which was founded in 1994.“We need to have
100% uptime—that’s something that we have
to guarantee to our customers and we have to
provide it. A UPS helps us to guarantee 100%
uptime,” he says, adding that the company
serves several industries in which data is criti-
cal, such as travel and medical, and small com-
panies to multimillion-dollar corporations.
Haines acknowledges that Atlantic.net
is served well by its power supplier, Progress
Energy, which routinely conducts line tests
and trims trees located near wires. Normally,
problems only occur with the power sup-
ply as a result of human mishaps, he adds.
Regardless, the company employs a 2-MW
Caterpillar generator for standby power and
management recognizes the importance of a
foolproof power supply.
But like nearly everyone, management
also recognized the fact that energy costs had
been steadily ticking upward during the past
decade. Clients were making infrastructure
adjustments to try and keep up. The company
responded to the demand by opting for new
high-efficiency, modular Eaton BladeUPS
systems for the server racks.
“More and more, our clients have been
virtualizing the components that they use—
they’re going from more servers down to a
few,” says Haines. “As more clients come in and
use our space, the virtualization helps because it
reduces our power needs, but as more clients come in, we
need more power. In those fewer servers, they’re using more
energy and they’re also putting out more heat, so we try to
minimize our heat load on the floor as much as possible, and
the BladeUPS help because they’re more efficient.”
The BladeUPS system is a three-phase, rack-based UPS
system new three-phase system designed primarily for mod-
ularity. According to the manufacturer, users can expand
their UPS capacity from 12 kW to 60 kW in a 19-inch enclo-
sure by adding from one to six parallel BladeUPS modules to
create redundancy. The units
reportedly provide up to 34
minutes of run time and are
98% efficient.
As of early fall 2010,
Atlantic.net had installed nine
BladeUPS racks and a total
of 50 modules, in addition to
the two Eaton 9315s still in
service. Haines reports that
bridges typically last 15
seconds with a maximum
of 29 seconds, not that it
has been put to use very
often. One time, a car had
struck a power pole and an
Left: Flywheel-
based UPS
recently installed
by Profitability.net
Right: The Beth
Israel Deaconess
Medical Center
and Ty Dell
recently imple-
mented flywheel
UPS systems
to help protect
two data centers
against power
outages.
entire grid section was shut down, according to
Haines. The UPS bridged the outage for 20 sec-
onds, and the generator ran for two hours with
no adverse impact on clients’ equipment.
The modularity of the new UPS system
suits cloud computing, an Atlantic.net capabil-
ity. “As more clients come, we’re going to need
more computers online for our new cloud
product,” says Haines. “The way we can do
that with our UPSs is to put in redundant UPS
systems. What we did was put two BladeUPS
modules into each rack so now, in case one
component fails or a battery isn’t up to par, we
have those in place.
“As you increase the load, UPSs become
more efficient and you don’t want to have large
400- or 500-KVa modules sitting there with
10% load—that’s not very efficient.” He adds
that the BladeUPS modules operate at 40% for
“fail-over” capability.
Medical Facility Goes Green With
Flywheels
Beth Israel Deaconess Medical Center
(BIDMC) in Boston, MA, a 550-bed adult
medical-surgical teaching hospital affiliated
with Harvard Medical School, recently estab-
lished a goal to increase green purchasing by
15% by Fiscal Year 2012. A major element of
this initiative is the selection of “clean energy”
flywheel systems to help protect the BIDMC’s
two data centers against power outages. The
main 7,000 square-foot Renaissance Data
Center is located 1.5 miles from BIDMC’s hospital cam-
pus and the separate Span Data Center 3,000-square-foot
disaster recovery data center is housed at the main campus.
These data centers provide critical clinical support to the
facility’s medical records, pharmacy, laboratory, chemother-
apy suite, and operating rooms.
The UPSs protecting the servers, switches, routers, data
storage devices, and PDUs utilize flywheel systems from
Vycon. The Span Data Center contains a standalone 225-kVA
ActivePower
Vycon
OnStat Power Systems’ Silent
Sentry could be described as a
self-contained UPS for various
non-life-threatening surgical
procedures.
SilentSentry
January/February 2011 • 25
UPS that uses two Vycon flywheels rated at 275 kVA for
11.7 seconds. A 200-kW computer load provides 15 seconds
of run time on the flywheel before the generator starts.
The BIDMC staff is in the process of making this facility’s
electrical and cooling systems as redundant as those in the
Renaissance Data Center. The latter facility receives power
from the utility vault through four automatic transfer
switches (ATSs) that switch to a generator during a pro-
longed power event. The cooling system and computer load
are supported by two sets of redundant ATSs; if either one
loses an ATS, the data center remains operational.
Two sets of Vycon VDC flywheels to back up the two
parallel 225kVA UPSs. According to Ty Dell, data center plant
manager for information systems, during a power outage the
facility obtains 30 seconds of flywheel runtime at 400 kW of
computer load before the generator starts up. Dell points out
that this is plenty of time, as the generator must come online
within 10 seconds in order to meet the National Fire Protec-
tion Association’s NFPA 99 regulations for Emergency Power
Systems; the Joint Commission on Accreditation of Health-
“Stored kinetic energy doesn’t lie—if you’ve got a wheel
rotating at a certain rpm, you know you have a certain
amount of power.”
Ecommerce Inc. had two Generac 500-kW MPS Diesel generators installed
for standby power for its data center.
Generac
26 • www.distributedenergy.com
care Organizations (JCAHO) requires that the generator
must come online within 12 seconds.
The flywheels have a maximum energy storage of 3,000
kW per second at 100 kW and a rotational speed of 18,500 to
36,000 rpm. For the short term, management is opting to use
batteries and the flywheel systems in tandem. Dell reports
that the staff is currently evaluating whether to eliminate the
batteries, noting that a rapid flywheel recharge time of less
than 150 seconds provides reliability and that the flywheels
do not require special cooling.
Redundancy in Standby Generators
Redundancy is often a high priority for standby generators,
too. That was definitely the case for Columbus, OH-based
Ecommerce Inc., a company founded in late 1999 that
houses nearly half a million Web sites or nearly half of 1%
of the Internet. In fall 2007, the firm was constructing a new
data center in Columbus and was selecting a backup power
solution and needed a scalable system to address future
growth in the climate-controlled facility that would soon be
filled with industrial-grade servers. One option was a single
2-MW generator and transfer switch with no redundancy,
a solution that would have taken nearly a year to install.
Rick Gideon, vice president of operations for Ecom-
merce Inc., was introduced to an alternative redundant
solution by chance. The company and Columbus-based
Generator Systems Inc. (GSI) had the same real estate agent,
which is how Gideon was introduced to GSI. He met with
Brian Kennedy, vice president, sales and marketing for GSI,
who recommended the Generac Modular Power System
(MPS) for protecting Ecommerce, Inc.’s 10,000 1U server
room. Rather than installing 2-MW gensets immediately, the
company had two Generac 500-kW MPS Diesel generators
installed that are providing 100% redundancy at a lower cost.
Enough space is available to add three more 500-kW MPS
Diesel units to allow for future growth within the facility.
A Different Kind of Medical Backup Power
Cardiac Equipment Services, Nassau County, NY, provides
slightly different medical backup power systems that could
be described as self-contained UPSs. The company is owned
by Charlie Bergin, who has worked in the biomedical engi-
neering field for 25 years—the past 15 as a provider of med-
ical power backup systems. He often recommends one of
two systems—OnStat Power Systems’ Reassurance or Silent
Sentry—for office-based surgical centers.
The Reassurance product, developed by Medi+Products
in the early 1990s, is a fully enclosed, stainless steel, cabinet
Counterclockwise from left:
Norfolk Naval Air Station, Norfolk,
VA, “tower” and walking surface
Bottom right: County Juvi Prison,
San Bernardino, CA.
(Note the large exhaust particulate
filter on top.)
GenSysSupport
January/February 2011 • 27
use in equipment such as standby generators. In 1988, the
US Environmental Protection Agency (EPA) mandated that
underground storage tank (UST) owners comply with new
standards for corrosion resistance, leak detection, and spill-
age and overfill protection by the end of 1998.
This regulatory development has created a market for
related equipment: AST platforms. Larry Hill, CEO of Col-
lierville, TN-based Generator System Support (GSS) and
engineering manager at Thompson Power Corp. in Memphis,
TN, points out that the proliferation of ASTs has meant that
gensets are sometimes located too high for proper service and
maintenance. GSS constructs aluminum service platforms that
allow access to two sides and one end of gensets.
The platforms use 0.125-inch aluminum tread plate mate-
rial that is bolted together in the field. Platforms in the stan-
dard configuration do not touch the concrete pad; they have a
cantilever design that uses the fuel tank base as the supporting
member. The platform usually is located 36–48 inches above the
concrete pad. DE
Don Talend is a frequent contributor to Distributed Energy and
specializes in covering technology and innovation.
system on a castor base. The top surface has a 30-inch height
and the unit is equipped with front panel outlets.
The Silent Sentry is a static subpanel designed for mini-
mal impact on interior design. The unit provides 2,000, 2500,
or 3,000 W and 4 kWh of stored energy, and is based on 12-V
battery banks with built-in UL-489 branch-circuit protectors
for distributed loads. It can be inset into a wall cavity between
wall studs and has a protrusion of as little as 4½ inches. The
unit integrates branch-circuit interrupters into the system it-
self, making the battery-powered generator an uninterruptible
subpanel, eliminating the need for an emergency subpanel.
The two units have several common features, including
five-stage battery recharging, a recharger with four-stage
automatic recharging and manual equalization, battery
monitoring, an optional charge/discharge monitoring sys-
tem for tracking energy in and out of the battery bank, and
split-phase output.
Surgeons can plug their powered surgical equipment into
these units to maintain procedural continuity. Bergin points
out that the units are designed for procedures that are not
life-threatening, such as gastroenterology and plastic surgery.
“Many doctors are fearful,” says Bergin.“When the power
goes out, they don’t know how long it’s going to be—they
just want enough time to close and get out. They may not
finish the procedure. It depends on where they are in the
procedure—if it happens right at the beginning, they might
just close up and have the patient come back.”
Still, JCAHO mandates two hours of standby power.
Gastroenterologists power equipment such as vital sign moni-
tors and O2 concentrators, and plastic surgeons need to wire
entire operating rooms because they use general anesthesia.
“All of the procedures are elective, and all are outpatient,”
says Bergin.“It’s not like they need hospital-based generators,
which are diesel-based and located outside the building.”
Bergin indicates that a market for standby power for
non-life-threatening medical procedures has been steadily
growing in recent years.“Today, most outpatient surgery can
be done in an ambulatory environment outside of the hospi-
tal,” he says.“It’s happening more and more where there are a
lot more facilities opening that do opening types of surgery,
from orthopedics to OB-Gyn.”
Service Platforms for Raised Tanks
Recent federal regulations have created a new market for
aboveground storage tanks (ASTs) for fuel that is stored for
Online extras
www.distributedenergy.com/backup
Uninterrupted savings!
A market for standby
power for non-life-
threatening medical
procedures has been
steadily growing in
recent years.

More Related Content

PDF
Net_Alliant_Technologies
PDF
PDF
Big Data Analytics Transforms Utilities and Cities
DOCX
Eficiencia Data Center
PDF
1.1 integrating renewables srm
PDF
ARC White paper: Schneider Electric Introduces First ePAC, Combines PAC with...
PDF
[Case study] Kissimmee Utility Authority: Best compilation of products from o...
PPTX
Funding Infrastructure Investments with Guaranteed Performance
Net_Alliant_Technologies
Big Data Analytics Transforms Utilities and Cities
Eficiencia Data Center
1.1 integrating renewables srm
ARC White paper: Schneider Electric Introduces First ePAC, Combines PAC with...
[Case study] Kissimmee Utility Authority: Best compilation of products from o...
Funding Infrastructure Investments with Guaranteed Performance

What's hot (20)

PDF
Data centers on the Edge
PDF
5 cired2013 planning of power distribution systems
PDF
Smart Energy Systems of Future
PDF
Implementing energy efficient data centers
PPTX
Building Analytics: Energy Information Systems
PDF
Best Practices for Creating Your Smart Grid Network Model
PDF
Comprehensive Energy Management Strategy
PDF
Designing a metering system for small and mid sized buildings
PDF
Helping mining companies with their sustainability strategies
PDF
Hacking the Conventional Data Center Infrastructure
PPTX
Process Automation - The Future
PDF
Customer magazine insider october 2012 final
PPT
Schneider electrics building_business_presentation
PDF
The Advanced Distribution Management System (ADMS)
PDF
Air Flow Presentation 0218
PDF
Big Data Analytics at Vestas Wind Systems
PPTX
How Process Industry takes advantage of our solutions
PPT
2009 Going Green Data Center Presentation
PDF
Big Data innovation in Japan’s energy industry - EBA Fieldwork 2015
PPTX
Schenider Electric company story
Data centers on the Edge
5 cired2013 planning of power distribution systems
Smart Energy Systems of Future
Implementing energy efficient data centers
Building Analytics: Energy Information Systems
Best Practices for Creating Your Smart Grid Network Model
Comprehensive Energy Management Strategy
Designing a metering system for small and mid sized buildings
Helping mining companies with their sustainability strategies
Hacking the Conventional Data Center Infrastructure
Process Automation - The Future
Customer magazine insider october 2012 final
Schneider electrics building_business_presentation
The Advanced Distribution Management System (ADMS)
Air Flow Presentation 0218
Big Data Analytics at Vestas Wind Systems
How Process Industry takes advantage of our solutions
2009 Going Green Data Center Presentation
Big Data innovation in Japan’s energy industry - EBA Fieldwork 2015
Schenider Electric company story
Ad

Similar to Equipped for Continuity (20)

PPTX
AP intro - Industrial June 2016_compressed 2
PPT
Power Protection and Management from the Desktop to the Data Center - Keith W...
PPTX
Uninterruptible Power Supply (UPS)
PPTX
Uninterruptible power supply (ups)
PDF
Evaluating the Opportunity for DC Power in the Data Center
PDF
Project Report of Automatic Source Selection
PDF
Riello flywheel-energy-storge-systems
PDF
Power protection 00000
PDF
Koomeyondatacenterelectricityuse v9
PDF
Powering-Up the Industrial Network
PPTX
Smart Energy in the Data Center
PDF
Energy Logic Presentation
PDF
Best Practices for Achieving Return on Investment through Energy Efficient Co...
PDF
Facility Optimization
PDF
DCD_FOCUS on POWER Article
PDF
Application Note – UPS Power System Design Parameters
PDF
Energy Logic: Reducing Data Center Energy Consumption by Creating Savings tha...
PDF
Low Complexity + Low Cost = High Availability
PDF
Renewable Watch Magazine - Beyond Big Data
AP intro - Industrial June 2016_compressed 2
Power Protection and Management from the Desktop to the Data Center - Keith W...
Uninterruptible Power Supply (UPS)
Uninterruptible power supply (ups)
Evaluating the Opportunity for DC Power in the Data Center
Project Report of Automatic Source Selection
Riello flywheel-energy-storge-systems
Power protection 00000
Koomeyondatacenterelectricityuse v9
Powering-Up the Industrial Network
Smart Energy in the Data Center
Energy Logic Presentation
Best Practices for Achieving Return on Investment through Energy Efficient Co...
Facility Optimization
DCD_FOCUS on POWER Article
Application Note – UPS Power System Design Parameters
Energy Logic: Reducing Data Center Energy Consumption by Creating Savings tha...
Low Complexity + Low Cost = High Availability
Renewable Watch Magazine - Beyond Big Data
Ad

More from Don Talend (20)

PDF
Don Talend Ghostwritten Article - Enhancing Developer Productivity with AI
DOC
DonTalend Editorial Content Manager Resume
PDF
Don Talend Networking Bio, December 2024
PDF
Don Talend Refuse Content Portfolio - Long-form Trade Press Articles
PDF
Don Talend Energy Industry Content Portfolio
PDF
Don Talend Energy Industry Content Portfolio
PDF
Don Talend Energy-Efficient Lighting Article
PDF
Don Talend Turbine Efficiency Article
PDF
Don Talend Uninterruptible Power Supply Article
PDF
Don Talend Intelligent Energy Management article
PDF
Thermal Management article - Engine Technology International magazine
PDF
Distributed Energy magazine - Intelligent Energy Management
PDF
Don Talend Digital Portfolio
PDF
CertificateOfCompletion_Creating Online Video with Android Phones.pdf
PDF
Expert Insights - Social Media Marketing - Skillsoft_Badge.pdf
PDF
Don Talend stepper motors article
PDF
UX Foundations: Content Strategy - Certificate of Completion
PDF
Online Marketing Foundations - Certificate of Completion
PDF
Learning to Write Marketing Copy - Certificate of Completion
PDF
Viral Marketing - Certificate of Completion
Don Talend Ghostwritten Article - Enhancing Developer Productivity with AI
DonTalend Editorial Content Manager Resume
Don Talend Networking Bio, December 2024
Don Talend Refuse Content Portfolio - Long-form Trade Press Articles
Don Talend Energy Industry Content Portfolio
Don Talend Energy Industry Content Portfolio
Don Talend Energy-Efficient Lighting Article
Don Talend Turbine Efficiency Article
Don Talend Uninterruptible Power Supply Article
Don Talend Intelligent Energy Management article
Thermal Management article - Engine Technology International magazine
Distributed Energy magazine - Intelligent Energy Management
Don Talend Digital Portfolio
CertificateOfCompletion_Creating Online Video with Android Phones.pdf
Expert Insights - Social Media Marketing - Skillsoft_Badge.pdf
Don Talend stepper motors article
UX Foundations: Content Strategy - Certificate of Completion
Online Marketing Foundations - Certificate of Completion
Learning to Write Marketing Copy - Certificate of Completion
Viral Marketing - Certificate of Completion

Recently uploaded (20)

PDF
Biography of Brady Beitlich
PPTX
CH 1 AN INTRODUCTION OF INTEGRATED MARKETING COMMUNICATION (COMBINE)
PDF
Boost Sales Around the Clock with AI Chatbots for Marketing
PDF
Digital Marketing Agency vs Freelancers and VAs: Which Should You Hire in 2025
PDF
You Need SEO for Your Business. Here’s Why..pdf
PPTX
Best Mobile App Development Company in Lucknow
PDF
5 free to use google tools to understand your customers online behavior in 20...
PDF
DigiBrandX: Crafting Identities That Resonate
PDF
20K Btc Enabled Cash App Accounts – Safe, Fast, Verified.pdf
PPTX
Choose the Right SEO Agency India - 7 Key Tips by Clickbold Media
PPTX
hnk joint business plan for_Rooftop_Plan
PPT
Market Segmentation and Positioning(3).ppt
PPTX
APA Examples Reference Examples Style and
PDF
How to Break Into AI Search with Andrew Holland
PDF
AI powered Digital Marketing- How AI changes
PPTX
SaaS intelligence platform for B2B founders and marketers - Toksta
PDF
sm_67a1bc7f35716dcb1a9195ea_382528b8-2159-47be-a7ba-d034a449f849.pdf
PPTX
Mastering in Website Competitor Analysis
PPTX
CH 2 The Role of IMC in the Marketing Process (combined)
PDF
Pay-Per-Click Marketing: Strategies That Actually Work in 2025
Biography of Brady Beitlich
CH 1 AN INTRODUCTION OF INTEGRATED MARKETING COMMUNICATION (COMBINE)
Boost Sales Around the Clock with AI Chatbots for Marketing
Digital Marketing Agency vs Freelancers and VAs: Which Should You Hire in 2025
You Need SEO for Your Business. Here’s Why..pdf
Best Mobile App Development Company in Lucknow
5 free to use google tools to understand your customers online behavior in 20...
DigiBrandX: Crafting Identities That Resonate
20K Btc Enabled Cash App Accounts – Safe, Fast, Verified.pdf
Choose the Right SEO Agency India - 7 Key Tips by Clickbold Media
hnk joint business plan for_Rooftop_Plan
Market Segmentation and Positioning(3).ppt
APA Examples Reference Examples Style and
How to Break Into AI Search with Andrew Holland
AI powered Digital Marketing- How AI changes
SaaS intelligence platform for B2B founders and marketers - Toksta
sm_67a1bc7f35716dcb1a9195ea_382528b8-2159-47be-a7ba-d034a449f849.pdf
Mastering in Website Competitor Analysis
CH 2 The Role of IMC in the Marketing Process (combined)
Pay-Per-Click Marketing: Strategies That Actually Work in 2025

Equipped for Continuity

  • 1. January/February 2011www.distributedenergy.com Efficient Lighting | Backup | CCHP ENERGY AUDITS Increasing efficiency and decreasing costs
  • 2. 22 • www.distributedenergy.com I t’s difficult to imagine a business to which backup power is more critical than Profitability.net, a Cincinnati, OH-based provider of private data center space, hosted applications, cloud computing capacity, and network storage. Redundant security is a major element of how the firm defines itself, both in terms of clients’ data and equipment, and the power supply to the equipment. Any unauthorized personnel attempting to access an infra- structure cabinet would run into five layers of security; the cabinets themselves are electronically secure and provide 24/7 notification of unauthorized attempts at access. The company, which was founded in 2002, also uses a redundant flywheel UPS system to prevent outages from compromising data cen- ter cooling infrastructure and, thus, data security. Aaron Larkins, Profitability.net’s president and CEO, says that UPS redundancy has always been considered mandatory at the company’s 23,000-square-foot facility, which can be expanded by 12,000 additional square feet. Until late 2008, two separate battery-based systems had been used as a redundant UPS for the company’s single generator. “We have public company clients, medical groups, and large manufacturing multi-site companies that rely on our data center to access their business applications,” says Larkins.“So we made a decision that we would have a primary and redun- dant power source from the UPS forward to ensure that no matter what happens in that primary line, whether it’s a fatal problem with the UPS, or the power distribution unit [PDU], or the circuit breakers that are feeding individual branch cir- cuits, the customer has a secondary source of power.” In late 2008, the company had a CleanSource UPS from Active Power installed for the redundant system, and then added a second unit for the primary system a little less than a year later, replacing battery UPS systems that had reached the end of their service lives. Profitability.net’s experience demonstrates the choices in equipment that managers at companies in a wide variety of industries have in protecting Business owners explore a wide variety of electrical equipment options and renewable energy alternatives for their backup power operations. BY DON TALEND Equipped for ActivePower Continuity their power supply. The CleanSource UPS uses a flywheel that normally spins at 7,700 rpm and stores kinetic energy. In event of a power outage, discharge energy from the flywheel provides about 15 seconds of “ride-through” power, typically a sufficient length of time for standby generators to kick in. According to the manufacturer, the system is 98% efficient. The flywheel is located between top and bottom mechanical bearings and the entire unit is enclosed in a cast-iron housing. Rather than turning on a vertical shaft, magnetic pulses turn the flywheel. The UPS steadies the kinetic energy produced by the flywheel to a 480-V, 60-Hertz output, and an automatic transfer switch transfers power from the flywheel to the standby system. Each client’s cabinet has a primary and redundant power source from the UPS forward. Each UPS feeds its own PDU that feeds the individual cabinets.
  • 3. January/February 2011 • 23 “The flywheel systems are designed to give us sufficient run time until our generators start up, which in our case, is a little less than 10 seconds in the event of a power outage or voltage drop in the grid,” says Larkins. Each system never has more than a 50% load, allowing a “bridge” of longer than 15 seconds should a power outage or voltage drop occur. “In this business, power infrastructure invest- ments are pretty substantial, and you have to take the long view on what your costs of operation are going to be over time,” points out Larkins. “Our analysis in 2008 showed that energy costs were already starting to pop up, and our thought was that energy isn’t going to get any cheaper over the next 10 or 15 years, so whatever we deploy needs to be the highest-efficiency available.” Larkins adds that the new system also offers continual monitoring ca- pability. “Stored kinetic energy doesn’t lie—if you’ve got a wheel rotating at a certain rpm [revolutions per minute], you know you have a certain amount of power,” he says. The system performed as intended dur- ing a brief power outage along the down- town Cincinnati corridor shortly before 1 a.m. on July 24, 2009. The company’s monitoring systems immediately identi- fied the power issue from Duke Energy and signaled the generator power system to start. The transition occurred in less than 10 seconds. “Before [the outage], we had a confidence level that they would work, because we saw them in operation every day and we saw the consistency in how they performed,” says Larkins. He adds that the company has realized financial benefits from the new installation as well. It was possible to shut down one of two 10-ton air conditioners that were dedicated to the UPS room. Additionally, the company saves about $18,000 in the form of lower maintenance costs every year since the installation, according to Larkins. Growth Meets Modularity When Atlantic.net, an Orlando, FL-based provider of busi- ness data services such as server colocation, dedicated serv- ers, data backup, security, and private networks looked at the impact of future growth on its 25,000-square foot facility, it was clear that growth, reliable power, and sustainability did not have to be mutually exclusive. In 2003, the company built the facility—which is fully steel reinforced and meets Category 5 hurricane require- ments—and had two Eaton 9315 battery-powered UPS units rated at 225–750 kVA installed. By 2007, the 9315s had reached capacity and the company began looking to expand its UPS capacity. Minimizing energy consumption and costs were a major consideration, however. “We have global customers, so just because we’re in the Eastern time zone, that doesn’t mean that when we go home, Client demands, infrastructure adjustments, and an overall desire to minimize energy consumption led Atlantic.net to expand its UPS capacity. Photosthispage:Eaton
  • 4. 24 • www.distributedenergy.com our clients stop working,” points out Brett Haines, operations manager for Atlantic.net, which was founded in 1994.“We need to have 100% uptime—that’s something that we have to guarantee to our customers and we have to provide it. A UPS helps us to guarantee 100% uptime,” he says, adding that the company serves several industries in which data is criti- cal, such as travel and medical, and small com- panies to multimillion-dollar corporations. Haines acknowledges that Atlantic.net is served well by its power supplier, Progress Energy, which routinely conducts line tests and trims trees located near wires. Normally, problems only occur with the power sup- ply as a result of human mishaps, he adds. Regardless, the company employs a 2-MW Caterpillar generator for standby power and management recognizes the importance of a foolproof power supply. But like nearly everyone, management also recognized the fact that energy costs had been steadily ticking upward during the past decade. Clients were making infrastructure adjustments to try and keep up. The company responded to the demand by opting for new high-efficiency, modular Eaton BladeUPS systems for the server racks. “More and more, our clients have been virtualizing the components that they use— they’re going from more servers down to a few,” says Haines. “As more clients come in and use our space, the virtualization helps because it reduces our power needs, but as more clients come in, we need more power. In those fewer servers, they’re using more energy and they’re also putting out more heat, so we try to minimize our heat load on the floor as much as possible, and the BladeUPS help because they’re more efficient.” The BladeUPS system is a three-phase, rack-based UPS system new three-phase system designed primarily for mod- ularity. According to the manufacturer, users can expand their UPS capacity from 12 kW to 60 kW in a 19-inch enclo- sure by adding from one to six parallel BladeUPS modules to create redundancy. The units reportedly provide up to 34 minutes of run time and are 98% efficient. As of early fall 2010, Atlantic.net had installed nine BladeUPS racks and a total of 50 modules, in addition to the two Eaton 9315s still in service. Haines reports that bridges typically last 15 seconds with a maximum of 29 seconds, not that it has been put to use very often. One time, a car had struck a power pole and an Left: Flywheel- based UPS recently installed by Profitability.net Right: The Beth Israel Deaconess Medical Center and Ty Dell recently imple- mented flywheel UPS systems to help protect two data centers against power outages. entire grid section was shut down, according to Haines. The UPS bridged the outage for 20 sec- onds, and the generator ran for two hours with no adverse impact on clients’ equipment. The modularity of the new UPS system suits cloud computing, an Atlantic.net capabil- ity. “As more clients come, we’re going to need more computers online for our new cloud product,” says Haines. “The way we can do that with our UPSs is to put in redundant UPS systems. What we did was put two BladeUPS modules into each rack so now, in case one component fails or a battery isn’t up to par, we have those in place. “As you increase the load, UPSs become more efficient and you don’t want to have large 400- or 500-KVa modules sitting there with 10% load—that’s not very efficient.” He adds that the BladeUPS modules operate at 40% for “fail-over” capability. Medical Facility Goes Green With Flywheels Beth Israel Deaconess Medical Center (BIDMC) in Boston, MA, a 550-bed adult medical-surgical teaching hospital affiliated with Harvard Medical School, recently estab- lished a goal to increase green purchasing by 15% by Fiscal Year 2012. A major element of this initiative is the selection of “clean energy” flywheel systems to help protect the BIDMC’s two data centers against power outages. The main 7,000 square-foot Renaissance Data Center is located 1.5 miles from BIDMC’s hospital cam- pus and the separate Span Data Center 3,000-square-foot disaster recovery data center is housed at the main campus. These data centers provide critical clinical support to the facility’s medical records, pharmacy, laboratory, chemother- apy suite, and operating rooms. The UPSs protecting the servers, switches, routers, data storage devices, and PDUs utilize flywheel systems from Vycon. The Span Data Center contains a standalone 225-kVA ActivePower Vycon OnStat Power Systems’ Silent Sentry could be described as a self-contained UPS for various non-life-threatening surgical procedures. SilentSentry
  • 5. January/February 2011 • 25 UPS that uses two Vycon flywheels rated at 275 kVA for 11.7 seconds. A 200-kW computer load provides 15 seconds of run time on the flywheel before the generator starts. The BIDMC staff is in the process of making this facility’s electrical and cooling systems as redundant as those in the Renaissance Data Center. The latter facility receives power from the utility vault through four automatic transfer switches (ATSs) that switch to a generator during a pro- longed power event. The cooling system and computer load are supported by two sets of redundant ATSs; if either one loses an ATS, the data center remains operational. Two sets of Vycon VDC flywheels to back up the two parallel 225kVA UPSs. According to Ty Dell, data center plant manager for information systems, during a power outage the facility obtains 30 seconds of flywheel runtime at 400 kW of computer load before the generator starts up. Dell points out that this is plenty of time, as the generator must come online within 10 seconds in order to meet the National Fire Protec- tion Association’s NFPA 99 regulations for Emergency Power Systems; the Joint Commission on Accreditation of Health- “Stored kinetic energy doesn’t lie—if you’ve got a wheel rotating at a certain rpm, you know you have a certain amount of power.” Ecommerce Inc. had two Generac 500-kW MPS Diesel generators installed for standby power for its data center. Generac
  • 6. 26 • www.distributedenergy.com care Organizations (JCAHO) requires that the generator must come online within 12 seconds. The flywheels have a maximum energy storage of 3,000 kW per second at 100 kW and a rotational speed of 18,500 to 36,000 rpm. For the short term, management is opting to use batteries and the flywheel systems in tandem. Dell reports that the staff is currently evaluating whether to eliminate the batteries, noting that a rapid flywheel recharge time of less than 150 seconds provides reliability and that the flywheels do not require special cooling. Redundancy in Standby Generators Redundancy is often a high priority for standby generators, too. That was definitely the case for Columbus, OH-based Ecommerce Inc., a company founded in late 1999 that houses nearly half a million Web sites or nearly half of 1% of the Internet. In fall 2007, the firm was constructing a new data center in Columbus and was selecting a backup power solution and needed a scalable system to address future growth in the climate-controlled facility that would soon be filled with industrial-grade servers. One option was a single 2-MW generator and transfer switch with no redundancy, a solution that would have taken nearly a year to install. Rick Gideon, vice president of operations for Ecom- merce Inc., was introduced to an alternative redundant solution by chance. The company and Columbus-based Generator Systems Inc. (GSI) had the same real estate agent, which is how Gideon was introduced to GSI. He met with Brian Kennedy, vice president, sales and marketing for GSI, who recommended the Generac Modular Power System (MPS) for protecting Ecommerce, Inc.’s 10,000 1U server room. Rather than installing 2-MW gensets immediately, the company had two Generac 500-kW MPS Diesel generators installed that are providing 100% redundancy at a lower cost. Enough space is available to add three more 500-kW MPS Diesel units to allow for future growth within the facility. A Different Kind of Medical Backup Power Cardiac Equipment Services, Nassau County, NY, provides slightly different medical backup power systems that could be described as self-contained UPSs. The company is owned by Charlie Bergin, who has worked in the biomedical engi- neering field for 25 years—the past 15 as a provider of med- ical power backup systems. He often recommends one of two systems—OnStat Power Systems’ Reassurance or Silent Sentry—for office-based surgical centers. The Reassurance product, developed by Medi+Products in the early 1990s, is a fully enclosed, stainless steel, cabinet Counterclockwise from left: Norfolk Naval Air Station, Norfolk, VA, “tower” and walking surface Bottom right: County Juvi Prison, San Bernardino, CA. (Note the large exhaust particulate filter on top.) GenSysSupport
  • 7. January/February 2011 • 27 use in equipment such as standby generators. In 1988, the US Environmental Protection Agency (EPA) mandated that underground storage tank (UST) owners comply with new standards for corrosion resistance, leak detection, and spill- age and overfill protection by the end of 1998. This regulatory development has created a market for related equipment: AST platforms. Larry Hill, CEO of Col- lierville, TN-based Generator System Support (GSS) and engineering manager at Thompson Power Corp. in Memphis, TN, points out that the proliferation of ASTs has meant that gensets are sometimes located too high for proper service and maintenance. GSS constructs aluminum service platforms that allow access to two sides and one end of gensets. The platforms use 0.125-inch aluminum tread plate mate- rial that is bolted together in the field. Platforms in the stan- dard configuration do not touch the concrete pad; they have a cantilever design that uses the fuel tank base as the supporting member. The platform usually is located 36–48 inches above the concrete pad. DE Don Talend is a frequent contributor to Distributed Energy and specializes in covering technology and innovation. system on a castor base. The top surface has a 30-inch height and the unit is equipped with front panel outlets. The Silent Sentry is a static subpanel designed for mini- mal impact on interior design. The unit provides 2,000, 2500, or 3,000 W and 4 kWh of stored energy, and is based on 12-V battery banks with built-in UL-489 branch-circuit protectors for distributed loads. It can be inset into a wall cavity between wall studs and has a protrusion of as little as 4½ inches. The unit integrates branch-circuit interrupters into the system it- self, making the battery-powered generator an uninterruptible subpanel, eliminating the need for an emergency subpanel. The two units have several common features, including five-stage battery recharging, a recharger with four-stage automatic recharging and manual equalization, battery monitoring, an optional charge/discharge monitoring sys- tem for tracking energy in and out of the battery bank, and split-phase output. Surgeons can plug their powered surgical equipment into these units to maintain procedural continuity. Bergin points out that the units are designed for procedures that are not life-threatening, such as gastroenterology and plastic surgery. “Many doctors are fearful,” says Bergin.“When the power goes out, they don’t know how long it’s going to be—they just want enough time to close and get out. They may not finish the procedure. It depends on where they are in the procedure—if it happens right at the beginning, they might just close up and have the patient come back.” Still, JCAHO mandates two hours of standby power. Gastroenterologists power equipment such as vital sign moni- tors and O2 concentrators, and plastic surgeons need to wire entire operating rooms because they use general anesthesia. “All of the procedures are elective, and all are outpatient,” says Bergin.“It’s not like they need hospital-based generators, which are diesel-based and located outside the building.” Bergin indicates that a market for standby power for non-life-threatening medical procedures has been steadily growing in recent years.“Today, most outpatient surgery can be done in an ambulatory environment outside of the hospi- tal,” he says.“It’s happening more and more where there are a lot more facilities opening that do opening types of surgery, from orthopedics to OB-Gyn.” Service Platforms for Raised Tanks Recent federal regulations have created a new market for aboveground storage tanks (ASTs) for fuel that is stored for Online extras www.distributedenergy.com/backup Uninterrupted savings! A market for standby power for non-life- threatening medical procedures has been steadily growing in recent years.