Latest Developments in Data Centre
Energy and Power Issues

Bill St. Arnaud
Bill.st.arnaud@gmail.com
Theme of this talk
• Electrical energy cost and its reliability are
increasingly the two biggest concerns for most
data center operators
• This talk will focus on the latest developments on
alternate energy sources and power reliability for
data centers
• But consideration of power issues and reliability
also impacts data and network architecture of
data center
2
Cost of power for data centers
•

•
•

Power consumption is jumping astronomically
– 19% last year, 15% this year
Electrical cost also increasing significantly
– E.g 30% in Ontario
Within next 5 – 10 years we will have carbon tax
or cap and trade
– Will raise prices another 5-20%

3
Growth Projections Data Centers
• Half of ICT consumption is data centers
• In ten years 50% of today’s Data Centers and major
science facilities in the US will have insufficient power
and cooling;*
• CO2 emissions from US datacenters greater than all
CO2 emissions from Netherlands or Argentina
http://bit.ly/cW6jEY
• Data center electricity is 31GW globally, and that will
increase 19 percent in 2012 http://dlvr.it/1RwhWG

*Source: Gartner; Meeting the DC power and cooling challenge
Reliability of the Grid
•

Weather related outages and duration have
increased significantly

•

Other threats include :
– Geo-magnetic solar storms
– EMP and RF weapons used by terrorists

•

Easy to protect data center from such events,
but much harder to protect electrical grid
infrastructure

•

Particular vulnerability is Large Power
Transformers (LPTs), which are customdesigned, expensive to replace and hard to
transport.
– LPTs weight between 100 and 400 tons, cost
millions of dollars and can take as long as 20
months to manufacture

5
Scary reading
• “US Energy sector vulnerabilities to climate change and extreme
weather” US Department of Energy July 2013
– http://energy.gov/sites/prod/files/2013/07/f2/20130716Energy%20Sector%20Vulnerabilities%20Report.pdf
•

•

Recent Sample outages

Rising water temps forcing power
plant shutdowns
Coal and nuclear power generating
capacity will decrease by between
4 and 16 percent in the United
States and a 6 to 19 percent
decline in Europe due to lack of
cooling water.
• http://www.reuters.com/artic
le/2012/06/04/climate-waterenergyidUSL3E8H41SO20120604
6
Half of US experienced record
droughts or deluges in 2012
2010 warmest year ever – we
are only at the start of the
curve of the hockey stick. The
worst is yet to come
Blame it on Canada
How warming in the Arctic affects weather in Texas and Europe
• Warming Arctic slowing down jet stream
– There’s been a 20 percent drop in the zonal
wind speeds.

• As get stream slows down, it leads to those
bigger, long lived kinks in the jet stream.
– That amplification is associated with
persistent weather patterns that lead to
“extremes” like drought, flooding and heat
waves.

• Those slow-moving, persistent waves of
weather energy may have played a role in the
big snows that hammered Europe this
winters, as well as the extreme drought that
hit South West US
• http://summitcountyvoice.com/2012/01/14/
global-warming-revenge-of-the-atmosphere/
8
Future Droughts
• Palmer Drought Severity Index,
or PDSI.
• The most severe drought in
recent history, in the Sahel region
of western Africa in the 1970s, had
a PDSI of -3 or -4.

• By 2030 Western USA could see
-4 to -6. Drought in Texas clearly
caused by global warming:
http://goo.gl/QjHRS

• By 2100 some parts of the U.S.
and Latin America could see -8 to 10 PDSI, while Mediterranean
areas could see drought in the -15
or -20 range.

http://www.msnbc.msn.com/id/39741525/ns/us_new
s-environment/
Dramatic changes in precipitation

•
•

•

Every continent has suffered record rainfalls
Rains submerged one-fifth of Pakistan, a
thousand-year deluge swamped Nashville and
storms just north of Rio caused the deadliest
landslides Brazil has ever seen.
Observed increase in precipitation in the last few
decades has been due in large part to a
disproportionate increase in heavy and extreme
precipitation rates which are exceeding
predictions made in models
What does 1C average temperature
mean?
• In the 1700s – when global average
temperature was .8C colder than now,
New Yorkers could walk from
Manhattan to Staten Island on ice as
thick as 8 feet
– http://green.blogs.nytimes.com/2012/01/31
/in-the-little-ice-age-lessons-for-today/

11
What is the solution for DC operator?
Reduce dependency on electrical grid as much as possible:
1.

Develop Climate Change Preparedness plan as per President
Obama’s Executive Order

2.

Make sure your diesel generator is properly installed and serviced

3.

Get independent source of electrical power from your own dams,
windmills or solar panel array

4.

Use natural gas or bio-gas to generate electricity through microturbines, cogen or fuel cells

5.

Build highly distributed data centers using following the wind or
follow the sun architectures
12
President Obama’s Executive Order on
Climate Change Preparedness
• All US government departments, agencies, data centers, etc must develop
climate change preparedness plans
• States, municipalities, universities and other institutions are also
encouraged to develop similar plans

• Disaster preparedness plans must cover range of scenarios of severe
flooding, droughts, hurricanes, long term power outages, etc
• DC operators must look at number of scenarios that could significantly
impact operations

Presentation title
Lessons from Sandy about backup
diesels
•

Make sure fuel is changed every year
– Diesel fuel deteriorates much faster than gasoline

•

Arrange for long term, high priority fuel contracts from
a number of refineries

•

Make sure IT staff know how to change fuel and air
filters

•

Make sure fuel pumps are self priming, collocated with
diesel and connected to UPS

•

Make sure all electrical cabling, transformers and
switch gear are in water tight compartments
– Double check all egress and ingress ports through
walls

14
Many DCs are acquiring their own
power dams
•

OVH in Montreal - worlds largest data center
operator

•

Cisco, EMC in Holyoke, MA

•

Google in Finland

•

There are many abandoned paper mills,
aluminum smelters, etc in Canada with their
own power dams

•

Some DCs are looking to deploy “run of the
river” generating systems that require no dams
Many other examples

Ecotricity in UK builds windmills at
data center locations with no capital
cost to user
Hydro-electric powered data centers

ASIO solar powered data centers
17
Fuel Cells, Microturbines, Cogen
• Several data centers being built independent of
electrical grid using natural gas
• Converting gas to electricity can be done with
micro turbines, fuel cells or traditional cogen
• Cost of electricity from gas much cheaper than
from grid
– Can sell excess power to the grid
– Standby propone tank in case of disruption in gas
feed
– Power distribution system can be sized as demand
warrants from growth in data center

• In Europe and US several data centers are using
biogas from farm or human waste
17
Follow the Sun/Wind Distributed Data
Center

GreenStar Network
World’s First Zero Carbon Cloud/Internet
SDN Follow the wind/Follow the sun
European GSN
Domain

Canadian GSN
Domain
Export VM

Notify EU
Cloud Manager

Cloud Manager

Host
Resource

Network
Manager

Cloud Manager

Internet
Dynamically Configure
IP Tunnel

Host
Resource

• Shudown VM
• Copy Image

• Update VM Context
• Start VM

Mantychore2
VM

Shared
storage

Shared
storage

VM

Lightpath
Host

Cloud Proxy

Optical switch

Optical switch
Cloud Proxy

Host
Hewlett Packard & Clarkson U
GreenCloud
• Optimizing the utilization of the available
renewable power for computing by intelligently
redistributing computational load;
• Minimizing losses associated with power
transmission by placing the PODs near the power
source;
• Providing energy and design efficiency through
the use of additional passive cooling for the PODs
• Use the wind power that is currently stranded, i.e.
not-delivered to the grid due to the T&D constraints.
IBM National GreenCloud Vision
Don’t forget the wide area network
• Network is just as vulnerable as data center to reliability in electrical
grid
• Most telco based networks have multiple electrical powered
repeater huts for amplification and add/drop
– Usually in remote locations and more difficult to service, or re-fuel
generators

• Most DC operators are choosing dark fiber for reliability reasons
– Modern dark fiber networks can operate at distances up to 1500km
without a single electrical repeater
– Optical repeaters only draw 40W power and can easily be powered
with batteries and solar charging
– Architecture is far simpler than telco network and thus easier to
manage and upgrade
22
Let’s Keep The Conversation Going
Bill St. Arnaud is a R&E Network and Green IT
consultant who works with clients on a variety
of subjects such as green data centers and
networks. He also works with clients to
develop practical solutions to reduce GHG
emissions from ICT (See http://greenbroadband.blogspot.com/) .

E-mail
Bill.St.Arnaud@gmail.com

Blogs
http://green-broadband.blogspot.com

Twitter
http://twitter.com/BillStArnaud

More Related Content

PPTX
University climate change preparedness
PPTX
Surf utrecht nov 10
PPT
Lead To Win May 18
PPT
IBM Science Meeting
PPT
OCRI Cleantech
PPTX
China green it
PPT
Boston Optical Fiber East May 10
PPT
Stanford Synchrotron
University climate change preparedness
Surf utrecht nov 10
Lead To Win May 18
IBM Science Meeting
OCRI Cleantech
China green it
Boston Optical Fiber East May 10
Stanford Synchrotron

What's hot (20)

PPT
JISC April 10
PDF
NREN strategies for Data-Intensive Science in a Carbon Constrained World
PPT
Ottawa Foresight May 14
PPT
OGF Panel Presentation
PPTX
NREN climate change preparedness
PPTX
TNC 2014 nren climate change preparedness
PDF
Top Ten Renewable Energy Market Drivers020409
PPT
Ottawa U - Deploying 5G networks
PPTX
GLIF geneva
PPTX
Green it case western mar 28 2011
PPT
SURA Meeting Washington
PPTX
Green it overview jan 6 2011
PPTX
Analysis of Community Microgrids: The path to resilient and sustainable commu...
PPT
Gsn Retreat Feb 8
PDF
Aging Power Infrastucture in the US: Towards a Solution
PPT
CENIC Green IT
PPTX
Ocri technology and business opportunities in green it in
PPT
Government CIO and Climate Change
PPT
IT Benefits of Climate Change to Canada
PPT
Digital Infrastructure in a Carbon Constrained World
JISC April 10
NREN strategies for Data-Intensive Science in a Carbon Constrained World
Ottawa Foresight May 14
OGF Panel Presentation
NREN climate change preparedness
TNC 2014 nren climate change preparedness
Top Ten Renewable Energy Market Drivers020409
Ottawa U - Deploying 5G networks
GLIF geneva
Green it case western mar 28 2011
SURA Meeting Washington
Green it overview jan 6 2011
Analysis of Community Microgrids: The path to resilient and sustainable commu...
Gsn Retreat Feb 8
Aging Power Infrastucture in the US: Towards a Solution
CENIC Green IT
Ocri technology and business opportunities in green it in
Government CIO and Climate Change
IT Benefits of Climate Change to Canada
Digital Infrastructure in a Carbon Constrained World
Ad

Viewers also liked (13)

PDF
Android exploiting ubiquitous data collection for mobile users in wireless s...
PPTX
PPT
Climate Check Canarie Workshop March4
PPT
NYSERnet july 28
PPTX
The Future of R&E networks and cyber-infrastructure
PPT
Jerry Sheehan Green Canarie
PPT
Canadian Telecom Summit
PPT
Climate Check Canarie Workshop March4
PPT
Victor Rejiis Manticore Vr 03
PPTX
Dynamic charging (on the move) of
PPT
Prompt Charles Despins
PPTX
Victries japan
PPTX
Building an Energy Internet as an alternative renewable power distribution sy...
Android exploiting ubiquitous data collection for mobile users in wireless s...
Climate Check Canarie Workshop March4
NYSERnet july 28
The Future of R&E networks and cyber-infrastructure
Jerry Sheehan Green Canarie
Canadian Telecom Summit
Climate Check Canarie Workshop March4
Victor Rejiis Manticore Vr 03
Dynamic charging (on the move) of
Prompt Charles Despins
Victries japan
Building an Energy Internet as an alternative renewable power distribution sy...
Ad

Similar to Future challenges for data centers (18)

PPTX
Week 8 -The Future of Renewable Energy Systems in Ontario.pptx
DOCX
1115161Wind Power Now, Tomorrow C.P. (Case) .docx
PPT
Building A Zero Carbon Internet
PPT
energy applications of process control.ppt
PPT
pptnew.ppt
PPTX
Joint techs keynote january
PPTX
ِAdvanced Nuclear Energy
PDF
IDRIM Conference 2016
PPTX
Surfnet utrecht
PPTX
Energy
PPT
Canarie Green It Presentation
PPT
PPTX
Okanagan
PPT
Cips Edmonton
PDF
The Growing Interdependence of the Internet and Climate Change
PDF
Securing Australia's Energy Future: The Challenge - Simon Gamble, Hydro Tasmania
PDF
Data Center Market and Technology Trends Power Electronics presentation held ...
Week 8 -The Future of Renewable Energy Systems in Ontario.pptx
1115161Wind Power Now, Tomorrow C.P. (Case) .docx
Building A Zero Carbon Internet
energy applications of process control.ppt
pptnew.ppt
Joint techs keynote january
ِAdvanced Nuclear Energy
IDRIM Conference 2016
Surfnet utrecht
Energy
Canarie Green It Presentation
Okanagan
Cips Edmonton
The Growing Interdependence of the Internet and Climate Change
Securing Australia's Energy Future: The Challenge - Simon Gamble, Hydro Tasmania
Data Center Market and Technology Trends Power Electronics presentation held ...

More from Bill St. Arnaud (11)

PPTX
Energy internet
PPTX
Green bond fund opportunities for NRENs and universities 2016
PPTX
Internet climate adaptation and preparednessstrategy
PPTX
Dynamic charging latest developments
PPTX
Okanagan
PPTX
TICAL 2011 green it
PPTX
Cisco green tnc
PPTX
On vector looking forward
PDF
20110302 on vector green datacenters
PPT
Overview carbonaccountingprotocol v1
PPT
NRC july 6
Energy internet
Green bond fund opportunities for NRENs and universities 2016
Internet climate adaptation and preparednessstrategy
Dynamic charging latest developments
Okanagan
TICAL 2011 green it
Cisco green tnc
On vector looking forward
20110302 on vector green datacenters
Overview carbonaccountingprotocol v1
NRC july 6

Recently uploaded (20)

PDF
Training And Development of Employee .pdf
PDF
Nidhal Samdaie CV - International Business Consultant
PDF
Types of control:Qualitative vs Quantitative
PDF
Outsourced Audit & Assurance in USA Why Globus Finanza is Your Trusted Choice
PPTX
CkgxkgxydkydyldylydlydyldlyddolydyoyyU2.pptx
PDF
MSPs in 10 Words - Created by US MSP Network
PDF
Elevate Cleaning Efficiency Using Tallfly Hair Remover Roller Factory Expertise
PDF
How to Get Funding for Your Trucking Business
PPTX
Dragon_Fruit_Cultivation_in Nepal ppt.pptx
PPT
Chapter four Project-Preparation material
PPTX
ICG2025_ICG 6th steering committee 30-8-24.pptx
PDF
Reconciliation AND MEMORANDUM RECONCILATION
PDF
kom-180-proposal-for-a-directive-amending-directive-2014-45-eu-and-directive-...
PDF
Ôn tập tiếng anh trong kinh doanh nâng cao
DOCX
unit 1 COST ACCOUNTING AND COST SHEET
PDF
WRN_Investor_Presentation_August 2025.pdf
PPTX
AI-assistance in Knowledge Collection and Curation supporting Safe and Sustai...
PDF
COST SHEET- Tender and Quotation unit 2.pdf
PDF
Power and position in leadershipDOC-20250808-WA0011..pdf
PDF
BsN 7th Sem Course GridNNNNNNNN CCN.pdf
Training And Development of Employee .pdf
Nidhal Samdaie CV - International Business Consultant
Types of control:Qualitative vs Quantitative
Outsourced Audit & Assurance in USA Why Globus Finanza is Your Trusted Choice
CkgxkgxydkydyldylydlydyldlyddolydyoyyU2.pptx
MSPs in 10 Words - Created by US MSP Network
Elevate Cleaning Efficiency Using Tallfly Hair Remover Roller Factory Expertise
How to Get Funding for Your Trucking Business
Dragon_Fruit_Cultivation_in Nepal ppt.pptx
Chapter four Project-Preparation material
ICG2025_ICG 6th steering committee 30-8-24.pptx
Reconciliation AND MEMORANDUM RECONCILATION
kom-180-proposal-for-a-directive-amending-directive-2014-45-eu-and-directive-...
Ôn tập tiếng anh trong kinh doanh nâng cao
unit 1 COST ACCOUNTING AND COST SHEET
WRN_Investor_Presentation_August 2025.pdf
AI-assistance in Knowledge Collection and Curation supporting Safe and Sustai...
COST SHEET- Tender and Quotation unit 2.pdf
Power and position in leadershipDOC-20250808-WA0011..pdf
BsN 7th Sem Course GridNNNNNNNN CCN.pdf

Future challenges for data centers

  • 1. Latest Developments in Data Centre Energy and Power Issues Bill St. Arnaud Bill.st.arnaud@gmail.com
  • 2. Theme of this talk • Electrical energy cost and its reliability are increasingly the two biggest concerns for most data center operators • This talk will focus on the latest developments on alternate energy sources and power reliability for data centers • But consideration of power issues and reliability also impacts data and network architecture of data center 2
  • 3. Cost of power for data centers • • • Power consumption is jumping astronomically – 19% last year, 15% this year Electrical cost also increasing significantly – E.g 30% in Ontario Within next 5 – 10 years we will have carbon tax or cap and trade – Will raise prices another 5-20% 3
  • 4. Growth Projections Data Centers • Half of ICT consumption is data centers • In ten years 50% of today’s Data Centers and major science facilities in the US will have insufficient power and cooling;* • CO2 emissions from US datacenters greater than all CO2 emissions from Netherlands or Argentina http://bit.ly/cW6jEY • Data center electricity is 31GW globally, and that will increase 19 percent in 2012 http://dlvr.it/1RwhWG *Source: Gartner; Meeting the DC power and cooling challenge
  • 5. Reliability of the Grid • Weather related outages and duration have increased significantly • Other threats include : – Geo-magnetic solar storms – EMP and RF weapons used by terrorists • Easy to protect data center from such events, but much harder to protect electrical grid infrastructure • Particular vulnerability is Large Power Transformers (LPTs), which are customdesigned, expensive to replace and hard to transport. – LPTs weight between 100 and 400 tons, cost millions of dollars and can take as long as 20 months to manufacture 5
  • 6. Scary reading • “US Energy sector vulnerabilities to climate change and extreme weather” US Department of Energy July 2013 – http://energy.gov/sites/prod/files/2013/07/f2/20130716Energy%20Sector%20Vulnerabilities%20Report.pdf • • Recent Sample outages Rising water temps forcing power plant shutdowns Coal and nuclear power generating capacity will decrease by between 4 and 16 percent in the United States and a 6 to 19 percent decline in Europe due to lack of cooling water. • http://www.reuters.com/artic le/2012/06/04/climate-waterenergyidUSL3E8H41SO20120604 6
  • 7. Half of US experienced record droughts or deluges in 2012 2010 warmest year ever – we are only at the start of the curve of the hockey stick. The worst is yet to come
  • 8. Blame it on Canada How warming in the Arctic affects weather in Texas and Europe • Warming Arctic slowing down jet stream – There’s been a 20 percent drop in the zonal wind speeds. • As get stream slows down, it leads to those bigger, long lived kinks in the jet stream. – That amplification is associated with persistent weather patterns that lead to “extremes” like drought, flooding and heat waves. • Those slow-moving, persistent waves of weather energy may have played a role in the big snows that hammered Europe this winters, as well as the extreme drought that hit South West US • http://summitcountyvoice.com/2012/01/14/ global-warming-revenge-of-the-atmosphere/ 8
  • 9. Future Droughts • Palmer Drought Severity Index, or PDSI. • The most severe drought in recent history, in the Sahel region of western Africa in the 1970s, had a PDSI of -3 or -4. • By 2030 Western USA could see -4 to -6. Drought in Texas clearly caused by global warming: http://goo.gl/QjHRS • By 2100 some parts of the U.S. and Latin America could see -8 to 10 PDSI, while Mediterranean areas could see drought in the -15 or -20 range. http://www.msnbc.msn.com/id/39741525/ns/us_new s-environment/
  • 10. Dramatic changes in precipitation • • • Every continent has suffered record rainfalls Rains submerged one-fifth of Pakistan, a thousand-year deluge swamped Nashville and storms just north of Rio caused the deadliest landslides Brazil has ever seen. Observed increase in precipitation in the last few decades has been due in large part to a disproportionate increase in heavy and extreme precipitation rates which are exceeding predictions made in models
  • 11. What does 1C average temperature mean? • In the 1700s – when global average temperature was .8C colder than now, New Yorkers could walk from Manhattan to Staten Island on ice as thick as 8 feet – http://green.blogs.nytimes.com/2012/01/31 /in-the-little-ice-age-lessons-for-today/ 11
  • 12. What is the solution for DC operator? Reduce dependency on electrical grid as much as possible: 1. Develop Climate Change Preparedness plan as per President Obama’s Executive Order 2. Make sure your diesel generator is properly installed and serviced 3. Get independent source of electrical power from your own dams, windmills or solar panel array 4. Use natural gas or bio-gas to generate electricity through microturbines, cogen or fuel cells 5. Build highly distributed data centers using following the wind or follow the sun architectures 12
  • 13. President Obama’s Executive Order on Climate Change Preparedness • All US government departments, agencies, data centers, etc must develop climate change preparedness plans • States, municipalities, universities and other institutions are also encouraged to develop similar plans • Disaster preparedness plans must cover range of scenarios of severe flooding, droughts, hurricanes, long term power outages, etc • DC operators must look at number of scenarios that could significantly impact operations Presentation title
  • 14. Lessons from Sandy about backup diesels • Make sure fuel is changed every year – Diesel fuel deteriorates much faster than gasoline • Arrange for long term, high priority fuel contracts from a number of refineries • Make sure IT staff know how to change fuel and air filters • Make sure fuel pumps are self priming, collocated with diesel and connected to UPS • Make sure all electrical cabling, transformers and switch gear are in water tight compartments – Double check all egress and ingress ports through walls 14
  • 15. Many DCs are acquiring their own power dams • OVH in Montreal - worlds largest data center operator • Cisco, EMC in Holyoke, MA • Google in Finland • There are many abandoned paper mills, aluminum smelters, etc in Canada with their own power dams • Some DCs are looking to deploy “run of the river” generating systems that require no dams
  • 16. Many other examples Ecotricity in UK builds windmills at data center locations with no capital cost to user Hydro-electric powered data centers ASIO solar powered data centers 17
  • 17. Fuel Cells, Microturbines, Cogen • Several data centers being built independent of electrical grid using natural gas • Converting gas to electricity can be done with micro turbines, fuel cells or traditional cogen • Cost of electricity from gas much cheaper than from grid – Can sell excess power to the grid – Standby propone tank in case of disruption in gas feed – Power distribution system can be sized as demand warrants from growth in data center • In Europe and US several data centers are using biogas from farm or human waste 17
  • 18. Follow the Sun/Wind Distributed Data Center GreenStar Network World’s First Zero Carbon Cloud/Internet
  • 19. SDN Follow the wind/Follow the sun European GSN Domain Canadian GSN Domain Export VM Notify EU Cloud Manager Cloud Manager Host Resource Network Manager Cloud Manager Internet Dynamically Configure IP Tunnel Host Resource • Shudown VM • Copy Image • Update VM Context • Start VM Mantychore2 VM Shared storage Shared storage VM Lightpath Host Cloud Proxy Optical switch Optical switch Cloud Proxy Host
  • 20. Hewlett Packard & Clarkson U GreenCloud • Optimizing the utilization of the available renewable power for computing by intelligently redistributing computational load; • Minimizing losses associated with power transmission by placing the PODs near the power source; • Providing energy and design efficiency through the use of additional passive cooling for the PODs • Use the wind power that is currently stranded, i.e. not-delivered to the grid due to the T&D constraints.
  • 22. Don’t forget the wide area network • Network is just as vulnerable as data center to reliability in electrical grid • Most telco based networks have multiple electrical powered repeater huts for amplification and add/drop – Usually in remote locations and more difficult to service, or re-fuel generators • Most DC operators are choosing dark fiber for reliability reasons – Modern dark fiber networks can operate at distances up to 1500km without a single electrical repeater – Optical repeaters only draw 40W power and can easily be powered with batteries and solar charging – Architecture is far simpler than telco network and thus easier to manage and upgrade 22
  • 23. Let’s Keep The Conversation Going Bill St. Arnaud is a R&E Network and Green IT consultant who works with clients on a variety of subjects such as green data centers and networks. He also works with clients to develop practical solutions to reduce GHG emissions from ICT (See http://greenbroadband.blogspot.com/) . E-mail Bill.St.Arnaud@gmail.com Blogs http://green-broadband.blogspot.com Twitter http://twitter.com/BillStArnaud

Editor's Notes

  • #16: Building a zero carbon ICT infrastructurePurchasing green power locally is expensive with significant transmission line lossesDemand for green power within cities expected to grow dramaticallyICT facilities DON’T NEED TO BE LOCATED IN CITIES-Cooling also a major problem in citiesBut most renewable energy sites are very remote and impractical to connect to electrical grid. Can be easily reached by an optical network Provide independence from electrical utility and high costs in wheeling power Savings in transmission line losses (up to 15%) alone, plus carbon offsets can pay for moving ICT facilities to renewable energy siteICT is only industry ideally suited to relocate to renewable energy sites Also ideal for business continuity in event of climate catastrophe