This document provides guidance on properly sizing condensate return units. It discusses determining the boiler load, evaporation rate, required discharge pressure, condensate return temperature, and condensate tank sizing. The key steps are to size the pump for 2-3 times the boiler's evaporation rate, account for temperature effects on NPSHA, calculate pressure drops, and provide 1 minute of net storage in the condensate tank. Sizing the unit correctly ensures efficient condensate return without cavitation or short-cycling issues.