EE 369
POWER SYSTEM ANALYSIS
Lecture 8
Transformers, Per Unit
Tom Overbye and Ross Baldick
1
Announcements
• For lectures 8 to 10 read Chapter 3.
• HW 6 is problems 5.14, 5.16, 5.19, 5.26, 5.31, 5.32,
5.33, 5.36; case study questions chapter 5 a, b, c, d,
is due Thursday, 10/6.
• Power plant tour is 10/6.
• Instead of coming to class, go to UT power plant.
Turn in homework at beginning of tour.
• Homework 7 is 5.8, 5.15, 5.17, 5.24, 5.27, 5.28,
5.29, 5.34, 5.37, 5.38, 5.43, 5.45; due 10/20.
2
Transformers Overview
• Power systems are characterized by many different
voltage levels, ranging from 765 kV down to 240/120
volts.
• Transformers are used to transfer power between
different voltage levels.
• The ability to inexpensively change voltage levels is a
key advantage of ac systems over dc systems.
• In this section we’ll development models for the
transformer and discuss various ways of connecting
three phase transformers.
3
Ideal Transformer
First we review the voltage/current relationships for an
ideal transformer
– no real power losses
– magnetic core has infinite permeability
– no leakage flux
We’ll define the “primary” side of the transformer as
the side that usually receives power from a line etc, and
the secondary as the side that usually delivers power to
a load etc:
– primary is usually the side with the higher voltage, but may
be the low voltage side on a generator step-up transformer.
4
Ideal Transformer Relationships
1
1 1 2 2
1 2
1 1 2 2
1 2 1 1
1 2 2 2
Assume we have flux in magnetic material.
Then flux linking coil 1 having turns is:
, and similarly
,
= turns ratio
m
m m
m m
m
N
N N
d d
d d
v N v N
dt dt dt dt
d v v V N
a
dt N N V N

   
 
 

 
   
    
Note that I2 and I2’
are in opposite directions
5
Current Relationships
'
1 1 2 2
'
1 1 2 2
'
1 1 2 2
To get the current relationships use ampere's law
with path around core having total length :
mmf
Assuming uniform flux density in the core
having area ,
L
d N i N i
H L N i N i
B L
N i N i
A


  
  

 
H L


'
1 1 2 2
then B A
L
N i N i
A



 

 
 6
Current/Voltage Relationships
'
1 1 2 2
'
1 2 1 2
2 2
'
1 2 1
2
1
2
1 2
1 2
If is infinite then 0 . Hence
1
or , where
1
Then: and:
0
1
0
N i N i
i N i N
i i
N i N a
i
I
I a
a
V V
I I
a
  
    

 
   
 

   
 
   
 
7
Impedance Transformation
Example
•Example: Calculate the primary voltage and current
for an impedance load Z on the secondary
2
1
2
1
2 2 / and substituting:
0
1
0
a V
V
V
I
Z
a
I V Z
   
   
  
   
  
 
 


2
1 2 1
2
1
1
1
primary referred value of
secondary load impedance
V
V aV I
a Z
V
a Z
I
 
 
8
Real Transformers
• Real transformers
– have losses
– have leakage flux
– have finite permeability of magnetic core
• Real power losses
– resistance in windings (I2
R)
– core losses due to eddy currents and hysteresis
9
Transformer Core losses
Eddy currents arise because of changing flux in core.
Eddy currents are reduced by laminating the core
Hysteresis losses are proportional to area of BH curve
and the frequency
These losses are reduced
by using material with a
“thin” BH curve
10
Effect of Leakage Flux
1 1 1 1
2 2 2 2
1 1 1 2 2
Not all flux is within the transformer core
, where is the coil 1 leakage flux,
, where is the coil 2 leakage flux,
Assuming a linear magnetic medium we get
l m l
l m l
l l l l
N
N
L i L i
   
   
 
 
 
  2
2
2
'
1
1 1 1 1 1
1
'
'
2 2 2 2 2
, including winding
resistance ,
, including resistance .
m
l
m
l
d
di
v ri L N
dt dt
r
di d
v r i L N r
dt dt


  
  
11
Effect of Finite Core Permeability
m
11 2 2 m
m 2
1 2
1 1
1 m
Finite core permeability means a non-zero mmf
is required to maintain in the core
,
where is the reluctance.
This effect is usually modeled as a magnetizing current
N i N i R
R
R N
i i
N N
N
i i



 
 
  2 m
2 m
1 1
where ,
modeled by resistance and inductance.
R
i i
N N


12
Transformer Equivalent Circuit
Using the previous relationships, we can derive an
equivalent circuit model for the real transformer
' 2 '
2 2 1 2
' 2 '
2 2 1 2
This model is further simplified by referring all
impedances to the primary side (and approximating
by swapping the referred elements and the shunts):
e
e
r a r r r r
x a x x x x
  
   13
Simplified Equivalent Circuit
14
Calculation of Model Parameters
The parameters of the model are determined
based upon:
– nameplate data: gives the rated voltages and power
– open circuit test: rated voltage is applied to primary
with secondary open; measure the primary current and
losses (the test may also be done applying the rated
voltage to the secondary, calculating the values, then
referring the values back to the primary side).
– short circuit test: with secondary shorted, apply (lower
than rated) voltage to primary to get rated primary
current to flow; measure voltage and losses. 15
Transformer Example
•Example: A single phase, 100 MVA, 200/80 kV
transformer has the following test data:
–open circuit: 20 amps, with 10 kW losses
–short circuit: 30 kV, with 500 kW losses
•Determine the model parameters.
16
Transformer Example, cont’d
2 2 2
2 2
2 2 2
rated
100MVA 30 kV
500 A, 60
200kV 500 A
500 kW / 500,000/(500) 2 ,
Hence 60 2 60
( ) (200) (kV)
4M
10 kW
sc e e
sc e sc e sc sc
e
c
oc
e
I R jX
P R I R P I
X
V
R
P
R
     
      
   
   

From the short circuit test
From the open circuit test
rated 200 kV
10,000 10,000
20 A
e m m
oc
V
jX jX X
I
      
17
Residential Distribution
Transformers
Single phase transformers are commonly used in
residential distribution systems. Most distribution
systems are 4 wire, with a multi-grounded, common
neutral.
18
Per Unit Calculations
A key problem in analyzing power systems is the large
number of transformers.
– It would be very difficult to continually have to refer
impedances to the different sides of the transformers
This problem is avoided by a normalization of all
variables.
This normalization is known as per unit analysis.
actual quantity
quantity in per unit
base value of quantity

19
Per Unit Conversion Procedure, 1
1. Pick a 1 VA base for the entire system, SB
2. Pick a voltage base for each different voltage level,
VB. Voltage bases are related by transformer turns
ratios. Voltages are line to neutral.
3. Calculate the impedance base, ZB= (VB)2
/SB
4. Calculate the current base, IB = VB/ZB
5. Convert actual values to per unit
Note, per unit conversion affects magnitudes, not
the angles. Also, per unit quantities no longer have
units (i.e., a voltage is 1.0 p.u., not 1 p.u. volts) 20
Per Unit Solution Procedure
1. Convert to per unit (p.u.) (many problems
are already in per unit)
2. Solve
3. Convert back to actual as necessary
21
Per Unit Example
Solve for the current, load voltage and load power
in the circuit shown below using per unit analysis
with an SB of 100 MVA, and voltage bases of
8 kV, 80 kV and 16 kV, respectively.
Original Circuit
22
Per Unit Example, cont’d
2 2
2 2
2 2
8 (kV)
0.64
100MVA
80 (kV)
64
100MVA
16 (kV)
2.56
100MVA
Left
B
Middle
B
Right
B
Z
Z
Z
  
  
  
Same circuit, with
values expressed
in per unit.
23
Per Unit Example, cont’d
2
*
1.0 0
0.22 30.8 p.u. (not amps)
3.91 2.327
1.0 0 0.22 30.8
p.u.
0.189 p.u.
1.0 0 0.22 30.8 30.8 p.u.
L
L
L L L
G
I
j
V
V
S V I
Z
S
 
    

       
   
  
       
24
Per Unit Example, cont’d
To convert back to actual values just multiply the
per unit values by their per unit base
Actual
Actual
Actual
Middle
Actual
Middle
0.859 30.8 16 kV 13.7 30.8 kV
0.189 0 100 MVA 18.9 0 MVA
0.22 30.8 100 MVA 22.0 30.8 MVA
100 MVA
1250 Amps
80 kV
0.22 30.8 275 30.8
L
L
G
B
V
S
S
I
I
        
      
      
 
    
    

25
Three Phase Per Unit
1. Pick a 3 VA base for the entire system,
2. Pick a voltage base for each different voltage
level, VB,LL. Voltages are line to line.
3. Calculate the impedance base
Procedure is very similar to 1 except we use a 3
VA base, and use line to line voltage bases
3
B
S 
2 2 2
, , ,
3 1 1
( 3 )
3
B LL B LN B LN
B
B B B
V V V
Z
S S S
  
  
Exactly the same impedance bases as with single phase using
the corresponding single phase VA base and voltage base!
26
Three Phase Per Unit, cont'd
4. Calculate the current base, IB
5. Convert actual values to per unit
3 1 1
3 1
B B
, , ,
3
3 3 3
B B B
B LL B LN B LN
S S S
I I
V V V
  
 
   
Exactly the same current bases as with single phase!
27
Three Phase Per Unit Example
•Solve for the current, load voltage and load power in
the previous circuit, assuming:
–a 3 power base of 300 MVA,
–and line to line voltage bases of 13.8 kV, 138 kV and 27.6
kV (square root of 3 larger than the 1 example voltages)
–the generator is Y-connected so its line to line voltage is
13.8 kV.
Convert to per unit
as before.
Note the system is
exactly the same!
28
3 Per Unit Example, cont'd
2
*
1.0 0
0.22 30.8 p.u. (not amps)
3.91 2.327
1.0 0 0.22 30.8
p.u.
0.189 p.u.
1.0 0 0.22 30.8 30.8 p.u.
L
L
L L L
G
I
j
V
V
S V I
Z
S
 
    

       
   
  
       
Again, analysis is exactly the same!
29
3 Per Unit Example, cont'd
L
Actual
Actual
L
Actual
G
Middle
B
Actual
Middle
0.859 30.8 27.6 kV 23.8 30.8 kV
0.189 0 300 MVA 56.7 0 MVA
0.22 30.8 300 MVA 66.0 30.8 MVA
300 MVA
125 (same cu
0 Amps
3138 kV
0.22 30
rrent
8
!)
.
V
S
S
I
I
        
      
      
 
     Amps 275 30.8
    

Differences appear when we convert back to actual values
30

More Related Content

PPT
Power system analysis per unit calculations
PPT
Lecture 8
PPT
UNIT -I per unit calculation,EQUIVALENT CIRCUIT
PPTX
per_unit_system.pptx
PDF
1_Intro + Per Unit.pdf
PDF
BEF43303 - 201620171 W1 Power System Analysis and Protection.pdf
PPTX
Power system analysis notes PPT ,pu methods, reactance diagram
PPT
ENERGY_CONVERSION 5_.................ppt
Power system analysis per unit calculations
Lecture 8
UNIT -I per unit calculation,EQUIVALENT CIRCUIT
per_unit_system.pptx
1_Intro + Per Unit.pdf
BEF43303 - 201620171 W1 Power System Analysis and Protection.pdf
Power system analysis notes PPT ,pu methods, reactance diagram
ENERGY_CONVERSION 5_.................ppt

Similar to Lecture_8 transformer per unit analysis in power system (20)

PPT
Engineering science lesson 10 1
PPT
Engineering science lesson 10
PPT
Unit1-Transformers.ppt
PPT
Unit5-Transformers.ppt
PPTX
5_2020_12_01!02_20_41_PM.pptx
PPTX
Power system analysis in load flow analysis.pptx
PPTX
Transformers_SNH.pptx
PDF
pdfcoffee.com_transformer-ppt-for-first-year-pdf-free.pdf
PPT
Lecture 9
PDF
Power System Analysis and Design
PDF
Chapter 7 transformers
PPTX
TRANSFORMERS FOR EE-UY-2613.pptx
PDF
Transformers devices and its efficiency of it
PPTX
Transformer.pptx
PDF
USC EE443 Lecture 7W7 10-5-23F Final.pdf
PPT
Unit4 -Power supplies on electronics.ppt
PDF
Symmetrical Components Fault Calculations
PDF
Lecture1
PDF
Power system Analysis By Sharif Kakar
PPT
fdocuments.in_chapter-2-the-per-unit-system-new.ppt
Engineering science lesson 10 1
Engineering science lesson 10
Unit1-Transformers.ppt
Unit5-Transformers.ppt
5_2020_12_01!02_20_41_PM.pptx
Power system analysis in load flow analysis.pptx
Transformers_SNH.pptx
pdfcoffee.com_transformer-ppt-for-first-year-pdf-free.pdf
Lecture 9
Power System Analysis and Design
Chapter 7 transformers
TRANSFORMERS FOR EE-UY-2613.pptx
Transformers devices and its efficiency of it
Transformer.pptx
USC EE443 Lecture 7W7 10-5-23F Final.pdf
Unit4 -Power supplies on electronics.ppt
Symmetrical Components Fault Calculations
Lecture1
Power system Analysis By Sharif Kakar
fdocuments.in_chapter-2-the-per-unit-system-new.ppt
Ad

More from addisalem15 (6)

PPT
Lecture - 1, 08.11.2017.ppt on power systems
PPTX
Introduction to DSE 08.11.2017.pptx introduction to power systems
PPT
power system 25471_ENERGY_CONVERSION_7 - Copy.ppt
PPT
per unit system chapter_1_per_unit_august_2011.ppt
PPTX
Symmetrical Components in fault analysis.pptx
PPTX
Symetrical Faults in power system analysis.pptx
Lecture - 1, 08.11.2017.ppt on power systems
Introduction to DSE 08.11.2017.pptx introduction to power systems
power system 25471_ENERGY_CONVERSION_7 - Copy.ppt
per unit system chapter_1_per_unit_august_2011.ppt
Symmetrical Components in fault analysis.pptx
Symetrical Faults in power system analysis.pptx
Ad

Recently uploaded (20)

PDF
keyrequirementskkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkk
PPTX
FINAL REVIEW FOR COPD DIANOSIS FOR PULMONARY DISEASE.pptx
PPTX
CYBER-CRIMES AND SECURITY A guide to understanding
PDF
Enhancing Cyber Defense Against Zero-Day Attacks using Ensemble Neural Networks
PPTX
bas. eng. economics group 4 presentation 1.pptx
PDF
Embodied AI: Ushering in the Next Era of Intelligent Systems
PDF
Operating System & Kernel Study Guide-1 - converted.pdf
PPTX
Construction Project Organization Group 2.pptx
PDF
TFEC-4-2020-Design-Guide-for-Timber-Roof-Trusses.pdf
PDF
Mohammad Mahdi Farshadian CV - Prospective PhD Student 2026
PPT
CRASH COURSE IN ALTERNATIVE PLUMBING CLASS
PPTX
Engineering Ethics, Safety and Environment [Autosaved] (1).pptx
PPT
Project quality management in manufacturing
DOCX
ASol_English-Language-Literature-Set-1-27-02-2023-converted.docx
PPTX
web development for engineering and engineering
PPTX
Infosys Presentation by1.Riyan Bagwan 2.Samadhan Naiknavare 3.Gaurav Shinde 4...
PDF
BMEC211 - INTRODUCTION TO MECHATRONICS-1.pdf
PPTX
UNIT 4 Total Quality Management .pptx
PDF
Evaluating the Democratization of the Turkish Armed Forces from a Normative P...
PDF
SM_6th-Sem__Cse_Internet-of-Things.pdf IOT
keyrequirementskkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkk
FINAL REVIEW FOR COPD DIANOSIS FOR PULMONARY DISEASE.pptx
CYBER-CRIMES AND SECURITY A guide to understanding
Enhancing Cyber Defense Against Zero-Day Attacks using Ensemble Neural Networks
bas. eng. economics group 4 presentation 1.pptx
Embodied AI: Ushering in the Next Era of Intelligent Systems
Operating System & Kernel Study Guide-1 - converted.pdf
Construction Project Organization Group 2.pptx
TFEC-4-2020-Design-Guide-for-Timber-Roof-Trusses.pdf
Mohammad Mahdi Farshadian CV - Prospective PhD Student 2026
CRASH COURSE IN ALTERNATIVE PLUMBING CLASS
Engineering Ethics, Safety and Environment [Autosaved] (1).pptx
Project quality management in manufacturing
ASol_English-Language-Literature-Set-1-27-02-2023-converted.docx
web development for engineering and engineering
Infosys Presentation by1.Riyan Bagwan 2.Samadhan Naiknavare 3.Gaurav Shinde 4...
BMEC211 - INTRODUCTION TO MECHATRONICS-1.pdf
UNIT 4 Total Quality Management .pptx
Evaluating the Democratization of the Turkish Armed Forces from a Normative P...
SM_6th-Sem__Cse_Internet-of-Things.pdf IOT

Lecture_8 transformer per unit analysis in power system

  • 1. EE 369 POWER SYSTEM ANALYSIS Lecture 8 Transformers, Per Unit Tom Overbye and Ross Baldick 1
  • 2. Announcements • For lectures 8 to 10 read Chapter 3. • HW 6 is problems 5.14, 5.16, 5.19, 5.26, 5.31, 5.32, 5.33, 5.36; case study questions chapter 5 a, b, c, d, is due Thursday, 10/6. • Power plant tour is 10/6. • Instead of coming to class, go to UT power plant. Turn in homework at beginning of tour. • Homework 7 is 5.8, 5.15, 5.17, 5.24, 5.27, 5.28, 5.29, 5.34, 5.37, 5.38, 5.43, 5.45; due 10/20. 2
  • 3. Transformers Overview • Power systems are characterized by many different voltage levels, ranging from 765 kV down to 240/120 volts. • Transformers are used to transfer power between different voltage levels. • The ability to inexpensively change voltage levels is a key advantage of ac systems over dc systems. • In this section we’ll development models for the transformer and discuss various ways of connecting three phase transformers. 3
  • 4. Ideal Transformer First we review the voltage/current relationships for an ideal transformer – no real power losses – magnetic core has infinite permeability – no leakage flux We’ll define the “primary” side of the transformer as the side that usually receives power from a line etc, and the secondary as the side that usually delivers power to a load etc: – primary is usually the side with the higher voltage, but may be the low voltage side on a generator step-up transformer. 4
  • 5. Ideal Transformer Relationships 1 1 1 2 2 1 2 1 1 2 2 1 2 1 1 1 2 2 2 Assume we have flux in magnetic material. Then flux linking coil 1 having turns is: , and similarly , = turns ratio m m m m m m N N N d d d d v N v N dt dt dt dt d v v V N a dt N N V N                      Note that I2 and I2’ are in opposite directions 5
  • 6. Current Relationships ' 1 1 2 2 ' 1 1 2 2 ' 1 1 2 2 To get the current relationships use ampere's law with path around core having total length : mmf Assuming uniform flux density in the core having area , L d N i N i H L N i N i B L N i N i A            H L   ' 1 1 2 2 then B A L N i N i A          6
  • 7. Current/Voltage Relationships ' 1 1 2 2 ' 1 2 1 2 2 2 ' 1 2 1 2 1 2 1 2 1 2 If is infinite then 0 . Hence 1 or , where 1 Then: and: 0 1 0 N i N i i N i N i i N i N a i I I a a V V I I a                               7
  • 8. Impedance Transformation Example •Example: Calculate the primary voltage and current for an impedance load Z on the secondary 2 1 2 1 2 2 / and substituting: 0 1 0 a V V V I Z a I V Z                         2 1 2 1 2 1 1 1 primary referred value of secondary load impedance V V aV I a Z V a Z I     8
  • 9. Real Transformers • Real transformers – have losses – have leakage flux – have finite permeability of magnetic core • Real power losses – resistance in windings (I2 R) – core losses due to eddy currents and hysteresis 9
  • 10. Transformer Core losses Eddy currents arise because of changing flux in core. Eddy currents are reduced by laminating the core Hysteresis losses are proportional to area of BH curve and the frequency These losses are reduced by using material with a “thin” BH curve 10
  • 11. Effect of Leakage Flux 1 1 1 1 2 2 2 2 1 1 1 2 2 Not all flux is within the transformer core , where is the coil 1 leakage flux, , where is the coil 2 leakage flux, Assuming a linear magnetic medium we get l m l l m l l l l l N N L i L i                 2 2 2 ' 1 1 1 1 1 1 1 ' ' 2 2 2 2 2 , including winding resistance , , including resistance . m l m l d di v ri L N dt dt r di d v r i L N r dt dt         11
  • 12. Effect of Finite Core Permeability m 11 2 2 m m 2 1 2 1 1 1 m Finite core permeability means a non-zero mmf is required to maintain in the core , where is the reluctance. This effect is usually modeled as a magnetizing current N i N i R R R N i i N N N i i          2 m 2 m 1 1 where , modeled by resistance and inductance. R i i N N   12
  • 13. Transformer Equivalent Circuit Using the previous relationships, we can derive an equivalent circuit model for the real transformer ' 2 ' 2 2 1 2 ' 2 ' 2 2 1 2 This model is further simplified by referring all impedances to the primary side (and approximating by swapping the referred elements and the shunts): e e r a r r r r x a x x x x       13
  • 15. Calculation of Model Parameters The parameters of the model are determined based upon: – nameplate data: gives the rated voltages and power – open circuit test: rated voltage is applied to primary with secondary open; measure the primary current and losses (the test may also be done applying the rated voltage to the secondary, calculating the values, then referring the values back to the primary side). – short circuit test: with secondary shorted, apply (lower than rated) voltage to primary to get rated primary current to flow; measure voltage and losses. 15
  • 16. Transformer Example •Example: A single phase, 100 MVA, 200/80 kV transformer has the following test data: –open circuit: 20 amps, with 10 kW losses –short circuit: 30 kV, with 500 kW losses •Determine the model parameters. 16
  • 17. Transformer Example, cont’d 2 2 2 2 2 2 2 2 rated 100MVA 30 kV 500 A, 60 200kV 500 A 500 kW / 500,000/(500) 2 , Hence 60 2 60 ( ) (200) (kV) 4M 10 kW sc e e sc e sc e sc sc e c oc e I R jX P R I R P I X V R P R                       From the short circuit test From the open circuit test rated 200 kV 10,000 10,000 20 A e m m oc V jX jX X I        17
  • 18. Residential Distribution Transformers Single phase transformers are commonly used in residential distribution systems. Most distribution systems are 4 wire, with a multi-grounded, common neutral. 18
  • 19. Per Unit Calculations A key problem in analyzing power systems is the large number of transformers. – It would be very difficult to continually have to refer impedances to the different sides of the transformers This problem is avoided by a normalization of all variables. This normalization is known as per unit analysis. actual quantity quantity in per unit base value of quantity  19
  • 20. Per Unit Conversion Procedure, 1 1. Pick a 1 VA base for the entire system, SB 2. Pick a voltage base for each different voltage level, VB. Voltage bases are related by transformer turns ratios. Voltages are line to neutral. 3. Calculate the impedance base, ZB= (VB)2 /SB 4. Calculate the current base, IB = VB/ZB 5. Convert actual values to per unit Note, per unit conversion affects magnitudes, not the angles. Also, per unit quantities no longer have units (i.e., a voltage is 1.0 p.u., not 1 p.u. volts) 20
  • 21. Per Unit Solution Procedure 1. Convert to per unit (p.u.) (many problems are already in per unit) 2. Solve 3. Convert back to actual as necessary 21
  • 22. Per Unit Example Solve for the current, load voltage and load power in the circuit shown below using per unit analysis with an SB of 100 MVA, and voltage bases of 8 kV, 80 kV and 16 kV, respectively. Original Circuit 22
  • 23. Per Unit Example, cont’d 2 2 2 2 2 2 8 (kV) 0.64 100MVA 80 (kV) 64 100MVA 16 (kV) 2.56 100MVA Left B Middle B Right B Z Z Z          Same circuit, with values expressed in per unit. 23
  • 24. Per Unit Example, cont’d 2 * 1.0 0 0.22 30.8 p.u. (not amps) 3.91 2.327 1.0 0 0.22 30.8 p.u. 0.189 p.u. 1.0 0 0.22 30.8 30.8 p.u. L L L L L G I j V V S V I Z S                                24
  • 25. Per Unit Example, cont’d To convert back to actual values just multiply the per unit values by their per unit base Actual Actual Actual Middle Actual Middle 0.859 30.8 16 kV 13.7 30.8 kV 0.189 0 100 MVA 18.9 0 MVA 0.22 30.8 100 MVA 22.0 30.8 MVA 100 MVA 1250 Amps 80 kV 0.22 30.8 275 30.8 L L G B V S S I I                                     25
  • 26. Three Phase Per Unit 1. Pick a 3 VA base for the entire system, 2. Pick a voltage base for each different voltage level, VB,LL. Voltages are line to line. 3. Calculate the impedance base Procedure is very similar to 1 except we use a 3 VA base, and use line to line voltage bases 3 B S  2 2 2 , , , 3 1 1 ( 3 ) 3 B LL B LN B LN B B B B V V V Z S S S       Exactly the same impedance bases as with single phase using the corresponding single phase VA base and voltage base! 26
  • 27. Three Phase Per Unit, cont'd 4. Calculate the current base, IB 5. Convert actual values to per unit 3 1 1 3 1 B B , , , 3 3 3 3 B B B B LL B LN B LN S S S I I V V V          Exactly the same current bases as with single phase! 27
  • 28. Three Phase Per Unit Example •Solve for the current, load voltage and load power in the previous circuit, assuming: –a 3 power base of 300 MVA, –and line to line voltage bases of 13.8 kV, 138 kV and 27.6 kV (square root of 3 larger than the 1 example voltages) –the generator is Y-connected so its line to line voltage is 13.8 kV. Convert to per unit as before. Note the system is exactly the same! 28
  • 29. 3 Per Unit Example, cont'd 2 * 1.0 0 0.22 30.8 p.u. (not amps) 3.91 2.327 1.0 0 0.22 30.8 p.u. 0.189 p.u. 1.0 0 0.22 30.8 30.8 p.u. L L L L L G I j V V S V I Z S                                Again, analysis is exactly the same! 29
  • 30. 3 Per Unit Example, cont'd L Actual Actual L Actual G Middle B Actual Middle 0.859 30.8 27.6 kV 23.8 30.8 kV 0.189 0 300 MVA 56.7 0 MVA 0.22 30.8 300 MVA 66.0 30.8 MVA 300 MVA 125 (same cu 0 Amps 3138 kV 0.22 30 rrent 8 !) . V S S I I                               Amps 275 30.8       Differences appear when we convert back to actual values 30