16394 Environmental Engineering Design
Lighting Design Lecture
Introduction
The prime objectives behind the design of a lighting system are as follows:
the safety and comfort of occupants – the nature of a task or process performed in a
space will dictate the illuminance level which must be provided by the lighting system
(lx or lm/m2
). Tasks involving high degrees of visual acuity will require higher
lighting levels.
the minimisation of energy consumption – minimisation of energy consumption
involves the development of the most energy efficient lighting systems which is
suitable for the task, this can be achieved by selecting high efficiency equipment and
making use of available daylight.
colour rendering or the creation of a specific atmosphere – the colour
characteristics of a lighting scheme will affects tasks performed when the lighting
system is on. For example tasks which require the accurate representation of colour
require a light with the spectral characteristics of daylight. Alternatively,. to create a
“warm atmosphere” in a restaurant requires the selection of lights skewed to the red
end of the spectrum.
A lighting design has several stages. These are as follows:
1) Identification of the requirements for the lighting system, illuminance levels,
colour requirements, available space, etc;
2) Selection of equipment, lamps, luminaires: lighting systems consist of numerous
components, the two most important of which are: lamps, which influence the
lighting level, colour characteristics and efficiency of the lighting system;
luminaires affect the efficiency with which the light is distributed and so affect
lighting efficiency and uniformity
3) Design of the lighting system: lighting systems are designed to achieve a
reasonably uniform distribution of light on a particular plane (usually horizontal),
avoidance of glare with a minimum expenditure of energy. The most rudimentary
form of lighting design is done using a manual calculation – the lumen method.
However lighting design is increasingly done by computer.
4) System control: once a lighting system has been designed it can be controlled in
such a way as to make maximum use of available daylight, through selection of
appropriate switching mechanisms and daylight responsive controls.
16394 Environmental Engineering Design
Identification of Lighting Requirements
Lighting requirements are primarily dictated by the function of a space or the tasks
being performed within it. Lighting requirements are usually specified by the required
lighting level and the colour rendering requirements.
For example:
• a general office requires an illumination level of 500 lux; colour rendering is mot
particularly important;
• an architects drawing office requires higher lighting levels of 750 lux due the
more visually tasks being conducted within the office. In addition as colour work
is being done the lighting system must have good colour rendering.
Examples of lighting level requirements are given in the table below:
Building Area Standard Maintained
Illuminance (lux)
Colour Rendering
Entrance hall 200 -
Corridors 100 -
Kitchens 300 -
General offices 500 -
Drawing Rooms 750 Good colour rendering
may be required
Classrooms 300 -
Lecture Theatres 300 -
Art rooms 500 Excellent colour rendering
required
Table 1 Lighting level requirements.
Lighting requirements are summarised in the CIBSE Code for interior lighting,
available from the library.
The colour properties of a particular lamp are supplied by the manufacturer in the
form of a lighting catalogue: the Philips lighting catalogue is available in the design
room alternatively the catalogue is available on-line at: www.philips.com
The colour rendering properties of a particular lamp are described by its colour
rendering group or the CIE number (Commission Internationale de L’Eclairage):
Colour
rendering group
CIE colour rendering index
(Ra)
Comments
1A Ra > 90 Used wherever accurate colour
matching is required
1B 80 < Ra < 90 Used when accurate colour
matching is required e.g. clothes
shops
16394 Environmental Engineering Design
2 60 < Ra < 80 Where moderate colour rendering is
required
3 40 < Ra < 60 Where colour rendering is
unimportant but distortion of colour
is unacceptable
4 60 > Ra Where marked colour distortion is
acceptable e.g. street lighting
Table 2 Colour rendering groups
Selection of Components
Selection of components follows from the identification of systems requirements.
The luminaires are normally chosen first: lighting catalogues usually describe the uses
for particular types of luminaire, these also come with different types of reflectors1
for
different applications e.g. low glare reflectors for computer rooms.
Figure 1 The components of a typical luminaire.
Lamps are selected based on those which are compatible (lamp type, dimensions,
frequency of operation, etc) with the selected luminaire and which have the
appropriate colour-rendering index.
For example the Philips TCS 660 luminaire comes with a choice of 8 different
reflector types.
The lamps that can be fitted to this luminaire must be Philips high frequency
fluorescent tubes that can be 1200mm or 1500 mm long. The luminaire can be fitted
with a maximum of 2 fluorescent tubes.
1
Reflectors govern the light output characteristic of a luminaire.
reflector
lamp
casing
16394 Environmental Engineering Design
Design of the Lighting System
A simple means of designing lighting systems is achieved by means of the lumen
method; this is a simplified design approach to enable the designer to achieve an even
light distribution in spaces of reasonably simple geometry (i.e. rectangular).
The basis of the lumen method is the following equation:
(1)
N - is the number of luminaires required;
E - is the required illuminance (lux);
A - is the area to be lit;
N - is the number of lamps per luminaire;
F - is the lamp lumen output (lumens);
MF - is known as the maintenance factor, which is a combination of three
factors;
UF - is the utilisation and is a function of the luminaire properties and room
geometry.
Utilisation Factor (UF)
The room geometry is a crucial factor in determining the utilisation factor term in the
lumen equation. Several parameters are important.
Figure 2 important dimensional parameters for the Lumen Method
In the Lumen method of design the room geometry is characterised by a room index
(K):
(2)
The reflectances (ρs) of surfaces are also important properties in the calculation of
terms for equation (1). The reflectances of walls floors and ceilings is represented by
UFMFFn
AE
N
×××
×
=
floor cavity
ceiling cavity
working plane
ceiling plane hm
length L
width W
mhWL
WL
K
)( +
×
=
16394 Environmental Engineering Design
a number between 0 and 1: 0 – no light is reflected back from the surface, 1 – all
incident light is reflected back from the surface.
The calculation of surface reflectances is more complicated for imaginary planes such
as the luminaire and working planes, in these cases the reflectances of these planes
must be calculated as an equivalent cavity reflectance (ρe):
(3)
Where n is the number of surfaces in the cavity and A is the area of the surface within
the cavity.
The utilisation factor can be obtained once the surface reflectances (or effective
reflectances) are known along with the room index (K); each luminaire produced by a
manufacturer has a lookup table for UF (UF values in bold):
Reflectances Room Index (K)
Ceiling Wall floor 0.75 1.00 … 5.00
0.7 0.3 0.2 0.45 0.51 … 0.69
Table 3 Utilisation Factors
Maintenance Factor (MF)
The maintenance factor is a value designed to account for the reduction in light output
from a lighting system due to: the ageing of the lamps and the accumulation of dirt
and dust on the light fittings and room surfaces. The MF is therefore time varying and
is the product of 4 factors:
Lamp lumen maintenance factor (LLMF) – a value between 0 and 1 which accounts
for the degradation of lamp output over time:
The LLMF for any time t can be obtained from manufacturer’s data.
Lamp survival factor (LSF) – this accounts for the failure of lamps over time, if failed
lamps are replaced immediately this factor can be ignored.
Luminaire maintenance factor (LMF) – a value between 0 and 1 that accounts for dirt
and dust accumulation on the luminaire. The luminaire maintenance factor
∑
∑
=
=
= n
s
i
n
s
ii
e
A
A
1
1
ρ
ρ
outputlumeninitial
ttimeatoutputlumen
tLLMF =)(
16394 Environmental Engineering Design
a number between 0 and 1: 0 – no light is reflected back from the surface, 1 – all
incident light is reflected back from the surface.
The calculation of surface reflectances is more complicated for imaginary planes such
as the luminaire and working planes, in these cases the reflectances of these planes
must be calculated as an equivalent cavity reflectance (ρe):
(3)
Where n is the number of surfaces in the cavity and A is the area of the surface within
the cavity.
The utilisation factor can be obtained once the surface reflectances (or effective
reflectances) are known along with the room index (K); each luminaire produced by a
manufacturer has a lookup table for UF (UF values in bold):
Reflectances Room Index (K)
Ceiling Wall floor 0.75 1.00 … 5.00
0.7 0.3 0.2 0.45 0.51 … 0.69
Table 3 Utilisation Factors
Maintenance Factor (MF)
The maintenance factor is a value designed to account for the reduction in light output
from a lighting system due to: the ageing of the lamps and the accumulation of dirt
and dust on the light fittings and room surfaces. The MF is therefore time varying and
is the product of 4 factors:
Lamp lumen maintenance factor (LLMF) – a value between 0 and 1 which accounts
for the degradation of lamp output over time:
The LLMF for any time t can be obtained from manufacturer’s data.
Lamp survival factor (LSF) – this accounts for the failure of lamps over time, if failed
lamps are replaced immediately this factor can be ignored.
Luminaire maintenance factor (LMF) – a value between 0 and 1 that accounts for dirt
and dust accumulation on the luminaire. The luminaire maintenance factor
∑
∑
=
=
= n
s
i
n
s
ii
e
A
A
1
1
ρ
ρ
outputlumeninitial
ttimeatoutputlumen
tLLMF =)(

More Related Content

PPTX
Principle of lumination design
PPTX
Types of lighting their uses,availability
PPT
Building service.ppt of neeru and aprajeeta
PDF
Lighting architecture lecture 6
PDF
IND314 Lighting for interior design, Course File
PPTX
THEORY: Color, Light, & Texture
PDF
Lighting architecture lecture 3
PPTX
Lighting & colour in interior
Principle of lumination design
Types of lighting their uses,availability
Building service.ppt of neeru and aprajeeta
Lighting architecture lecture 6
IND314 Lighting for interior design, Course File
THEORY: Color, Light, & Texture
Lighting architecture lecture 3
Lighting & colour in interior

What's hot (20)

PPTX
Facade Lighting
PPTX
LIGHT AND LIGHTING FIXTURES
PPTX
Illumination.
PPTX
Daylighting
PPTX
Natural lighting
PPTX
Lighting design.pptx
PPTX
artificial lighting
PPT
Illumination
PPTX
الإضاءة 3 - lighting 3
PPTX
Lighting design considerations
PPTX
Ambient/Task/Accent Lighting
PDF
LIGHTING SYSTEMS AND THEIR DESIGN..MAU---JMI-2014
PPTX
Day lighting
PPTX
Lighting Design - Theory and Calculations
PPTX
Lighting design requirements
PDF
Architecture lighting thesis presentation
PDF
BASIC TYPES OF ARTIFICIAL LIGHTING
PPTX
Artificial lighting
Facade Lighting
LIGHT AND LIGHTING FIXTURES
Illumination.
Daylighting
Natural lighting
Lighting design.pptx
artificial lighting
Illumination
الإضاءة 3 - lighting 3
Lighting design considerations
Ambient/Task/Accent Lighting
LIGHTING SYSTEMS AND THEIR DESIGN..MAU---JMI-2014
Day lighting
Lighting Design - Theory and Calculations
Lighting design requirements
Architecture lighting thesis presentation
BASIC TYPES OF ARTIFICIAL LIGHTING
Artificial lighting
Ad

Viewers also liked (17)

PDF
Building EA capabilities in Tatra banka
PPTX
COMPANY PROFILE
PPT
Canada 2012
PPT
Autoestima y rendimiento escolar.
PPTX
3 cerditos
PDF
ENGLISH
DOCX
Carol Barry Resume
PPTX
Uñas Degradadas
PDF
PortFolioEnglish
PPTX
SHINE 3-STEP HEAD SHAVING SYSTEM
PDF
Gestor de proyecto educativo tic editable
PDF
云计算 系统实例与研究现状
PPTX
Denilson morales
PPTX
Ppt social
PDF
Let’s have a fun school year
PDF
CliqTags - Engaging Mobile Campaign Sites
Building EA capabilities in Tatra banka
COMPANY PROFILE
Canada 2012
Autoestima y rendimiento escolar.
3 cerditos
ENGLISH
Carol Barry Resume
Uñas Degradadas
PortFolioEnglish
SHINE 3-STEP HEAD SHAVING SYSTEM
Gestor de proyecto educativo tic editable
云计算 系统实例与研究现状
Denilson morales
Ppt social
Let’s have a fun school year
CliqTags - Engaging Mobile Campaign Sites
Ad

Similar to Lighting design lecture (20)

PPTX
Lighting_Design2010.pptx
PPT
Illumination
PDF
Building science 2 final
PPTX
Electrical lighting design and calculations
PPTX
seminar 2021.pptx
PPT
Calculations of illumination
PPTX
Energy performance assessment of lighting systems
PDF
Lighting & power design citam
PDF
Project 2 integration project
PDF
Lighting system
PPTX
GROUP-8-BU-2.pptx
PDF
Lighting basics book
PDF
lighting-design-essentials.pdf
PPT
esd m2.ppt Lighting schemes and calculations
PPTX
PPTX
lecture on illumination.pptx .hbjrdjtghg
PDF
lighting system
PDF
Final distribution book and bms
PPTX
electrical lighting calculation
PDF
Building Science 2 - Integration Project (Report)
Lighting_Design2010.pptx
Illumination
Building science 2 final
Electrical lighting design and calculations
seminar 2021.pptx
Calculations of illumination
Energy performance assessment of lighting systems
Lighting & power design citam
Project 2 integration project
Lighting system
GROUP-8-BU-2.pptx
Lighting basics book
lighting-design-essentials.pdf
esd m2.ppt Lighting schemes and calculations
lecture on illumination.pptx .hbjrdjtghg
lighting system
Final distribution book and bms
electrical lighting calculation
Building Science 2 - Integration Project (Report)

Recently uploaded (20)

PDF
composite construction of structures.pdf
PDF
Enhancing Cyber Defense Against Zero-Day Attacks using Ensemble Neural Networks
DOCX
573137875-Attendance-Management-System-original
PDF
PRIZ Academy - 9 Windows Thinking Where to Invest Today to Win Tomorrow.pdf
PPTX
MET 305 2019 SCHEME MODULE 2 COMPLETE.pptx
PPTX
OOP with Java - Java Introduction (Basics)
PDF
BMEC211 - INTRODUCTION TO MECHATRONICS-1.pdf
PPTX
MCN 401 KTU-2019-PPE KITS-MODULE 2.pptx
PPTX
Welding lecture in detail for understanding
PPTX
Geodesy 1.pptx...............................................
PDF
Mohammad Mahdi Farshadian CV - Prospective PhD Student 2026
PPTX
bas. eng. economics group 4 presentation 1.pptx
PDF
Embodied AI: Ushering in the Next Era of Intelligent Systems
PPTX
Engineering Ethics, Safety and Environment [Autosaved] (1).pptx
PPTX
UNIT 4 Total Quality Management .pptx
DOCX
ASol_English-Language-Literature-Set-1-27-02-2023-converted.docx
PPTX
KTU 2019 -S7-MCN 401 MODULE 2-VINAY.pptx
PPTX
web development for engineering and engineering
PPTX
UNIT-1 - COAL BASED THERMAL POWER PLANTS
PPTX
CARTOGRAPHY AND GEOINFORMATION VISUALIZATION chapter1 NPTE (2).pptx
composite construction of structures.pdf
Enhancing Cyber Defense Against Zero-Day Attacks using Ensemble Neural Networks
573137875-Attendance-Management-System-original
PRIZ Academy - 9 Windows Thinking Where to Invest Today to Win Tomorrow.pdf
MET 305 2019 SCHEME MODULE 2 COMPLETE.pptx
OOP with Java - Java Introduction (Basics)
BMEC211 - INTRODUCTION TO MECHATRONICS-1.pdf
MCN 401 KTU-2019-PPE KITS-MODULE 2.pptx
Welding lecture in detail for understanding
Geodesy 1.pptx...............................................
Mohammad Mahdi Farshadian CV - Prospective PhD Student 2026
bas. eng. economics group 4 presentation 1.pptx
Embodied AI: Ushering in the Next Era of Intelligent Systems
Engineering Ethics, Safety and Environment [Autosaved] (1).pptx
UNIT 4 Total Quality Management .pptx
ASol_English-Language-Literature-Set-1-27-02-2023-converted.docx
KTU 2019 -S7-MCN 401 MODULE 2-VINAY.pptx
web development for engineering and engineering
UNIT-1 - COAL BASED THERMAL POWER PLANTS
CARTOGRAPHY AND GEOINFORMATION VISUALIZATION chapter1 NPTE (2).pptx

Lighting design lecture

  • 1. 16394 Environmental Engineering Design Lighting Design Lecture Introduction The prime objectives behind the design of a lighting system are as follows: the safety and comfort of occupants – the nature of a task or process performed in a space will dictate the illuminance level which must be provided by the lighting system (lx or lm/m2 ). Tasks involving high degrees of visual acuity will require higher lighting levels. the minimisation of energy consumption – minimisation of energy consumption involves the development of the most energy efficient lighting systems which is suitable for the task, this can be achieved by selecting high efficiency equipment and making use of available daylight. colour rendering or the creation of a specific atmosphere – the colour characteristics of a lighting scheme will affects tasks performed when the lighting system is on. For example tasks which require the accurate representation of colour require a light with the spectral characteristics of daylight. Alternatively,. to create a “warm atmosphere” in a restaurant requires the selection of lights skewed to the red end of the spectrum. A lighting design has several stages. These are as follows: 1) Identification of the requirements for the lighting system, illuminance levels, colour requirements, available space, etc; 2) Selection of equipment, lamps, luminaires: lighting systems consist of numerous components, the two most important of which are: lamps, which influence the lighting level, colour characteristics and efficiency of the lighting system; luminaires affect the efficiency with which the light is distributed and so affect lighting efficiency and uniformity 3) Design of the lighting system: lighting systems are designed to achieve a reasonably uniform distribution of light on a particular plane (usually horizontal), avoidance of glare with a minimum expenditure of energy. The most rudimentary form of lighting design is done using a manual calculation – the lumen method. However lighting design is increasingly done by computer. 4) System control: once a lighting system has been designed it can be controlled in such a way as to make maximum use of available daylight, through selection of appropriate switching mechanisms and daylight responsive controls.
  • 2. 16394 Environmental Engineering Design Identification of Lighting Requirements Lighting requirements are primarily dictated by the function of a space or the tasks being performed within it. Lighting requirements are usually specified by the required lighting level and the colour rendering requirements. For example: • a general office requires an illumination level of 500 lux; colour rendering is mot particularly important; • an architects drawing office requires higher lighting levels of 750 lux due the more visually tasks being conducted within the office. In addition as colour work is being done the lighting system must have good colour rendering. Examples of lighting level requirements are given in the table below: Building Area Standard Maintained Illuminance (lux) Colour Rendering Entrance hall 200 - Corridors 100 - Kitchens 300 - General offices 500 - Drawing Rooms 750 Good colour rendering may be required Classrooms 300 - Lecture Theatres 300 - Art rooms 500 Excellent colour rendering required Table 1 Lighting level requirements. Lighting requirements are summarised in the CIBSE Code for interior lighting, available from the library. The colour properties of a particular lamp are supplied by the manufacturer in the form of a lighting catalogue: the Philips lighting catalogue is available in the design room alternatively the catalogue is available on-line at: www.philips.com The colour rendering properties of a particular lamp are described by its colour rendering group or the CIE number (Commission Internationale de L’Eclairage): Colour rendering group CIE colour rendering index (Ra) Comments 1A Ra > 90 Used wherever accurate colour matching is required 1B 80 < Ra < 90 Used when accurate colour matching is required e.g. clothes shops
  • 3. 16394 Environmental Engineering Design 2 60 < Ra < 80 Where moderate colour rendering is required 3 40 < Ra < 60 Where colour rendering is unimportant but distortion of colour is unacceptable 4 60 > Ra Where marked colour distortion is acceptable e.g. street lighting Table 2 Colour rendering groups Selection of Components Selection of components follows from the identification of systems requirements. The luminaires are normally chosen first: lighting catalogues usually describe the uses for particular types of luminaire, these also come with different types of reflectors1 for different applications e.g. low glare reflectors for computer rooms. Figure 1 The components of a typical luminaire. Lamps are selected based on those which are compatible (lamp type, dimensions, frequency of operation, etc) with the selected luminaire and which have the appropriate colour-rendering index. For example the Philips TCS 660 luminaire comes with a choice of 8 different reflector types. The lamps that can be fitted to this luminaire must be Philips high frequency fluorescent tubes that can be 1200mm or 1500 mm long. The luminaire can be fitted with a maximum of 2 fluorescent tubes. 1 Reflectors govern the light output characteristic of a luminaire. reflector lamp casing
  • 4. 16394 Environmental Engineering Design Design of the Lighting System A simple means of designing lighting systems is achieved by means of the lumen method; this is a simplified design approach to enable the designer to achieve an even light distribution in spaces of reasonably simple geometry (i.e. rectangular). The basis of the lumen method is the following equation: (1) N - is the number of luminaires required; E - is the required illuminance (lux); A - is the area to be lit; N - is the number of lamps per luminaire; F - is the lamp lumen output (lumens); MF - is known as the maintenance factor, which is a combination of three factors; UF - is the utilisation and is a function of the luminaire properties and room geometry. Utilisation Factor (UF) The room geometry is a crucial factor in determining the utilisation factor term in the lumen equation. Several parameters are important. Figure 2 important dimensional parameters for the Lumen Method In the Lumen method of design the room geometry is characterised by a room index (K): (2) The reflectances (ρs) of surfaces are also important properties in the calculation of terms for equation (1). The reflectances of walls floors and ceilings is represented by UFMFFn AE N ××× × = floor cavity ceiling cavity working plane ceiling plane hm length L width W mhWL WL K )( + × =
  • 5. 16394 Environmental Engineering Design a number between 0 and 1: 0 – no light is reflected back from the surface, 1 – all incident light is reflected back from the surface. The calculation of surface reflectances is more complicated for imaginary planes such as the luminaire and working planes, in these cases the reflectances of these planes must be calculated as an equivalent cavity reflectance (ρe): (3) Where n is the number of surfaces in the cavity and A is the area of the surface within the cavity. The utilisation factor can be obtained once the surface reflectances (or effective reflectances) are known along with the room index (K); each luminaire produced by a manufacturer has a lookup table for UF (UF values in bold): Reflectances Room Index (K) Ceiling Wall floor 0.75 1.00 … 5.00 0.7 0.3 0.2 0.45 0.51 … 0.69 Table 3 Utilisation Factors Maintenance Factor (MF) The maintenance factor is a value designed to account for the reduction in light output from a lighting system due to: the ageing of the lamps and the accumulation of dirt and dust on the light fittings and room surfaces. The MF is therefore time varying and is the product of 4 factors: Lamp lumen maintenance factor (LLMF) – a value between 0 and 1 which accounts for the degradation of lamp output over time: The LLMF for any time t can be obtained from manufacturer’s data. Lamp survival factor (LSF) – this accounts for the failure of lamps over time, if failed lamps are replaced immediately this factor can be ignored. Luminaire maintenance factor (LMF) – a value between 0 and 1 that accounts for dirt and dust accumulation on the luminaire. The luminaire maintenance factor ∑ ∑ = = = n s i n s ii e A A 1 1 ρ ρ outputlumeninitial ttimeatoutputlumen tLLMF =)(
  • 6. 16394 Environmental Engineering Design a number between 0 and 1: 0 – no light is reflected back from the surface, 1 – all incident light is reflected back from the surface. The calculation of surface reflectances is more complicated for imaginary planes such as the luminaire and working planes, in these cases the reflectances of these planes must be calculated as an equivalent cavity reflectance (ρe): (3) Where n is the number of surfaces in the cavity and A is the area of the surface within the cavity. The utilisation factor can be obtained once the surface reflectances (or effective reflectances) are known along with the room index (K); each luminaire produced by a manufacturer has a lookup table for UF (UF values in bold): Reflectances Room Index (K) Ceiling Wall floor 0.75 1.00 … 5.00 0.7 0.3 0.2 0.45 0.51 … 0.69 Table 3 Utilisation Factors Maintenance Factor (MF) The maintenance factor is a value designed to account for the reduction in light output from a lighting system due to: the ageing of the lamps and the accumulation of dirt and dust on the light fittings and room surfaces. The MF is therefore time varying and is the product of 4 factors: Lamp lumen maintenance factor (LLMF) – a value between 0 and 1 which accounts for the degradation of lamp output over time: The LLMF for any time t can be obtained from manufacturer’s data. Lamp survival factor (LSF) – this accounts for the failure of lamps over time, if failed lamps are replaced immediately this factor can be ignored. Luminaire maintenance factor (LMF) – a value between 0 and 1 that accounts for dirt and dust accumulation on the luminaire. The luminaire maintenance factor ∑ ∑ = = = n s i n s ii e A A 1 1 ρ ρ outputlumeninitial ttimeatoutputlumen tLLMF =)(