SlideShare a Scribd company logo
Design Standards




       Although several organizations are involved in establishing
       standards for the design, construction, and application of
       motor control centers, the primary standards are established
       by UL, NEMA, and the National Electrical Code® (NEC®). The
       following organizations have established standards which may
       be applied to motor control centers. It is beyond the scope of
       this course to cover every standard; however, reference will be
       made throughout the course to many important standards with
       which Siemens motor control centers comply.

UL     Underwriters Laboratories (UL) is a private company that is
       nationally recognized as an independent testing laboratory. UL
       tests products for safety and products that pass UL tests can
       carry a UL mark. Siemens motor control centers are designed
       to UL 845 standards.

NEMA   The National Electrical Manufacturers Association (NEMA) is an
       organization that, among other things, develops standards for
       electrical equipment.

NEC    The National Fire Protection Association (NFPA) is a nonprofit
       organization which publishes the National Electrical Code®
       (NEC®). The intent of the NEC® is to describe safe electrical
       practices.

ANSI   The American National Standards Institute (ANSI) is a
       nongovernmental organization that facilitates the development
       of standards by establishing a consensus among qualified
       groups.

IEEE   The Institute of Electrical and Electronic Engineers (IEEE) is
       an organization open to individual membership and provides a
       variety of services for its members. It also develops numerous
       standards for electrical and electronic equipment and practices.

IEC    The International Electrotechnical Commission (IEC) is an
       organization based in Geneva, Switzerland, with over 50
       member nations. IEC writes standards for electrical and
       electronic equipment practices.

       NEC® and National Electrical Code® are registered trademarks of the
       National Fire Protection Association.
                                                                             13
Need for Circuit Protection




Current and Temperature   Current flow in a conductor always generates heat. The greater
                          the current flow in any one size conductor, the hotter the
                          conductor. Excess heat is damaging to electrical components
                          and conductor insulation. For that reason conductors have
                          a rated, continuous current-carrying capacity or ampacity.
                          Overcurrent protection devices, such as fuses, are used to
                          protect conductors from excessive current flow.




                          Excessive current is referred to as overcurrent. The National
                          Electrical Code® defines overcurrent as any current in excess of
                          the rated current of equipment or the ampacity of a conductor.
                          It may result from overload, short circuit, or ground fault (Article
                          100-definitions).




                          NEC® and National Electrical Code® are registered trademarks of the
                          National Fire Protection Association. Reprinted with permission from NFPA
                          70-2002, the National Electrical Code®, Copyright© 2001, National Fire
                          Protection Association, Quincy, MA 02269.
14
Overloads              An overload occurs when too many devices are operated on a
                       single circuit, or a piece of electrical equipment is made to work
                       harder than it is rated design. For example, a motor rated for
                       10 amperes may draw 20, 30, or more amperes in an overload
                       condition. In the following illustration, a package has become
                       jammed on a conveyor, causing the motor to work harder and
                       draw more current. Because the motor is drawing more current,
                       it heats up. Damage will occur to the motor in a short time if
                       the problem is not corrected or if the circuit not is shut down by
                       the overcurrent protector.




Conductor Insulation   Motors, of course, are not the only devices that require circuit
                       protection for an overload condition. Every circuit requires some
                       form of protection against overcurrent. Heat is one of the major
                       causes of insulation failure of any electrical component. High
                       levels of heat to insulated wire can cause the insulation to
                       breakdown, melt, or flake off, exposing conductors.




                                                                                      15
Short Circuits   When two bare conductors touch, a short circuit occurs. When
                 a short circuit occurs, resistance drops to almost zero. Short
                 circuit current can be thousands of times higher than normal
                 operating current.




                 Ohm’s Law demonstrates the relationship of current, voltage,
                 and resistance. For example, a 240 volt motor with 24 Ω (ohms)
                 of resistance would normally draw 10 amperes of current.




                 When a short circuit develops, resistance drops. If resistance
                 drops to 24 milliohms, current will be 10,000 amperes.




16
Short-Circuit Current on        When a short circuit occurs, current will continue to flow
Unprotected Electrical          in an unprotected electrical circuit. The peak short-circuit
Circuits                        current of the first cycle is the greatest and is referred to as
                                peak let-thru current (IP). The force of this current can cause
                                damage to wires, switches, and other electrical components of
                                a circuit.




                                                                 2
                                There is also energy let-thru (I t). This destructive thermal force
                                is capable of melting conductors.




Short-Circuit Current on        A properly used, overcurrent-protection device will open the
                                                                                                  2
Protected Electrical Circuits   circuit quickly, limiting peak let-thru current (IP) and energy (I t).




                                                                                                     17
Article 240      Circuit protection would be unnecessary if overloads and short
                 circuits could be eliminated. Unfortunately, overloads and short
                 circuits do occur.

                 Article 240 of the NEC® covers overcurrent protection. You are
                 encouraged to become familiar with this material. Article 240.1
                 states that:

                 Overcurrent protection for conductors and equipment is
                 provided to open the circuit if the current reaches a value that
                 will cause an excessive or dangerous temperature in conductors
                 or conductor insulation.

Article 430.94   The National Electrical Code® requires overcurrent protection
                 for motor control centers. NEC® article 430.94 states:

                 Motor control centers shall be provided with overcurrent
                 protection in accordance with Parts I, II, and IX of Article 240.
                 The ampere rating or setting of the overcurrent protective
                 device shall not exceed the rating of the common power
                 bus. This protection shall be provided by (1) an overcurrent-
                 protective device located ahead of the motor control center
                 or (2) a main overcurrent-protective device located within the
                 motor control center.

                 There are two ways Article 430.94 can be met. An overcurrent-
                 protection device can be installed ahead of the motor control
                 center. A switchboard, for example, located upstream of the
                 motor control center may contain the overcurrent-protection
                 device for the motor control center. The second way to meet
                 this requirement is to install a main over-current protection
                 device within the motor control center.




                 NEC® and National Electrical Code® are registered trademarks of the
                 National Fire Protection Association. Reprinted with permission from NFPA
                 70-2002, the National Electrical Code®, Copyright© 2001, National Fire
                 Protection Association, Quincy, MA 02269.
18
Overcurrent-Protection Devices




                            An overcurrent-protection device must be able to recognize
                            the difference between an overcurrent and short circuit and
                            respond in the proper way. Slight overcurrents can be allowed
                            to continue for some period of time; but as the current
                            magnitude increases, the protection device must open faster.
                            Short circuits must be interrupted instantly.

Fusible Disconnect Switch   A fusible disconnect switch is one type of device used to
                            provide overcurrent protection. Properly sized fuses located
                            in the switch open the circuit when an overcurrent condition
                            exists.




Fuse                        A fuse is a one-shot device. The heat produced by overcurrent
                            causes the current carrying element to melt open,
                            disconnecting the load from the source voltage.




                                                                                            19
Nontime-Delay Fuses   Nontime-delay fuses provide excellent short-circuit protection.
                      When an overcurrent occurs, heat builds up rapidly in the
                      fuse. Nontime-delay fuses usually hold 500% of their rating
                      for approximately one-fourth second, after which the current-
                      carrying element melts. This means that these fuses should
                      not be used in motor circuits which often have inrush currents
                      greater than 500%.

Time-Delay Fuses      Time-delay fuses provide overload and short-circuit protection.
                      Time-delay fuses usually allow five times the rated current for
                      up to ten seconds to allow motors to start.

Fuse Classes          Fuses are grouped into classes based on their operating
                      and construction characteristics. Each class has an ampere
                      interrupting capacity (AIC) which is the amount of fault current
                      they are capable of interrupting without destroying the fuse
                      casing. Fuses are also rated according to the maximum
                      continuous current and maximum voltage they can handle.
                      Underwriters Laboratories (UL) establishes and standardizes
                      basic performance and physical specifications to develop
                      its safety-test procedures. These standards have resulted in
                      distinct classes of low-voltage fuses rated at 600 volts or less.
                      The following chart lists the fuse class and its AIC rating.




20
Circuit Breakers   Another device used for overcurrent protection is a circuit
                   breaker. The National Electrical Code® defines a circuit
                   breaker as a device designed to open and close a circuit by
                   nonautomatic means, and to open the circuit automatically on
                   a predetermined overcurrent without damage to itself when
                   properly applied within its rating.

                   Circuit breakers provide a manual means of energizing and
                   de-energizing a circuit. In addition, circuit breakers provide
                   automatic overcurrent protection of a circuit. A circuit breaker
                   allows a circuit to be reactivated quickly after a short circuit or
                   overload is cleared. Since it merely needs to be reset there is
                   nothing to replace after a short circuit.




Ampere Rating      Like fuses, every circuit breaker has a specific ampere, voltage,
                   and fault-current interruption rating. The ampere rating is the
                   maximum continuous current a circuit breaker can carry without
                   exceeding its rating. As a general rule, the circuit breaker
                   ampere rating should not exceed the conductor ampere rating.
                   For example, if the conductor is rated for 20 amps, the circuit
                   breaker rating should not exceed 20 amps. Siemens breakers
                   are rated on the basis of using 60° C or 75° C conductors. This
                   means that even if a conductor with a higher temperature rating
                   were used, the ampacity of the conductor must be figured on
                   its 60° C or 75° C rating.




                   NEC® and National Electrical Code® are registered trademarks of the
                   National Fire Protection Association. Reprinted with permission from NFPA
                   70-2002, the National Electrical Code®, Copyright© 2001, National Fire
                   Protection Association, Quincy, MA 02269.
                                                                                          21
There are some specific circumstances when the ampere rating
                      is permitted to be greater than the current-carrying capacity of
                      the circuit. For example, motor and welder circuits can exceed
                      conductor ampacity to allow for inrush currents and duty cycles
                      within limits established by NEC®.

                      Generally the ampere rating of a circuit breaker is selected at
                      125% of the continuous load current. This usually corresponds
                      to the conductor ampacity which is also selected at 125% of
                      continuous load current. For example, a 125 amp circuit breaker
                      would be selected for a load of 100 amps.

Voltage Rating        The voltage rating of the circuit breaker must be at least equal
                      to the supply voltage. The voltage rating of a circuit breaker can
                      be higher than the supply voltage, but never lower. For example,
                      a 480 VAC circuit breaker could be used on a 240 VAC circuit. A
                      240 VAC circuit breaker could not be used on a 480 VAC circuit.
                      The voltage rating is a function of the circuit breaker’s ability to
                      suppress the internal arc that occurs when the circuit breaker’s
                      contacts open.

Fault-Current         Circuit breakers are also rated according to the level of fault
Interrupting Rating   current they can interrupt. When applying a circuit breaker, one
                      must be selected to sustain the largest potential short-circuit
                      current which can occur in the selected application. Siemens
                      circuit breakers have interrupting ratings from 10,000 to
                      200,000 amps.




Review 2
                       1.   ____________ ____________ is a private company that
                            is nationally recognized as an independent testing
                            laboratory.

                       2.   The ____________ ____________ ____________
                            ____________ publishes the National Electrical Code®

                       3.   Class R fuses have an interupting rating of
                            ____________ amps.

                       4.   Installing an overcurrent protective device ahead of an
                            MCC or installing a main overcurrent protective device
                            within an MCC are two methods of meeting NEC®
                            Article ____________ .




22
Motor Control Centers




NEMA Definition   NEMA defines a motor control center in ICS-2-322 as being
                  a floor-mounted assembly of one or more enclosed vertical
                  sections having a horizontal common power bus and principally
                  containing combination motor control units. These units are
                  mounted one above the other in the vertical sections. The
                  sections may incorporate vertical buses connected to the
                  common power bus, thus extending the common power supply
                  to the individual units. Units may also connect directly to the
                  common power bus by suitable wiring.

                  According to the NEMA definition, motor control centers:

                  •    Are floor-mounted assemblies

                  •    Have one or more enclosed vertical sections

                  •    Have a common horizontal power bus

                  •    May incorporate vertical buses connected to the
                       common bus

                  •    Principally contain combination motor control units




                                                                              23
Vertical Sections             The motor control center is made up of a steel structure to
                              contain the combination motor control units, wireways, internal
                              wiring, and bus bars. From the NEMA definition it can be seen
                              that a motor control center is a floor-mounted assembly made
                              up of enclosed vertical sections. One vertical section may stand
                              alone as a complete motor control center, or several sections
                              may be bolted and bussed together. Vertical sections are
                              generally 20” wide by 90” high.




Horizontal and Vertical Bus   A bus is a conductor that serves as a common connection
                              for two or more circuits. It is represented schematically by a
                              straight line with a number of connections made to it.




24
In power circuits, such as motor control centers, a bus is made
              of a heavy-duty metal bar. These bars provide power to each
              of the combination motor control units. The vertical bus is
              connected to a corresponding horizontal bus and is isolated
              from the other bus bars.




Bus Support   The NEC® discusses bus bars used in motor control centers in
              Article 430.97(A), which states that busbars shall be protected
              from physical damage and be held firmly in place.

              Bus bracing is very important due to the increased available
              fault current in today’s modern power systems. In this example
              of a Siemens motor control center the horizontal bus is firmly
              bolted to molded supports. The vertical bus is either encased in
              a molded support or supported by bus brackets, depending on
              which MCC is supplied.




              NEC® and National Electrical Code® are registered trademarks of the
              National Fire Protection Association. Reprinted with permission from NFPA
              70-2002, the National Electrical Code®, Copyright© 2001, National Fire
              Protection Association, Quincy, MA 02269.
                                                                                     25
Bus Spacing              In addition, NEC® Table 430.97 requires 1” of clearance
                         between a live bus and ground, 1” of clearance between
                         phases through air, and 2” of clearance across a surface for
                         voltages over 250 volts. These spacings are used throughout
                         the horizontal and vertical bus in the MCC.




NEMA Phase Arrangement   NEMA requires bus bars to have phases in sequence so that
                         an installer can have the same fixed phase arrangement at each
                         termination point in any motor control center. The following
                         diagram illustrates accepted NEMA phase arrangements. It is
                         possible to have a non-NEMA phase sequence; however, this
                         would have to be clearly marked.




26
It should be noted that the NEMA phase arrangement
                  illustrated in the previous drawing is viewed from the front. The
                  vertical bus bars appear to be in reverse order when viewed
                  from the rear. Some motor control centers can have devices
                  installed on the front and rear of the motor control center.




Shipping Splits   When a motor control center is made up of more than one
                  vertical section, the sections are assembled together with a
                  common top- and bottom-frame assembly. For shipping, this
                  assembly can consist of a maximum of four 20” wide vertical
                  sections (80” maximum). Several assemblies can be bolted
                  and bussed together at the installation site to form a complete
                  lineup. In the following illustration one vertical section has been
                  moved to show the horizontal bus. In this case each horizontal
                  bus bar is a single continuous piece that extends through all
                  three sections.




                                                                                   27
When there are more than four sections or the customer
                           specifies a split between two vertical sections a splice kit
                           between the horizontal bus bars can be installed.




Combination Motor          Motor control centers are distinguished from other distribution
Control Units              devices, such as panelboards and switchboards, in that motor
                           control centers principally contain combination motor control
                           units. Panelboards and switchboards principally contain branch
                           circuit-protection devices such as circuit breakers and fusible
                           disconnects.

Underwriter’s Laboratory   UL defines a motor control center similarly to NEMA. UL will
                           allow use of branch circuit-protection units in a motor control
                           center provided their use does not make up a major portion of
                           the motor control center. In addition, UL 845 allows the use of
                           associated auxiliary devices and panelboards to be part of a
                           motor control center. Often, lighting transformers, panelboards,
                           and load centers are incorporated in motor control centers.




28

More Related Content

PDF
MCC Motor Control Center 1
PPT
Substation Training presentation
PDF
Basics of motor control centers
PPT
protection and relay scheme
PPTX
Resonant Converter
PPT
Bus Bar Protection
PDF
Tutorial on Distance and Over Current Protection
PPT
electric relay
MCC Motor Control Center 1
Substation Training presentation
Basics of motor control centers
protection and relay scheme
Resonant Converter
Bus Bar Protection
Tutorial on Distance and Over Current Protection
electric relay

What's hot (20)

PPT
POWER SYSTEM PROTECTION
PPTX
Lecture 7 Relay Coordination.pptx
PPTX
Protection & switchgear
PDF
Introduction to mv switchgear
PPTX
Motor Control Centre
PPTX
Power system protection devices
PDF
Switchgear presentation
PPTX
PPTX
automatic power factor correction
PPTX
Self Switching Power Supply
PPTX
Gas insulated substation
DOCX
Vaccum Circuit Breaker
PPTX
Sub station training ppt
PDF
SUB-STATION DESIGN AND PROTECTION (AN OVERVIEW)
PPT
PLC and Sensors Based Protection and Fault Detection of Induction Motors
PPTX
Switchgear and protection lecture 1
PDF
Inplant training about 110kv/11kv substation
PDF
A Case-Study on Blackout
PPT
Power System Protection basics
PDF
Sample calculation-for-differential-relays
POWER SYSTEM PROTECTION
Lecture 7 Relay Coordination.pptx
Protection & switchgear
Introduction to mv switchgear
Motor Control Centre
Power system protection devices
Switchgear presentation
automatic power factor correction
Self Switching Power Supply
Gas insulated substation
Vaccum Circuit Breaker
Sub station training ppt
SUB-STATION DESIGN AND PROTECTION (AN OVERVIEW)
PLC and Sensors Based Protection and Fault Detection of Induction Motors
Switchgear and protection lecture 1
Inplant training about 110kv/11kv substation
A Case-Study on Blackout
Power System Protection basics
Sample calculation-for-differential-relays
Ad

Similar to MCC Motor Control Center 2 (20)

PDF
Circuit breakers
PDF
Circuit Breakers
PPT
1-introducing-electricity-and-electrical-safety.ppt
PDF
Microcontroller based over voltage and under voltage protection circuit
PDF
Molded Case Circuit Breakers Technical Information
PDF
Fuji BC Series MCB
PPT
apm-et13e-chapter-10-electrical-safety.ppt
PPT
Electrical Safety Presentation for Basics Learning
PPT
Pd Maintenance
PDF
Lecture 3.pdf ,
PDF
Spd electrical protection handbook
PDF
Circuits breakers for industrial automation and process controling
PDF
Residential Surge Protection 2
PPTX
Element 11. ELECTRICITY safety and hazards
PDF
WIRING-AND-PROTECTION.pdf
PDF
Residential Surge Protection 1
PDF
Ocpd 07-23-13
PPTX
Short circuit
PPTX
Electrical-Safety-and-Human-Workplace123
Circuit breakers
Circuit Breakers
1-introducing-electricity-and-electrical-safety.ppt
Microcontroller based over voltage and under voltage protection circuit
Molded Case Circuit Breakers Technical Information
Fuji BC Series MCB
apm-et13e-chapter-10-electrical-safety.ppt
Electrical Safety Presentation for Basics Learning
Pd Maintenance
Lecture 3.pdf ,
Spd electrical protection handbook
Circuits breakers for industrial automation and process controling
Residential Surge Protection 2
Element 11. ELECTRICITY safety and hazards
WIRING-AND-PROTECTION.pdf
Residential Surge Protection 1
Ocpd 07-23-13
Short circuit
Electrical-Safety-and-Human-Workplace123
Ad

More from Sakshi Vashist (20)

PDF
Puzzles to puzzle you
PDF
Mind blowing puzzles
DOC
400 challenging puzzles
PDF
400 infy puzzles
PDF
Aptitude testing puzzles for freshers
PDF
MCC Motor Control Center 4
PDF
MCC Motor Control Center 3
PDF
Residential Surge Protection 3
PDF
Plc operation part 4
PDF
Plc operation part 3
PDF
Plc operation part 2
PDF
PLC operation part 1
PPT
Tg turbine
PPT
variable frequency drive (VFD) installation
PPT
Power plant instrumentation
PPT
All about paper making process
PPTX
About ballarpur industries limited
PPT
Basics of an ac drive - with motor basics
PPTX
Power saving ideas implemented practically
PPT
Boiler operation
Puzzles to puzzle you
Mind blowing puzzles
400 challenging puzzles
400 infy puzzles
Aptitude testing puzzles for freshers
MCC Motor Control Center 4
MCC Motor Control Center 3
Residential Surge Protection 3
Plc operation part 4
Plc operation part 3
Plc operation part 2
PLC operation part 1
Tg turbine
variable frequency drive (VFD) installation
Power plant instrumentation
All about paper making process
About ballarpur industries limited
Basics of an ac drive - with motor basics
Power saving ideas implemented practically
Boiler operation

Recently uploaded (20)

PDF
Elevate Cleaning Efficiency Using Tallfly Hair Remover Roller Factory Expertise
PDF
Katrina Stoneking: Shaking Up the Alcohol Beverage Industry
PPTX
HR Introduction Slide (1).pptx on hr intro
PPTX
New Microsoft PowerPoint Presentation - Copy.pptx
PDF
Types of control:Qualitative vs Quantitative
PPTX
Belch_12e_PPT_Ch18_Accessible_university.pptx
PDF
COST SHEET- Tender and Quotation unit 2.pdf
PDF
Traveri Digital Marketing Seminar 2025 by Corey and Jessica Perlman
PDF
SIMNET Inc – 2023’s Most Trusted IT Services & Solution Provider
PDF
Power and position in leadershipDOC-20250808-WA0011..pdf
PPTX
Business Ethics - An introduction and its overview.pptx
PDF
Dr. Enrique Segura Ense Group - A Self-Made Entrepreneur And Executive
PPTX
The Marketing Journey - Tracey Phillips - Marketing Matters 7-2025.pptx
PPTX
Probability Distribution, binomial distribution, poisson distribution
PDF
Deliverable file - Regulatory guideline analysis.pdf
PDF
Stem Cell Market Report | Trends, Growth & Forecast 2025-2034
PDF
Training And Development of Employee .pdf
PDF
Ôn tập tiếng anh trong kinh doanh nâng cao
DOCX
unit 1 COST ACCOUNTING AND COST SHEET
PPTX
Dragon_Fruit_Cultivation_in Nepal ppt.pptx
Elevate Cleaning Efficiency Using Tallfly Hair Remover Roller Factory Expertise
Katrina Stoneking: Shaking Up the Alcohol Beverage Industry
HR Introduction Slide (1).pptx on hr intro
New Microsoft PowerPoint Presentation - Copy.pptx
Types of control:Qualitative vs Quantitative
Belch_12e_PPT_Ch18_Accessible_university.pptx
COST SHEET- Tender and Quotation unit 2.pdf
Traveri Digital Marketing Seminar 2025 by Corey and Jessica Perlman
SIMNET Inc – 2023’s Most Trusted IT Services & Solution Provider
Power and position in leadershipDOC-20250808-WA0011..pdf
Business Ethics - An introduction and its overview.pptx
Dr. Enrique Segura Ense Group - A Self-Made Entrepreneur And Executive
The Marketing Journey - Tracey Phillips - Marketing Matters 7-2025.pptx
Probability Distribution, binomial distribution, poisson distribution
Deliverable file - Regulatory guideline analysis.pdf
Stem Cell Market Report | Trends, Growth & Forecast 2025-2034
Training And Development of Employee .pdf
Ôn tập tiếng anh trong kinh doanh nâng cao
unit 1 COST ACCOUNTING AND COST SHEET
Dragon_Fruit_Cultivation_in Nepal ppt.pptx

MCC Motor Control Center 2

  • 1. Design Standards Although several organizations are involved in establishing standards for the design, construction, and application of motor control centers, the primary standards are established by UL, NEMA, and the National Electrical Code® (NEC®). The following organizations have established standards which may be applied to motor control centers. It is beyond the scope of this course to cover every standard; however, reference will be made throughout the course to many important standards with which Siemens motor control centers comply. UL Underwriters Laboratories (UL) is a private company that is nationally recognized as an independent testing laboratory. UL tests products for safety and products that pass UL tests can carry a UL mark. Siemens motor control centers are designed to UL 845 standards. NEMA The National Electrical Manufacturers Association (NEMA) is an organization that, among other things, develops standards for electrical equipment. NEC The National Fire Protection Association (NFPA) is a nonprofit organization which publishes the National Electrical Code® (NEC®). The intent of the NEC® is to describe safe electrical practices. ANSI The American National Standards Institute (ANSI) is a nongovernmental organization that facilitates the development of standards by establishing a consensus among qualified groups. IEEE The Institute of Electrical and Electronic Engineers (IEEE) is an organization open to individual membership and provides a variety of services for its members. It also develops numerous standards for electrical and electronic equipment and practices. IEC The International Electrotechnical Commission (IEC) is an organization based in Geneva, Switzerland, with over 50 member nations. IEC writes standards for electrical and electronic equipment practices. NEC® and National Electrical Code® are registered trademarks of the National Fire Protection Association. 13
  • 2. Need for Circuit Protection Current and Temperature Current flow in a conductor always generates heat. The greater the current flow in any one size conductor, the hotter the conductor. Excess heat is damaging to electrical components and conductor insulation. For that reason conductors have a rated, continuous current-carrying capacity or ampacity. Overcurrent protection devices, such as fuses, are used to protect conductors from excessive current flow. Excessive current is referred to as overcurrent. The National Electrical Code® defines overcurrent as any current in excess of the rated current of equipment or the ampacity of a conductor. It may result from overload, short circuit, or ground fault (Article 100-definitions). NEC® and National Electrical Code® are registered trademarks of the National Fire Protection Association. Reprinted with permission from NFPA 70-2002, the National Electrical Code®, Copyright© 2001, National Fire Protection Association, Quincy, MA 02269. 14
  • 3. Overloads An overload occurs when too many devices are operated on a single circuit, or a piece of electrical equipment is made to work harder than it is rated design. For example, a motor rated for 10 amperes may draw 20, 30, or more amperes in an overload condition. In the following illustration, a package has become jammed on a conveyor, causing the motor to work harder and draw more current. Because the motor is drawing more current, it heats up. Damage will occur to the motor in a short time if the problem is not corrected or if the circuit not is shut down by the overcurrent protector. Conductor Insulation Motors, of course, are not the only devices that require circuit protection for an overload condition. Every circuit requires some form of protection against overcurrent. Heat is one of the major causes of insulation failure of any electrical component. High levels of heat to insulated wire can cause the insulation to breakdown, melt, or flake off, exposing conductors. 15
  • 4. Short Circuits When two bare conductors touch, a short circuit occurs. When a short circuit occurs, resistance drops to almost zero. Short circuit current can be thousands of times higher than normal operating current. Ohm’s Law demonstrates the relationship of current, voltage, and resistance. For example, a 240 volt motor with 24 Ω (ohms) of resistance would normally draw 10 amperes of current. When a short circuit develops, resistance drops. If resistance drops to 24 milliohms, current will be 10,000 amperes. 16
  • 5. Short-Circuit Current on When a short circuit occurs, current will continue to flow Unprotected Electrical in an unprotected electrical circuit. The peak short-circuit Circuits current of the first cycle is the greatest and is referred to as peak let-thru current (IP). The force of this current can cause damage to wires, switches, and other electrical components of a circuit. 2 There is also energy let-thru (I t). This destructive thermal force is capable of melting conductors. Short-Circuit Current on A properly used, overcurrent-protection device will open the 2 Protected Electrical Circuits circuit quickly, limiting peak let-thru current (IP) and energy (I t). 17
  • 6. Article 240 Circuit protection would be unnecessary if overloads and short circuits could be eliminated. Unfortunately, overloads and short circuits do occur. Article 240 of the NEC® covers overcurrent protection. You are encouraged to become familiar with this material. Article 240.1 states that: Overcurrent protection for conductors and equipment is provided to open the circuit if the current reaches a value that will cause an excessive or dangerous temperature in conductors or conductor insulation. Article 430.94 The National Electrical Code® requires overcurrent protection for motor control centers. NEC® article 430.94 states: Motor control centers shall be provided with overcurrent protection in accordance with Parts I, II, and IX of Article 240. The ampere rating or setting of the overcurrent protective device shall not exceed the rating of the common power bus. This protection shall be provided by (1) an overcurrent- protective device located ahead of the motor control center or (2) a main overcurrent-protective device located within the motor control center. There are two ways Article 430.94 can be met. An overcurrent- protection device can be installed ahead of the motor control center. A switchboard, for example, located upstream of the motor control center may contain the overcurrent-protection device for the motor control center. The second way to meet this requirement is to install a main over-current protection device within the motor control center. NEC® and National Electrical Code® are registered trademarks of the National Fire Protection Association. Reprinted with permission from NFPA 70-2002, the National Electrical Code®, Copyright© 2001, National Fire Protection Association, Quincy, MA 02269. 18
  • 7. Overcurrent-Protection Devices An overcurrent-protection device must be able to recognize the difference between an overcurrent and short circuit and respond in the proper way. Slight overcurrents can be allowed to continue for some period of time; but as the current magnitude increases, the protection device must open faster. Short circuits must be interrupted instantly. Fusible Disconnect Switch A fusible disconnect switch is one type of device used to provide overcurrent protection. Properly sized fuses located in the switch open the circuit when an overcurrent condition exists. Fuse A fuse is a one-shot device. The heat produced by overcurrent causes the current carrying element to melt open, disconnecting the load from the source voltage. 19
  • 8. Nontime-Delay Fuses Nontime-delay fuses provide excellent short-circuit protection. When an overcurrent occurs, heat builds up rapidly in the fuse. Nontime-delay fuses usually hold 500% of their rating for approximately one-fourth second, after which the current- carrying element melts. This means that these fuses should not be used in motor circuits which often have inrush currents greater than 500%. Time-Delay Fuses Time-delay fuses provide overload and short-circuit protection. Time-delay fuses usually allow five times the rated current for up to ten seconds to allow motors to start. Fuse Classes Fuses are grouped into classes based on their operating and construction characteristics. Each class has an ampere interrupting capacity (AIC) which is the amount of fault current they are capable of interrupting without destroying the fuse casing. Fuses are also rated according to the maximum continuous current and maximum voltage they can handle. Underwriters Laboratories (UL) establishes and standardizes basic performance and physical specifications to develop its safety-test procedures. These standards have resulted in distinct classes of low-voltage fuses rated at 600 volts or less. The following chart lists the fuse class and its AIC rating. 20
  • 9. Circuit Breakers Another device used for overcurrent protection is a circuit breaker. The National Electrical Code® defines a circuit breaker as a device designed to open and close a circuit by nonautomatic means, and to open the circuit automatically on a predetermined overcurrent without damage to itself when properly applied within its rating. Circuit breakers provide a manual means of energizing and de-energizing a circuit. In addition, circuit breakers provide automatic overcurrent protection of a circuit. A circuit breaker allows a circuit to be reactivated quickly after a short circuit or overload is cleared. Since it merely needs to be reset there is nothing to replace after a short circuit. Ampere Rating Like fuses, every circuit breaker has a specific ampere, voltage, and fault-current interruption rating. The ampere rating is the maximum continuous current a circuit breaker can carry without exceeding its rating. As a general rule, the circuit breaker ampere rating should not exceed the conductor ampere rating. For example, if the conductor is rated for 20 amps, the circuit breaker rating should not exceed 20 amps. Siemens breakers are rated on the basis of using 60° C or 75° C conductors. This means that even if a conductor with a higher temperature rating were used, the ampacity of the conductor must be figured on its 60° C or 75° C rating. NEC® and National Electrical Code® are registered trademarks of the National Fire Protection Association. Reprinted with permission from NFPA 70-2002, the National Electrical Code®, Copyright© 2001, National Fire Protection Association, Quincy, MA 02269. 21
  • 10. There are some specific circumstances when the ampere rating is permitted to be greater than the current-carrying capacity of the circuit. For example, motor and welder circuits can exceed conductor ampacity to allow for inrush currents and duty cycles within limits established by NEC®. Generally the ampere rating of a circuit breaker is selected at 125% of the continuous load current. This usually corresponds to the conductor ampacity which is also selected at 125% of continuous load current. For example, a 125 amp circuit breaker would be selected for a load of 100 amps. Voltage Rating The voltage rating of the circuit breaker must be at least equal to the supply voltage. The voltage rating of a circuit breaker can be higher than the supply voltage, but never lower. For example, a 480 VAC circuit breaker could be used on a 240 VAC circuit. A 240 VAC circuit breaker could not be used on a 480 VAC circuit. The voltage rating is a function of the circuit breaker’s ability to suppress the internal arc that occurs when the circuit breaker’s contacts open. Fault-Current Circuit breakers are also rated according to the level of fault Interrupting Rating current they can interrupt. When applying a circuit breaker, one must be selected to sustain the largest potential short-circuit current which can occur in the selected application. Siemens circuit breakers have interrupting ratings from 10,000 to 200,000 amps. Review 2 1. ____________ ____________ is a private company that is nationally recognized as an independent testing laboratory. 2. The ____________ ____________ ____________ ____________ publishes the National Electrical Code® 3. Class R fuses have an interupting rating of ____________ amps. 4. Installing an overcurrent protective device ahead of an MCC or installing a main overcurrent protective device within an MCC are two methods of meeting NEC® Article ____________ . 22
  • 11. Motor Control Centers NEMA Definition NEMA defines a motor control center in ICS-2-322 as being a floor-mounted assembly of one or more enclosed vertical sections having a horizontal common power bus and principally containing combination motor control units. These units are mounted one above the other in the vertical sections. The sections may incorporate vertical buses connected to the common power bus, thus extending the common power supply to the individual units. Units may also connect directly to the common power bus by suitable wiring. According to the NEMA definition, motor control centers: • Are floor-mounted assemblies • Have one or more enclosed vertical sections • Have a common horizontal power bus • May incorporate vertical buses connected to the common bus • Principally contain combination motor control units 23
  • 12. Vertical Sections The motor control center is made up of a steel structure to contain the combination motor control units, wireways, internal wiring, and bus bars. From the NEMA definition it can be seen that a motor control center is a floor-mounted assembly made up of enclosed vertical sections. One vertical section may stand alone as a complete motor control center, or several sections may be bolted and bussed together. Vertical sections are generally 20” wide by 90” high. Horizontal and Vertical Bus A bus is a conductor that serves as a common connection for two or more circuits. It is represented schematically by a straight line with a number of connections made to it. 24
  • 13. In power circuits, such as motor control centers, a bus is made of a heavy-duty metal bar. These bars provide power to each of the combination motor control units. The vertical bus is connected to a corresponding horizontal bus and is isolated from the other bus bars. Bus Support The NEC® discusses bus bars used in motor control centers in Article 430.97(A), which states that busbars shall be protected from physical damage and be held firmly in place. Bus bracing is very important due to the increased available fault current in today’s modern power systems. In this example of a Siemens motor control center the horizontal bus is firmly bolted to molded supports. The vertical bus is either encased in a molded support or supported by bus brackets, depending on which MCC is supplied. NEC® and National Electrical Code® are registered trademarks of the National Fire Protection Association. Reprinted with permission from NFPA 70-2002, the National Electrical Code®, Copyright© 2001, National Fire Protection Association, Quincy, MA 02269. 25
  • 14. Bus Spacing In addition, NEC® Table 430.97 requires 1” of clearance between a live bus and ground, 1” of clearance between phases through air, and 2” of clearance across a surface for voltages over 250 volts. These spacings are used throughout the horizontal and vertical bus in the MCC. NEMA Phase Arrangement NEMA requires bus bars to have phases in sequence so that an installer can have the same fixed phase arrangement at each termination point in any motor control center. The following diagram illustrates accepted NEMA phase arrangements. It is possible to have a non-NEMA phase sequence; however, this would have to be clearly marked. 26
  • 15. It should be noted that the NEMA phase arrangement illustrated in the previous drawing is viewed from the front. The vertical bus bars appear to be in reverse order when viewed from the rear. Some motor control centers can have devices installed on the front and rear of the motor control center. Shipping Splits When a motor control center is made up of more than one vertical section, the sections are assembled together with a common top- and bottom-frame assembly. For shipping, this assembly can consist of a maximum of four 20” wide vertical sections (80” maximum). Several assemblies can be bolted and bussed together at the installation site to form a complete lineup. In the following illustration one vertical section has been moved to show the horizontal bus. In this case each horizontal bus bar is a single continuous piece that extends through all three sections. 27
  • 16. When there are more than four sections or the customer specifies a split between two vertical sections a splice kit between the horizontal bus bars can be installed. Combination Motor Motor control centers are distinguished from other distribution Control Units devices, such as panelboards and switchboards, in that motor control centers principally contain combination motor control units. Panelboards and switchboards principally contain branch circuit-protection devices such as circuit breakers and fusible disconnects. Underwriter’s Laboratory UL defines a motor control center similarly to NEMA. UL will allow use of branch circuit-protection units in a motor control center provided their use does not make up a major portion of the motor control center. In addition, UL 845 allows the use of associated auxiliary devices and panelboards to be part of a motor control center. Often, lighting transformers, panelboards, and load centers are incorporated in motor control centers. 28