Miniature circuit breaker(mcb)
Miniature Circuit Breakers (MCB)
Multi 9
 Protect cables against
overloads and short
circuits
 Let the current flow
without overheating on
cables
 Open and close a circuit
under rated current
 Protect against insulation
faults (see earth leakage
protection module)
Definition
Main functions
Miniature circuit = switch + trip unit breaker (MCB) 4
 Symbol
 A mechanical system to open and close the
circuit
 A bimetal strip to act against overloads
 A magnetic trip to act against short circuits
Definition
A Multi 9 circuit breaker has:
Miniature circuit = switch + trip unit breaker (MCB) 4
 It has standardized modular dimensions
  125A
  50 kA
  440 V CA
Definition
Main performances
It fits in your pocket... 4
Definition
 Multi 9 standard
 Multi 9 switchgear comes in 9 mm pitch 4
width
symmetrical
rail
external
part
depth
60
10 maxi
35
45
maxi
44 maxi
21.3
81
 The modular design meets 2
criteria:
 mounting on a 35 mm
symmetrical rail
 dimensions
- modules in widths of
17.5 mm + 0.5 - 0
- external part = 45 mm
- depth between 55 and 70 mm
The technology
Active parts
C60N NC100 / NC125
terminal
fixed contact
moving
contact
strip braid
magnetic
trip
load side
terminal
terminal
bimetral strip
strip braid
moving
contact
magnetic trip
load side
terminal
strip braid
bimetal strip
4
Overload protection
bimetal
tripping bar
bimetal
tripping bar
screw
calibration
strip
braid
NC45 NC100 / NC125
 A bimetal strip is used:
 to protect the cable against overloads
 symbol:
 principle of the bimetal: in a Multi 9 circuit
breaker 4
 Thermal tripping curve
 the "thermal" part of the
tripping curve must be in
accordance with the
standard
Overload protection
Legend:
In = rated current
Ind = no tripping current
Id = tripping current 4
tripping
no
tripping
destruction
of bimetal
accuracy
t (s)
I/In
In Ind Id
Overload protection
Simultaneous multi-pole tripping 4
 Temperature derating
 our circuit breakers do not have temperature
compensation
 if the calibration temperature is different from
the ambient temperature: derating is required
Short-circuit protection
Short-circuit current is given as RMS or peak
(Isc or Îsc)
RMS = Root Mean Square in symmetrical DC
(with PF = I)
Short-circuit protection must limit thermal stress in the
cable in order to prevent cable damage (which may
reach vaporization of the copper in some cases)
Comments slide 29
Short-circuit protection
"By-pass" technique for the
protection of sensitive parts
of the circuit breaker DC
breaking is difficult
"By-pass" technique for the protection of
sensitive parts of the circuit breaker (magnetic
trip)
The arc in Multi 9 circuit breakers
2 breaking techniques used by Multi 9 4
arcing
horn arcing
horn
NC45 NC100 / NC125
Short-circuit protection
Magnetic tripping curve
Our curves are instantaneous tripping curves 4
Legend:
Ind = no tripping current
Id = tripping current
destruction
of the solenoid
tripping
no
tripping
t (s)
I/In
Ind Id
 B curve
 3 and 5 In protection
low short-circuit current
generators
The magnetic tripping levels with high inrush
current:
like LV/LV transformers
 C Curve
 5 and 10 In control and protection of
circuits with high short-circuit current
in industrial and domestic distributions
 D and K curves tripping betwen
 tripping: 10 to 14 In; more particulary
adopted for installations with high
inrush currents like LV/LV transformers
 Z curve
 2.4 to 3.6 In protection against
electronic circuits
 MA curve
 12 In; protection only against
short-circuit and high inrush currents
such as motors, coil 4
G
M
 Side panel marking:
Marking
 Front panel marking:
Circuit breaker marking is governed by strict
rules in accordance with the standards and
decisions made by the manufacturer 4
Choosing a circuit breaker
In conclusion
 A Multi 9 circuit breaker is determined by:
 rating
 breaking capacity
 number of poles
 voltage
 tripping curve
 standard
 frequency
 type of load 4
Auxiliaries: C60
 SD: alarm switch
 MX + OF: shunt trip
 MN: undervoltage release
The information is transmitted via a
mechanical link C60/NC100 and NC125
auxiliaries are not compatible 4
54 mm maxi
 4 types of auxiliaries for our
Multi 9 circuit breakers
 OF: indication switch
MX+OF
OF SD C60
44/3
MN
51/3
52/3
54/3
53/3
Auxiliaries: NC100 - NC125
The information is transmitted via a
mechanical link C60/NC100 and NC125
auxiliaries are not compatible 4
NC100H MX+OF
or Vigi
MN or
OF SD
33/3
34/3
35/3
36/3
27/3
 SD: alarm switch
 MX + OF: shunt trip
 MN: undervoltage release
 4 types of auxiliaries for our
Multi 9 circuit breakers
 OF: indication switch
THANKYOU

More Related Content

PDF
PPTX
Protection & switchgear
PDF
Power system protection topic 1
PDF
Wiring man en 2012
PPTX
Basics of Diesel Generator System
PPTX
Presentation on switchgear
PPTX
control circuit
Protection & switchgear
Power system protection topic 1
Wiring man en 2012
Basics of Diesel Generator System
Presentation on switchgear
control circuit

What's hot (20)

PPT
PDF
Schneider Technical Guide - Medium Voltage Equipment Designers
PPTX
Operation of hydro power plants
PPTX
Electrical HT/LT Motor protection
PPTX
Switchgear and protection 5
PDF
Basics of Electrical Machines
PPTX
Electrical transmission line
PPT
Electrical power transmission system
PDF
MCC PANEL WIRING, GA and BOM Sample
DOCX
5. Switchyard & Substation
PPTX
Read and Understand The Electrical Diagram
PPTX
Basics of overcurrent protection
PPT
POWER SYSTEM PROTECTION
PPTX
Types of relay
PPTX
Circuit protection devices perfect ppt
PDF
Switchgear presentation
PPTX
ppt of EEE(MCB)
PPTX
ELECTRICAL WIRING AND MAINTENANCE
PPTX
Earthing system
PDF
Electrical Design calculations
Schneider Technical Guide - Medium Voltage Equipment Designers
Operation of hydro power plants
Electrical HT/LT Motor protection
Switchgear and protection 5
Basics of Electrical Machines
Electrical transmission line
Electrical power transmission system
MCC PANEL WIRING, GA and BOM Sample
5. Switchyard & Substation
Read and Understand The Electrical Diagram
Basics of overcurrent protection
POWER SYSTEM PROTECTION
Types of relay
Circuit protection devices perfect ppt
Switchgear presentation
ppt of EEE(MCB)
ELECTRICAL WIRING AND MAINTENANCE
Earthing system
Electrical Design calculations
Ad

Similar to Miniature Circuit breaker.ppt (20)

PPT
Miniature Circuit Breakers (MCB) By Chhotray Tiyu
PPTX
Circuit Breakers for Low Voltage Applications
PPTX
Double Pole Mcb
PDF
MCC Design and understanding iec6139 standard
PPSX
Electrical System.ppsx
PPTX
Low Voltage Circuit Breaker
PDF
Mcb catalogue
PDF
Tongou electrical catalogue
PDF
Mccb elcb technical note dienhathe.org
PPTX
Failure of fuse & mcb
PPTX
Failure of fuse & mcb
PPT
Circuit Breaker
PPTX
Circuit breaker
PPTX
Circuit breaker
PPTX
protection scheme of a grid substation prsentation
PPTX
MCB and Fuse (2) (3).pptx
PPTX
MCB and Fuse (11).pptx
PDF
PPS
Electromagnetic and-electronic-circuitbreaker-[technolead]
PPTX
Electrical Installation PPT (Basic Electrical Engineering)
Miniature Circuit Breakers (MCB) By Chhotray Tiyu
Circuit Breakers for Low Voltage Applications
Double Pole Mcb
MCC Design and understanding iec6139 standard
Electrical System.ppsx
Low Voltage Circuit Breaker
Mcb catalogue
Tongou electrical catalogue
Mccb elcb technical note dienhathe.org
Failure of fuse & mcb
Failure of fuse & mcb
Circuit Breaker
Circuit breaker
Circuit breaker
protection scheme of a grid substation prsentation
MCB and Fuse (2) (3).pptx
MCB and Fuse (11).pptx
Electromagnetic and-electronic-circuitbreaker-[technolead]
Electrical Installation PPT (Basic Electrical Engineering)
Ad

Recently uploaded (20)

PPTX
Fundamentals of safety and accident prevention -final (1).pptx
PDF
Level 2 – IBM Data and AI Fundamentals (1)_v1.1.PDF
DOCX
ASol_English-Language-Literature-Set-1-27-02-2023-converted.docx
PDF
Automation-in-Manufacturing-Chapter-Introduction.pdf
PPTX
6ME3A-Unit-II-Sensors and Actuators_Handouts.pptx
PDF
Unit I ESSENTIAL OF DIGITAL MARKETING.pdf
PDF
null (2) bgfbg bfgb bfgb fbfg bfbgf b.pdf
PPT
Mechanical Engineering MATERIALS Selection
DOCX
573137875-Attendance-Management-System-original
PDF
Embodied AI: Ushering in the Next Era of Intelligent Systems
PDF
737-MAX_SRG.pdf student reference guides
PPTX
CARTOGRAPHY AND GEOINFORMATION VISUALIZATION chapter1 NPTE (2).pptx
PPTX
Safety Seminar civil to be ensured for safe working.
PDF
BMEC211 - INTRODUCTION TO MECHATRONICS-1.pdf
PPT
Project quality management in manufacturing
PPTX
Sustainable Sites - Green Building Construction
PPTX
Foundation to blockchain - A guide to Blockchain Tech
PPTX
UNIT 4 Total Quality Management .pptx
PPTX
Internet of Things (IOT) - A guide to understanding
PPTX
Current and future trends in Computer Vision.pptx
Fundamentals of safety and accident prevention -final (1).pptx
Level 2 – IBM Data and AI Fundamentals (1)_v1.1.PDF
ASol_English-Language-Literature-Set-1-27-02-2023-converted.docx
Automation-in-Manufacturing-Chapter-Introduction.pdf
6ME3A-Unit-II-Sensors and Actuators_Handouts.pptx
Unit I ESSENTIAL OF DIGITAL MARKETING.pdf
null (2) bgfbg bfgb bfgb fbfg bfbgf b.pdf
Mechanical Engineering MATERIALS Selection
573137875-Attendance-Management-System-original
Embodied AI: Ushering in the Next Era of Intelligent Systems
737-MAX_SRG.pdf student reference guides
CARTOGRAPHY AND GEOINFORMATION VISUALIZATION chapter1 NPTE (2).pptx
Safety Seminar civil to be ensured for safe working.
BMEC211 - INTRODUCTION TO MECHATRONICS-1.pdf
Project quality management in manufacturing
Sustainable Sites - Green Building Construction
Foundation to blockchain - A guide to Blockchain Tech
UNIT 4 Total Quality Management .pptx
Internet of Things (IOT) - A guide to understanding
Current and future trends in Computer Vision.pptx

Miniature Circuit breaker.ppt

  • 1. Vadodara institute of engineering,kotambi NAME:NAFISKHANPATHAN(13ELEE181) BARIYA VIPUL(13ELEE182) PATEL AMIT(13ELEE180) BRANCH:EE-2 PPT OF EEE
  • 4.  Protect cables against overloads and short circuits  Let the current flow without overheating on cables  Open and close a circuit under rated current  Protect against insulation faults (see earth leakage protection module) Definition Main functions Miniature circuit = switch + trip unit breaker (MCB) 4  Symbol
  • 5.  A mechanical system to open and close the circuit  A bimetal strip to act against overloads  A magnetic trip to act against short circuits Definition A Multi 9 circuit breaker has: Miniature circuit = switch + trip unit breaker (MCB) 4
  • 6.  It has standardized modular dimensions   125A   50 kA   440 V CA Definition Main performances It fits in your pocket... 4
  • 7. Definition  Multi 9 standard  Multi 9 switchgear comes in 9 mm pitch 4 width symmetrical rail external part depth 60 10 maxi 35 45 maxi 44 maxi 21.3 81  The modular design meets 2 criteria:  mounting on a 35 mm symmetrical rail  dimensions - modules in widths of 17.5 mm + 0.5 - 0 - external part = 45 mm - depth between 55 and 70 mm
  • 8. The technology Active parts C60N NC100 / NC125 terminal fixed contact moving contact strip braid magnetic trip load side terminal terminal bimetral strip strip braid moving contact magnetic trip load side terminal strip braid bimetal strip 4
  • 9. Overload protection bimetal tripping bar bimetal tripping bar screw calibration strip braid NC45 NC100 / NC125  A bimetal strip is used:  to protect the cable against overloads  symbol:  principle of the bimetal: in a Multi 9 circuit breaker 4
  • 10.  Thermal tripping curve  the "thermal" part of the tripping curve must be in accordance with the standard Overload protection Legend: In = rated current Ind = no tripping current Id = tripping current 4 tripping no tripping destruction of bimetal accuracy t (s) I/In In Ind Id
  • 11. Overload protection Simultaneous multi-pole tripping 4  Temperature derating  our circuit breakers do not have temperature compensation  if the calibration temperature is different from the ambient temperature: derating is required
  • 12. Short-circuit protection Short-circuit current is given as RMS or peak (Isc or Îsc) RMS = Root Mean Square in symmetrical DC (with PF = I) Short-circuit protection must limit thermal stress in the cable in order to prevent cable damage (which may reach vaporization of the copper in some cases) Comments slide 29
  • 13. Short-circuit protection "By-pass" technique for the protection of sensitive parts of the circuit breaker DC breaking is difficult "By-pass" technique for the protection of sensitive parts of the circuit breaker (magnetic trip) The arc in Multi 9 circuit breakers 2 breaking techniques used by Multi 9 4 arcing horn arcing horn NC45 NC100 / NC125
  • 14. Short-circuit protection Magnetic tripping curve Our curves are instantaneous tripping curves 4 Legend: Ind = no tripping current Id = tripping current destruction of the solenoid tripping no tripping t (s) I/In Ind Id
  • 15.  B curve  3 and 5 In protection low short-circuit current generators The magnetic tripping levels with high inrush current: like LV/LV transformers  C Curve  5 and 10 In control and protection of circuits with high short-circuit current in industrial and domestic distributions  D and K curves tripping betwen  tripping: 10 to 14 In; more particulary adopted for installations with high inrush currents like LV/LV transformers  Z curve  2.4 to 3.6 In protection against electronic circuits  MA curve  12 In; protection only against short-circuit and high inrush currents such as motors, coil 4 G M
  • 16.  Side panel marking: Marking  Front panel marking: Circuit breaker marking is governed by strict rules in accordance with the standards and decisions made by the manufacturer 4
  • 17. Choosing a circuit breaker In conclusion  A Multi 9 circuit breaker is determined by:  rating  breaking capacity  number of poles  voltage  tripping curve  standard  frequency  type of load 4
  • 18. Auxiliaries: C60  SD: alarm switch  MX + OF: shunt trip  MN: undervoltage release The information is transmitted via a mechanical link C60/NC100 and NC125 auxiliaries are not compatible 4 54 mm maxi  4 types of auxiliaries for our Multi 9 circuit breakers  OF: indication switch MX+OF OF SD C60 44/3 MN 51/3 52/3 54/3 53/3
  • 19. Auxiliaries: NC100 - NC125 The information is transmitted via a mechanical link C60/NC100 and NC125 auxiliaries are not compatible 4 NC100H MX+OF or Vigi MN or OF SD 33/3 34/3 35/3 36/3 27/3  SD: alarm switch  MX + OF: shunt trip  MN: undervoltage release  4 types of auxiliaries for our Multi 9 circuit breakers  OF: indication switch