SlideShare a Scribd company logo
9
Most read
10
Most read
11
Most read
NGR & Zig-Zag Transformer.pptx
 What is NGR ?
 Why use an NGR ?
 What is a Zig – Zag Transformer ?
 How a Zig – Zag Transformer works
 Neutral Grounding Devices Data
 NGR System before Co-Gen
 NGR System after Co-Gen
 Ground Fault Detection
 NGR Operational Schemes
 Ground Fault Protection Settings
 NGR stands for Neutral Grounding Resistor (also called Neutral Earthing
Resistor )
 NGR limits the current that would flow through the neutral point of a
transformer or generator in the event of an earth fault.
 NGR limits fault currents to a value that does not cause any further
damage to switchgear, generators or transformers beyond what has
already been caused by the fault itself.
 There are various types of system grounding, including:
 Solid grounding
 High resistance grounding
 Low resistance grounding
 An Electrical Power System is usually a 3 phase
balanced system
 Under normal load the treatment of neutral does
not effect behavior of network
 However in case of a line to ground fault the
behavior of network depends decisively on the
neutral grounding method used
NGR & Zig-Zag Transformer.pptx
 Also known as earthing transformer
 A Zigzag transformer is a special purpose
transformer with a zigzag winding arrangement
 It has primary windings but no secondary winding
 Application
 To derive an earth reference point for an ungrounded
electrical system To control harmonic currents
NGR & Zig-Zag Transformer.pptx
NGR & Zig-Zag Transformer.pptx
 As with other three-phase
transformers, the zigzag transformer
contains six coils on three cores. The
first coil on each core is connected
contrariwise to the second coil on the
next core. The second coils are then
all tied together to form the neutral
and the phases are connected to the
primary coils. Each phase, therefore,
couples with each other phase and
the voltages cancel out. As such, there
would be negligible current through
the neutral pole and it can be tied to
ground.
 If one phase, or more, faults to earth, the
voltage applied to each phase of the
transformer is no longer in balance; fluxes
in the windings no longer oppose. Zero
sequence (earth fault) current exists
between the transformer’s neutral to the
faulting phase. Hence, the purpose of a
zigzag transformer is to provide a return
path for earth faults on delta-connected
systems. With negligible current in the
neutral under normal conditions, engineers
typically elect to under size the
transformer; a short time rating is applied
(i.e., the transformer can only carry full
rated current for, say, 60 s).
 NGR
 Nominal voltage = 6 / √3 kV
 Short time current = 1000 A
 Resistance = 3.1 Ω
 Operation time = 10 Sec
 Earthing Transformer
 Vector group ZN
 Nominal voltage = 6kV
 Short time current = 1000 A
 Short time power = 3.46 MVA
 Operation time = 10 Sec
 The neutrals of all STGs were connected to one common neutral
resistor
 The old NGR has a resistance of 3.2 Ω to limit the earth fault
current to 1000 A
 The protection relays and their respective CTs are chosen
accordingly (800/1, 1200/1)
 Relays are set to 20% i.e. 160A & 240A
 At least two times of this current is required to ensure tripping
time of less than 1 sec
NGR & Zig-Zag Transformer.pptx
 Three new GTGs of 14 MVA each
 The neutrals of the three generators are connected to three
individual neutral resistors
 Each NGR has a resistance of 340 Ω and in case of fault feeds a
neutral current of 10 A
 An EDG of 2.25 MVA is also installed with an NGR of 9 Ω and feeds
a current of 250 A
 No more than three out of six STGs or GTGs can be operated at a
time to limit the max S.C current to the rated value of SWGR
NGR & Zig-Zag Transformer.pptx
 If at least one STG is running, the ground fault current is high enough to
ensure ground fault detection & tripping
 However if only GTGs are running the ground fault is a max of 30 A
 This current is clearly lower than min current that can be detected by
existing protection relays
 The only way to ensure selective ground fault tripping is to increase the
ground fault current to a level which ensures clear detection by existing
relays
 To increase ground fault current a zig-zag transformer with an NGR is
installed which shall limit ground fault current to 1000 A
NGR & Zig-Zag Transformer.pptx
NGR & Zig-Zag Transformer.pptx
NGR & Zig-Zag Transformer.pptx
 Load feeders
 Characteristic: Normal inverse
 Pick-up current: 240 A
 Time multiplier: 0.1 sec
 Inter tie cables
 Characteristic: Normal inverse
 Pick-up current: 300 A (10% of nominal CT current)
 Time multiplier: 0.1 sec
 Earthing transformer
 Characteristic: definite time
 Pick-up current: 600 A
 Time multiplier: 0.1 sec
 Motors
 Characteristic: Normal inverse
 Pick-up current: 30-50 A (10% of nominal CT current)
 Time multiplier: 0.1 sec
NGR & Zig-Zag Transformer.pptx

More Related Content

PDF
Line Differential - Test report for Alstom make Micom P546 relay
PPTX
Calculation of short circuit currents
PPTX
ALSTOM – Micom
PDF
Protective Device Coordination
PDF
NETWORK PROTECTION & AUTOMATION GUIDE, EDITION
PPT
CT design aspects - Nageswar-6
PDF
Auto synch considerations methods
PDF
Relay testing procedure
Line Differential - Test report for Alstom make Micom P546 relay
Calculation of short circuit currents
ALSTOM – Micom
Protective Device Coordination
NETWORK PROTECTION & AUTOMATION GUIDE, EDITION
CT design aspects - Nageswar-6
Auto synch considerations methods
Relay testing procedure

What's hot (20)

PDF
RTCC & AVR
PDF
Sample calculation-for-differential-relays
PPTX
presentation on substation layout and BUS bar arrangement.
PDF
Overcurrent protection
PPT
Installation Operation & Maintenance of 33kV & 11kV Switchgear
DOCX
Interlocking on switchgear principles
PPT
Instrument transformer CT & PT
PDF
Practical handbook-for-relay-protection-engineers
PPT
Transformer design and protection
PPTX
Unit 4 Automatic Generation Control
PDF
Transformer protection
PDF
Switchgear presentation
PPTX
PPTX
Current Transformer.pptx
PDF
Per unit calculation
PPTX
Electrical Grid Substation
PPTX
Various Bus-Bar Arrangements.
PPT
Reactors
PPT
EXCITATION SYSTEM.ppt
PPT
Per unit systems in power systems
RTCC & AVR
Sample calculation-for-differential-relays
presentation on substation layout and BUS bar arrangement.
Overcurrent protection
Installation Operation & Maintenance of 33kV & 11kV Switchgear
Interlocking on switchgear principles
Instrument transformer CT & PT
Practical handbook-for-relay-protection-engineers
Transformer design and protection
Unit 4 Automatic Generation Control
Transformer protection
Switchgear presentation
Current Transformer.pptx
Per unit calculation
Electrical Grid Substation
Various Bus-Bar Arrangements.
Reactors
EXCITATION SYSTEM.ppt
Per unit systems in power systems
Ad

Similar to NGR & Zig-Zag Transformer.pptx (20)

PDF
NEUTRAL TO GROUND BONDING.pdf
PDF
Parameter Estimation of Neutral Grounding Reactor for a Single Line to Ground...
PDF
Generator grounding
PDF
Neutral Grounding Resistors
PPTX
Generator Grounding Slides In Power Systems Protection.pptx
PDF
Vignettes in Grounding
PPTX
ECONOMICS_RAZA SHAUD_35501622018.pptx for all
PPT
Generator protection by bhushan kumbhalkar
PDF
Power Station Electrical Protection
PPTX
Mv system neutral grounding
PPTX
TOPIC 6.2- Power System Faults and Protection System.pptx
PPTX
Power System Faults and Protection System
PPTX
Earthing grounding protection Difference between earthing and grounding.pptx
PPTX
PSP - Slides CH # 1 (Introdution to Protective Relaying).pptx
PPTX
Neutral grounding
PPTX
Malay ppt psa
PPTX
Explains about Basic of engineering BoE Unit 1.pptx
PPTX
GIS substation Information (Detailed Report)
PPTX
Multi – Grounding in the Distribution System.pptx
PPTX
Earthing and grounding.pptx
NEUTRAL TO GROUND BONDING.pdf
Parameter Estimation of Neutral Grounding Reactor for a Single Line to Ground...
Generator grounding
Neutral Grounding Resistors
Generator Grounding Slides In Power Systems Protection.pptx
Vignettes in Grounding
ECONOMICS_RAZA SHAUD_35501622018.pptx for all
Generator protection by bhushan kumbhalkar
Power Station Electrical Protection
Mv system neutral grounding
TOPIC 6.2- Power System Faults and Protection System.pptx
Power System Faults and Protection System
Earthing grounding protection Difference between earthing and grounding.pptx
PSP - Slides CH # 1 (Introdution to Protective Relaying).pptx
Neutral grounding
Malay ppt psa
Explains about Basic of engineering BoE Unit 1.pptx
GIS substation Information (Detailed Report)
Multi – Grounding in the Distribution System.pptx
Earthing and grounding.pptx
Ad

Recently uploaded (20)

PPTX
Infosys Presentation by1.Riyan Bagwan 2.Samadhan Naiknavare 3.Gaurav Shinde 4...
PPTX
Strings in CPP - Strings in C++ are sequences of characters used to store and...
PPTX
KTU 2019 -S7-MCN 401 MODULE 2-VINAY.pptx
PDF
PRIZ Academy - 9 Windows Thinking Where to Invest Today to Win Tomorrow.pdf
PPTX
UNIT 4 Total Quality Management .pptx
PDF
PPT on Performance Review to get promotions
PPTX
M Tech Sem 1 Civil Engineering Environmental Sciences.pptx
PPTX
MET 305 2019 SCHEME MODULE 2 COMPLETE.pptx
PDF
keyrequirementskkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkk
PDF
Digital Logic Computer Design lecture notes
PDF
composite construction of structures.pdf
PPTX
Foundation to blockchain - A guide to Blockchain Tech
PPTX
Construction Project Organization Group 2.pptx
PDF
Arduino robotics embedded978-1-4302-3184-4.pdf
PPTX
Geodesy 1.pptx...............................................
PDF
July 2025 - Top 10 Read Articles in International Journal of Software Enginee...
PDF
BMEC211 - INTRODUCTION TO MECHATRONICS-1.pdf
PDF
Evaluating the Democratization of the Turkish Armed Forces from a Normative P...
PPTX
Sustainable Sites - Green Building Construction
PPTX
CARTOGRAPHY AND GEOINFORMATION VISUALIZATION chapter1 NPTE (2).pptx
Infosys Presentation by1.Riyan Bagwan 2.Samadhan Naiknavare 3.Gaurav Shinde 4...
Strings in CPP - Strings in C++ are sequences of characters used to store and...
KTU 2019 -S7-MCN 401 MODULE 2-VINAY.pptx
PRIZ Academy - 9 Windows Thinking Where to Invest Today to Win Tomorrow.pdf
UNIT 4 Total Quality Management .pptx
PPT on Performance Review to get promotions
M Tech Sem 1 Civil Engineering Environmental Sciences.pptx
MET 305 2019 SCHEME MODULE 2 COMPLETE.pptx
keyrequirementskkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkk
Digital Logic Computer Design lecture notes
composite construction of structures.pdf
Foundation to blockchain - A guide to Blockchain Tech
Construction Project Organization Group 2.pptx
Arduino robotics embedded978-1-4302-3184-4.pdf
Geodesy 1.pptx...............................................
July 2025 - Top 10 Read Articles in International Journal of Software Enginee...
BMEC211 - INTRODUCTION TO MECHATRONICS-1.pdf
Evaluating the Democratization of the Turkish Armed Forces from a Normative P...
Sustainable Sites - Green Building Construction
CARTOGRAPHY AND GEOINFORMATION VISUALIZATION chapter1 NPTE (2).pptx

NGR & Zig-Zag Transformer.pptx

  • 2.  What is NGR ?  Why use an NGR ?  What is a Zig – Zag Transformer ?  How a Zig – Zag Transformer works  Neutral Grounding Devices Data  NGR System before Co-Gen  NGR System after Co-Gen  Ground Fault Detection  NGR Operational Schemes  Ground Fault Protection Settings
  • 3.  NGR stands for Neutral Grounding Resistor (also called Neutral Earthing Resistor )  NGR limits the current that would flow through the neutral point of a transformer or generator in the event of an earth fault.  NGR limits fault currents to a value that does not cause any further damage to switchgear, generators or transformers beyond what has already been caused by the fault itself.  There are various types of system grounding, including:  Solid grounding  High resistance grounding  Low resistance grounding
  • 4.  An Electrical Power System is usually a 3 phase balanced system  Under normal load the treatment of neutral does not effect behavior of network  However in case of a line to ground fault the behavior of network depends decisively on the neutral grounding method used
  • 6.  Also known as earthing transformer  A Zigzag transformer is a special purpose transformer with a zigzag winding arrangement  It has primary windings but no secondary winding  Application  To derive an earth reference point for an ungrounded electrical system To control harmonic currents
  • 9.  As with other three-phase transformers, the zigzag transformer contains six coils on three cores. The first coil on each core is connected contrariwise to the second coil on the next core. The second coils are then all tied together to form the neutral and the phases are connected to the primary coils. Each phase, therefore, couples with each other phase and the voltages cancel out. As such, there would be negligible current through the neutral pole and it can be tied to ground.
  • 10.  If one phase, or more, faults to earth, the voltage applied to each phase of the transformer is no longer in balance; fluxes in the windings no longer oppose. Zero sequence (earth fault) current exists between the transformer’s neutral to the faulting phase. Hence, the purpose of a zigzag transformer is to provide a return path for earth faults on delta-connected systems. With negligible current in the neutral under normal conditions, engineers typically elect to under size the transformer; a short time rating is applied (i.e., the transformer can only carry full rated current for, say, 60 s).
  • 11.  NGR  Nominal voltage = 6 / √3 kV  Short time current = 1000 A  Resistance = 3.1 Ω  Operation time = 10 Sec  Earthing Transformer  Vector group ZN  Nominal voltage = 6kV  Short time current = 1000 A  Short time power = 3.46 MVA  Operation time = 10 Sec
  • 12.  The neutrals of all STGs were connected to one common neutral resistor  The old NGR has a resistance of 3.2 Ω to limit the earth fault current to 1000 A  The protection relays and their respective CTs are chosen accordingly (800/1, 1200/1)  Relays are set to 20% i.e. 160A & 240A  At least two times of this current is required to ensure tripping time of less than 1 sec
  • 14.  Three new GTGs of 14 MVA each  The neutrals of the three generators are connected to three individual neutral resistors  Each NGR has a resistance of 340 Ω and in case of fault feeds a neutral current of 10 A  An EDG of 2.25 MVA is also installed with an NGR of 9 Ω and feeds a current of 250 A  No more than three out of six STGs or GTGs can be operated at a time to limit the max S.C current to the rated value of SWGR
  • 16.  If at least one STG is running, the ground fault current is high enough to ensure ground fault detection & tripping  However if only GTGs are running the ground fault is a max of 30 A  This current is clearly lower than min current that can be detected by existing protection relays  The only way to ensure selective ground fault tripping is to increase the ground fault current to a level which ensures clear detection by existing relays  To increase ground fault current a zig-zag transformer with an NGR is installed which shall limit ground fault current to 1000 A
  • 20.  Load feeders  Characteristic: Normal inverse  Pick-up current: 240 A  Time multiplier: 0.1 sec  Inter tie cables  Characteristic: Normal inverse  Pick-up current: 300 A (10% of nominal CT current)  Time multiplier: 0.1 sec
  • 21.  Earthing transformer  Characteristic: definite time  Pick-up current: 600 A  Time multiplier: 0.1 sec  Motors  Characteristic: Normal inverse  Pick-up current: 30-50 A (10% of nominal CT current)  Time multiplier: 0.1 sec