OPTIMIZATION OF ENERGY USE INTENSITY IN A DESIGN-BUILD FRAMEWORK S. Sunil Babu1, D. Neeraja2 1M.Tech, Energy and Environmental, VIT University, Tamil Nadu, India 2Assistant Professor, Department of civil Engineering, VIT University, Tamil Nadu, India Abstract The demand for sustainable building is increasing with minimal environmental impact, with increasing energy cost and more concern about environmental issues. In developing countries building does not provide sustainable condition, so the energy efficiency of the building is less. The objective is to analyze the criteria for energy efficiency, resulting in a series of feasible solution that can minimize the usage of energy and thereby reducing the energy demand and providing thermal comfort for the building occupant. And necessary improvement is performed in the building and the modeling is carried out for optimizing energy efficiency. Modeling is done qualitatively to ensure economical factors of building energy efficiency. By optimizing building energy use intensity, it offers sustainable savings in energy consumption. Building fabrics determine the energy use intensity in a residential building. By optimizing the building envelope the sustainable condition is obtained. Reducing energy use intensity from home will lower the energy production from fossil fuels. The building energy performance depends on the energy use intensity; the parameters which determine the energy efficiency of buildings are thermal comfort, water and energy. The simulation program guides the retrofitting of residential building, by optimizing the design-built framework the efficiency is improved in an economical way. Keywords: Sustainable building, energy efficiency, thermal comfort, energy demand, energy performance, energy use intensity. 
--------------------------------------------------------------------***---------------------------------------------------------------------- 1. INTRODUCTION The demand for energy in developing countries is becoming alarming, whereas the means of electricity production remains limited. Due to climatic change, high temperature and humidity, significantly increases the use of air conditioners to attain better thermal comfort. Depletion of fossil fuels and increase in fuel cost leads to an electricity shortage. And, the energy crisis made an effort in reducing the overall energy consumption in building sector. The residential sector in India consumes 37% of energy reflecting the importance of the sector in the national energy scenario. Electricity consumption is mainly influenced by seasonal variation in residential building. Most of the energy consumed for cooling, electrical appliances and water heating, these depend mainly on the ambient temperature. Many cities in India experienced rapid urban growth without any references to the evolving urban environment. This puts a pressure on the energy demand in the country. The demand for comfort conditions in buildings are significantly increased as a result of exposure to uncomfortable outdoor temperature [1]. 
In the context of Vellore, overheated outdoor climate of the location has contributed to a lower indoor comfort. The buildings in tropical climate are overheated due to solar gain in the daytime through the building envelope [2]. The climatic conditions affect the temperature and air flow, which thereby affects the thermal comfort of the building. Due to the high intensity of heat transient from building envelope the residential buildings are subject to increase in cooling demand. By significant increase in thermal comfort can improve energy savings. Around of 50% of annual energy is consumed for air-conditioning with an average electric energy ratio of 100 kWh/m2 of floor space. The aimed work will explore all possible parameters that can be modelled under the Energy Simulation program. On the guidelines of ASHRAE standards the Building simulation is done. ASHRAE standard specifies the test procedures for evaluating the technical capabilities and ranges of applicability of computer programs that calculate the thermal performance of the buildings and their HVAC systems. The ASHRAE includes weather data, instructions for building envelopes, Service water heating, and HVAC, Power, Lighting, and Equipment details. Reduction of energy usage in the building has a positive impact on the environment; energy generation mostly has a negative impact on the environment. By reduction of building energy usage there is a positive impact on the economy for the building occupants. Over utilization of energy might deplete the environment and it concerns society, there will be a positive impact on the environment by reduction in energy usage. 
The specific problems that signify the importance of energy efficiency in buildings are as follows, growing population,
IJRET: International Journal of Research in Engineering and Technology eISSN: 2319-1163 | pISSN: 2321-7308 
_______________________________________________________________________________________ 
Volume: 03 Special Issue: 11 | NCAMESHE - 2014 | Jun-2014, Available @ http://www.ijret.org 92 
rising number of buildings, increased living standards, high energy usage and interrupted power supply. The research performance can provide further improvements in the design and knowledge of buildings within the sub-tropical climate. The actual research performance will determine the justification in the advancement of design and knowledge. The four parameters considered such as design variables (geometrical dimensions of building elements such as orientation, roof, wall, window, door, etc.), material properties (thermal conductivity, specific heat, transmissivity, etc.) weather data (ambient temperature, solar radiation, wind speed, etc.) and building usage data (electricity, lighting, and etc.). 2. METHODOLOGY The research analysis and methods broadly focused on different phases, in which the main work is divided. In the first step the recognition and annotation of technique are done by a theoretical framework. A methodology of DIN V 18599 series is followed in calculating the overall energy balance of the building. The next step is to propose improvements for energy efficiency of buildings. This part is accomplished by working with the simulation programs Climate consultant 5.4, HEED (Home Energy Efficient Design), Net Zero Energy Building evaluation tool and Ecotect analysis 2011. The following task is to calculate the improved building energy efficiencies, when necessary improvements are followed. 2.1 Climate, Site and Orientation The proposed residential building is located on the geographical coordinates of 12°56’N, 79°20’E located in sub-tropical climate region, within the mean maximum temperature ranges from 28.2°C to 36.5°C and the mean minimum temperature ranges from 17.3°C to 27.4°C and relatively low rainfall [3]. Building orientation is considered according to the interaction with solar radiation as well as wind direction. The building orientation is north-south for habitable rooms. The kitchen receives the maximum amount of sunlight throughout the day. Prior to determining the energy balance, a building is divided into various zones. 2.2 Thermal Behavior of the Building The maximum heat gain in the building zones is due to the interaction of solar radiation. The ambient temperature is higher than the indoor temperature; heat enters the building by convection. The outer surface of the wall will convert the incoming solar radiation to heat and will radiate it into the building zones. The heat gain of the building occurs by conduction, the inner zones of the building have temperature fluctuation by air leakage. Thermal performance of a building depends on the prevailing outdoor temperature. 
The building zone comfort is improved by U-value and R- value, lower the U-value and larger the R-value better the insulation effectiveness. Most of the window openings are facing southern wall and thus it makes the maximum uncomfortable condition in peak summer [4]. 
The overall indoor energy balance is influenced by the building fabric, thus the thermal comfort of the zones is depended mainly on the thermodynamic process. The indoor air temperature increases through windows opening and indirectly by building component. The study building is accompanied by high solar radiation, high humidity and low velocity which results in thermal discomfort of the building zones in most part of the year. Thermal comfort is achieved through ventilation, the total heat gain accounts for 25-28% through windows adding to infiltration. For thermal comfort, the optimum air velocity is 0.7 ms-1 at normal climatic condition. The ventilation rate will be less when the number of Air changer per hour (ACH) is less than the minimum value and thus indoor air quality will be poor. Maximum airflow provides an uncomfortable indoor environment. The window opening relies on occupant behaviour and it provides hygienic airflow in the building zones. ASHRAE RP884 proposed the following algorithm: Tcomf = 0.31 x Ta,out + 17.8 (°C) (1) Where, Tcomf is thermal comfort, Ta,out is mean outdoor dry bulb temperature. The relationship between indoor comfort and outdoor temperature has been expressed (ASHRAE 55-2004) in terms of the monthly mean of the outdoor temperature. Important variations of outdoor temperature occur at much shorter than monthly intervals. Adaptive theory suggests that people respond on the basis of their thermal experience, with more recent experience being more important [5]. A running mean of outdoor temperatures weighted according to their distance in the past may be used to characterize the response [6]. Feasibility comfort mainly depended on window to wall ratio, when feasible factor is greater than 0.25, then visual comfort is potential. The building visual comfort is determined according to the window opening. Window opening is more than lower the thermal comfort of the zone. 2.3 Water Conservation The building is located in relatively lower rainfall region and ground water level is low. To pump required water, lots of energy is required; it depends upon the aquifer level. Lots of energy is utilized to procure, treat and store water, which increases the electricity consumption by reducing building energy efficiency. 
Rain water harvesting is flexible and it provides a supplement to the regular water source. And it is used for non-portable purpose. The rainwater harvesting is not present in the building. The efficient use of rainwater can minimize water demand and thereby it improves the energy
IJRET: International Journal of Research in Engineering and Technology eISSN: 2319-1163 | pISSN: 2321-7308 
_______________________________________________________________________________________ 
Volume: 03 Special Issue: 11 | NCAMESHE - 2014 | Jun-2014, Available @ http://www.ijret.org 93 
efficiency of the building. Water conservation varies 
according to the building location, so this factor varies the 
efficiency depending upon the climate. 
2.4 Electricity Consumption and Demand 
The annual electricity consumption of the building is high. 
The building mainly depends on the delivered energy from 
the central electricity grid. Around 2 to 4 hours of electricity 
shut down every day. Inverters are used in building to 
overcome the electricity shortage, the inverter consumes of 
lots of energy to charge batteries, and thus it increases the 
electricity consumption and reduces the building energy 
efficiency. 
Energy intensity is a measure of the building energy 
efficiency. The standard of living determines the electricity 
consumption of the building. Electricity consumption varies 
with respect to season. The electrical appliances depend on 
the occupant living standard and thermal comfort. 
2.5 Simulation Parameters 
To perform the simulation certain parameter need to be 
finalized and set in the simulation program, such as the 
dimension and location of the proposed window, depth and 
pattern of the shading device and glazing specification 
(Visible Light Transmission), internal reflectance of 
floor/wall and ceiling, outdoor luminance and sky condition. 
The procedure adopted for analysis is as follows to develop 
the model of the building, load the weather data as per the 
location of the building, assign building material properties, 
draw the analysis grid at a work plane height of 1200 mm 
from floor finish, Set the outdoor design sky condition data 
as per the climate data to be selected and start the simulation 
process as per ECBC. 
3. RESULTS AND DISCUSSION 
Based on the analysis done, the factor for each zone does 
not satisfy the recommended factor by Energy Conservation 
Building Code (ECBC) and Green Rating for Integrated 
Habitat Assessment (GRIHA). 
As the total heat gain is positive, it represents the building 
heat transfer. During the May month, maximum value of 
heat is observed in the zones. The U-factor varies depending 
on the envelope element, as shown in table 1. By standard 
insulating the building thermal behavior can be optimized 
and which lowers the heat transfer from the outdoor 
environment. Maximum radiation is received in the south 
facing wall, during summer it attains a peak temperature. 
The occurrence of thermal comfort in the building can be 
achieved below 27.46°C with considering the WWR. If 
WWR is minimized, the air flow would not be effective. 
The passive adaptive index of the building is 0.81, as shown 
in Fig. 1. The peak temperature would be 31°C, by window 
opening an air velocity of 0.6mps and thus temperature 
become 27.2°C and it is considered comfortable by 
ASHARE (American Society of Heating, Refrigerating and 
Air Conditioning Engineers). By window opening there is a 
chance of a decrease in thermal comfort, these can be 
optimized with adaptability index. Using predicted mean 
value (PMV) model the comfort zone value of the people in 
residential building is calculated, as shown in Fig. 2. Dry 
bulb temperature variation influences the comfort band. 
Table -1: Building Envelope 
Envelope element 
Design case 
Assembly 
structure 
"U" Factor 
(Btu/h·ft2·°F 
) 
Roof 
As per ASHRAE 
90.1.2007 0.063 
Wall above grade 
Cement Concrete 
Blocks 0.375 
Wall below grade NA 0.375 
Floor 
As per ASHRAE 
90.1.2007 0.350 
Glass 
As per 
manufacturer 
catalogue 0.998 
Fig -1: Adaptability index of the study building 
Fig -2: Thermal comfort of the study building using Ecotect 
analysis 2011. 
Average daylight factor of the overall zones in a building is 
2.34% and average day lighting level is 201.34. By 
0 10 20 30 40 C 
C 
0 
10 
20 
30 
40 
Zone Temperature >> 
Outside Air Temperature >> 
Index: 0.76 
ADAPTABILITY INDEX - Study 1st January - 31st December
IJRET: International Journal of Research in Engineering and Technology eISSN: 2319-1163 | pISSN: 2321-7308 
_______________________________________________________________________________________ 
Volume: 03 Special Issue: 11 | NCAMESHE - 2014 | Jun-2014, Available @ http://www.ijret.org 94 
providing proper visual comfort, the artificial lighting can be reduced in the building. Daylight factor depends on the window opening and the orientation. Windows on the south facing wall as higher visual comfort, when compared to the other wall facings. Due to obstruction the feasibility factor is less than 0.25 in the kitchen zone, by removing obstruction the daylight factor is 2.70% and for living zone it is 2.07%, as shown in Fig. 3 & Fig. 4. 
Fig -3: Daylight factor of the kitchen zone using HEED 
Fig -4: Daylight factor of the living zone using HEED 
Fig -5: Daylight analysis of the study building using Ecotect analysis 2011 
The daylight factor in the southern zone (living region) is higher, as shown in Fig.5. Thus the thermal comfort in the bedrooms is very poor. Thus, by optimizing the window wall ratio (WWR), the daylight factor can be optimized. Higher visual comfort in these zones leads to the utilization of mechanical cooling, thereby increases in energy utilization, by optimized WWR the energy efficiency is improved. Proper selection of glazing can reduce the heat transfer through the air flow. 
A month by month assessment is complicated and thus separate primary energy factor is calculated for summer and winter of a year. The primary energy factors relating to the provision of delivering energy comprise all the factors of primary energy with all preceding activities. The energy chains are determined by modeling with these factors. The efficiency of building varies with respect to the ambient temperature and there is no much fluctuation of energy use intensity, it depends mainly on seasonal comfort. Fabric loss is high and which reduces the building energy efficiency, as shown in Fig 6. Sol-air gain is higher and which fluctuates the thermal comfort of the building, as shown in Table 2. Table -2: Passive Gains Breakdown 
Category 
Losses 
Gains 
Fabric 
71.50% 
20.40% 
Sol-air 
0.00% 
58.30% 
Solar 
0.00% 
6.70% 
Ventilation 
21.10% 
6.50% 
Internal 
0.00% 
6.40% 
Inter-zonal 
7.30% 
1.70% 
By upgrading the building fabric and insulting it qualitatively improves energy performance of a building. The energy performance index (kWh/m2/year) for a non air- conditioned zone is 45 and for an air-conditioned zone is 135. Percentage reduction in energy performance compared to the benchmarked energy efficiency is 42.7%. Energy performance index of building is 34.13 kWh/m2/year. 
Fig -6: Passive gains breakdown of the study building 
The annual energy performance of a building depends on the total area of the building. The energy balance is calculated in accordance with DIN V 18599 series, it interacts with the building energy usage and building factors considered within the building series. The energy quality of the building is compared with the measured energy rating in a qualitative
IJRET: International Journal of Research in Engineering and Technology eISSN: 2319-1163 | pISSN: 2321-7308 
_______________________________________________________________________________________ 
Volume: 03 Special Issue: 11 | NCAMESHE - 2014 | Jun-2014, Available @ http://www.ijret.org 95 
manner. From the series, the primary and delivered energy of the particular building is optimized, as shown in table 3. Table -3: Annual Energy Performance 
Total area (m2) 
148.52 
Total annual predicted energy performance (kWh) 
8345.27 
Energy performance Index (kWh/m2/year) 24*7 
34.13 
Percentage reduction in energy performance compared to the benchmarked energy performance 
42.78% 
The energy need for cooling of the building is determined by iteration method. All energy sources are compared with a heat sink that depends on the building energy usage. The characteristics of each area served by building zone and it is grouped together and optimized to provide energy efficiency. The internal gain of the building fluctuates with respect to the building envelope. The series group the building zone with respect to the optimized condition. 
The optimized building energy efficiency is 68.4% in peak summer and 77% in winter. By optimizing the building primary parameters, the energy efficiency is improved. The major loss of energy is due to building fabric, by proper insulation of the building envelope, the loss is being reduced. Residential building should be ventilated properly, to provide a better indoor environment, 5 air changes per hour occurs in the building zones. Thus, the airborne diseases are reduced and improve thermal comfort. 4. CONCLUSIONS 
By incorporating, renewable energy source in a building which significantly reduces the usage of delivering energy in the building during an operation. Passive solar strategies can be utilized to reduce the energy consumption. By optimizing, the building envelope the energy efficiency is improved. The building comprises of a minimum energy efficient factor as recommended by GRIHA rating system for the regularly occupied zones. 7% of total CO2 emissions from the building envelope relate to building materials. The cooling demand can be reduced by proper ventilation. The building energy efficiency improves 18% in summer comfort and 13% in the winter. The baseline energy performance provides the rating method in the ASHARE standard 90.1-2007, and the building is optimized for the standard. Water conservation is also an important factor in determining the energy efficiency of the building. By generating the energy, it reduces the purchased energy from the grid. By optimizing the building to the standard, the efficiency is increased. ACKNOWLEDGEMENTS The authors wish to thank occupants for allowing to use their house to conduct the study. 
REFERENCES 
[1]. K.S. Ahmed, “Comfort in urban spaces: defining the boundaries. of outdoor thermal comfort for the tropical urban environments”, Energy Build. 35:103, 2003. 
[2]. P. Prianto, Depecker, “Optimization of architectural design elements in tropical humid region with thermal comfort approach”, Energy and Buildings, 35:273–280, 2003 [3]. G. Balamurugan, Dr. S. Rajendran, V. Tirukumaran, Impacts of climate, topography and weathering profile on hydrology and water resource assessment in semi- arid terrain. Using Earth observation- 1 ALI, ASTER-DEM and GIS techniques. International journal of Geomatics and Geosciences volume 1, No 2, 2010. [4]. B. Givoni, “Passive and low energy cooling of buildings”, New York, International Thomson Publishing ITP, 1994. [5]. P.O. Fanger & J. Toftum, “Extension of the PMV model for non air-conditioned buildings in warm climates” , Energy and buildings, 34, 533-536,2002. [6]. Al-Tamimi & S.F. Syed Fadzil, “ Experimental and simulation study for thermal performance analysis in residential buildings in Hot-humid climate (comparative study)”, Journal of Science and Technology, 15 (1), 17-25, 2010. BIOGRAPHIES 
S. Sunil Babu, pursing M. Tech Energy and Environmental from VIT university, Vellore. Presently working on M.Tech project entitled “Optimization of energy use intensity in residential building”. Also worked on a project entitled optimization of biomass power plant and co-firing station 
Dr. D. Neeraja, Assistant Professor in Department of civil Engineering from VIT university. She has versatile knowledge on green building materials. Recently, worked on “Experimental investigations on strength characteristics of steel fiber Re-enforced concrete”

More Related Content

PDF
The impact of outdoor thermal environment on iraqi building
PDF
Concept and realisation_of_an_eib_based_automated_
PDF
Energy saving by integrated control of natural ventilation and hvac
PDF
Sustainable design for building envelope in hot ‎climates; a case study for t...
PDF
Air Water System Design using Revit Mep for a Residential Building
PDF
Design for Future Climate: Adapting Buildings, June 2010
PDF
Application of Passive Cooling Techniques in Residential Buildings: A Case St...
PDF
Energy adit microproject of chemical engineering
The impact of outdoor thermal environment on iraqi building
Concept and realisation_of_an_eib_based_automated_
Energy saving by integrated control of natural ventilation and hvac
Sustainable design for building envelope in hot ‎climates; a case study for t...
Air Water System Design using Revit Mep for a Residential Building
Design for Future Climate: Adapting Buildings, June 2010
Application of Passive Cooling Techniques in Residential Buildings: A Case St...
Energy adit microproject of chemical engineering

What's hot (20)

PDF
Effects of nocturnal ventilation and radiant cooling heating floors on indoor...
PDF
Double cooling coil model for non linear hvac system using rlf method, author...
DOC
Project on energy audit (mahindra & mahindra)
RTF
PDF
Example of natural air ventilation using CFD modelling
PDF
Final Report Condensed
PDF
20320140501007 2
PDF
Heat loss through wall/slab/foundation joint for high-rise buildings
PPTX
Integrating hydronics with indoor environmental quality, by Max Rohr | HRAI A...
PDF
V01 i030602
PPTX
Energy efficient building
PDF
Climate and the built environment
PDF
Study and Optimization of a Renewable System of Small Power Generation
PDF
Lecture 3 heat transfer in buildings
PPTX
SP1037 TECHFEST
PDF
Sustainability
PDF
Paper arch073
PDF
Climate change and Architects role and resposibilities
PDF
C3 - Geothermal reservoir management and sustainable use
PDF
Climate change paper genge and kerr
Effects of nocturnal ventilation and radiant cooling heating floors on indoor...
Double cooling coil model for non linear hvac system using rlf method, author...
Project on energy audit (mahindra & mahindra)
Example of natural air ventilation using CFD modelling
Final Report Condensed
20320140501007 2
Heat loss through wall/slab/foundation joint for high-rise buildings
Integrating hydronics with indoor environmental quality, by Max Rohr | HRAI A...
V01 i030602
Energy efficient building
Climate and the built environment
Study and Optimization of a Renewable System of Small Power Generation
Lecture 3 heat transfer in buildings
SP1037 TECHFEST
Sustainability
Paper arch073
Climate change and Architects role and resposibilities
C3 - Geothermal reservoir management and sustainable use
Climate change paper genge and kerr
Ad

Viewers also liked (20)

PDF
An enhanced adaptive scoring job scheduling algorithm with replication strate...
PDF
Digital signal processing techniques for lti fiber
PDF
Secure data storage and retrieval in the cloud
PDF
Ad hoc networks filter based addressing protocol
PDF
Electronic voting machine using zigbee
PDF
Cfd analaysis of flow through a conical exhaust
PDF
Test case prioritization using hyperlink rankinga
PDF
Effect of bacteria on partial replacement of concrete with fly ash and ggbs
PDF
Next generation engine immobiliser
PDF
Achieving operational excellence by implementing an erp (enterprise resource ...
PDF
Predicting construction project duration with support
PDF
Dead node detection in teen protocol survey
PDF
Architecture and implementation issues of multi core processors and caching –...
PDF
A novel approach on a robot for the blind people which can trained and operat...
PDF
Three phase vienna rectifier for wind power generation system
PDF
Lv side distributed power factor correction system
PDF
Isolated word recognition using lpc & vector quantization
PDF
An efficient monitoring system for sports person using wi fi communication
PDF
Analysis of aerodynamic characteristics of a supercritical airfoil for low sp...
PDF
Parallel unit connected generator model for third
An enhanced adaptive scoring job scheduling algorithm with replication strate...
Digital signal processing techniques for lti fiber
Secure data storage and retrieval in the cloud
Ad hoc networks filter based addressing protocol
Electronic voting machine using zigbee
Cfd analaysis of flow through a conical exhaust
Test case prioritization using hyperlink rankinga
Effect of bacteria on partial replacement of concrete with fly ash and ggbs
Next generation engine immobiliser
Achieving operational excellence by implementing an erp (enterprise resource ...
Predicting construction project duration with support
Dead node detection in teen protocol survey
Architecture and implementation issues of multi core processors and caching –...
A novel approach on a robot for the blind people which can trained and operat...
Three phase vienna rectifier for wind power generation system
Lv side distributed power factor correction system
Isolated word recognition using lpc & vector quantization
An efficient monitoring system for sports person using wi fi communication
Analysis of aerodynamic characteristics of a supercritical airfoil for low sp...
Parallel unit connected generator model for third
Ad

Similar to Optimization of energy use intensity in a design build framework (20)

PDF
IRJET- Experimental Model Design and Simulation of Air Conditioning System fo...
PDF
Institutional smart buildings energy audit
PDF
Energy, economic and environmental analysis of fuzzy logic controllers used i...
PDF
Anand2020
PDF
Bl36378381
PPTX
1. Control systems.pptx
PDF
Building Energy Simulation project by using eQuest
PDF
Financial Evaluation of Solar Powered Absorption Cooling System for Computer ...
PDF
An occupancy-based strategy employing computer vision for reducing cooling en...
PDF
Comparative Analysis of Conventional and Energy Efficient Materials for Resid...
PDF
Human Habits and Energy Consumption in Residential Buildings
PPTX
Chapter 1 hvac
PDF
Functions of fuzzy logic based controllers used in smart building
PDF
Energy Audit and Analysis of an Institutional Building under Subtropical Clim...
PDF
Estimation of HVAC energy saving potential in San Diego apartment units throu...
PDF
Ijciet 10 02_048
DOCX
energyproject
PDF
Pgb unit iii a kameswara rao marthi
PDF
Sustainable Energy Resource Buildings: Some Relevant Feautures for Built Envi...
PDF
A REVIEW ON ENERGY EFFICIENT BUILDINGS - USING PHASE CHANGE MATERIALS, GREEN ...
IRJET- Experimental Model Design and Simulation of Air Conditioning System fo...
Institutional smart buildings energy audit
Energy, economic and environmental analysis of fuzzy logic controllers used i...
Anand2020
Bl36378381
1. Control systems.pptx
Building Energy Simulation project by using eQuest
Financial Evaluation of Solar Powered Absorption Cooling System for Computer ...
An occupancy-based strategy employing computer vision for reducing cooling en...
Comparative Analysis of Conventional and Energy Efficient Materials for Resid...
Human Habits and Energy Consumption in Residential Buildings
Chapter 1 hvac
Functions of fuzzy logic based controllers used in smart building
Energy Audit and Analysis of an Institutional Building under Subtropical Clim...
Estimation of HVAC energy saving potential in San Diego apartment units throu...
Ijciet 10 02_048
energyproject
Pgb unit iii a kameswara rao marthi
Sustainable Energy Resource Buildings: Some Relevant Feautures for Built Envi...
A REVIEW ON ENERGY EFFICIENT BUILDINGS - USING PHASE CHANGE MATERIALS, GREEN ...

More from eSAT Publishing House (20)

PDF
Likely impacts of hudhud on the environment of visakhapatnam
PDF
Impact of flood disaster in a drought prone area – case study of alampur vill...
PDF
Hudhud cyclone – a severe disaster in visakhapatnam
PDF
Groundwater investigation using geophysical methods a case study of pydibhim...
PDF
Flood related disasters concerned to urban flooding in bangalore, india
PDF
Enhancing post disaster recovery by optimal infrastructure capacity building
PDF
Effect of lintel and lintel band on the global performance of reinforced conc...
PDF
Wind damage to trees in the gitam university campus at visakhapatnam by cyclo...
PDF
Wind damage to buildings, infrastrucuture and landscape elements along the be...
PDF
Shear strength of rc deep beam panels – a review
PDF
Role of voluntary teams of professional engineers in dissater management – ex...
PDF
Risk analysis and environmental hazard management
PDF
Review study on performance of seismically tested repaired shear walls
PDF
Monitoring and assessment of air quality with reference to dust particles (pm...
PDF
Low cost wireless sensor networks and smartphone applications for disaster ma...
PDF
Coastal zones – seismic vulnerability an analysis from east coast of india
PDF
Can fracture mechanics predict damage due disaster of structures
PDF
Assessment of seismic susceptibility of rc buildings
PDF
A geophysical insight of earthquake occurred on 21 st may 2014 off paradip, b...
PDF
Effect of hudhud cyclone on the development of visakhapatnam as smart and gre...
Likely impacts of hudhud on the environment of visakhapatnam
Impact of flood disaster in a drought prone area – case study of alampur vill...
Hudhud cyclone – a severe disaster in visakhapatnam
Groundwater investigation using geophysical methods a case study of pydibhim...
Flood related disasters concerned to urban flooding in bangalore, india
Enhancing post disaster recovery by optimal infrastructure capacity building
Effect of lintel and lintel band on the global performance of reinforced conc...
Wind damage to trees in the gitam university campus at visakhapatnam by cyclo...
Wind damage to buildings, infrastrucuture and landscape elements along the be...
Shear strength of rc deep beam panels – a review
Role of voluntary teams of professional engineers in dissater management – ex...
Risk analysis and environmental hazard management
Review study on performance of seismically tested repaired shear walls
Monitoring and assessment of air quality with reference to dust particles (pm...
Low cost wireless sensor networks and smartphone applications for disaster ma...
Coastal zones – seismic vulnerability an analysis from east coast of india
Can fracture mechanics predict damage due disaster of structures
Assessment of seismic susceptibility of rc buildings
A geophysical insight of earthquake occurred on 21 st may 2014 off paradip, b...
Effect of hudhud cyclone on the development of visakhapatnam as smart and gre...

Recently uploaded (20)

PDF
Enhancing Cyber Defense Against Zero-Day Attacks using Ensemble Neural Networks
PDF
TFEC-4-2020-Design-Guide-for-Timber-Roof-Trusses.pdf
DOCX
573137875-Attendance-Management-System-original
PDF
Well-logging-methods_new................
PDF
Evaluating the Democratization of the Turkish Armed Forces from a Normative P...
PPTX
UNIT-1 - COAL BASED THERMAL POWER PLANTS
PPTX
MCN 401 KTU-2019-PPE KITS-MODULE 2.pptx
PDF
The CXO Playbook 2025 – Future-Ready Strategies for C-Suite Leaders Cerebrai...
PPTX
CARTOGRAPHY AND GEOINFORMATION VISUALIZATION chapter1 NPTE (2).pptx
PDF
Automation-in-Manufacturing-Chapter-Introduction.pdf
PDF
Embodied AI: Ushering in the Next Era of Intelligent Systems
PDF
Operating System & Kernel Study Guide-1 - converted.pdf
PPTX
Internet of Things (IOT) - A guide to understanding
PDF
PPT on Performance Review to get promotions
PPTX
FINAL REVIEW FOR COPD DIANOSIS FOR PULMONARY DISEASE.pptx
DOCX
ASol_English-Language-Literature-Set-1-27-02-2023-converted.docx
PPTX
Engineering Ethics, Safety and Environment [Autosaved] (1).pptx
PDF
July 2025 - Top 10 Read Articles in International Journal of Software Enginee...
PPTX
Infosys Presentation by1.Riyan Bagwan 2.Samadhan Naiknavare 3.Gaurav Shinde 4...
PPT
CRASH COURSE IN ALTERNATIVE PLUMBING CLASS
Enhancing Cyber Defense Against Zero-Day Attacks using Ensemble Neural Networks
TFEC-4-2020-Design-Guide-for-Timber-Roof-Trusses.pdf
573137875-Attendance-Management-System-original
Well-logging-methods_new................
Evaluating the Democratization of the Turkish Armed Forces from a Normative P...
UNIT-1 - COAL BASED THERMAL POWER PLANTS
MCN 401 KTU-2019-PPE KITS-MODULE 2.pptx
The CXO Playbook 2025 – Future-Ready Strategies for C-Suite Leaders Cerebrai...
CARTOGRAPHY AND GEOINFORMATION VISUALIZATION chapter1 NPTE (2).pptx
Automation-in-Manufacturing-Chapter-Introduction.pdf
Embodied AI: Ushering in the Next Era of Intelligent Systems
Operating System & Kernel Study Guide-1 - converted.pdf
Internet of Things (IOT) - A guide to understanding
PPT on Performance Review to get promotions
FINAL REVIEW FOR COPD DIANOSIS FOR PULMONARY DISEASE.pptx
ASol_English-Language-Literature-Set-1-27-02-2023-converted.docx
Engineering Ethics, Safety and Environment [Autosaved] (1).pptx
July 2025 - Top 10 Read Articles in International Journal of Software Enginee...
Infosys Presentation by1.Riyan Bagwan 2.Samadhan Naiknavare 3.Gaurav Shinde 4...
CRASH COURSE IN ALTERNATIVE PLUMBING CLASS

Optimization of energy use intensity in a design build framework

  • 1. IJRET: International Journal of Research in Engineering and Technology eISSN: 2319-1163 | pISSN: 2321-7308 _______________________________________________________________________________________ Volume: 03 Special Issue: 11 | NCAMESHE - 2014 | Jun-2014, Available @ http://www.ijret.org 91 OPTIMIZATION OF ENERGY USE INTENSITY IN A DESIGN-BUILD FRAMEWORK S. Sunil Babu1, D. Neeraja2 1M.Tech, Energy and Environmental, VIT University, Tamil Nadu, India 2Assistant Professor, Department of civil Engineering, VIT University, Tamil Nadu, India Abstract The demand for sustainable building is increasing with minimal environmental impact, with increasing energy cost and more concern about environmental issues. In developing countries building does not provide sustainable condition, so the energy efficiency of the building is less. The objective is to analyze the criteria for energy efficiency, resulting in a series of feasible solution that can minimize the usage of energy and thereby reducing the energy demand and providing thermal comfort for the building occupant. And necessary improvement is performed in the building and the modeling is carried out for optimizing energy efficiency. Modeling is done qualitatively to ensure economical factors of building energy efficiency. By optimizing building energy use intensity, it offers sustainable savings in energy consumption. Building fabrics determine the energy use intensity in a residential building. By optimizing the building envelope the sustainable condition is obtained. Reducing energy use intensity from home will lower the energy production from fossil fuels. The building energy performance depends on the energy use intensity; the parameters which determine the energy efficiency of buildings are thermal comfort, water and energy. The simulation program guides the retrofitting of residential building, by optimizing the design-built framework the efficiency is improved in an economical way. Keywords: Sustainable building, energy efficiency, thermal comfort, energy demand, energy performance, energy use intensity. --------------------------------------------------------------------***---------------------------------------------------------------------- 1. INTRODUCTION The demand for energy in developing countries is becoming alarming, whereas the means of electricity production remains limited. Due to climatic change, high temperature and humidity, significantly increases the use of air conditioners to attain better thermal comfort. Depletion of fossil fuels and increase in fuel cost leads to an electricity shortage. And, the energy crisis made an effort in reducing the overall energy consumption in building sector. The residential sector in India consumes 37% of energy reflecting the importance of the sector in the national energy scenario. Electricity consumption is mainly influenced by seasonal variation in residential building. Most of the energy consumed for cooling, electrical appliances and water heating, these depend mainly on the ambient temperature. Many cities in India experienced rapid urban growth without any references to the evolving urban environment. This puts a pressure on the energy demand in the country. The demand for comfort conditions in buildings are significantly increased as a result of exposure to uncomfortable outdoor temperature [1]. In the context of Vellore, overheated outdoor climate of the location has contributed to a lower indoor comfort. The buildings in tropical climate are overheated due to solar gain in the daytime through the building envelope [2]. The climatic conditions affect the temperature and air flow, which thereby affects the thermal comfort of the building. Due to the high intensity of heat transient from building envelope the residential buildings are subject to increase in cooling demand. By significant increase in thermal comfort can improve energy savings. Around of 50% of annual energy is consumed for air-conditioning with an average electric energy ratio of 100 kWh/m2 of floor space. The aimed work will explore all possible parameters that can be modelled under the Energy Simulation program. On the guidelines of ASHRAE standards the Building simulation is done. ASHRAE standard specifies the test procedures for evaluating the technical capabilities and ranges of applicability of computer programs that calculate the thermal performance of the buildings and their HVAC systems. The ASHRAE includes weather data, instructions for building envelopes, Service water heating, and HVAC, Power, Lighting, and Equipment details. Reduction of energy usage in the building has a positive impact on the environment; energy generation mostly has a negative impact on the environment. By reduction of building energy usage there is a positive impact on the economy for the building occupants. Over utilization of energy might deplete the environment and it concerns society, there will be a positive impact on the environment by reduction in energy usage. The specific problems that signify the importance of energy efficiency in buildings are as follows, growing population,
  • 2. IJRET: International Journal of Research in Engineering and Technology eISSN: 2319-1163 | pISSN: 2321-7308 _______________________________________________________________________________________ Volume: 03 Special Issue: 11 | NCAMESHE - 2014 | Jun-2014, Available @ http://www.ijret.org 92 rising number of buildings, increased living standards, high energy usage and interrupted power supply. The research performance can provide further improvements in the design and knowledge of buildings within the sub-tropical climate. The actual research performance will determine the justification in the advancement of design and knowledge. The four parameters considered such as design variables (geometrical dimensions of building elements such as orientation, roof, wall, window, door, etc.), material properties (thermal conductivity, specific heat, transmissivity, etc.) weather data (ambient temperature, solar radiation, wind speed, etc.) and building usage data (electricity, lighting, and etc.). 2. METHODOLOGY The research analysis and methods broadly focused on different phases, in which the main work is divided. In the first step the recognition and annotation of technique are done by a theoretical framework. A methodology of DIN V 18599 series is followed in calculating the overall energy balance of the building. The next step is to propose improvements for energy efficiency of buildings. This part is accomplished by working with the simulation programs Climate consultant 5.4, HEED (Home Energy Efficient Design), Net Zero Energy Building evaluation tool and Ecotect analysis 2011. The following task is to calculate the improved building energy efficiencies, when necessary improvements are followed. 2.1 Climate, Site and Orientation The proposed residential building is located on the geographical coordinates of 12°56’N, 79°20’E located in sub-tropical climate region, within the mean maximum temperature ranges from 28.2°C to 36.5°C and the mean minimum temperature ranges from 17.3°C to 27.4°C and relatively low rainfall [3]. Building orientation is considered according to the interaction with solar radiation as well as wind direction. The building orientation is north-south for habitable rooms. The kitchen receives the maximum amount of sunlight throughout the day. Prior to determining the energy balance, a building is divided into various zones. 2.2 Thermal Behavior of the Building The maximum heat gain in the building zones is due to the interaction of solar radiation. The ambient temperature is higher than the indoor temperature; heat enters the building by convection. The outer surface of the wall will convert the incoming solar radiation to heat and will radiate it into the building zones. The heat gain of the building occurs by conduction, the inner zones of the building have temperature fluctuation by air leakage. Thermal performance of a building depends on the prevailing outdoor temperature. The building zone comfort is improved by U-value and R- value, lower the U-value and larger the R-value better the insulation effectiveness. Most of the window openings are facing southern wall and thus it makes the maximum uncomfortable condition in peak summer [4]. The overall indoor energy balance is influenced by the building fabric, thus the thermal comfort of the zones is depended mainly on the thermodynamic process. The indoor air temperature increases through windows opening and indirectly by building component. The study building is accompanied by high solar radiation, high humidity and low velocity which results in thermal discomfort of the building zones in most part of the year. Thermal comfort is achieved through ventilation, the total heat gain accounts for 25-28% through windows adding to infiltration. For thermal comfort, the optimum air velocity is 0.7 ms-1 at normal climatic condition. The ventilation rate will be less when the number of Air changer per hour (ACH) is less than the minimum value and thus indoor air quality will be poor. Maximum airflow provides an uncomfortable indoor environment. The window opening relies on occupant behaviour and it provides hygienic airflow in the building zones. ASHRAE RP884 proposed the following algorithm: Tcomf = 0.31 x Ta,out + 17.8 (°C) (1) Where, Tcomf is thermal comfort, Ta,out is mean outdoor dry bulb temperature. The relationship between indoor comfort and outdoor temperature has been expressed (ASHRAE 55-2004) in terms of the monthly mean of the outdoor temperature. Important variations of outdoor temperature occur at much shorter than monthly intervals. Adaptive theory suggests that people respond on the basis of their thermal experience, with more recent experience being more important [5]. A running mean of outdoor temperatures weighted according to their distance in the past may be used to characterize the response [6]. Feasibility comfort mainly depended on window to wall ratio, when feasible factor is greater than 0.25, then visual comfort is potential. The building visual comfort is determined according to the window opening. Window opening is more than lower the thermal comfort of the zone. 2.3 Water Conservation The building is located in relatively lower rainfall region and ground water level is low. To pump required water, lots of energy is required; it depends upon the aquifer level. Lots of energy is utilized to procure, treat and store water, which increases the electricity consumption by reducing building energy efficiency. Rain water harvesting is flexible and it provides a supplement to the regular water source. And it is used for non-portable purpose. The rainwater harvesting is not present in the building. The efficient use of rainwater can minimize water demand and thereby it improves the energy
  • 3. IJRET: International Journal of Research in Engineering and Technology eISSN: 2319-1163 | pISSN: 2321-7308 _______________________________________________________________________________________ Volume: 03 Special Issue: 11 | NCAMESHE - 2014 | Jun-2014, Available @ http://www.ijret.org 93 efficiency of the building. Water conservation varies according to the building location, so this factor varies the efficiency depending upon the climate. 2.4 Electricity Consumption and Demand The annual electricity consumption of the building is high. The building mainly depends on the delivered energy from the central electricity grid. Around 2 to 4 hours of electricity shut down every day. Inverters are used in building to overcome the electricity shortage, the inverter consumes of lots of energy to charge batteries, and thus it increases the electricity consumption and reduces the building energy efficiency. Energy intensity is a measure of the building energy efficiency. The standard of living determines the electricity consumption of the building. Electricity consumption varies with respect to season. The electrical appliances depend on the occupant living standard and thermal comfort. 2.5 Simulation Parameters To perform the simulation certain parameter need to be finalized and set in the simulation program, such as the dimension and location of the proposed window, depth and pattern of the shading device and glazing specification (Visible Light Transmission), internal reflectance of floor/wall and ceiling, outdoor luminance and sky condition. The procedure adopted for analysis is as follows to develop the model of the building, load the weather data as per the location of the building, assign building material properties, draw the analysis grid at a work plane height of 1200 mm from floor finish, Set the outdoor design sky condition data as per the climate data to be selected and start the simulation process as per ECBC. 3. RESULTS AND DISCUSSION Based on the analysis done, the factor for each zone does not satisfy the recommended factor by Energy Conservation Building Code (ECBC) and Green Rating for Integrated Habitat Assessment (GRIHA). As the total heat gain is positive, it represents the building heat transfer. During the May month, maximum value of heat is observed in the zones. The U-factor varies depending on the envelope element, as shown in table 1. By standard insulating the building thermal behavior can be optimized and which lowers the heat transfer from the outdoor environment. Maximum radiation is received in the south facing wall, during summer it attains a peak temperature. The occurrence of thermal comfort in the building can be achieved below 27.46°C with considering the WWR. If WWR is minimized, the air flow would not be effective. The passive adaptive index of the building is 0.81, as shown in Fig. 1. The peak temperature would be 31°C, by window opening an air velocity of 0.6mps and thus temperature become 27.2°C and it is considered comfortable by ASHARE (American Society of Heating, Refrigerating and Air Conditioning Engineers). By window opening there is a chance of a decrease in thermal comfort, these can be optimized with adaptability index. Using predicted mean value (PMV) model the comfort zone value of the people in residential building is calculated, as shown in Fig. 2. Dry bulb temperature variation influences the comfort band. Table -1: Building Envelope Envelope element Design case Assembly structure "U" Factor (Btu/h·ft2·°F ) Roof As per ASHRAE 90.1.2007 0.063 Wall above grade Cement Concrete Blocks 0.375 Wall below grade NA 0.375 Floor As per ASHRAE 90.1.2007 0.350 Glass As per manufacturer catalogue 0.998 Fig -1: Adaptability index of the study building Fig -2: Thermal comfort of the study building using Ecotect analysis 2011. Average daylight factor of the overall zones in a building is 2.34% and average day lighting level is 201.34. By 0 10 20 30 40 C C 0 10 20 30 40 Zone Temperature >> Outside Air Temperature >> Index: 0.76 ADAPTABILITY INDEX - Study 1st January - 31st December
  • 4. IJRET: International Journal of Research in Engineering and Technology eISSN: 2319-1163 | pISSN: 2321-7308 _______________________________________________________________________________________ Volume: 03 Special Issue: 11 | NCAMESHE - 2014 | Jun-2014, Available @ http://www.ijret.org 94 providing proper visual comfort, the artificial lighting can be reduced in the building. Daylight factor depends on the window opening and the orientation. Windows on the south facing wall as higher visual comfort, when compared to the other wall facings. Due to obstruction the feasibility factor is less than 0.25 in the kitchen zone, by removing obstruction the daylight factor is 2.70% and for living zone it is 2.07%, as shown in Fig. 3 & Fig. 4. Fig -3: Daylight factor of the kitchen zone using HEED Fig -4: Daylight factor of the living zone using HEED Fig -5: Daylight analysis of the study building using Ecotect analysis 2011 The daylight factor in the southern zone (living region) is higher, as shown in Fig.5. Thus the thermal comfort in the bedrooms is very poor. Thus, by optimizing the window wall ratio (WWR), the daylight factor can be optimized. Higher visual comfort in these zones leads to the utilization of mechanical cooling, thereby increases in energy utilization, by optimized WWR the energy efficiency is improved. Proper selection of glazing can reduce the heat transfer through the air flow. A month by month assessment is complicated and thus separate primary energy factor is calculated for summer and winter of a year. The primary energy factors relating to the provision of delivering energy comprise all the factors of primary energy with all preceding activities. The energy chains are determined by modeling with these factors. The efficiency of building varies with respect to the ambient temperature and there is no much fluctuation of energy use intensity, it depends mainly on seasonal comfort. Fabric loss is high and which reduces the building energy efficiency, as shown in Fig 6. Sol-air gain is higher and which fluctuates the thermal comfort of the building, as shown in Table 2. Table -2: Passive Gains Breakdown Category Losses Gains Fabric 71.50% 20.40% Sol-air 0.00% 58.30% Solar 0.00% 6.70% Ventilation 21.10% 6.50% Internal 0.00% 6.40% Inter-zonal 7.30% 1.70% By upgrading the building fabric and insulting it qualitatively improves energy performance of a building. The energy performance index (kWh/m2/year) for a non air- conditioned zone is 45 and for an air-conditioned zone is 135. Percentage reduction in energy performance compared to the benchmarked energy efficiency is 42.7%. Energy performance index of building is 34.13 kWh/m2/year. Fig -6: Passive gains breakdown of the study building The annual energy performance of a building depends on the total area of the building. The energy balance is calculated in accordance with DIN V 18599 series, it interacts with the building energy usage and building factors considered within the building series. The energy quality of the building is compared with the measured energy rating in a qualitative
  • 5. IJRET: International Journal of Research in Engineering and Technology eISSN: 2319-1163 | pISSN: 2321-7308 _______________________________________________________________________________________ Volume: 03 Special Issue: 11 | NCAMESHE - 2014 | Jun-2014, Available @ http://www.ijret.org 95 manner. From the series, the primary and delivered energy of the particular building is optimized, as shown in table 3. Table -3: Annual Energy Performance Total area (m2) 148.52 Total annual predicted energy performance (kWh) 8345.27 Energy performance Index (kWh/m2/year) 24*7 34.13 Percentage reduction in energy performance compared to the benchmarked energy performance 42.78% The energy need for cooling of the building is determined by iteration method. All energy sources are compared with a heat sink that depends on the building energy usage. The characteristics of each area served by building zone and it is grouped together and optimized to provide energy efficiency. The internal gain of the building fluctuates with respect to the building envelope. The series group the building zone with respect to the optimized condition. The optimized building energy efficiency is 68.4% in peak summer and 77% in winter. By optimizing the building primary parameters, the energy efficiency is improved. The major loss of energy is due to building fabric, by proper insulation of the building envelope, the loss is being reduced. Residential building should be ventilated properly, to provide a better indoor environment, 5 air changes per hour occurs in the building zones. Thus, the airborne diseases are reduced and improve thermal comfort. 4. CONCLUSIONS By incorporating, renewable energy source in a building which significantly reduces the usage of delivering energy in the building during an operation. Passive solar strategies can be utilized to reduce the energy consumption. By optimizing, the building envelope the energy efficiency is improved. The building comprises of a minimum energy efficient factor as recommended by GRIHA rating system for the regularly occupied zones. 7% of total CO2 emissions from the building envelope relate to building materials. The cooling demand can be reduced by proper ventilation. The building energy efficiency improves 18% in summer comfort and 13% in the winter. The baseline energy performance provides the rating method in the ASHARE standard 90.1-2007, and the building is optimized for the standard. Water conservation is also an important factor in determining the energy efficiency of the building. By generating the energy, it reduces the purchased energy from the grid. By optimizing the building to the standard, the efficiency is increased. ACKNOWLEDGEMENTS The authors wish to thank occupants for allowing to use their house to conduct the study. REFERENCES [1]. K.S. Ahmed, “Comfort in urban spaces: defining the boundaries. of outdoor thermal comfort for the tropical urban environments”, Energy Build. 35:103, 2003. [2]. P. Prianto, Depecker, “Optimization of architectural design elements in tropical humid region with thermal comfort approach”, Energy and Buildings, 35:273–280, 2003 [3]. G. Balamurugan, Dr. S. Rajendran, V. Tirukumaran, Impacts of climate, topography and weathering profile on hydrology and water resource assessment in semi- arid terrain. Using Earth observation- 1 ALI, ASTER-DEM and GIS techniques. International journal of Geomatics and Geosciences volume 1, No 2, 2010. [4]. B. Givoni, “Passive and low energy cooling of buildings”, New York, International Thomson Publishing ITP, 1994. [5]. P.O. Fanger & J. Toftum, “Extension of the PMV model for non air-conditioned buildings in warm climates” , Energy and buildings, 34, 533-536,2002. [6]. Al-Tamimi & S.F. Syed Fadzil, “ Experimental and simulation study for thermal performance analysis in residential buildings in Hot-humid climate (comparative study)”, Journal of Science and Technology, 15 (1), 17-25, 2010. BIOGRAPHIES S. Sunil Babu, pursing M. Tech Energy and Environmental from VIT university, Vellore. Presently working on M.Tech project entitled “Optimization of energy use intensity in residential building”. Also worked on a project entitled optimization of biomass power plant and co-firing station Dr. D. Neeraja, Assistant Professor in Department of civil Engineering from VIT university. She has versatile knowledge on green building materials. Recently, worked on “Experimental investigations on strength characteristics of steel fiber Re-enforced concrete”