PowerQuality
Guide for electrical design engineers
Katarzyna Strzalka-Goluszka
Doctoral Student of Faculty of Electrical Engineering,
Automatics, IT & Electronics
AGH University of Science & Technology
kstrzalka@op.pl
Power Quality
Overload Capacity of Power
Transformers
Time of day
Loadfactor
t
24 h0
K2
K1
Power Quality
2
www.leonardo-energy.org
1. Introduction
For over three decades, since the early seventies, the principles of sizing oil-
immersed transformers and evaluation their overload capacity have been defined
in standard PN-71/E-81000 [1]. These principles are presented in the course
book [3], and examples of practical calculations and transformers sizing are
provided in the course book [4].
The basic criterion adopted in standard [1] for determining power transformers
loading limits is the thermal life of insulation. The standard defines transformer
overload capacity assuming nominal transformer insulation life and reduced
insulation life expectancy corresponding to overloading a transformer under
disturbed conditions.
The basis for consideration in standard [1] was a representative two-step load
cycle determined from the known or expected ordered 24-hour load curve of a
transformer, described by:
• equivalent initial load Sp,
• equivalent final load Sk,
• duration of the final load tk.
The above equivalent load values should be computed as a root mean square
average according to the relation:
(1)
where:
Si – load over the time interval Δti,
Δti – the considered time interval.
The initial and final equivalent loads are determined from the representative load:
(2)
nt
p
p
S
S
K =
nt
k
k
S
S
K =
∑
∑
Δ
Δ
=
i
ii
t
tS
S
2
Overload Capacity of PowerTransformers
3
www.leonardo-energy.org
where: Snt – transformer nominal power.
The permissible equivalent final load Kk = f(Kp, tk) is given in standard PN-71/E-
81000 [1] in the form of curves and tables, assuming the following parameters:
• ambient temperature ϑo = - 10, 0, 10, 20 and 30ºC
• equivalent initial load Kp = 0.25÷1.0
• duration of the final load tk = 0.5, 1, 2, 4, 8, 12 and 24h.
Standard PN-IEC 60354 [2] implemented in 1999 considerably alters the
principles of determining the overload capacity of oil-immersed transformers. The
most important changes are discussed further in this paper.
2. Main assumptions of the standard PN-IEC 60354
methodology
The normal service life of transformer is a conventional reference basis for
continuous operation in normal ambient temperature under nominal operating
conditions. Loading beyond nameplate rating and/or higher ambient temperature
involves a risk and results accelerated insulation ageing. Both the loading and
temperature rise above the rated values will result in risk of premature failure of a
transformer that may occur either immediately or after certain time, due to
deterioration of the transformer components. The standard gives guidelines on
transformer loading in relation to the operating temperature rise and thermal
ageing of insulation; the insulation relative ageing rate is assessed using the hot
spot temperature. Since the transformer sensitivity to overloading depends
evidently on its size, the standard specifies three categories of transformers:
• Distribution transformers (with maximum power of 2500 kVA), for which
only the hot-spot temperature and thermal deterioration have to be
considered;
• Medium power transformers (not exceeding 100 MVA), in which the cooling
modes shall be considered;
• Large power transformers (exceeding 100 MVA), where the effects of stray
leakage flux are significant and the consequences of failure are severe.
For each category the standard defines separate requirements.
Table 1 shows limit currents and temperatures for the above transformer
categories, applicable to loading beyond nameplate rating.
Power Quality
4
www.leonardo-energy.org
Table 1 : Currents and temperature limits applicable to loading beyond
nameplate rating
As can be seen from table 1, the standard recommendations apply to three types
of transformer loading:
• continuous loading,
• cyclic loading,
• long-time emergency cyclic loading.
Standard [2] provides the method for determining thermal behaviour of
transformers with various cooling modes and comprises computation results in
the form of thermal characteristics for adopted assumptions, among which the
most important are:
• ambient temperature Θa = 20ºC,
• hot-spot temperature rise ΔΘhr = 78ºC.
As the basis for analysis of transformer insulation thermal ageing the rule of 6ºC
is taken, i.e. the rate of insulation ageing doubles for every increment of
approximately 6ºC.
Assuming the relative rate of ageing V at the hot-spot temperature Θh = 98ºC
equals unity V = 1, thus at the temperature Θh = 104ºC V = 2, and at
Θh = 110ºC V = 4.
Standard [2] provides the method for calculation of transformer daily loss-of-
life, expressed in terms of "normal" days, i.e. equivalent days of operation with
rated power at the ambient temperature 20ºC.
TYPE OF LOADING DISTRIBUTION
TRANSFORMERS
MEDIUM POWER
TRANSFORMERS
LARGE POWER
TRANSFORMERS
Normal cyclic load:
Current [p.u.]
Hot-spot temperature [°C]
Top-oil temperature [°C]
1.5
140
105
1.5
140
105
1.3
120
105
Long-time emergency cyclic loading:
Current [p.u.]
Hot-spot temperature [°C]
Top-oil temperature [°C]
1.8
150
115
1.5
140
115
1.3
130
115
Short-time emergency loading:
Current [p.u.]
Hot-spot temperature [°C]
Top-oil temperature [°C]
2.0
-
-
1.8
160
115
1.5
160
115
Overload Capacity of PowerTransformers
5
www.leonardo-energy.org
3. Method of representing an actual load by an equivalent
two-step load cycle
Fig. 1. Equivalent two-step load cycle
The load steps in figure 1 shall be K1 and K2, where K2 is the peak load. The
duration of the peak load is t hours. Standard [2] describes the method of
determining this duration for different shapes of actual load cycles. In the case
of a load cycle with one peak the value of t should be selected on the equal
areas basis as indicated in Fig. 2. For the off-peak portion of the load cycle, the
value of K1 is selected to correspond to the average off-peak load.
Fig. 2. Load cycle with one peak
In the case where there are two peaks of nearly equal amplitude but different
duration (Fig. 3), the value of time t is determined for the peak of a longer
duration and the value of K1 is selected to correspond to the average of the
remaining daily load.
Time of day
Loadfactor
t
24 h0
K2
K1
Power Quality
6
www.leonardo-energy.org
Fig. 3. Load cycle with two peaks of equal amplitude and different duration
For the load cycle where two peaks occur in close succession (Fig. 4), the value
of t is made long enough to enclose both peaks, and K1 is selected accordingly to
the average load during the remaining portion of the day.
Fig. 4. Load cycle with peaks in close succession
4. Determining permissible transformer load for various
types of loadings
For a normal continuous loading, which shows no pronounced variation over
a day, the standard [2] recommends the use of a constant equivalent load
current. Table 2 gives an acceptable load factor K = K24 for continuous duty
and different ambient temperatures.
Overload Capacity of PowerTransformers
7
www.leonardo-energy.org
Table 2 Acceptable load factor K24 for continuous duty at different ambient
temperatures (ON, OF and OD cooling)
For normal cycling loading and various types of transformers and eight
different ambient temperatures (Θa = -25, -20, -10, 0, 10, 20, 30 and 40°C)
standard PN-IEC 60354: 1999 [2] gives curves that can be used to determine the
permissible peak load K2 for a given duration t and a given initial load K1. If the
ambient temperature value falls between two values, the standard
recommends interpolation between the two nearest curves. Figure 5 shows an
example of relations K2 = f(K1, t) for distribution transformers with ONAN cooling,
and the ambient temperature Θa = +20°C.
Fig. 5. Permissible loading of distribution transformers at the ambient
temperature 20°C
AM BIENT TEM PERATURE, °C -25 -20 -10 0 10 20 30 40
Hot-spot temperature rise, °C 123 118 108 98 88 78 68 58
K24 Distribution
transformers
ONAN 1.37 1.33 1.25 1.17 1.09 1.00 0.91 0.81
Medium and large
power
transformers
ON 1.33 1.30 1.22 1.15 1.08 1.00 0.92 0.82
OF 1.31 1.28 1.21 1.14 1.08 1.00 0.92 0.83
OD 1.24 1.22 1.17 1.11 1.06 1.00 0.94 0.87
Power Quality
8
www.leonardo-energy.org
If the supply voltage remains constant the curves K2 = f(K1, t) can also be used
for determining the rated power of a transformer (with normal life duration) for a
given rectangular load profile defined as the ratio K2/K1.
For this purpose it is necessary is to find the intersection of the curve
corresponding to the duration of the load K2 with the line of constant slope K2/K1,
which can be found by marking corresponding points on ordinate K2 = 1 and
abscissa K1 = 1. Figure 1 shows the line for K2/K1 = 1.75, which allows
determining the factors K2 = 1.15 and K1 = 0.66 for duration t = 8h.
For emergency cyclic loading the standard PN-IEC 60354: 1999 [2] gives
tables that can be used to ascertain whether a load characterized by particular
values K1 and K2 is permissible for a given ambient temperature, and
determine a daily loss of life expressed in "normal" days. These tables
correspond to six duration values t (0.5 to 24 h) and four types of transformers.
The below example table 4 determines relative ageing rates V and winding hot-
spot temperature rise ΔΘh for distribution transformers with ONAN cooling and
duration t = 4 h.
Table 3 Conversion factor related to the ambient temperature
In order to determine whether a daily load diagram characterized by particular
values of K1 and K2 is permissible and to evaluate the daily loss of life entailed,
the following steps should be preceded:
- From table 4 find the hot-spot temperature rise ΔΘh and determine the hot-spot
temperature Θh from the formula:
Θh = ΔΘh + Θa (3)
where: Θa - ambient temperature
- If the resulting hot-spot temperature exceeds the limit stated in table 1, the
loading is not permissible.
AMBIENT
TEMPERATURE°C
40°C 30°C 20°C 10°C 0°C -10°C -20°C -25°C
Conversion factor kp 10 3.2 1 0.32 0.1 0.032 0.01 0.0055
Overload Capacity of PowerTransformers
9
www.leonardo-energy.org
- From table 4 find relative ageing rate V and determine the daily insulation loss
of life L from the formula:
L = V .
kp (4)
where: kp – the conversion factor related to the ambient temperature according to
table 3.
Table 4 relative ageing rate V (daily loss of life) and winding hot-spot
temperature rise Dqh for distribution transformers with ONAN cooling and
duration t = 4 h.
0.25 0.50 0.70 0.80 0.90 1.00 1.10 1.20 1.30 1.40 1.50
0.7 V
Δθh
0.003
43
0.080
46
0.032
48
0.8 V
Δθh
0.005
51
0.012
53
0.040
56
0.093
57
0.9 V
Δθh
0.010
59
0.020
61
0.056
64
0.117
66
0.292
67
1.0 V
Δθh
0.023
68
0.039
70
0.091
73
0.170
74
0.377
76
1.00
78
1.1 V
Δθh
0.056
77
0.091
73
0.178
83
0.294
84
0.566
86
1.32
87
3.72
89
1.2 V
Δθh
0.154
87
0.236
89
0.417
92
0.621
94
1.04
95
2.06
97
5.00
99
14.9
101
1.3 V
Δθh
0.455
98
0.677
100
1.12
103
1.56
104
2.36
106
4.02
108
8.13
110
20.5
112
64.7
114
1.4 V
Δθh
1.45
109
2.11
111
3.36
114
4.50
115
6.38
117
9.76
119
16.8
121
34.7
123
90.6
125
302
127
1.5 V
Δθh
4.94
120
7.09
122
11.00
125
14.4
127
19.7
128
28.2
130
43.7
132
76.1
134
160
137
431
139
1510
141
1.6 V
Δθh
17.9
132
25.5
134
38.8
137
50.1
139
66.8
140
93.7
142
135
144
211
146
371
149
790
151
2200
153
1.7 V
Δθh
69.0
144
97.3
147
146
149
187
151
246
153
334
155
470
157
694
159
110
161
1950
163
4190
166
1.8 V
Δθh
282
157
394
160
587
162
745
164
971
166
1300
167
1790
169
1560
172
3830
174
6110
176
+
179
1.9 V
Δθh
1220
171
1690
173
2500
176
3150
177
4080
179
5410
180
7370
183
+
+
+
+
+
+
+
+
2.0 V
Δθh
5540
184
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
K1
K2
Power Quality
10
www.leonardo-energy.org
5. Conclusion
The standard PN-IEC 60354 implemented in 1999, introduced considerable
changes to the principles of assessing thermal effects of transformers
overloading under various types of load. An essential advantage of the
recommended methods of verification of overloading capacity of transformers is
that the size and cooling modes of transformers are considered.
The tables and curves, provided in this standard, being the result of thermal
calculations allow determining permissible loading of transformers under different
operating conditions.
References
[1] PN-71/E-81000 Transformers. Loading of oil-immersed transformers.
[2] IEC 60354: Loading guide for oil immersed transformers.
[3] Strojny J., Strzałka J.: Design of Electric Power Equipment, (in Polish),
SU1609, AGH-UST Publisher, Krakow 2001.
[4] Strzałka J.: Electric Power Equipment ― Problem Book, (in Polish), SU1674,
AGH-UST Publishers Krakow 2005.

More Related Content

PPTX
PPT
Vacuum circuit breaker
PDF
Saes a-114
PDF
Distribution System Voltage Drop and Power Loss Calculation
PPT
Circuit breaker
PDF
LS Busway Catalogue
PPT
Installation, Testing and Troubleshooting of Transformers
PDF
Industrial communication protocol
Vacuum circuit breaker
Saes a-114
Distribution System Voltage Drop and Power Loss Calculation
Circuit breaker
LS Busway Catalogue
Installation, Testing and Troubleshooting of Transformers
Industrial communication protocol

What's hot (20)

PPTX
Protection Of Generator
PPTX
Fault Level Calculation
PDF
IEEE substation design
PPTX
Overcurrent Protection
PPTX
importance of reactive power in power system
PPSX
Switch yard & Protection
PDF
Practical handbook-for-relay-protection-engineers
PDF
ETAP - Transformer sizing using etap
PPTX
3. INTRODUCTION TO PROTECTIVE RELAYING.pptx
PPT
Reactors
PPTX
Faults on Power System
PDF
Transformer & OLTC
PPTX
On load tap changer
PPTX
Tan delta test for power transformers
PDF
Principles of Cable Sizing
PPT
Power Flow in a Transmission line
PPTX
Static var compensator
PDF
Testing of transformer
PDF
Transformer vector group_test_conditions
PPTX
Protection schemes and zones
Protection Of Generator
Fault Level Calculation
IEEE substation design
Overcurrent Protection
importance of reactive power in power system
Switch yard & Protection
Practical handbook-for-relay-protection-engineers
ETAP - Transformer sizing using etap
3. INTRODUCTION TO PROTECTIVE RELAYING.pptx
Reactors
Faults on Power System
Transformer & OLTC
On load tap changer
Tan delta test for power transformers
Principles of Cable Sizing
Power Flow in a Transmission line
Static var compensator
Testing of transformer
Transformer vector group_test_conditions
Protection schemes and zones
Ad

Similar to Overload capacity of power transformers (20)

PDF
Layer-Type Power Transformer Thermal Analysis Considering Effective Parameter...
PPT
Heat transfer course : physical origins and rate equations
PPT
chap3firstlawthermodynamics-130703012634-phpapp02.ppt
PPTX
Process Heat Transfer 2022-4.pptx
PDF
Analysis of thermal models to determine the loss of life of mineral oil immer...
PDF
02 GTP-14-1384
PDF
Principles-of-Thermodynamics
PDF
4.4.heat exchanger
PDF
Answers to Problems in Heat and Mass Transfer 5th Edition by Yunus Cengel & A...
PPT
carnot cycle.ppt basic thermodynamics...
PDF
Experimental and Analytical Performance of Gas Gap Cryogenic Thermal Switch ...
PDF
chapter 4 first law of thermodynamics thermodynamics 1
PDF
IRJET- Heat Exchanger Analysis and Method to Improve its Effectiveness
PDF
An Efficient High Gain DC-DC Converter for Automotive Applications
PDF
HEAT TRANSFER
PDF
A109210305 thermodynamics1
PPT
carnot cycle (a theoretical thermodynamic cycle).ppt
PPT
carnot cycle.ppt
PDF
Math cad effective radiation heat transfer coefficient.xmcd
DOC
J2006 termodinamik 1 unit9
Layer-Type Power Transformer Thermal Analysis Considering Effective Parameter...
Heat transfer course : physical origins and rate equations
chap3firstlawthermodynamics-130703012634-phpapp02.ppt
Process Heat Transfer 2022-4.pptx
Analysis of thermal models to determine the loss of life of mineral oil immer...
02 GTP-14-1384
Principles-of-Thermodynamics
4.4.heat exchanger
Answers to Problems in Heat and Mass Transfer 5th Edition by Yunus Cengel & A...
carnot cycle.ppt basic thermodynamics...
Experimental and Analytical Performance of Gas Gap Cryogenic Thermal Switch ...
chapter 4 first law of thermodynamics thermodynamics 1
IRJET- Heat Exchanger Analysis and Method to Improve its Effectiveness
An Efficient High Gain DC-DC Converter for Automotive Applications
HEAT TRANSFER
A109210305 thermodynamics1
carnot cycle (a theoretical thermodynamic cycle).ppt
carnot cycle.ppt
Math cad effective radiation heat transfer coefficient.xmcd
J2006 termodinamik 1 unit9
Ad

More from Leonardo ENERGY (20)

PDF
A new generation of instruments and tools to monitor buildings performance
PDF
Addressing the Energy Efficiency First Principle in a National Energy and Cli...
PDF
Auctions for energy efficiency and the experience of renewables
PDF
Energy efficiency first – retrofitting the building stock final
PDF
How auction design affects the financing of renewable energy projects
PDF
Energy Efficiency Funds in Europe (updated)
PDF
Energy Efficiency Funds in Europe
PDF
Five actions fit for 55: streamlining energy savings calculations
PDF
Recent energy efficiency trends in the EU
PDF
Energy and mobility poverty: Will the Social Climate Fund be enough to delive...
PDF
Does the EU Emission Trading Scheme ETS Promote Energy Efficiency?
PPTX
Energy efficiency, structural change and energy savings in the manufacturing ...
PPTX
Energy Sufficiency Indicators and Policies (Lea Gynther, Motiva)
PDF
The Super-efficient Equipment and Appliance Deployment (SEAD) Initiative Prod...
PDF
Modelling and optimisation of electric motors with hairpin windings
PDF
Casting zero porosity rotors
PDF
Direct coil cooling through hollow wire
PDF
Motor renovation - Potential savings and views from various EU Member States
PDF
The need for an updated European Motor Study - key findings from the 2021 US...
PDF
Efficient motor systems for a Net Zero world, by Conrad U. Brunner - Impact E...
A new generation of instruments and tools to monitor buildings performance
Addressing the Energy Efficiency First Principle in a National Energy and Cli...
Auctions for energy efficiency and the experience of renewables
Energy efficiency first – retrofitting the building stock final
How auction design affects the financing of renewable energy projects
Energy Efficiency Funds in Europe (updated)
Energy Efficiency Funds in Europe
Five actions fit for 55: streamlining energy savings calculations
Recent energy efficiency trends in the EU
Energy and mobility poverty: Will the Social Climate Fund be enough to delive...
Does the EU Emission Trading Scheme ETS Promote Energy Efficiency?
Energy efficiency, structural change and energy savings in the manufacturing ...
Energy Sufficiency Indicators and Policies (Lea Gynther, Motiva)
The Super-efficient Equipment and Appliance Deployment (SEAD) Initiative Prod...
Modelling and optimisation of electric motors with hairpin windings
Casting zero porosity rotors
Direct coil cooling through hollow wire
Motor renovation - Potential savings and views from various EU Member States
The need for an updated European Motor Study - key findings from the 2021 US...
Efficient motor systems for a Net Zero world, by Conrad U. Brunner - Impact E...

Recently uploaded (20)

PPTX
Welding lecture in detail for understanding
PDF
BMEC211 - INTRODUCTION TO MECHATRONICS-1.pdf
PDF
Mitigating Risks through Effective Management for Enhancing Organizational Pe...
PPTX
CYBER-CRIMES AND SECURITY A guide to understanding
PPTX
Foundation to blockchain - A guide to Blockchain Tech
PPTX
Engineering Ethics, Safety and Environment [Autosaved] (1).pptx
PPTX
Lecture Notes Electrical Wiring System Components
PDF
R24 SURVEYING LAB MANUAL for civil enggi
PDF
Operating System & Kernel Study Guide-1 - converted.pdf
DOCX
573137875-Attendance-Management-System-original
PPTX
Infosys Presentation by1.Riyan Bagwan 2.Samadhan Naiknavare 3.Gaurav Shinde 4...
PPTX
CARTOGRAPHY AND GEOINFORMATION VISUALIZATION chapter1 NPTE (2).pptx
PDF
July 2025 - Top 10 Read Articles in International Journal of Software Enginee...
PDF
Mohammad Mahdi Farshadian CV - Prospective PhD Student 2026
PDF
Evaluating the Democratization of the Turkish Armed Forces from a Normative P...
PDF
TFEC-4-2020-Design-Guide-for-Timber-Roof-Trusses.pdf
PPTX
MCN 401 KTU-2019-PPE KITS-MODULE 2.pptx
PPTX
web development for engineering and engineering
PPTX
Construction Project Organization Group 2.pptx
PPTX
IOT PPTs Week 10 Lecture Material.pptx of NPTEL Smart Cities contd
Welding lecture in detail for understanding
BMEC211 - INTRODUCTION TO MECHATRONICS-1.pdf
Mitigating Risks through Effective Management for Enhancing Organizational Pe...
CYBER-CRIMES AND SECURITY A guide to understanding
Foundation to blockchain - A guide to Blockchain Tech
Engineering Ethics, Safety and Environment [Autosaved] (1).pptx
Lecture Notes Electrical Wiring System Components
R24 SURVEYING LAB MANUAL for civil enggi
Operating System & Kernel Study Guide-1 - converted.pdf
573137875-Attendance-Management-System-original
Infosys Presentation by1.Riyan Bagwan 2.Samadhan Naiknavare 3.Gaurav Shinde 4...
CARTOGRAPHY AND GEOINFORMATION VISUALIZATION chapter1 NPTE (2).pptx
July 2025 - Top 10 Read Articles in International Journal of Software Enginee...
Mohammad Mahdi Farshadian CV - Prospective PhD Student 2026
Evaluating the Democratization of the Turkish Armed Forces from a Normative P...
TFEC-4-2020-Design-Guide-for-Timber-Roof-Trusses.pdf
MCN 401 KTU-2019-PPE KITS-MODULE 2.pptx
web development for engineering and engineering
Construction Project Organization Group 2.pptx
IOT PPTs Week 10 Lecture Material.pptx of NPTEL Smart Cities contd

Overload capacity of power transformers

  • 1. PowerQuality Guide for electrical design engineers Katarzyna Strzalka-Goluszka Doctoral Student of Faculty of Electrical Engineering, Automatics, IT & Electronics AGH University of Science & Technology kstrzalka@op.pl Power Quality Overload Capacity of Power Transformers Time of day Loadfactor t 24 h0 K2 K1
  • 2. Power Quality 2 www.leonardo-energy.org 1. Introduction For over three decades, since the early seventies, the principles of sizing oil- immersed transformers and evaluation their overload capacity have been defined in standard PN-71/E-81000 [1]. These principles are presented in the course book [3], and examples of practical calculations and transformers sizing are provided in the course book [4]. The basic criterion adopted in standard [1] for determining power transformers loading limits is the thermal life of insulation. The standard defines transformer overload capacity assuming nominal transformer insulation life and reduced insulation life expectancy corresponding to overloading a transformer under disturbed conditions. The basis for consideration in standard [1] was a representative two-step load cycle determined from the known or expected ordered 24-hour load curve of a transformer, described by: • equivalent initial load Sp, • equivalent final load Sk, • duration of the final load tk. The above equivalent load values should be computed as a root mean square average according to the relation: (1) where: Si – load over the time interval Δti, Δti – the considered time interval. The initial and final equivalent loads are determined from the representative load: (2) nt p p S S K = nt k k S S K = ∑ ∑ Δ Δ = i ii t tS S 2
  • 3. Overload Capacity of PowerTransformers 3 www.leonardo-energy.org where: Snt – transformer nominal power. The permissible equivalent final load Kk = f(Kp, tk) is given in standard PN-71/E- 81000 [1] in the form of curves and tables, assuming the following parameters: • ambient temperature ϑo = - 10, 0, 10, 20 and 30ºC • equivalent initial load Kp = 0.25÷1.0 • duration of the final load tk = 0.5, 1, 2, 4, 8, 12 and 24h. Standard PN-IEC 60354 [2] implemented in 1999 considerably alters the principles of determining the overload capacity of oil-immersed transformers. The most important changes are discussed further in this paper. 2. Main assumptions of the standard PN-IEC 60354 methodology The normal service life of transformer is a conventional reference basis for continuous operation in normal ambient temperature under nominal operating conditions. Loading beyond nameplate rating and/or higher ambient temperature involves a risk and results accelerated insulation ageing. Both the loading and temperature rise above the rated values will result in risk of premature failure of a transformer that may occur either immediately or after certain time, due to deterioration of the transformer components. The standard gives guidelines on transformer loading in relation to the operating temperature rise and thermal ageing of insulation; the insulation relative ageing rate is assessed using the hot spot temperature. Since the transformer sensitivity to overloading depends evidently on its size, the standard specifies three categories of transformers: • Distribution transformers (with maximum power of 2500 kVA), for which only the hot-spot temperature and thermal deterioration have to be considered; • Medium power transformers (not exceeding 100 MVA), in which the cooling modes shall be considered; • Large power transformers (exceeding 100 MVA), where the effects of stray leakage flux are significant and the consequences of failure are severe. For each category the standard defines separate requirements. Table 1 shows limit currents and temperatures for the above transformer categories, applicable to loading beyond nameplate rating.
  • 4. Power Quality 4 www.leonardo-energy.org Table 1 : Currents and temperature limits applicable to loading beyond nameplate rating As can be seen from table 1, the standard recommendations apply to three types of transformer loading: • continuous loading, • cyclic loading, • long-time emergency cyclic loading. Standard [2] provides the method for determining thermal behaviour of transformers with various cooling modes and comprises computation results in the form of thermal characteristics for adopted assumptions, among which the most important are: • ambient temperature Θa = 20ºC, • hot-spot temperature rise ΔΘhr = 78ºC. As the basis for analysis of transformer insulation thermal ageing the rule of 6ºC is taken, i.e. the rate of insulation ageing doubles for every increment of approximately 6ºC. Assuming the relative rate of ageing V at the hot-spot temperature Θh = 98ºC equals unity V = 1, thus at the temperature Θh = 104ºC V = 2, and at Θh = 110ºC V = 4. Standard [2] provides the method for calculation of transformer daily loss-of- life, expressed in terms of "normal" days, i.e. equivalent days of operation with rated power at the ambient temperature 20ºC. TYPE OF LOADING DISTRIBUTION TRANSFORMERS MEDIUM POWER TRANSFORMERS LARGE POWER TRANSFORMERS Normal cyclic load: Current [p.u.] Hot-spot temperature [°C] Top-oil temperature [°C] 1.5 140 105 1.5 140 105 1.3 120 105 Long-time emergency cyclic loading: Current [p.u.] Hot-spot temperature [°C] Top-oil temperature [°C] 1.8 150 115 1.5 140 115 1.3 130 115 Short-time emergency loading: Current [p.u.] Hot-spot temperature [°C] Top-oil temperature [°C] 2.0 - - 1.8 160 115 1.5 160 115
  • 5. Overload Capacity of PowerTransformers 5 www.leonardo-energy.org 3. Method of representing an actual load by an equivalent two-step load cycle Fig. 1. Equivalent two-step load cycle The load steps in figure 1 shall be K1 and K2, where K2 is the peak load. The duration of the peak load is t hours. Standard [2] describes the method of determining this duration for different shapes of actual load cycles. In the case of a load cycle with one peak the value of t should be selected on the equal areas basis as indicated in Fig. 2. For the off-peak portion of the load cycle, the value of K1 is selected to correspond to the average off-peak load. Fig. 2. Load cycle with one peak In the case where there are two peaks of nearly equal amplitude but different duration (Fig. 3), the value of time t is determined for the peak of a longer duration and the value of K1 is selected to correspond to the average of the remaining daily load. Time of day Loadfactor t 24 h0 K2 K1
  • 6. Power Quality 6 www.leonardo-energy.org Fig. 3. Load cycle with two peaks of equal amplitude and different duration For the load cycle where two peaks occur in close succession (Fig. 4), the value of t is made long enough to enclose both peaks, and K1 is selected accordingly to the average load during the remaining portion of the day. Fig. 4. Load cycle with peaks in close succession 4. Determining permissible transformer load for various types of loadings For a normal continuous loading, which shows no pronounced variation over a day, the standard [2] recommends the use of a constant equivalent load current. Table 2 gives an acceptable load factor K = K24 for continuous duty and different ambient temperatures.
  • 7. Overload Capacity of PowerTransformers 7 www.leonardo-energy.org Table 2 Acceptable load factor K24 for continuous duty at different ambient temperatures (ON, OF and OD cooling) For normal cycling loading and various types of transformers and eight different ambient temperatures (Θa = -25, -20, -10, 0, 10, 20, 30 and 40°C) standard PN-IEC 60354: 1999 [2] gives curves that can be used to determine the permissible peak load K2 for a given duration t and a given initial load K1. If the ambient temperature value falls between two values, the standard recommends interpolation between the two nearest curves. Figure 5 shows an example of relations K2 = f(K1, t) for distribution transformers with ONAN cooling, and the ambient temperature Θa = +20°C. Fig. 5. Permissible loading of distribution transformers at the ambient temperature 20°C AM BIENT TEM PERATURE, °C -25 -20 -10 0 10 20 30 40 Hot-spot temperature rise, °C 123 118 108 98 88 78 68 58 K24 Distribution transformers ONAN 1.37 1.33 1.25 1.17 1.09 1.00 0.91 0.81 Medium and large power transformers ON 1.33 1.30 1.22 1.15 1.08 1.00 0.92 0.82 OF 1.31 1.28 1.21 1.14 1.08 1.00 0.92 0.83 OD 1.24 1.22 1.17 1.11 1.06 1.00 0.94 0.87
  • 8. Power Quality 8 www.leonardo-energy.org If the supply voltage remains constant the curves K2 = f(K1, t) can also be used for determining the rated power of a transformer (with normal life duration) for a given rectangular load profile defined as the ratio K2/K1. For this purpose it is necessary is to find the intersection of the curve corresponding to the duration of the load K2 with the line of constant slope K2/K1, which can be found by marking corresponding points on ordinate K2 = 1 and abscissa K1 = 1. Figure 1 shows the line for K2/K1 = 1.75, which allows determining the factors K2 = 1.15 and K1 = 0.66 for duration t = 8h. For emergency cyclic loading the standard PN-IEC 60354: 1999 [2] gives tables that can be used to ascertain whether a load characterized by particular values K1 and K2 is permissible for a given ambient temperature, and determine a daily loss of life expressed in "normal" days. These tables correspond to six duration values t (0.5 to 24 h) and four types of transformers. The below example table 4 determines relative ageing rates V and winding hot- spot temperature rise ΔΘh for distribution transformers with ONAN cooling and duration t = 4 h. Table 3 Conversion factor related to the ambient temperature In order to determine whether a daily load diagram characterized by particular values of K1 and K2 is permissible and to evaluate the daily loss of life entailed, the following steps should be preceded: - From table 4 find the hot-spot temperature rise ΔΘh and determine the hot-spot temperature Θh from the formula: Θh = ΔΘh + Θa (3) where: Θa - ambient temperature - If the resulting hot-spot temperature exceeds the limit stated in table 1, the loading is not permissible. AMBIENT TEMPERATURE°C 40°C 30°C 20°C 10°C 0°C -10°C -20°C -25°C Conversion factor kp 10 3.2 1 0.32 0.1 0.032 0.01 0.0055
  • 9. Overload Capacity of PowerTransformers 9 www.leonardo-energy.org - From table 4 find relative ageing rate V and determine the daily insulation loss of life L from the formula: L = V . kp (4) where: kp – the conversion factor related to the ambient temperature according to table 3. Table 4 relative ageing rate V (daily loss of life) and winding hot-spot temperature rise Dqh for distribution transformers with ONAN cooling and duration t = 4 h. 0.25 0.50 0.70 0.80 0.90 1.00 1.10 1.20 1.30 1.40 1.50 0.7 V Δθh 0.003 43 0.080 46 0.032 48 0.8 V Δθh 0.005 51 0.012 53 0.040 56 0.093 57 0.9 V Δθh 0.010 59 0.020 61 0.056 64 0.117 66 0.292 67 1.0 V Δθh 0.023 68 0.039 70 0.091 73 0.170 74 0.377 76 1.00 78 1.1 V Δθh 0.056 77 0.091 73 0.178 83 0.294 84 0.566 86 1.32 87 3.72 89 1.2 V Δθh 0.154 87 0.236 89 0.417 92 0.621 94 1.04 95 2.06 97 5.00 99 14.9 101 1.3 V Δθh 0.455 98 0.677 100 1.12 103 1.56 104 2.36 106 4.02 108 8.13 110 20.5 112 64.7 114 1.4 V Δθh 1.45 109 2.11 111 3.36 114 4.50 115 6.38 117 9.76 119 16.8 121 34.7 123 90.6 125 302 127 1.5 V Δθh 4.94 120 7.09 122 11.00 125 14.4 127 19.7 128 28.2 130 43.7 132 76.1 134 160 137 431 139 1510 141 1.6 V Δθh 17.9 132 25.5 134 38.8 137 50.1 139 66.8 140 93.7 142 135 144 211 146 371 149 790 151 2200 153 1.7 V Δθh 69.0 144 97.3 147 146 149 187 151 246 153 334 155 470 157 694 159 110 161 1950 163 4190 166 1.8 V Δθh 282 157 394 160 587 162 745 164 971 166 1300 167 1790 169 1560 172 3830 174 6110 176 + 179 1.9 V Δθh 1220 171 1690 173 2500 176 3150 177 4080 179 5410 180 7370 183 + + + + + + + + 2.0 V Δθh 5540 184 + + + + + + + + + + + + + + + + + + + + K1 K2
  • 10. Power Quality 10 www.leonardo-energy.org 5. Conclusion The standard PN-IEC 60354 implemented in 1999, introduced considerable changes to the principles of assessing thermal effects of transformers overloading under various types of load. An essential advantage of the recommended methods of verification of overloading capacity of transformers is that the size and cooling modes of transformers are considered. The tables and curves, provided in this standard, being the result of thermal calculations allow determining permissible loading of transformers under different operating conditions. References [1] PN-71/E-81000 Transformers. Loading of oil-immersed transformers. [2] IEC 60354: Loading guide for oil immersed transformers. [3] Strojny J., Strzałka J.: Design of Electric Power Equipment, (in Polish), SU1609, AGH-UST Publisher, Krakow 2001. [4] Strzałka J.: Electric Power Equipment ― Problem Book, (in Polish), SU1674, AGH-UST Publishers Krakow 2005.