SlideShare a Scribd company logo
SUMMER
INDUSTRIAL
TRAINING REPORT
JULY-2015
Submitted By- Lovit Sawhney
RVNL_Report_ppt
Overview
 SBOQ- Standard Bill of
Quantities
 TRD- Traction Distribution
 TPC- Traction Power
Control
 TSS- Traction Substation
 OHE- Over Head
Equipments
 Mast(Poles)- used for
Cantilever Assembly
Cantilever Assembly
Cantilever
Assembly
in a Metro
Station
(DMRC)
Tenders
SBD- Standard Bidding Document
 Technical Bid
 Financial Bid
PMC Contract- Project Management
Consultancy --> Monitors the
Project
Reviewed SBOQ for Railway
Electrification and General Electrical
works.
Reviewed the Detailed Project
Report for New Metro Corridors in
Kolkata
Reviewed Sanctioned Estimate for Power Supply &
Distribution and Traction Third Rail for Kavi
Subhash(New Garia) to VIP Road Section on Kavi
Subhash(New Garia)- Biman Bandar(Airport)
Corridor for Kolkata Metro Project
Office Working
ED(Executive
Director)/Electrical
GGM(Group
General
Manager)/E
DGM(Deputy
General
Manager)/E
Sr. Mgr./E
Site Engr.(e.g.
Kolkata Metro)
GGM/E/P(Projects)
Some Projects Under
RVNL
 Electrification- Rani-
Palampur(RE/High Rise)
 Metro- Kolkata Metro
 Joka- BBD bagh(16.72 km)
 New Garia- Airport(32 km)
 Bara nagar- Barrackpur(12.5
km)[Focus on the above both
right now.]
Others(GEW)
 Rishikesh- Karnaprayag= New
Line
 Lucknow- Pilibhit= Gauge
conversion
 Ahmedabad- Botad= Gauge
Conversion
 Palampur- Samakhiali= Doubling
Interruptor No
Relay provided
with this
Isolator Manual
motor by TPC
Circuit
Breaker(C
.B.)
ABCB(in
GSS)
BOCB(Bul
k Oil)
MOCB(Me
tal Oil)
SF6(Gas)
VCB(Vacu
um)
SCADA
 Supervision
Control and Data
Acquisition-
Centralised Control
System(For
ON/OFF)
 SCADA System
reads the
measured flow and
level, and sends
the setpoints to the
PCCs.
E&M Design
(ASS-
Auxillary
Substation)
 Transformer
Sizing
 DG Sizing,
UPS System
 Fault
Calculation
 Lighting
 Cable Sizing
 HVAC
 Fire Action
 Fire Alarm &
Detection
 Fire Fighting
Transport Networks
 Rail Network:
 12 rail alignments
 105 suburban passenger railway stations(with an
avg. interval of 2-2.5 km)
 Important Terminals: Sealdah and Howrah
 Administered by Eastern Railway and SE Railway
 Circular Rail
 Total Length: 34 km
 16 km over the existing suburban route of Majerhat-
Ballygunge- Dum Dum via Kankgachi Chord of
Sealdah division
 18 km over Old Calcutta Port Trust Railways and
Eastern Railway’s Chitpur Yard
 Suburban Railway
 10 rail alignments of 1230 km length
 Metro System
 Extension from Dum Dum to Naopara- Metro
Railway
 East West Corridor(from Howrah Maidan upto Salt
Lake Sector V)- KMRCL
 Naopara to Dashineshwar- RVNL
 Naopara to Barasat- Metro Railway
Study of Final Detailed Project Report for
New Metro Corridors in
Kolkata(December- 2012)- Joka to
Majerhat(Phase- I)
1
System Selection
 Gauge Selection
 Broad Gauge has been adopted for proposed
Kolkata Metro corridors
 Transport System Capacity
 Design Capacity of about 42,000 passengers per
hour per direction
 Train Length upto 8 coaches
 Traction System Selection
 750V dc third rail in Kolkata Metro
 1500V dc catenary in Mumbai suburban of
Central and Western Railways
 25kV ac catenary in Delhi Metro and Indian
Railways
 Signaling and Tele-communication
 DMRC, BMRCL, HYD. METRO, JMRC
 CATC- Continuous Automatic Control System:
 ATS- Automatic Train Supervision
 ATP- Automatic Train Protection
 Computer based interlocking
 AFTC- Audio Frequency Track Circuits
Train Operations
 COMPOSITION
 MC: Motor Coach
 DTC: Driving Trailer Coach
 TC: Non- Driving Trailer Coach
 DTC-MC-TC-MC-MC-TC-MC-DTC
 CAPACITY: 2600(430- Sitting & 2180-
Standing) 2
POWER SUPPLY SYSTEM
 Overview of existing PSS
 Kolkata Metro receives power from
CESC at 33kV
 PS is controlled through SCADA system
 Need for high reliability of power
supply
 Requirement of electric power supply
 For running trains
 For station services(lighting, ventilation,
lifts, escalators
 For depots and maintenance of
infrastructure
 Designed Load estimation
 8 car rake- headway of 150 seconds
 Specific Energy Consumption-
80kW/1000 GTKM
 Elevated/at grade station load(initially)-
250kW
 Underground Station load-
1500kW(initially)
 Depot auxiliary load- 1500kW(initially)
3
 Selection of Traction System
 750V dc third rail system
 1500V dc overhead catenary system
 25kV ac overhead catenary system
 Traction Power demand
estimation Year
2015 2025 2035
Train
Composition
8 car 8 car 8 car
Headway 8.6 min 7.5 min 6 min
No. of train/hr. 7 nos. 8 nos. 10 nos.
Section(Corridor) Year
2015 2025 2035
Joka-
Majerhat
section
(Joka-BBD
Bagh
Traction 4.12 4.71 5.89
Auxiliar
y
3.06 3.53 4.00
Total 7.18 8.24 9.89
Net demand considering
5% distribution losses
7.54 8.65 10.39
Train Operation Plan
Power Demand Estimation (MVA)
4
Section
(Corridor)
Grid sub-
station (input
source)
Location of
RSS
Approx.
Length
of 33kV
cables
Joka-
Majerhat
(Joka-BBD
Bagh)
Joka sub-
station
(WBSEDCL)
Joka Station 1 km,
(Double
circuit)
Majerhat sub-
station
(CESC)
Majerhat
Station
1 km,
(Double
Circuit)
 Power Supply Source
 Power Supply Distribution
Arrangement
33 kV drawn from two RSSs via
Joka and Majerhat distributed
through 33 kV ring main cable
network for feeding to traction as well
as auxiliary loads.
 Elimination of intermediate voltage grade of
11kV
 Advantages
 Improved Reliability
 Reduced Space Requirement
 Reduced Operational Cost
 Improved Voltage Regulation 5
MAJOR POWER SUPPLY EQUIPMENTS/SYSTEMS
 Traction Substations(33kV/780V dc)
 Traction Substation converter for energy recovery
 Third Rail
 Made of composite Aluminum Steel
 Switch Gear
 GIS(Gas Insulated Switch gear)
 Rectifier HSCB (High Speed Circuit Breaker)
Feeder HSCB
 Cables
 33kV cable network
 DC cable between rectifier to rectifier HSCB
 DC cable from TSS to third rail
Auxiliary Power Supply and Emergency Backup
 Auxiliary supply arrangements for stations and
depot(ASS)
 Two dry type cast resin transformers(33/0.415kV) of
500kVA & 2500kVA
 Standby Power Supply
 Standby DG set of 200kVA

SCADA SYSTEM
 Receiving, traction and auxiliary supply of power
supply shall be monitored and controlled from a
centralized operation Control centre (OCC) through
SCADA system.
6
E & M SYSTEM
 Design Criteria
 System Voltage: 4/5V 3 phase 4
wires/240V 1 phase 2 wires, 50 Hz
 Ambient Temp.: 40˚C
 Demand Factor: 80%
 Load Power Factor: 0.95
 Voltage Drop(Final Circuit): 5%
 Colour Code
For Cable and Busbar-
Phase A: Red
Phase B: Yellow
Phase C: Blue
Neutral: Black
Ground: Green or Yellow Strip Green
Emergency Lighting Cable: Orange
 Standards, Codes and Regulations
ASME American Society of Mech. Engrs.(USA)
ASTM American Society of Testing Materials
IS/BIS Bureau of Indian Standards
BS British Standard
EA The Electricity Act, 2008
EN European Norms
IEC International Electro-Technical Commission
IS Indian Standards
ISO International Organization for
Standardization
NBC National building Code of India, 2008
NEC National Electrical Code
NEMA National Electrical Manufacturers
7
 Low Voltage Power Distribution System
 Transformers and Cables
 Two dry type cast resin transformers(33/0.415kV) of 500kVA & 2500kVA
 IEC60502
IEC60331 and BS6387- Fire resistant cables(for safety purposes)
 Low Voltage Switchboards
 Over Current Protection
 Earth Fault Protection
 Under Voltage and Over Voltage Protection
 Voltmeter and Selector Switch
 Ammeter and Selector Switch
 Indicating Lamps
 Digital meter for kW, kVA, kVAR and Power Factor meter
 Power Factor Control
 ACB Shunt trip
 Auxiliary contacts for remote monitoring via E&M SCADA System
 Lighting System
240V, Single Phase 50Hz Power Supply
 Emergency Power Supply
 Lift Operation
 Essential Lighting
 Signaling and Telecommunication
 Fire Fighting System
 Fare Collection System
 E&M SCADA System
 Microprocessor based distributed controllers interface directly with sensors,
actuators and environment delivery systems, i.e. HVAC units, electrical
system, Fire Alarm system, Fire Fighting System, and Plumbing & Drainage
System.
 Remote Processing Units (RPU) required for interface with different stations.
 A serial link communication network to allow data exchange between devices
in the system, i.e. Fire Alarm System, Fire Fighting System, Lifts and
Escalators, HVAC, Plumbing and Drainage. System, Lighting System, Low
Voltage Power Supply System, etc.
 Marshalling Cabinets for terminating E&M SCADA interface monitor and
control signal wiring.
 Associated Power & Control Cables.
8
VIADUCT PIERS-
Earth Conductors
Cable Layout-
Joka Metro Station
(Concourse Level)
Traction Power Control- NDLS
Control Office- NDLS
Traction Substation-
Chanakyapuri
Power System Installation-
NDLS
FIELD TRIPS
Control office where operation of
lines(power supply facilities) are
held with the help of SCADA
Traction Power
Control- NDLS
The arrival time and
the departure time of
a specific train at a
specific station is give
as a input with the
help of the received
feedback.
Trains moving on
Line no. 2 and Line
no. 3 can gain their
maximum speeds,
whereas loop 1 and
loop 4 are used near
the stations and the
trains are required
to slow down on
these lines.
Control Office-
NDLS
Mapping of the timings of
the specific trains is done
simultaneously and
automatically, resulting in
a graph/map which is
used to track a train.
Delhi-Ambala
Division
Traction Sub-
Station-
Chanakyapuri
66 kV/25kV
Traction Sub-
Station
Traction Sub-
Station-
Chanakyapuri…cntd
1. Supply
Arrangement at
Railway TSS.
2. Systematical
Diagram of
66kV/25kV TSS.
3. Earthing
Arrangement at
TSS.
4. Various
Equipments in a
TSS.
Power Supply
Installation- NDLS
Auxiliary Transformers
which are paired up as (AT-
1, AT-2); (AT-3, AT-4); (AT-
5, AT-6).
POWER
SUPPLY
INSTALLATIO
N BOARD
Power Supply Installation-
NDLS… cntd.
Power
Supplies-
1.Local
Supply (3
phase, 230
V/50Hz
2.AT
Supply(50
Hz)
3.Generator
Supply (3
phase, 215
V/50 Hz

More Related Content

PDF
Brett Roberts - Some aspects of electrical power system protection in undergr...
PPTX
Power Electronic Converter
PPTX
Design of a 400kv Transmission network
PDF
Safety Evaluation of Live Line operators of 1200 KV UHV AC Exposed to Electri...
PPTX
Advance Power Electronic Converters for Renewable Energy Systems
PDF
Design and implementation of active power filter for harmonic elimination and...
PPTX
Advancements in inverter technology
PDF
Corrected Paper1
Brett Roberts - Some aspects of electrical power system protection in undergr...
Power Electronic Converter
Design of a 400kv Transmission network
Safety Evaluation of Live Line operators of 1200 KV UHV AC Exposed to Electri...
Advance Power Electronic Converters for Renewable Energy Systems
Design and implementation of active power filter for harmonic elimination and...
Advancements in inverter technology
Corrected Paper1

What's hot (20)

PDF
UPS Electrical Design and Installation
DOCX
Final report of 220kv gss working model
DOC
Ali Kamil CV
PDF
Comparision of svc and statcom
PPTX
Electrical power system management
PPTX
Single phase grid connected fuel system based on boost inverter
PDF
Neil Kirby: VSC HVDC Transmission and Emerging Technologies in DC Grids
PPTX
HVDC presentation
PDF
PDF
46584589 substation-design-data
PDF
Optimal Cable Sizing in PV Systems: Case Study
PDF
Lou Fusco - PG&E
PDF
Enhancement of reactive power capability of doubly fed induction generator 2-3
PDF
Elk 24-5-32-1410-127
PPTX
bi directional intelligent semiconductor transformer P
PPT
application of power electronics
PPTX
Improved reactive power capability with grid connected doubly fed induction g...
PDF
Solar Micro Inverter
PPTX
220 kV GSS Mansarovar Jaipur (RVPNL) Training PPT SM54
UPS Electrical Design and Installation
Final report of 220kv gss working model
Ali Kamil CV
Comparision of svc and statcom
Electrical power system management
Single phase grid connected fuel system based on boost inverter
Neil Kirby: VSC HVDC Transmission and Emerging Technologies in DC Grids
HVDC presentation
46584589 substation-design-data
Optimal Cable Sizing in PV Systems: Case Study
Lou Fusco - PG&E
Enhancement of reactive power capability of doubly fed induction generator 2-3
Elk 24-5-32-1410-127
bi directional intelligent semiconductor transformer P
application of power electronics
Improved reactive power capability with grid connected doubly fed induction g...
Solar Micro Inverter
220 kV GSS Mansarovar Jaipur (RVPNL) Training PPT SM54
Ad

Viewers also liked (20)

PPTX
PPT
Connect to Success with LinkedIn - The Art of Meaningful Conversation
DOCX
Bis220 final exam
DOCX
पिपरासी खुले से सौच मुक्त करने में मीडिया का सहयोग
PDF
WB GENDER DIMENSIONS OF EXTRACTIVE INDUSTRIES august 2009
DOC
Apa si substantele minerale
PDF
Networks All Around Us: Extracting networks from your problem domain
PPT
Agile Data Science: Hadoop Analytics Applications
PPSX
Your moment is Waiting
PDF
JSON-LD Update
PDF
Enabling Multimodel Graphs with Apache TinkerPop
PDF
SF Python Meetup: TextRank in Python
PDF
C0110913
PDF
Project report
PPT
Kolkata metro branding
PPTX
Cantina machito_Allison_Tania
PDF
Disrupção
Connect to Success with LinkedIn - The Art of Meaningful Conversation
Bis220 final exam
पिपरासी खुले से सौच मुक्त करने में मीडिया का सहयोग
WB GENDER DIMENSIONS OF EXTRACTIVE INDUSTRIES august 2009
Apa si substantele minerale
Networks All Around Us: Extracting networks from your problem domain
Agile Data Science: Hadoop Analytics Applications
Your moment is Waiting
JSON-LD Update
Enabling Multimodel Graphs with Apache TinkerPop
SF Python Meetup: TextRank in Python
C0110913
Project report
Kolkata metro branding
Cantina machito_Allison_Tania
Disrupção
Ad

Similar to RVNL_Report_ppt (20)

DOCX
INTERNSHIP REPORT (FINAL)
PDF
Metro rail project in india year 2017
DOCX
metro naveen
PPTX
jaipur metro railway corporation JMRC.pptx
PDF
2017 Atlanta Regional User Seminar - Using OPAL-RT Real-Time Simulation and H...
PPTX
Abhishek scada ppt
PPTX
Abhishek scada ppt
PPTX
SEMINAR-2015 (abhishek)
PDF
Transmission and Distribution.
PPT
ATC for congestion management in deregulated power system
PDF
Lecture No 0_installation_electrical.pdf
PPT
Sro Project Brief
PPTX
NMRC Summer Tanning/Internship PPT(Anand Mohan )
PPTX
Industrial Training PPT-Divyansh Khelani.pptx
PPTX
Electric traction
PDF
Understanding operation of shunt capacitors and oltc for transmission
PPTX
ELECTRIC TRACTION SYSTEM
PDF
Automation- Metering, Sub Station & Industrial Automation
PPTX
Electric traction system
PPTX
Electric Traction System benefits and different types of electric traction sy...
INTERNSHIP REPORT (FINAL)
Metro rail project in india year 2017
metro naveen
jaipur metro railway corporation JMRC.pptx
2017 Atlanta Regional User Seminar - Using OPAL-RT Real-Time Simulation and H...
Abhishek scada ppt
Abhishek scada ppt
SEMINAR-2015 (abhishek)
Transmission and Distribution.
ATC for congestion management in deregulated power system
Lecture No 0_installation_electrical.pdf
Sro Project Brief
NMRC Summer Tanning/Internship PPT(Anand Mohan )
Industrial Training PPT-Divyansh Khelani.pptx
Electric traction
Understanding operation of shunt capacitors and oltc for transmission
ELECTRIC TRACTION SYSTEM
Automation- Metering, Sub Station & Industrial Automation
Electric traction system
Electric Traction System benefits and different types of electric traction sy...

RVNL_Report_ppt

  • 3. Overview  SBOQ- Standard Bill of Quantities  TRD- Traction Distribution  TPC- Traction Power Control  TSS- Traction Substation  OHE- Over Head Equipments  Mast(Poles)- used for Cantilever Assembly
  • 5. Tenders SBD- Standard Bidding Document  Technical Bid  Financial Bid PMC Contract- Project Management Consultancy --> Monitors the Project Reviewed SBOQ for Railway Electrification and General Electrical works.
  • 6. Reviewed the Detailed Project Report for New Metro Corridors in Kolkata
  • 7. Reviewed Sanctioned Estimate for Power Supply & Distribution and Traction Third Rail for Kavi Subhash(New Garia) to VIP Road Section on Kavi Subhash(New Garia)- Biman Bandar(Airport) Corridor for Kolkata Metro Project
  • 9. Some Projects Under RVNL  Electrification- Rani- Palampur(RE/High Rise)  Metro- Kolkata Metro  Joka- BBD bagh(16.72 km)  New Garia- Airport(32 km)  Bara nagar- Barrackpur(12.5 km)[Focus on the above both right now.] Others(GEW)  Rishikesh- Karnaprayag= New Line  Lucknow- Pilibhit= Gauge conversion  Ahmedabad- Botad= Gauge Conversion  Palampur- Samakhiali= Doubling
  • 10. Interruptor No Relay provided with this Isolator Manual motor by TPC Circuit Breaker(C .B.) ABCB(in GSS) BOCB(Bul k Oil) MOCB(Me tal Oil) SF6(Gas) VCB(Vacu um) SCADA  Supervision Control and Data Acquisition- Centralised Control System(For ON/OFF)  SCADA System reads the measured flow and level, and sends the setpoints to the PCCs. E&M Design (ASS- Auxillary Substation)  Transformer Sizing  DG Sizing, UPS System  Fault Calculation  Lighting  Cable Sizing  HVAC  Fire Action  Fire Alarm & Detection  Fire Fighting
  • 11. Transport Networks  Rail Network:  12 rail alignments  105 suburban passenger railway stations(with an avg. interval of 2-2.5 km)  Important Terminals: Sealdah and Howrah  Administered by Eastern Railway and SE Railway  Circular Rail  Total Length: 34 km  16 km over the existing suburban route of Majerhat- Ballygunge- Dum Dum via Kankgachi Chord of Sealdah division  18 km over Old Calcutta Port Trust Railways and Eastern Railway’s Chitpur Yard  Suburban Railway  10 rail alignments of 1230 km length  Metro System  Extension from Dum Dum to Naopara- Metro Railway  East West Corridor(from Howrah Maidan upto Salt Lake Sector V)- KMRCL  Naopara to Dashineshwar- RVNL  Naopara to Barasat- Metro Railway Study of Final Detailed Project Report for New Metro Corridors in Kolkata(December- 2012)- Joka to Majerhat(Phase- I) 1
  • 12. System Selection  Gauge Selection  Broad Gauge has been adopted for proposed Kolkata Metro corridors  Transport System Capacity  Design Capacity of about 42,000 passengers per hour per direction  Train Length upto 8 coaches  Traction System Selection  750V dc third rail in Kolkata Metro  1500V dc catenary in Mumbai suburban of Central and Western Railways  25kV ac catenary in Delhi Metro and Indian Railways  Signaling and Tele-communication  DMRC, BMRCL, HYD. METRO, JMRC  CATC- Continuous Automatic Control System:  ATS- Automatic Train Supervision  ATP- Automatic Train Protection  Computer based interlocking  AFTC- Audio Frequency Track Circuits Train Operations  COMPOSITION  MC: Motor Coach  DTC: Driving Trailer Coach  TC: Non- Driving Trailer Coach  DTC-MC-TC-MC-MC-TC-MC-DTC  CAPACITY: 2600(430- Sitting & 2180- Standing) 2
  • 13. POWER SUPPLY SYSTEM  Overview of existing PSS  Kolkata Metro receives power from CESC at 33kV  PS is controlled through SCADA system  Need for high reliability of power supply  Requirement of electric power supply  For running trains  For station services(lighting, ventilation, lifts, escalators  For depots and maintenance of infrastructure  Designed Load estimation  8 car rake- headway of 150 seconds  Specific Energy Consumption- 80kW/1000 GTKM  Elevated/at grade station load(initially)- 250kW  Underground Station load- 1500kW(initially)  Depot auxiliary load- 1500kW(initially) 3
  • 14.  Selection of Traction System  750V dc third rail system  1500V dc overhead catenary system  25kV ac overhead catenary system  Traction Power demand estimation Year 2015 2025 2035 Train Composition 8 car 8 car 8 car Headway 8.6 min 7.5 min 6 min No. of train/hr. 7 nos. 8 nos. 10 nos. Section(Corridor) Year 2015 2025 2035 Joka- Majerhat section (Joka-BBD Bagh Traction 4.12 4.71 5.89 Auxiliar y 3.06 3.53 4.00 Total 7.18 8.24 9.89 Net demand considering 5% distribution losses 7.54 8.65 10.39 Train Operation Plan Power Demand Estimation (MVA) 4
  • 15. Section (Corridor) Grid sub- station (input source) Location of RSS Approx. Length of 33kV cables Joka- Majerhat (Joka-BBD Bagh) Joka sub- station (WBSEDCL) Joka Station 1 km, (Double circuit) Majerhat sub- station (CESC) Majerhat Station 1 km, (Double Circuit)  Power Supply Source  Power Supply Distribution Arrangement 33 kV drawn from two RSSs via Joka and Majerhat distributed through 33 kV ring main cable network for feeding to traction as well as auxiliary loads.  Elimination of intermediate voltage grade of 11kV  Advantages  Improved Reliability  Reduced Space Requirement  Reduced Operational Cost  Improved Voltage Regulation 5
  • 16. MAJOR POWER SUPPLY EQUIPMENTS/SYSTEMS  Traction Substations(33kV/780V dc)  Traction Substation converter for energy recovery  Third Rail  Made of composite Aluminum Steel  Switch Gear  GIS(Gas Insulated Switch gear)  Rectifier HSCB (High Speed Circuit Breaker) Feeder HSCB  Cables  33kV cable network  DC cable between rectifier to rectifier HSCB  DC cable from TSS to third rail Auxiliary Power Supply and Emergency Backup  Auxiliary supply arrangements for stations and depot(ASS)  Two dry type cast resin transformers(33/0.415kV) of 500kVA & 2500kVA  Standby Power Supply  Standby DG set of 200kVA  SCADA SYSTEM  Receiving, traction and auxiliary supply of power supply shall be monitored and controlled from a centralized operation Control centre (OCC) through SCADA system. 6
  • 17. E & M SYSTEM  Design Criteria  System Voltage: 4/5V 3 phase 4 wires/240V 1 phase 2 wires, 50 Hz  Ambient Temp.: 40˚C  Demand Factor: 80%  Load Power Factor: 0.95  Voltage Drop(Final Circuit): 5%  Colour Code For Cable and Busbar- Phase A: Red Phase B: Yellow Phase C: Blue Neutral: Black Ground: Green or Yellow Strip Green Emergency Lighting Cable: Orange  Standards, Codes and Regulations ASME American Society of Mech. Engrs.(USA) ASTM American Society of Testing Materials IS/BIS Bureau of Indian Standards BS British Standard EA The Electricity Act, 2008 EN European Norms IEC International Electro-Technical Commission IS Indian Standards ISO International Organization for Standardization NBC National building Code of India, 2008 NEC National Electrical Code NEMA National Electrical Manufacturers 7
  • 18.  Low Voltage Power Distribution System  Transformers and Cables  Two dry type cast resin transformers(33/0.415kV) of 500kVA & 2500kVA  IEC60502 IEC60331 and BS6387- Fire resistant cables(for safety purposes)  Low Voltage Switchboards  Over Current Protection  Earth Fault Protection  Under Voltage and Over Voltage Protection  Voltmeter and Selector Switch  Ammeter and Selector Switch  Indicating Lamps  Digital meter for kW, kVA, kVAR and Power Factor meter  Power Factor Control  ACB Shunt trip  Auxiliary contacts for remote monitoring via E&M SCADA System  Lighting System 240V, Single Phase 50Hz Power Supply  Emergency Power Supply  Lift Operation  Essential Lighting  Signaling and Telecommunication  Fire Fighting System  Fare Collection System  E&M SCADA System  Microprocessor based distributed controllers interface directly with sensors, actuators and environment delivery systems, i.e. HVAC units, electrical system, Fire Alarm system, Fire Fighting System, and Plumbing & Drainage System.  Remote Processing Units (RPU) required for interface with different stations.  A serial link communication network to allow data exchange between devices in the system, i.e. Fire Alarm System, Fire Fighting System, Lifts and Escalators, HVAC, Plumbing and Drainage. System, Lighting System, Low Voltage Power Supply System, etc.  Marshalling Cabinets for terminating E&M SCADA interface monitor and control signal wiring.  Associated Power & Control Cables. 8
  • 20. Cable Layout- Joka Metro Station (Concourse Level)
  • 21. Traction Power Control- NDLS Control Office- NDLS Traction Substation- Chanakyapuri Power System Installation- NDLS FIELD TRIPS
  • 22. Control office where operation of lines(power supply facilities) are held with the help of SCADA Traction Power Control- NDLS
  • 23. The arrival time and the departure time of a specific train at a specific station is give as a input with the help of the received feedback. Trains moving on Line no. 2 and Line no. 3 can gain their maximum speeds, whereas loop 1 and loop 4 are used near the stations and the trains are required to slow down on these lines. Control Office- NDLS Mapping of the timings of the specific trains is done simultaneously and automatically, resulting in a graph/map which is used to track a train. Delhi-Ambala Division
  • 25. Traction Sub- Station- Chanakyapuri…cntd 1. Supply Arrangement at Railway TSS. 2. Systematical Diagram of 66kV/25kV TSS. 3. Earthing Arrangement at TSS. 4. Various Equipments in a TSS.
  • 26. Power Supply Installation- NDLS Auxiliary Transformers which are paired up as (AT- 1, AT-2); (AT-3, AT-4); (AT- 5, AT-6). POWER SUPPLY INSTALLATIO N BOARD
  • 27. Power Supply Installation- NDLS… cntd. Power Supplies- 1.Local Supply (3 phase, 230 V/50Hz 2.AT Supply(50 Hz) 3.Generator Supply (3 phase, 215 V/50 Hz