BWR—04 Series
Transformer Winding
Temperature Indicator
Operation
Instructions
Hangzhou HuaLi Instrument Co.,Ltd
Address:27 Longwu Industrial Zone,West Lack District, Hangzhou Post code:
310024
Tel : 0571-87088120 E-mail: lanshan@mail.hz.zj.cn
Fax: 0571-87919920 Http://www.hz-hlyb.com
- 1 -
Thanks for using our products
Beforeoperatingit,pleasereadthismanualthoroughly
Contents
1.Brief Introduction …………………………………………………………………(1)
2.Model Illuminate……………………………………………………………………(1)
3.Composing And Function ………………………………………………………(1)
4.Main Technical Parameters………………………………………………………(4)
5.Installation …………………………………………………………………………… (5)
6.Wiring…………………………………………………………………………………… (6)
7. Setting & Adjusting ………………………………………………………………(8)
8.Points of Attention…………………………………………………………………(10)
9.Addendum ……………………………………………………………………………(11)
- 2 -
1.Brief Introduction
Transformer winding thermoregulator is specially designed for oil-immersed transformer,
which can indirectly measure the winding temperature by thermal simulation method.
Let T1 present the temperature of transformer winding and it is the sum of T2 and △T, i.e. T1
=T2+△T, where, T2 is the oil temperature in upper part of the transformer, and △T is the winding
temperature rise relative to the oil temperature. The △T depends on the winding current and the
secondary current of the current transformer (CT) is in proportion to the winding current. The
thermoregulator works in following. Principle: The current from the CT, which is in proportion to
the load, is first adjusted via a converter, and then flows through the heating element embedded in
the elastic component; the heat produced by the heating element leads to an additional displacement
of the elastic component, and thus a temperature indicated value higher than the oil temperature. By
this way, the thermoregulator can obtain an average indicated value of the winding temperature.
2.Model Illuminate
The model and illuminate of the transformer winding temperature indicator:
3. Composing And Function
1.BWR-04 series winding temperature indicator:
(1) Indicate the temperature of transformer winding.
(2)Afford four sets of switch (AC250V/15A) , which can be set within a whole span, are
employed to respectively control over the transformer cooling system, overheating alarming and
- 3 -
BWR
XMT 288 F C- Ⅲ
Design code(For BWR-04)
Output code
Rectangle
Control
digital display temperature indicator
Design code:
Ⅰ:Outside place of the convertor
(code abridges)
Ⅱ:Inside of the wire-wound potentiometer
Ⅲ:Inside of the convertor
Output function:
DC(4-20)mA(code abridge)
A:Pt100 platinum resistance
E:DC(0-5)V
Number of switches
For transformer
tripping, etc.
(3) Output (4~20)mA electricity signal to be the input of the digital display thermometer
which is in the controlling room.
The outline drawing and mounting dimension of the winding temperature indicator refer Figure
1.The outline drawing and mounting dimension of the export of BWR-04 refer addendum(offer the
overseas transformer producer)
Figure 1 BWR-04 thermoregulator outline drawing and mounting dimension
2.Convertor
The function of the convertor is got electricity for the CT of the main transformer. Then after
- 4 -
0 150
50 100
BWR-04
C
°
XMT-288FC
.
adjust, send it to the heating element of the winding temperature indicator. So that the indicator can
show a temperature value which is high then the oil temperature which is △T.
The convertor that bases on the different rating electricity, which is 5A, 3A, 2A, 1A,of CT of
the main transformer, which can be divide into four different connection. Idiographic connection
method refers table 2 or the connection diagram in the convertor cover .
The outline drawing and mounting dimension of the convertor refer Figure 2
Figure 2 Convertor outline drawing and mounting dimension
3.XMT—288FC—Ⅲ Digital Display Thermometer
The transformer change the temperature into the (4~20) mA electricity signal, then send into
the digital display thermometer XMT—288FC—Ⅲ, which is fixed in the controlling room. The
man who is on duty can expediently observe the temperature of the transformer in controlling
room. And it also can send the signals
whatever you need for computer as
follows:
(1)(4-20) mA direct current signal.
(2)(0-5)V or (1-5)V constant
voltage signal.
(3)RS232,RS485 communication
interface.
The outline drawing and
mounting dimension of XMT—288FC
—Ⅲ refer Figure 3.
Figure 3 XMT—288FC—Ⅲ outline drawing and mounting dimension
- 5 -
4. Main Technical Parameters
1.BWR-04 Main Technical Parameters:
(1) NORMAL WORKING CONDITION:(-40~+55)℃
(2)Range of measurement:(0~150)℃
(3)Indication accuracy:±3℃
(4)Controlling capability:
①Setting range:adjustable within the work span ②Setting accuracy:±3℃
③switch difference:6±2℃ ④RATED POWER:AC250V/15A
(5)standard setting point:
K1=55℃ K2=75℃ K3=90℃ K4=130℃
(6)Protection performance:IP55
2.Convertor Main Technical Parameters:
(1) NORMAL WORKING CONDITION:(-40~55)℃
(2) Protection performance:IP55
(3) Main technical parameters refer table 1.
3.XMT-288FC-ⅢMain Technical Parameters:
1. Normal working condition: (-10~50) ℃
2. Measuring range: (0~150) ℃
3.Input signal:DC (4-20) mA
4. Accuracy:1.0
5. Resolution ratio:0.1℃
6.Controlling capability
(1) Controlling mode:Upper limit contact
(2)Setting range :Adjustable within the work span
(3) Contact capacity:AC220V,3A
7.Output:DC(4-20)mA
Notice:It can be made with RS232,RS485 or other output signal according to customer’s
order.
- 6 -
TABLE 1 Convertor Technical Parameters
Type Input current
IP(A)
Output currrent Is/Input current Ip AdjustleadKconnect toport’s NO.
A 5≥Ip>3
0.30~0.35 17-6
0.24~0.30 17-7
0.15~0.24 17-8
0.10~0.15 17-9
B 3≥Ip>2
0.50~0.60 17-7
0.40~0.50 17-8
0.28~0.40 17-10
0.17~0.28 17-11
C 2≥Ip>1
0.75~0.90 17-12
0.60~0.75 17-13
0.40~0.60 17-14
0.25~0.40 17-15
D 1≥Ip>0.61
1.50~1.75 17-6
1.20~1.50 17-7
1.00~1.20 17-14
0.50~1.00 17-16
5. Installation
1. Installation of BWR-04 and Convertor
Screw 4 hexagonal bolts (M8) and 4 matched washers accessorized (φ10)with BWR—04 into
a mounting board of transformer.
Screw 4 hexagonal bolts (M6) and 4 matched washers accessorized (φ7)with Convertor into a
mounting board of transformer.
2. Installation of bulb
Wrap the installation screw thread on the bulb with appropriate seal material. Insert the bulb
into the transformer’s sleeve with oil inside it. Screw the mounting screw on the bulb into the sleeve
until fasten the sealing washer. At last screw the airproof bolt fast.
3. Installation of XMT-288FC-Ⅲ
- 7 -
The XMT-288FC-Ⅲ install on either an operations area or an instrument screen with two
mounting racks and two screws which provided. The size of aperture on instrument screen is high*
wide =(152*76) mm.
6. Wiring
1.Connection of convertor
You have to take off the cover to wire the adaptor convertor,loose the screws which is on the
lead terminal, take out the airproof in the lead terminal , and then you can connection the lead.
Depend on the difference of the maximum current of CT, the method of the convertor has A,B,C,D
four kinds. The connection diagrams of convertor refer to table 2.
TABLE 2 The Connection of Convertor
Type The Maximum
Current of CT
Connection Diagrams (R:Heating Element K:Adjusting Lead)
A 5.0A
B 3.0A
C 2.0A
- 8 -
D 1.0A
2.The connection of whole set of the indicator
First open the cover of the BWR-04,loose the screws which is on the lead terminal, take out
the airproof in the lead terminal , and then you can connection the lead.
The connecting diagrams of BWR—04/Convertor/XMT-288FC,BWR-04A/Conertor and BWR-
04/DC24V power source/Computer are showed respectively in figure 4. figure 5 and figure 6.
- 9 -
8
BWR-04
XMT-288FC-Ⅲ
Convertor(Kind A)
Transformer
CT
Input High
Bus Low
4~20mA
Earth Middle Phase
AC 220V
0~5V
Output
1 2 3 4 5 6 7
9 10 11 12 13 14
Figure 4 General connection of BWR-04/convertor / XMT-288FC-Ⅲ
Figure 5 BWR-04A /Convertor connecting diagram
- 10 -
DC24V Computer
BWR-04
4-20mA
Power source
CT BWR-04A
Transformer
Convertor(Kind A)
Figure 6 BWR-04/DC24V power source/Computor connecting diagram
7.Setting & Adjusting
1. Setting of switch of BWR-04
Each switch can be set individual. The temperature control switch K1,K2,K3,K4 of BWR
—04 have been already set at55℃,75℃,90℃,130℃before its delivery. If users need to change the
value of set points, please follow below procedures:
(1) Loose the round bolt at the point of the red arrowhead;
(2) Stir the red setting needles to set value planned;
(3) Screw down the round bolt;
(4) Circumgyrate the axes of the scale in a clockwise direction (suppose watch the axes form
the left direction). The value of the indicator will go form lower to higher. Check the value of the
indicator when the switch moves.
Notice:The axes will never circumgyrate the opposite direction; otherwise, it may change the
accuracy of the indicator.
2. Setting of convertor
Before the convertor delivery, the input current of the heating element had been set at
1.04A,depending on the Maximum Current of CT which is 5A and the average rising temperature
of the transformer winding which is △T=20K.
When the condition not accord with the parameter above, the convertor can be reset before use.
The adjusting connection refer Figure 7a.the instrument which used in the figure as follows:
If the customer has no AC electric source, can adjust to press the 2KVA regulating transformer and
1.2~1.5KW heating.The connecting diagram refer Figure 7b.The instrument which used in the figureas follfws:
(1)B:2KVA/250V Regulating transformer
(2)RL:Heating of 1.2KW~1.5KW
(3)A1:Model D26-A current meter of grade 0.5 for (0-5)A
(4) A2:Model D26-A current meter of grade 0.5 for (0-2)A
- 11 -
Figure 7 Adjusting connection of the convertor
- 12 -
Adjusting step as follows:
(1) According to the rating current of the transformer.and the no-load voltage ratio of current
transformer calculate the output current of the
current transformer.
For example:
the rating current of the transforme:400A
the no-load voltage ratio of the CT 400:5
Ip=400/(400/5)=5A
(2) Fine out the average rising
temperature(△T) from the transformer manual
or get it from the producer of the transformer.
For example, △T=20K
(3) According to the value of the △T, get
the value of Is from Figure 8. For example,
According to △T =20K, get Is=1.04A
△T(K) 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38
Ih (A) 0.74 0.80 0.86 0.92 0.98 1.04 1.09 1.14 1.19 1.24 1.28 1.32 1.63 1.40 1.44
Notice: If the value you want is not in the table, you can get it in the diagram above.
Figure 8 Temperature rising characteristics of heating element
(4)Calculate Is/Ip,after according to the value of Ip and Is/Ip, depending on Table 1,It will be
that the adjusting lead K is the wiring point.For example Is/Ip=1.04/5=0.208.Depending on Table
1, K from No.17 to No.8.
(5) Connect which as figure 7 shows.
(6) Turn on the power, initialize the output current of the AC electrical source equal to the
rating output current Ip of the current transformer(Figure 7a) .or adjust the regulating transformer
B to make the output current (the value of A1) equal to the rating output current Ip of the CT(Figure
7b). For example , Ip=5A.
(7) Adjust the rheostat in the convertor (W),make Is=1.04A(the value of A2).
8. Points of Attention
- 13 -
1.When checking BWR-04, the bulb must be immerged into constant temperature trough
entirely, the indicator must be fixed perpendicularly.
2. When fixing the BWR-04 or wiring, must be careful and gently. Please follow the step of the
manual strictly.
3. Make use of the solid wrench to open and close the meter cover. In particular, while closing
the cover, screw 4 hexagonal bolts on the cover with an uniform and balanced force to avoid
affecting its tightness。
4. While installing the unit, the surplus capillary tube should be wound into a circle of diameter
of over 150mm and properly fixed at every interval of 300mm (for example tied by some thin
copper wire etc).
5 .The test on the Digital Display Thermometer can be conducted by connecting it either with a
standard direct current signal source or with a BWR—04 with its bulb inserted into a constant
temperature trough.
6.During field installation attention must be paid to insert the entire bulb into the transformer’s
sleeve with oil inside it. In other words, the depth of inserted bulb should be at least no less than
150mm.
7. Water is forbidden to let in the transformer’s sleeve with oil inside. When the ambient
temperature drops below 0℃ and the transformer happens not to work. The water in the sleeve
probably freezes in an expansion to squeeze the bulb, which results in wrong indication of the
thermoregulator. So the attention must be paid to seal the bulb when mounting it to prevent
rainwater in.
8.If use the situation do not need the digital display thermometer should
install the DC24V power source , used to the transmitter inside of the winding
thermoregulator changes to send the operating power supply.
- 14 -
- 15 -
0
50
100
150
MC
G3/4"
C-installing
frame
BWY-04
010
浙制
BWR—04 Series
Winding Transformer
Temperature Indicator
Operation
Instructions
Hangzhou HuaLi Instrument & Meter Co.,Ltd
Address:27 Longwu Industrial Zone,Hangzhou Post code:310024
Tel : 0571-87088120 E-mail: lanshan@mail.hz.zj.cn
Fax: 0571-87919920 Http://www.hz-hlyb.com
- 16 -
Thanks for using our product
Before operating it, please read this manual thoroughly
Contents
1.Brief Introduction …………………………………………………………………………… (1)
2.Model Illuminate…………………………………………………………………………………(1)
3.Composing And Function ……………………………………………………………………(1)
4.Main Technical Parameters……………………………………………………………………(4)
5.Installation ………………………………………………………………………………………… (5)
6.Wiring………………………………………………………………………………………………… (6)
7. Setting & Adjusting ……………………………………………………………………………(9)
8.Points of Attention………………………………………………………………………………(12)
9.Addendum …………………………………………………………………………………………(13)
- 17 -

More Related Content

PPS
Primeira Guerra Mundial
PPTX
ÁSIA : ORIENTE MÉDIO
PPT
PPTX
Vitamin D3 fortification in Edible Oil
PPSX
Oriente Médio
PPTX
Modulo 11 - América Latina: aspectos humanos
PPT
Ásia Oriental
Primeira Guerra Mundial
ÁSIA : ORIENTE MÉDIO
Vitamin D3 fortification in Edible Oil
Oriente Médio
Modulo 11 - América Latina: aspectos humanos
Ásia Oriental

Similar to scribd.vpdfs.com_bwr-04-winding-thermometer.pdf (20)

PDF
IRJET- Signal Conditioning Card for Load Cell
PDF
510 277-283
PDF
PDF
Ct2000 es manual_english_version_1[1].0
PDF
IJSRED-V2I5P32
PDF
Advanced motion controls 30a8dd
PDF
Electronic multi measuring instrument-me96 series brochure dienhathe.vn
PDF
Quick guide aqua fc 200
PDF
Advanced motion controls 25a20dd
PDF
Advanced motion controls s30a40ac
PDF
Energy management-demand-controllers.pdf
PPTX
INTELLIGENT HELMET FOR COAL MINERS
PPT
AUTOMATIC TEMPERATURE FAN CONTROLLER
PDF
Air Circuit Breakers BT2 Series
PDF
Advanced motion controls s30a40
PPT
IMPLEMENTING A DIGITAL MULTIMETER
PDF
F5 m instruction manual
PDF
Digital stop watch
PDF
Cdvr service manual renr7941-00 _ sis - caterpillar
IRJET- Signal Conditioning Card for Load Cell
510 277-283
Ct2000 es manual_english_version_1[1].0
IJSRED-V2I5P32
Advanced motion controls 30a8dd
Electronic multi measuring instrument-me96 series brochure dienhathe.vn
Quick guide aqua fc 200
Advanced motion controls 25a20dd
Advanced motion controls s30a40ac
Energy management-demand-controllers.pdf
INTELLIGENT HELMET FOR COAL MINERS
AUTOMATIC TEMPERATURE FAN CONTROLLER
Air Circuit Breakers BT2 Series
Advanced motion controls s30a40
IMPLEMENTING A DIGITAL MULTIMETER
F5 m instruction manual
Digital stop watch
Cdvr service manual renr7941-00 _ sis - caterpillar
Ad

Recently uploaded (20)

PPTX
IOT-UNIT 3.pptxaaaasasasasasasaasasasasas
PPTX
Culture by Design.pptxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxx
PDF
150 caterpillar motor grader service repair manual EB4
PPTX
Dipak Presentation final 18 05 2018.pptx
PDF
Marketing project 2024 for marketing students
PDF
MES Chapter 3 Combined UNIVERSITY OF VISVESHWARAYA
PPT
Introduction to Hybrid Electric Vehicles
PDF
Engine Volvo EC55 Compact Excavator Service Repair Manual.pdf
PDF
Cylinder head Volvo EC55 Service Repair Manual.pdf
PDF
Fuel injection pump Volvo EC55 Repair Manual.pdf
PPTX
Money and credit.pptx from economice class IX
PPTX
Zeem: Transition Your Fleet, Seamlessly by Margaret Boelter
PDF
6. Chapter Twenty_Managing Mass Communications Advertising Sales Promotions E...
PPTX
internal combustion engine renewable new
PDF
Caterpillar Cat 324E LN Excavator (Prefix LDG) Service Repair Manual Instant ...
PPTX
Quarter-1-Lesson-5-sdf wgwefwgwefgwgwgwewgwewgwewwedgfwrwtudents-copy.pptx
PDF
Governor Volvo EC55 Service Repair Manual.pdf
PPTX
Small Fleets, Big Change: Market Acceleration by Niki Okuk
PPTX
Advance Module FI 160.pptx para pulsaar 160 y su sistema de encencido
PDF
Pharmacy is a goood college yvucc7t7tvy7tv7t
IOT-UNIT 3.pptxaaaasasasasasasaasasasasas
Culture by Design.pptxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxx
150 caterpillar motor grader service repair manual EB4
Dipak Presentation final 18 05 2018.pptx
Marketing project 2024 for marketing students
MES Chapter 3 Combined UNIVERSITY OF VISVESHWARAYA
Introduction to Hybrid Electric Vehicles
Engine Volvo EC55 Compact Excavator Service Repair Manual.pdf
Cylinder head Volvo EC55 Service Repair Manual.pdf
Fuel injection pump Volvo EC55 Repair Manual.pdf
Money and credit.pptx from economice class IX
Zeem: Transition Your Fleet, Seamlessly by Margaret Boelter
6. Chapter Twenty_Managing Mass Communications Advertising Sales Promotions E...
internal combustion engine renewable new
Caterpillar Cat 324E LN Excavator (Prefix LDG) Service Repair Manual Instant ...
Quarter-1-Lesson-5-sdf wgwefwgwefgwgwgwewgwewgwewwedgfwrwtudents-copy.pptx
Governor Volvo EC55 Service Repair Manual.pdf
Small Fleets, Big Change: Market Acceleration by Niki Okuk
Advance Module FI 160.pptx para pulsaar 160 y su sistema de encencido
Pharmacy is a goood college yvucc7t7tvy7tv7t
Ad

scribd.vpdfs.com_bwr-04-winding-thermometer.pdf

  • 1. BWR—04 Series Transformer Winding Temperature Indicator Operation Instructions Hangzhou HuaLi Instrument Co.,Ltd Address:27 Longwu Industrial Zone,West Lack District, Hangzhou Post code: 310024 Tel : 0571-87088120 E-mail: lanshan@mail.hz.zj.cn Fax: 0571-87919920 Http://www.hz-hlyb.com - 1 -
  • 2. Thanks for using our products Beforeoperatingit,pleasereadthismanualthoroughly Contents 1.Brief Introduction …………………………………………………………………(1) 2.Model Illuminate……………………………………………………………………(1) 3.Composing And Function ………………………………………………………(1) 4.Main Technical Parameters………………………………………………………(4) 5.Installation …………………………………………………………………………… (5) 6.Wiring…………………………………………………………………………………… (6) 7. Setting & Adjusting ………………………………………………………………(8) 8.Points of Attention…………………………………………………………………(10) 9.Addendum ……………………………………………………………………………(11) - 2 -
  • 3. 1.Brief Introduction Transformer winding thermoregulator is specially designed for oil-immersed transformer, which can indirectly measure the winding temperature by thermal simulation method. Let T1 present the temperature of transformer winding and it is the sum of T2 and △T, i.e. T1 =T2+△T, where, T2 is the oil temperature in upper part of the transformer, and △T is the winding temperature rise relative to the oil temperature. The △T depends on the winding current and the secondary current of the current transformer (CT) is in proportion to the winding current. The thermoregulator works in following. Principle: The current from the CT, which is in proportion to the load, is first adjusted via a converter, and then flows through the heating element embedded in the elastic component; the heat produced by the heating element leads to an additional displacement of the elastic component, and thus a temperature indicated value higher than the oil temperature. By this way, the thermoregulator can obtain an average indicated value of the winding temperature. 2.Model Illuminate The model and illuminate of the transformer winding temperature indicator: 3. Composing And Function 1.BWR-04 series winding temperature indicator: (1) Indicate the temperature of transformer winding. (2)Afford four sets of switch (AC250V/15A) , which can be set within a whole span, are employed to respectively control over the transformer cooling system, overheating alarming and - 3 - BWR XMT 288 F C- Ⅲ Design code(For BWR-04) Output code Rectangle Control digital display temperature indicator Design code: Ⅰ:Outside place of the convertor (code abridges) Ⅱ:Inside of the wire-wound potentiometer Ⅲ:Inside of the convertor Output function: DC(4-20)mA(code abridge) A:Pt100 platinum resistance E:DC(0-5)V Number of switches For transformer
  • 4. tripping, etc. (3) Output (4~20)mA electricity signal to be the input of the digital display thermometer which is in the controlling room. The outline drawing and mounting dimension of the winding temperature indicator refer Figure 1.The outline drawing and mounting dimension of the export of BWR-04 refer addendum(offer the overseas transformer producer) Figure 1 BWR-04 thermoregulator outline drawing and mounting dimension 2.Convertor The function of the convertor is got electricity for the CT of the main transformer. Then after - 4 - 0 150 50 100 BWR-04
  • 5. C ° XMT-288FC . adjust, send it to the heating element of the winding temperature indicator. So that the indicator can show a temperature value which is high then the oil temperature which is △T. The convertor that bases on the different rating electricity, which is 5A, 3A, 2A, 1A,of CT of the main transformer, which can be divide into four different connection. Idiographic connection method refers table 2 or the connection diagram in the convertor cover . The outline drawing and mounting dimension of the convertor refer Figure 2 Figure 2 Convertor outline drawing and mounting dimension 3.XMT—288FC—Ⅲ Digital Display Thermometer The transformer change the temperature into the (4~20) mA electricity signal, then send into the digital display thermometer XMT—288FC—Ⅲ, which is fixed in the controlling room. The man who is on duty can expediently observe the temperature of the transformer in controlling room. And it also can send the signals whatever you need for computer as follows: (1)(4-20) mA direct current signal. (2)(0-5)V or (1-5)V constant voltage signal. (3)RS232,RS485 communication interface. The outline drawing and mounting dimension of XMT—288FC —Ⅲ refer Figure 3. Figure 3 XMT—288FC—Ⅲ outline drawing and mounting dimension - 5 -
  • 6. 4. Main Technical Parameters 1.BWR-04 Main Technical Parameters: (1) NORMAL WORKING CONDITION:(-40~+55)℃ (2)Range of measurement:(0~150)℃ (3)Indication accuracy:±3℃ (4)Controlling capability: ①Setting range:adjustable within the work span ②Setting accuracy:±3℃ ③switch difference:6±2℃ ④RATED POWER:AC250V/15A (5)standard setting point: K1=55℃ K2=75℃ K3=90℃ K4=130℃ (6)Protection performance:IP55 2.Convertor Main Technical Parameters: (1) NORMAL WORKING CONDITION:(-40~55)℃ (2) Protection performance:IP55 (3) Main technical parameters refer table 1. 3.XMT-288FC-ⅢMain Technical Parameters: 1. Normal working condition: (-10~50) ℃ 2. Measuring range: (0~150) ℃ 3.Input signal:DC (4-20) mA 4. Accuracy:1.0 5. Resolution ratio:0.1℃ 6.Controlling capability (1) Controlling mode:Upper limit contact (2)Setting range :Adjustable within the work span (3) Contact capacity:AC220V,3A 7.Output:DC(4-20)mA Notice:It can be made with RS232,RS485 or other output signal according to customer’s order. - 6 -
  • 7. TABLE 1 Convertor Technical Parameters Type Input current IP(A) Output currrent Is/Input current Ip AdjustleadKconnect toport’s NO. A 5≥Ip>3 0.30~0.35 17-6 0.24~0.30 17-7 0.15~0.24 17-8 0.10~0.15 17-9 B 3≥Ip>2 0.50~0.60 17-7 0.40~0.50 17-8 0.28~0.40 17-10 0.17~0.28 17-11 C 2≥Ip>1 0.75~0.90 17-12 0.60~0.75 17-13 0.40~0.60 17-14 0.25~0.40 17-15 D 1≥Ip>0.61 1.50~1.75 17-6 1.20~1.50 17-7 1.00~1.20 17-14 0.50~1.00 17-16 5. Installation 1. Installation of BWR-04 and Convertor Screw 4 hexagonal bolts (M8) and 4 matched washers accessorized (φ10)with BWR—04 into a mounting board of transformer. Screw 4 hexagonal bolts (M6) and 4 matched washers accessorized (φ7)with Convertor into a mounting board of transformer. 2. Installation of bulb Wrap the installation screw thread on the bulb with appropriate seal material. Insert the bulb into the transformer’s sleeve with oil inside it. Screw the mounting screw on the bulb into the sleeve until fasten the sealing washer. At last screw the airproof bolt fast. 3. Installation of XMT-288FC-Ⅲ - 7 -
  • 8. The XMT-288FC-Ⅲ install on either an operations area or an instrument screen with two mounting racks and two screws which provided. The size of aperture on instrument screen is high* wide =(152*76) mm. 6. Wiring 1.Connection of convertor You have to take off the cover to wire the adaptor convertor,loose the screws which is on the lead terminal, take out the airproof in the lead terminal , and then you can connection the lead. Depend on the difference of the maximum current of CT, the method of the convertor has A,B,C,D four kinds. The connection diagrams of convertor refer to table 2. TABLE 2 The Connection of Convertor Type The Maximum Current of CT Connection Diagrams (R:Heating Element K:Adjusting Lead) A 5.0A B 3.0A C 2.0A - 8 -
  • 9. D 1.0A 2.The connection of whole set of the indicator First open the cover of the BWR-04,loose the screws which is on the lead terminal, take out the airproof in the lead terminal , and then you can connection the lead. The connecting diagrams of BWR—04/Convertor/XMT-288FC,BWR-04A/Conertor and BWR- 04/DC24V power source/Computer are showed respectively in figure 4. figure 5 and figure 6. - 9 - 8 BWR-04 XMT-288FC-Ⅲ Convertor(Kind A) Transformer CT Input High Bus Low 4~20mA Earth Middle Phase AC 220V 0~5V Output 1 2 3 4 5 6 7 9 10 11 12 13 14
  • 10. Figure 4 General connection of BWR-04/convertor / XMT-288FC-Ⅲ Figure 5 BWR-04A /Convertor connecting diagram - 10 - DC24V Computer BWR-04 4-20mA Power source CT BWR-04A Transformer Convertor(Kind A)
  • 11. Figure 6 BWR-04/DC24V power source/Computor connecting diagram 7.Setting & Adjusting 1. Setting of switch of BWR-04 Each switch can be set individual. The temperature control switch K1,K2,K3,K4 of BWR —04 have been already set at55℃,75℃,90℃,130℃before its delivery. If users need to change the value of set points, please follow below procedures: (1) Loose the round bolt at the point of the red arrowhead; (2) Stir the red setting needles to set value planned; (3) Screw down the round bolt; (4) Circumgyrate the axes of the scale in a clockwise direction (suppose watch the axes form the left direction). The value of the indicator will go form lower to higher. Check the value of the indicator when the switch moves. Notice:The axes will never circumgyrate the opposite direction; otherwise, it may change the accuracy of the indicator. 2. Setting of convertor Before the convertor delivery, the input current of the heating element had been set at 1.04A,depending on the Maximum Current of CT which is 5A and the average rising temperature of the transformer winding which is △T=20K. When the condition not accord with the parameter above, the convertor can be reset before use. The adjusting connection refer Figure 7a.the instrument which used in the figure as follows: If the customer has no AC electric source, can adjust to press the 2KVA regulating transformer and 1.2~1.5KW heating.The connecting diagram refer Figure 7b.The instrument which used in the figureas follfws: (1)B:2KVA/250V Regulating transformer (2)RL:Heating of 1.2KW~1.5KW (3)A1:Model D26-A current meter of grade 0.5 for (0-5)A (4) A2:Model D26-A current meter of grade 0.5 for (0-2)A - 11 -
  • 12. Figure 7 Adjusting connection of the convertor - 12 -
  • 13. Adjusting step as follows: (1) According to the rating current of the transformer.and the no-load voltage ratio of current transformer calculate the output current of the current transformer. For example: the rating current of the transforme:400A the no-load voltage ratio of the CT 400:5 Ip=400/(400/5)=5A (2) Fine out the average rising temperature(△T) from the transformer manual or get it from the producer of the transformer. For example, △T=20K (3) According to the value of the △T, get the value of Is from Figure 8. For example, According to △T =20K, get Is=1.04A △T(K) 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 Ih (A) 0.74 0.80 0.86 0.92 0.98 1.04 1.09 1.14 1.19 1.24 1.28 1.32 1.63 1.40 1.44 Notice: If the value you want is not in the table, you can get it in the diagram above. Figure 8 Temperature rising characteristics of heating element (4)Calculate Is/Ip,after according to the value of Ip and Is/Ip, depending on Table 1,It will be that the adjusting lead K is the wiring point.For example Is/Ip=1.04/5=0.208.Depending on Table 1, K from No.17 to No.8. (5) Connect which as figure 7 shows. (6) Turn on the power, initialize the output current of the AC electrical source equal to the rating output current Ip of the current transformer(Figure 7a) .or adjust the regulating transformer B to make the output current (the value of A1) equal to the rating output current Ip of the CT(Figure 7b). For example , Ip=5A. (7) Adjust the rheostat in the convertor (W),make Is=1.04A(the value of A2). 8. Points of Attention - 13 -
  • 14. 1.When checking BWR-04, the bulb must be immerged into constant temperature trough entirely, the indicator must be fixed perpendicularly. 2. When fixing the BWR-04 or wiring, must be careful and gently. Please follow the step of the manual strictly. 3. Make use of the solid wrench to open and close the meter cover. In particular, while closing the cover, screw 4 hexagonal bolts on the cover with an uniform and balanced force to avoid affecting its tightness。 4. While installing the unit, the surplus capillary tube should be wound into a circle of diameter of over 150mm and properly fixed at every interval of 300mm (for example tied by some thin copper wire etc). 5 .The test on the Digital Display Thermometer can be conducted by connecting it either with a standard direct current signal source or with a BWR—04 with its bulb inserted into a constant temperature trough. 6.During field installation attention must be paid to insert the entire bulb into the transformer’s sleeve with oil inside it. In other words, the depth of inserted bulb should be at least no less than 150mm. 7. Water is forbidden to let in the transformer’s sleeve with oil inside. When the ambient temperature drops below 0℃ and the transformer happens not to work. The water in the sleeve probably freezes in an expansion to squeeze the bulb, which results in wrong indication of the thermoregulator. So the attention must be paid to seal the bulb when mounting it to prevent rainwater in. 8.If use the situation do not need the digital display thermometer should install the DC24V power source , used to the transmitter inside of the winding thermoregulator changes to send the operating power supply. - 14 -
  • 16. BWR—04 Series Winding Transformer Temperature Indicator Operation Instructions Hangzhou HuaLi Instrument & Meter Co.,Ltd Address:27 Longwu Industrial Zone,Hangzhou Post code:310024 Tel : 0571-87088120 E-mail: lanshan@mail.hz.zj.cn Fax: 0571-87919920 Http://www.hz-hlyb.com - 16 -
  • 17. Thanks for using our product Before operating it, please read this manual thoroughly Contents 1.Brief Introduction …………………………………………………………………………… (1) 2.Model Illuminate…………………………………………………………………………………(1) 3.Composing And Function ……………………………………………………………………(1) 4.Main Technical Parameters……………………………………………………………………(4) 5.Installation ………………………………………………………………………………………… (5) 6.Wiring………………………………………………………………………………………………… (6) 7. Setting & Adjusting ……………………………………………………………………………(9) 8.Points of Attention………………………………………………………………………………(12) 9.Addendum …………………………………………………………………………………………(13) - 17 -