SlideShare a Scribd company logo
Testing and Troubleshooting 4
mA to 20 mA Control Loops
Process Troubleshooting
Webinar Series
What will be covered in this session
• What makes a 4 to 20 mA control loop “tick”
• What things can go wrong with a 4 to 20 mA loop?
• How do you troubleshoot? What tools are of most use?
• Measuring 4 to 20 mA signals and interpreting the measurements
– Multiple measurement methods
• Testing PLC, DCS and indicator inputs with 4 to 20 mA sourcing
tools
– Multiple methods and sourcing approaches
– Testing 1V to 5 V and 0 V to 10 V I/O
©2010 Fluke Corporation Troubleshooting 4 mA to 20 mA loops 2
What will be covered in this session
• Measuring loop power supplies, troubleshooting suspect power
supplies
– Testing and isolating a transmitter with substitution power supply
• Troubleshooting suspect transmitters
– mA simulate used for substitution testing
• Using a HART smart transmitter as a mA source
– Using the Loop Test HART command to test a loop
• Testing an I/P with 4 to 20 mA sourcing
• Testing a control valve with a 4 to 20 mA source
©2010 Fluke Corporation Troubleshooting 4 mA to 20 mA loops 3
24 V loop
supply
+–
What makes a 4 to 20 mA control loop “tick”
Indicators/Controllers:
Interpret the 4 to 20 mA signal as the temperature
or pressure being measured in the process. Often
issue commands to a final control element such as
a valve to regulate the process temperature or
pressure to within acceptable limits
Inputs to these devices is frequently a
1 V to 5 V input signal rather than 4 to 20 mA
ZERO SPAN
2200 ºC
4 to 20 mA
2 Wire Transmitter
Sensor input
• Temperature
• Pressure
• Flow
• Frequency
• PH
Readout/Controller
DCS/PLC/Recorder
250 ohm input shunt 
4 to 20 mA signal 

24 V loop power supply:
Provides power for the loop. Transmitters
regulate the 4 to 20 mA signal in the
circuit drawing power from this supply.
Transmitters:
Convert the measured temperature or
pressure to a 4 to 20 mA signal.
Typically are passive devices and
draw their power from an external 24 V
loop power supply.
2200 ºC
Example current loop
ZERO SPAN
4 to 20 mA
2 Wire Transmitter
Sensor input
• Temperature
• Pressure
• Flow
• Frequency
• PH
Readout/Controller
DCS/PLC/Recorder
250 ohm input shunt 
4 to 20 mA signal 

24 V loop
supply
+–
• 4 to 20 mA (dc) signal is proportional to sensor input or PV
• Series circuit dictates the current at one location must be
identical to other locations
• Big advantage sending in sending mA signals over long
distances compared to voltage or pressure signals
Temperature transmitters convert
measured temperature (PV) 4 to 20 mA signals
Measured PV:
The PV or primary/process
variable in this example is the
temperature of the process fluid
being measured by the
temperature transmitter.
Temperature transmitter:
Typically sense the temperature
of the process via either a
thermocouple or RTD sensor and
convert the measurement to a
4 to 20 mA signal. The
transmitter in this example has
an input span (range) of 0 °C
to 300 °C. The relationship of
the measured temperature and
mA signal is shown is the table.
Temperature
input
Current
output
Percent
of span
0 °C 4 mA 0 %
75 °C 8 mA 25 %
150 °C 12 mA 50 %
225 °C 16 mA 75 %
300 °C 20 mA 100 %
Temperature transmitter
Temperature transmitters convert
measured temperature (PV) 4 to 20 mA signals
Measured PV:
The PV or primary/process
variable in this example is the
temperature being measured by
the temperature transmitter.
Temperature transmitter:
Typically sense the temperature
of the process via either a
thermocouple or RTD sensor and
convert the measurement to a
4 to 20 mA signal. The
transmitter in this example has
an input span (range) of 0 °C
to 300 °C. The relationship of
the measured temperature and
mA signal is shown is the table.
Temperature
input
Current
output
Percent
of span
0 °C 4 mA 0 %
75 °C 8 mA 25 %
150 °C 12 mA 50 %
225 °C 16 mA 75 %
300 °C 20 mA 100 %
Temperature Transmitters convert
measured temperature (PV) 4 to 20 mA signals
Indicator/Controller:
In this example, the temperature
indicator/controller is programmed
to interpret a 4 mA signal as 0 °C
and a 20 mA signal as 300 °C.
Input/Output or I/O:
Refers to the input/output of the
control system or controller. In this
example the input to the controller
is the 4 to 20 mA signal. The
output from the controller is the
signal that controls the control
valve.
Flow Control Valve
Final control element. Opens and
closes based on commands from
the controller to increase or
decrease gas supplied to the
burner as required to maintain
temperature at the setpoint value.
Temperature
input
Current
output
Percent
of span
0 °C 4 mA 0 %
75 °C 8 mA 25 %
150 °C 12 mA 50 %
225 °C 16 mA 75 %
300 °C 20 mA 100 %
Temperature transmitter
Pressure Transmitters convert measured
pressure (PV) to 4 to 20 mA signals
Measured PV:
The PV or primary/process variable in this
example is the pressure being measured by the
pressure transmitter.
Pressure Transmitter:
Senses the pressure of the process directly and
converts the measurement to a 4 to 20 mA
signal. The transmitter in this example has an
input span (range) of 0 psi to 100 psi. The
relationship of the measured pressure and mA
signal is shown is the table.
Indicators/Controller:
In this example, the pressure indicator/controller
is programmed to interpret a 4 mA signal as 0
psi and a 20 mA signal as 100 psi.
Pressure relief valve:
Final control element. In this example if the
measured pressure is too high, the controller
instructs the valve to open to reduce the
pressure in the vessel.
Pressure
input
Current
output
Percent
of span
0 psi 4 mA 0 %
25 psi 8 mA 25 %
50 psi 12 mA 50 %
75 psi 16 mA 75 %
100 psi 20 mA 100 %
Pressure transmitter
What can go wrong with a 4 to 20 mA loop?
Pressure
input
Current
output
Percent
of span
0 psi 4 mA 0 %
25 psi 8 mA 25 %
50 psi 12 mA 50 %
75 psi 16 mA 75 %
100 psi 20 mA 100 %
Pressure transmitter
Wiring problems:
Bad terminations,
compromised insulation,
corrosion and contami-
nation can cause wiring
to negatively impact 4 to
20 mA loop operation.
24V loop
power supplies:
Noisy, defective or
overloaded power
supplies can cause
erratic mA loop
operation or failures.
Bad I/O into
the controller:
If the mA signal is correct
and the controller does
not interpret the mA signal
correctly the control of
the process is lost.
Temperature input Current output Percent of span
0 °C 4 mA 0 %
75 °C 8 mA 25 %
150 °C 12 mA 50 %
225 °C 16 mA 75 %
300 °C 20 mA 100 %
Temperature transmitter
What can go wrong with a 4 to 20 mA loop
Pressure
input
Current
output
Percent
of span
0 psi 4 mA 0 %
25 psi 8 mA 25 %
50 psi 12 mA 50 %
75 psi 16 mA 75 %
100 psi 20 mA 100 %
Pressure transmitter
Bad transmitter:
If the transmitter does
not change the mA
signal to correctly to
respond to the
measured PV the
control system will not
correct to adjust the
PV correctly.
Bad sensor or
clogged capillary:
If the temperature
sensor is defective the
transmitter cannot
sense the temperature.
In a pressure
transmitter if the
connection to the
process is clogged the
transmitter cannot
measure the pressure
accurately.
Temperature input Current output Percent of span
0 °C 4 mA 0 %
75 °C 8 mA 25 %
150 °C 12 mA 50 %
225 °C 16 mA 75 %
300 °C 20 mA 100 %
Temperature transmitter
How do you troubleshoot?
What tools are of the most use?
What can be
measured or
sourced
Measurement and
sourcing tool
What it tells
the technician
Measure 4 mA to 20 mA
signals
DMM. Loop calibrator, mA clamp,
ProcessMeter
If the measured mA value is the
expected value
Source 4 mA to 20 mA
signals
Loop calibrator, mA clamp,
ProcessMeter
If the I/O or other mA input device is
working correctly
Simulate 4 mA to 20 mA
signals
Loop calibrator, Fluke 772 or
773 mA Clamp, ProcessMeter
If the power supply, wiring and I/O is
working correctly, perform transmitter
substitution test
Measure 24 V loop
voltage
DMM, Loop calibrator,
Fluke 773 mA Clamp, ProcessMeter
If the full 24V supply available, if it is
defective or being loaded down?
Supply 24 V loop
voltage
Loop calibrator, mA clamp,
Fluke 789 ProcessMeter
If a substitution test for installed supply
fixes the problem
Source 0 V to 10 V,
1 V to 5 V
Loop calibrator with voltage source (715)
or specialized mA Clamp (773)
If the I/O or other voltage input device is
working correctly
Continuity
measurements
DMM, ProcessMeter, some multifunction
process calibrators
Find open circuits, bad terminations,
resistive connections and mis-wires
Measure the 4 mA to 20 mA signal
In series,
“Break the loop”
Temperature input Current output Percent of span
0 °C 4 mA 0 %
75 °C 8 mA 25 %
150 °C 12 mA 50 %
225 °C 16 mA 75 %
300 °C 20 mA 100 %
Temperature transmitter
Pressure
input
Current
output
Percent
of span
0 psi 4 mA 0 %
25 psi 8 mA 25 %
50 psi 12 mA 50 %
75 psi 16 mA 75 %
100 psi 20 mA 100 %
Pressure transmitter
Compare
measured mA
signal to the
expected
value on the
display
Measure the 4 mA to 20 mA signal;
Don’t break the loop
Don’t “Break
the loop”
Temperature input Current output Percent of span
0 °C 4 mA 0 %
75 °C 8 mA 25 %
150 °C 12 mA 50 %
225 °C 16 mA 75 %
300 °C 20 mA 100 %
Temperature transmitter
Pressure
input
Current
output
Percent
of span
0 psi 4 mA 0 %
25 psi 8 mA 25 %
50 psi 12 mA 50 %
75 psi 16 mA 75 %
100 psi 20 mA 100 %
Pressure transmitter
Compare
measured mA
signal to the
expected
value on the
display
Source a 4 mA to 20 mA signal
Temperature input Current output Percent of span
0 °C 4 mA 0 %
75 °C 8 mA 25 %
150 °C 12 mA 50 %
225 °C 16 mA 75 %
300 °C 20 mA 100 %
Temperature transmitter
Pressure
input
Current
output
Percent
of span
0 psi 4 mA 0 %
25 psi 8 mA 25 %
50 psi 12 mA 50 %
75 psi 16 mA 75 %
100 psi 20 mA 100 %
Pressure transmitter
Tests the
indicator,
controller or
PLC/Control
system I/O
directly. Verify
the value on
the display
Simulate a 4 mA to 20 mA signal
Simulate a
transmitter in a
loop, regulate
current
Temperature input Current output Percent of span
0 °C 4 mA 0 %
75 °C 8 mA 25 %
150 °C 12 mA 50 %
225 °C 16 mA 75 %
300 °C 20 mA 100 %
Temperature transmitter
Pressure
input
Current
output
Percent
of span
0 psi 4 mA 0 %
25 psi 8 mA 25 %
50 psi 12 mA 50 %
75 psi 16 mA 75 %
100 psi 20 mA 100 %
Pressure transmitter
Tests the wiring,
power supply,
indicator,
controller or
PLC/Control
system I/O.
Verify the value
on the display.
Perform a
transmitter
substitution test.
Measure 24V loop power
Temperature input Current output Percent of span
0 °C 4 mA 0 %
75 °C 8 mA 25 %
150 °C 12 mA 50 %
225 °C 16 mA 75 %
300 °C 20 mA 100 %
Temperature transmitter
Pressure
input
Current
output
Percent
of span
0 psi 4 mA 0 %
25 psi 8 mA 25 %
50 psi 12 mA 50 %
75 psi 16 mA 75 %
100 psi 20 mA 100 %
Pressure transmitter
Is the full 24 V
available or
is the power
supply being
loaded down
Test with external 24 V loop power supply
Temperature input Current output Percent of span
0 °C 4 mA 0 %
75 °C 8 mA 25 %
150 °C 12 mA 50 %
225 °C 16 mA 75 %
300 °C 20 mA 100 %
Temperature transmitter
Pressure
input
Current
output
Percent
of span
0 psi 4 mA 0 %
25 psi 8 mA 25 %
50 psi 12 mA 50 %
75 psi 16 mA 75 %
100 psi 20 mA 100 %
Pressure transmitter
Supply 24 V
loop power,
simultaneously
measure
mA signal.
Substitution
test for the
power supply.
Using a HART smart transmitter as a mA source
• Using loop test, the
Fluke 744 issues the mA
output command to the
transmitter over the
HART cable
• Transmitter sources a
mA signal into the I/O
• Verify correct indication
on the display
• Compare commanded
output value to mA
signal read by Fluke 754
• Tests transmitter
output, power supply,
wiring and I/O
HART
cable
Temperature input Current output Percent of span
0 °C 4 mA 0 %
75 °C 8 mA 25 %
150 °C 12 mA 50 %
225 °C 16 mA 75 %
300 °C 20 mA 100 %
Temperature transmitter
Instrument
Output
4 to 20 mA
output to
PLC or DCS
PVAO command
(from communicator, Fluke 744 or 754)
Loop test output trim
Smart transmitter output
• The input to many
control systems and
PLCs is a voltage signal
• 1 V to 5 V is most
common as 4 to 20 mA
through 250 ohms is
1 V to 5 V
• Some low power
transmitters have
1 V to 5 V outputs
• Many older chart
recorders and HVAC
systems have 1 V to 5 V
and 0 V to 10 V I/O
2200 ºC
Readout / Controller
DCS / PLC / Recorder
Troubleshooting, sourcing
1 V to 5 V and 0 V to 10 V
0.004 x 250 = 1.0 V
0.020 x 250 = 5.0 V
Ohms law
Testing I to P devices
I to P converts a 4 mA to 20 mA signal to a 3 psi to 15 psi pneumatic signal
•Often used with control valves
•Used as a bridge between 4 mA to 20 mA loop and 3 psi to 15 psi pneumatic technology
•Typically operate from a 20 psi or greater pressure supply
•Source 4 mA to 20 mA, verify/measure correct pressure output
4-20 mA
current
input
Pressure output
Supply
pressure
~20 PSI
Current input Pressure output Percent of span
4 mA 3 psi 0 %
8 mA 6 psi 25 %
12 mA 9 psi 50 %
16 mA 12 psi 75 %
20 mA 15 psi 100 %
Testing control valves
• Flow control, final control element
• 4 mA to 20 mA or 3 psi to 15 psi input
• Normally closed or open
–Normally closed fails closed with loss of power
–Normally open fails open with loss of power
• Apply a 4 mA to 20 mA signal and check for operation
per the applicable table below
Normally Closed Normally Open
Closed
ClosedOpen
Open
Closed Open
Pressure
input
Current
output
Percent
of travel
3 psi 4 mA 0 %
6 psi 8 mA 25 %
9 psi 12 mA 50 %
12 psi 16 mA 75 %
15 psi 20 mA 100 %
Pressure
input
Current
output
Percent
of travel
3 psi 4 mA 0 %
6 psi 8 mA 25 %
9 psi 12 mA 50 %
12 psi 16 mA 75 %
15 psi 20 mA 100 %
Testing HART control valves
• Testing HART valves require simultaneous HART
feedback, while energizing the valve and monitoring
travel.
• Underperforming valves can disrupt a process
unexpectedly, leading to expensive unplanned downtime.
• Even valves with no visible issues, may be contributing to
lowered quality and higher cost.
• Simple tools exist for quick verification of valve health to
avoid some common issues.
• Often control valves are critical components in safety &
shutdown systems
What can go wrong with a
Control Valve?
Mechanical Issues: Electrical Issues: Equipment Issues:
Stiction
Hysteresis
Dead Band
Stick-Slip
Over/Under Travel
PV Translation
Control Power
Loss
Out of Tolerance
Positioner
Communication
Transmitter
Malfunction
Under/Over-Sized
Valves
Nonlinearity
Applications
Review: Current loop devices and test methods
• Transmitters
–Apply input stimulus (temperature, pressure, etc)
–Measure for correct 4 to 20 mA output
–Use mA simulate for substitution testing
• 24 V loop power supplies
–Measure for correct voltage, substitution test to verify
• I to P, 4 mA to 20 mA input, 3 psi to 15 psi output
–Source 4 to 20 mA, verify/measure correct pressure output
• Control valves
–Source 4 mA to 20 mA, verify position indication
–Use mA signal ramping to test for smooth operation
• PLC, DCS, indicators, controllers, flow computers, and
chart recorders analog inputs
–Source 4 mA to 20 mA into the input and verify correct indication
Special Offers
• For a limited time only, Save $500 on Fluke 710 mA Loop Calibrator
Questions or Comments?
Email Nicole VanWert-Quinzi nvanwert@Transcat.com
Transcat: 800-828-1470
www.Transcat.com
For related product information, go to:
www.transcat.com/brand/fluke-store

More Related Content

PPTX
Calibrating HART Smart Pressure Transmitters
PPT
Process control 2 chapter
PPS
Basics Of Instrumentation
PPTX
DCS - Distributed Control System
PPTX
Control valve positioners
ODP
Push Button Switches
PPSX
Principle of mass flow meter
Calibrating HART Smart Pressure Transmitters
Process control 2 chapter
Basics Of Instrumentation
DCS - Distributed Control System
Control valve positioners
Push Button Switches
Principle of mass flow meter

What's hot (20)

PDF
Industrial Instrumentation An Introduction
PPS
107 basic instrumentation
PPTX
Proximity sensors
PPTX
Process Control Fundamentals and How to read P&IDs
PPTX
DCS Introduction
PPT
Introduction to Temperature Measurement and Calibration Presented by Fluke Ca...
PPTX
Final Control Element
PPT
Level Measurement
DOCX
PLC: Examen de unidad I PLC
PPTX
electro-pneumatics.pptx
PPTX
Fault finding method
PPSX
Instrumentation measurement principles
PPT
Control system
PDF
Lecture 22 flapper nozzle & ip converter
PDF
Level Measurement
PPTX
Introduction to SCADA
PPTX
ELECTRICAL WIRING DIAGRAM.pptx
PPTX
Transformer tests
PDF
Multimeter basics
Industrial Instrumentation An Introduction
107 basic instrumentation
Proximity sensors
Process Control Fundamentals and How to read P&IDs
DCS Introduction
Introduction to Temperature Measurement and Calibration Presented by Fluke Ca...
Final Control Element
Level Measurement
PLC: Examen de unidad I PLC
electro-pneumatics.pptx
Fault finding method
Instrumentation measurement principles
Control system
Lecture 22 flapper nozzle & ip converter
Level Measurement
Introduction to SCADA
ELECTRICAL WIRING DIAGRAM.pptx
Transformer tests
Multimeter basics
Ad

Similar to Testing and Troubleshooting 4-20 mA Control Loops Presented by Fluke and Transcat (20)

PPTX
Testing & Calibrationprocedure and different devices
DOC
Why Does The Transmitter Use 4-20mA Why Choose 4-20mA Instead Of 0-20mA
PDF
Yehai catalogue -tracy chow
PPTX
emmanuel and catherine project.pptx
PDF
Datasheet Fluke 1586A Super-DAQ Extended Specification. Hubungi PT. Siwali Sw...
PDF
Datasheet Fluke 726. Hubungi PT. Siwali Swantika 021-45850618
PPTX
ASC-400 Multifunction Calibrator
PPTX
How to make test boxes
PDF
Flashar 2014 by ATAC
PPTX
Tute 01 - Introduction to Laboratory Equipment.pptx
PDF
Gear flow meter and roots flow meter instruction manual wiring and parameter set
PDF
PPT
Introduction to Interfacing Temperature_Sensor.ppt
PPT
7_Temperature_Sensor.ppt_ajinkya_xxxxxxxx
PPT
Temperature sensor_Ajinkya kamble_pptxxx
PPTX
STUDY of WRM Furnace in Vizag Steel plant
PDF
Power vamp ps80
PPT
Instrumentation and adv measurements.ppt
Testing & Calibrationprocedure and different devices
Why Does The Transmitter Use 4-20mA Why Choose 4-20mA Instead Of 0-20mA
Yehai catalogue -tracy chow
emmanuel and catherine project.pptx
Datasheet Fluke 1586A Super-DAQ Extended Specification. Hubungi PT. Siwali Sw...
Datasheet Fluke 726. Hubungi PT. Siwali Swantika 021-45850618
ASC-400 Multifunction Calibrator
How to make test boxes
Flashar 2014 by ATAC
Tute 01 - Introduction to Laboratory Equipment.pptx
Gear flow meter and roots flow meter instruction manual wiring and parameter set
Introduction to Interfacing Temperature_Sensor.ppt
7_Temperature_Sensor.ppt_ajinkya_xxxxxxxx
Temperature sensor_Ajinkya kamble_pptxxx
STUDY of WRM Furnace in Vizag Steel plant
Power vamp ps80
Instrumentation and adv measurements.ppt
Ad

More from Transcat (20)

PPTX
NFPA 70B & 70E Changes and Additions Webinar Presented By Fluke
PPTX
Tools & Techniques for Commissioning and Maintaining PV Systems W-Animations ...
PPTX
Predictive Maintenance Best Practices Presented by Fluke.pptx
PPTX
Managing Instrument Calibration and Maintenance Presented by Fluke.pptx
PPTX
Tools and Techniques for Commissioning and Maintaining PV Systems
PPTX
Use of a Druck Pressure Calibrator as a Trouble Shooting Tool Presented by Druck
PPTX
Electrical Measurement Safety and Best Practices Webinar Presented by Fluke
PPTX
Solar Market Opportunities & Solutions - Presented by Fluke
PPTX
Pinpoint the leading causes of downtime with LinkIQ Cable and Network Tester
PPTX
How to Maintain Your Temperature Calibration Equipment Webinar
PPTX
Identifying Energy Waste in your Plant/Facility Webinar with Fluke
PPTX
Principals of Low Resistance Testing Webinar with Megger
PPTX
Leak Detection & Predictive/Preventative Maintenance Solutions Presented by FLIR
PPTX
Elevated Body Temperature Measurement with IR Thermometers and TI Cameras Web...
PPTX
Field Pressure Calibration Tips Webinar with Fluke Calibration
PPTX
Temperature Screening Solutions and Returning to Work Safely Webinar with Ame...
PPTX
Using a Portable Bath to Improve Calibration of Sanitary RTD's and Transmitte...
PPTX
Elevated Skin Temperature Screening Solutions – How to Get Back to Work Safel...
PPTX
Elevated Skin Temperature Screening - How to Get Back to Work Safely with FLIR
PPTX
Overhead & Underground Electric Safety Webinar Presented by Amprobe
NFPA 70B & 70E Changes and Additions Webinar Presented By Fluke
Tools & Techniques for Commissioning and Maintaining PV Systems W-Animations ...
Predictive Maintenance Best Practices Presented by Fluke.pptx
Managing Instrument Calibration and Maintenance Presented by Fluke.pptx
Tools and Techniques for Commissioning and Maintaining PV Systems
Use of a Druck Pressure Calibrator as a Trouble Shooting Tool Presented by Druck
Electrical Measurement Safety and Best Practices Webinar Presented by Fluke
Solar Market Opportunities & Solutions - Presented by Fluke
Pinpoint the leading causes of downtime with LinkIQ Cable and Network Tester
How to Maintain Your Temperature Calibration Equipment Webinar
Identifying Energy Waste in your Plant/Facility Webinar with Fluke
Principals of Low Resistance Testing Webinar with Megger
Leak Detection & Predictive/Preventative Maintenance Solutions Presented by FLIR
Elevated Body Temperature Measurement with IR Thermometers and TI Cameras Web...
Field Pressure Calibration Tips Webinar with Fluke Calibration
Temperature Screening Solutions and Returning to Work Safely Webinar with Ame...
Using a Portable Bath to Improve Calibration of Sanitary RTD's and Transmitte...
Elevated Skin Temperature Screening Solutions – How to Get Back to Work Safel...
Elevated Skin Temperature Screening - How to Get Back to Work Safely with FLIR
Overhead & Underground Electric Safety Webinar Presented by Amprobe

Recently uploaded (20)

PDF
keyrequirementskkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkk
PPTX
M Tech Sem 1 Civil Engineering Environmental Sciences.pptx
PPT
Introduction, IoT Design Methodology, Case Study on IoT System for Weather Mo...
PDF
Mohammad Mahdi Farshadian CV - Prospective PhD Student 2026
PDF
Evaluating the Democratization of the Turkish Armed Forces from a Normative P...
PPTX
web development for engineering and engineering
PDF
composite construction of structures.pdf
PPTX
Current and future trends in Computer Vision.pptx
PPTX
Infosys Presentation by1.Riyan Bagwan 2.Samadhan Naiknavare 3.Gaurav Shinde 4...
PPTX
Lecture Notes Electrical Wiring System Components
DOCX
573137875-Attendance-Management-System-original
DOCX
ASol_English-Language-Literature-Set-1-27-02-2023-converted.docx
PPTX
Engineering Ethics, Safety and Environment [Autosaved] (1).pptx
PPTX
Internet of Things (IOT) - A guide to understanding
PDF
PPT on Performance Review to get promotions
PDF
Well-logging-methods_new................
PPTX
OOP with Java - Java Introduction (Basics)
PPTX
CARTOGRAPHY AND GEOINFORMATION VISUALIZATION chapter1 NPTE (2).pptx
PPTX
bas. eng. economics group 4 presentation 1.pptx
PDF
TFEC-4-2020-Design-Guide-for-Timber-Roof-Trusses.pdf
keyrequirementskkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkk
M Tech Sem 1 Civil Engineering Environmental Sciences.pptx
Introduction, IoT Design Methodology, Case Study on IoT System for Weather Mo...
Mohammad Mahdi Farshadian CV - Prospective PhD Student 2026
Evaluating the Democratization of the Turkish Armed Forces from a Normative P...
web development for engineering and engineering
composite construction of structures.pdf
Current and future trends in Computer Vision.pptx
Infosys Presentation by1.Riyan Bagwan 2.Samadhan Naiknavare 3.Gaurav Shinde 4...
Lecture Notes Electrical Wiring System Components
573137875-Attendance-Management-System-original
ASol_English-Language-Literature-Set-1-27-02-2023-converted.docx
Engineering Ethics, Safety and Environment [Autosaved] (1).pptx
Internet of Things (IOT) - A guide to understanding
PPT on Performance Review to get promotions
Well-logging-methods_new................
OOP with Java - Java Introduction (Basics)
CARTOGRAPHY AND GEOINFORMATION VISUALIZATION chapter1 NPTE (2).pptx
bas. eng. economics group 4 presentation 1.pptx
TFEC-4-2020-Design-Guide-for-Timber-Roof-Trusses.pdf

Testing and Troubleshooting 4-20 mA Control Loops Presented by Fluke and Transcat

  • 1. Testing and Troubleshooting 4 mA to 20 mA Control Loops Process Troubleshooting Webinar Series
  • 2. What will be covered in this session • What makes a 4 to 20 mA control loop “tick” • What things can go wrong with a 4 to 20 mA loop? • How do you troubleshoot? What tools are of most use? • Measuring 4 to 20 mA signals and interpreting the measurements – Multiple measurement methods • Testing PLC, DCS and indicator inputs with 4 to 20 mA sourcing tools – Multiple methods and sourcing approaches – Testing 1V to 5 V and 0 V to 10 V I/O ©2010 Fluke Corporation Troubleshooting 4 mA to 20 mA loops 2
  • 3. What will be covered in this session • Measuring loop power supplies, troubleshooting suspect power supplies – Testing and isolating a transmitter with substitution power supply • Troubleshooting suspect transmitters – mA simulate used for substitution testing • Using a HART smart transmitter as a mA source – Using the Loop Test HART command to test a loop • Testing an I/P with 4 to 20 mA sourcing • Testing a control valve with a 4 to 20 mA source ©2010 Fluke Corporation Troubleshooting 4 mA to 20 mA loops 3
  • 4. 24 V loop supply +– What makes a 4 to 20 mA control loop “tick” Indicators/Controllers: Interpret the 4 to 20 mA signal as the temperature or pressure being measured in the process. Often issue commands to a final control element such as a valve to regulate the process temperature or pressure to within acceptable limits Inputs to these devices is frequently a 1 V to 5 V input signal rather than 4 to 20 mA ZERO SPAN 2200 ºC 4 to 20 mA 2 Wire Transmitter Sensor input • Temperature • Pressure • Flow • Frequency • PH Readout/Controller DCS/PLC/Recorder 250 ohm input shunt  4 to 20 mA signal   24 V loop power supply: Provides power for the loop. Transmitters regulate the 4 to 20 mA signal in the circuit drawing power from this supply. Transmitters: Convert the measured temperature or pressure to a 4 to 20 mA signal. Typically are passive devices and draw their power from an external 24 V loop power supply.
  • 5. 2200 ºC Example current loop ZERO SPAN 4 to 20 mA 2 Wire Transmitter Sensor input • Temperature • Pressure • Flow • Frequency • PH Readout/Controller DCS/PLC/Recorder 250 ohm input shunt  4 to 20 mA signal   24 V loop supply +– • 4 to 20 mA (dc) signal is proportional to sensor input or PV • Series circuit dictates the current at one location must be identical to other locations • Big advantage sending in sending mA signals over long distances compared to voltage or pressure signals
  • 6. Temperature transmitters convert measured temperature (PV) 4 to 20 mA signals Measured PV: The PV or primary/process variable in this example is the temperature of the process fluid being measured by the temperature transmitter. Temperature transmitter: Typically sense the temperature of the process via either a thermocouple or RTD sensor and convert the measurement to a 4 to 20 mA signal. The transmitter in this example has an input span (range) of 0 °C to 300 °C. The relationship of the measured temperature and mA signal is shown is the table. Temperature input Current output Percent of span 0 °C 4 mA 0 % 75 °C 8 mA 25 % 150 °C 12 mA 50 % 225 °C 16 mA 75 % 300 °C 20 mA 100 % Temperature transmitter
  • 7. Temperature transmitters convert measured temperature (PV) 4 to 20 mA signals Measured PV: The PV or primary/process variable in this example is the temperature being measured by the temperature transmitter. Temperature transmitter: Typically sense the temperature of the process via either a thermocouple or RTD sensor and convert the measurement to a 4 to 20 mA signal. The transmitter in this example has an input span (range) of 0 °C to 300 °C. The relationship of the measured temperature and mA signal is shown is the table. Temperature input Current output Percent of span 0 °C 4 mA 0 % 75 °C 8 mA 25 % 150 °C 12 mA 50 % 225 °C 16 mA 75 % 300 °C 20 mA 100 %
  • 8. Temperature Transmitters convert measured temperature (PV) 4 to 20 mA signals Indicator/Controller: In this example, the temperature indicator/controller is programmed to interpret a 4 mA signal as 0 °C and a 20 mA signal as 300 °C. Input/Output or I/O: Refers to the input/output of the control system or controller. In this example the input to the controller is the 4 to 20 mA signal. The output from the controller is the signal that controls the control valve. Flow Control Valve Final control element. Opens and closes based on commands from the controller to increase or decrease gas supplied to the burner as required to maintain temperature at the setpoint value. Temperature input Current output Percent of span 0 °C 4 mA 0 % 75 °C 8 mA 25 % 150 °C 12 mA 50 % 225 °C 16 mA 75 % 300 °C 20 mA 100 % Temperature transmitter
  • 9. Pressure Transmitters convert measured pressure (PV) to 4 to 20 mA signals Measured PV: The PV or primary/process variable in this example is the pressure being measured by the pressure transmitter. Pressure Transmitter: Senses the pressure of the process directly and converts the measurement to a 4 to 20 mA signal. The transmitter in this example has an input span (range) of 0 psi to 100 psi. The relationship of the measured pressure and mA signal is shown is the table. Indicators/Controller: In this example, the pressure indicator/controller is programmed to interpret a 4 mA signal as 0 psi and a 20 mA signal as 100 psi. Pressure relief valve: Final control element. In this example if the measured pressure is too high, the controller instructs the valve to open to reduce the pressure in the vessel. Pressure input Current output Percent of span 0 psi 4 mA 0 % 25 psi 8 mA 25 % 50 psi 12 mA 50 % 75 psi 16 mA 75 % 100 psi 20 mA 100 % Pressure transmitter
  • 10. What can go wrong with a 4 to 20 mA loop? Pressure input Current output Percent of span 0 psi 4 mA 0 % 25 psi 8 mA 25 % 50 psi 12 mA 50 % 75 psi 16 mA 75 % 100 psi 20 mA 100 % Pressure transmitter Wiring problems: Bad terminations, compromised insulation, corrosion and contami- nation can cause wiring to negatively impact 4 to 20 mA loop operation. 24V loop power supplies: Noisy, defective or overloaded power supplies can cause erratic mA loop operation or failures. Bad I/O into the controller: If the mA signal is correct and the controller does not interpret the mA signal correctly the control of the process is lost. Temperature input Current output Percent of span 0 °C 4 mA 0 % 75 °C 8 mA 25 % 150 °C 12 mA 50 % 225 °C 16 mA 75 % 300 °C 20 mA 100 % Temperature transmitter
  • 11. What can go wrong with a 4 to 20 mA loop Pressure input Current output Percent of span 0 psi 4 mA 0 % 25 psi 8 mA 25 % 50 psi 12 mA 50 % 75 psi 16 mA 75 % 100 psi 20 mA 100 % Pressure transmitter Bad transmitter: If the transmitter does not change the mA signal to correctly to respond to the measured PV the control system will not correct to adjust the PV correctly. Bad sensor or clogged capillary: If the temperature sensor is defective the transmitter cannot sense the temperature. In a pressure transmitter if the connection to the process is clogged the transmitter cannot measure the pressure accurately. Temperature input Current output Percent of span 0 °C 4 mA 0 % 75 °C 8 mA 25 % 150 °C 12 mA 50 % 225 °C 16 mA 75 % 300 °C 20 mA 100 % Temperature transmitter
  • 12. How do you troubleshoot? What tools are of the most use? What can be measured or sourced Measurement and sourcing tool What it tells the technician Measure 4 mA to 20 mA signals DMM. Loop calibrator, mA clamp, ProcessMeter If the measured mA value is the expected value Source 4 mA to 20 mA signals Loop calibrator, mA clamp, ProcessMeter If the I/O or other mA input device is working correctly Simulate 4 mA to 20 mA signals Loop calibrator, Fluke 772 or 773 mA Clamp, ProcessMeter If the power supply, wiring and I/O is working correctly, perform transmitter substitution test Measure 24 V loop voltage DMM, Loop calibrator, Fluke 773 mA Clamp, ProcessMeter If the full 24V supply available, if it is defective or being loaded down? Supply 24 V loop voltage Loop calibrator, mA clamp, Fluke 789 ProcessMeter If a substitution test for installed supply fixes the problem Source 0 V to 10 V, 1 V to 5 V Loop calibrator with voltage source (715) or specialized mA Clamp (773) If the I/O or other voltage input device is working correctly Continuity measurements DMM, ProcessMeter, some multifunction process calibrators Find open circuits, bad terminations, resistive connections and mis-wires
  • 13. Measure the 4 mA to 20 mA signal In series, “Break the loop” Temperature input Current output Percent of span 0 °C 4 mA 0 % 75 °C 8 mA 25 % 150 °C 12 mA 50 % 225 °C 16 mA 75 % 300 °C 20 mA 100 % Temperature transmitter Pressure input Current output Percent of span 0 psi 4 mA 0 % 25 psi 8 mA 25 % 50 psi 12 mA 50 % 75 psi 16 mA 75 % 100 psi 20 mA 100 % Pressure transmitter Compare measured mA signal to the expected value on the display
  • 14. Measure the 4 mA to 20 mA signal; Don’t break the loop Don’t “Break the loop” Temperature input Current output Percent of span 0 °C 4 mA 0 % 75 °C 8 mA 25 % 150 °C 12 mA 50 % 225 °C 16 mA 75 % 300 °C 20 mA 100 % Temperature transmitter Pressure input Current output Percent of span 0 psi 4 mA 0 % 25 psi 8 mA 25 % 50 psi 12 mA 50 % 75 psi 16 mA 75 % 100 psi 20 mA 100 % Pressure transmitter Compare measured mA signal to the expected value on the display
  • 15. Source a 4 mA to 20 mA signal Temperature input Current output Percent of span 0 °C 4 mA 0 % 75 °C 8 mA 25 % 150 °C 12 mA 50 % 225 °C 16 mA 75 % 300 °C 20 mA 100 % Temperature transmitter Pressure input Current output Percent of span 0 psi 4 mA 0 % 25 psi 8 mA 25 % 50 psi 12 mA 50 % 75 psi 16 mA 75 % 100 psi 20 mA 100 % Pressure transmitter Tests the indicator, controller or PLC/Control system I/O directly. Verify the value on the display
  • 16. Simulate a 4 mA to 20 mA signal Simulate a transmitter in a loop, regulate current Temperature input Current output Percent of span 0 °C 4 mA 0 % 75 °C 8 mA 25 % 150 °C 12 mA 50 % 225 °C 16 mA 75 % 300 °C 20 mA 100 % Temperature transmitter Pressure input Current output Percent of span 0 psi 4 mA 0 % 25 psi 8 mA 25 % 50 psi 12 mA 50 % 75 psi 16 mA 75 % 100 psi 20 mA 100 % Pressure transmitter Tests the wiring, power supply, indicator, controller or PLC/Control system I/O. Verify the value on the display. Perform a transmitter substitution test.
  • 17. Measure 24V loop power Temperature input Current output Percent of span 0 °C 4 mA 0 % 75 °C 8 mA 25 % 150 °C 12 mA 50 % 225 °C 16 mA 75 % 300 °C 20 mA 100 % Temperature transmitter Pressure input Current output Percent of span 0 psi 4 mA 0 % 25 psi 8 mA 25 % 50 psi 12 mA 50 % 75 psi 16 mA 75 % 100 psi 20 mA 100 % Pressure transmitter Is the full 24 V available or is the power supply being loaded down
  • 18. Test with external 24 V loop power supply Temperature input Current output Percent of span 0 °C 4 mA 0 % 75 °C 8 mA 25 % 150 °C 12 mA 50 % 225 °C 16 mA 75 % 300 °C 20 mA 100 % Temperature transmitter Pressure input Current output Percent of span 0 psi 4 mA 0 % 25 psi 8 mA 25 % 50 psi 12 mA 50 % 75 psi 16 mA 75 % 100 psi 20 mA 100 % Pressure transmitter Supply 24 V loop power, simultaneously measure mA signal. Substitution test for the power supply.
  • 19. Using a HART smart transmitter as a mA source • Using loop test, the Fluke 744 issues the mA output command to the transmitter over the HART cable • Transmitter sources a mA signal into the I/O • Verify correct indication on the display • Compare commanded output value to mA signal read by Fluke 754 • Tests transmitter output, power supply, wiring and I/O HART cable Temperature input Current output Percent of span 0 °C 4 mA 0 % 75 °C 8 mA 25 % 150 °C 12 mA 50 % 225 °C 16 mA 75 % 300 °C 20 mA 100 % Temperature transmitter Instrument Output 4 to 20 mA output to PLC or DCS PVAO command (from communicator, Fluke 744 or 754) Loop test output trim Smart transmitter output
  • 20. • The input to many control systems and PLCs is a voltage signal • 1 V to 5 V is most common as 4 to 20 mA through 250 ohms is 1 V to 5 V • Some low power transmitters have 1 V to 5 V outputs • Many older chart recorders and HVAC systems have 1 V to 5 V and 0 V to 10 V I/O 2200 ºC Readout / Controller DCS / PLC / Recorder Troubleshooting, sourcing 1 V to 5 V and 0 V to 10 V 0.004 x 250 = 1.0 V 0.020 x 250 = 5.0 V Ohms law
  • 21. Testing I to P devices I to P converts a 4 mA to 20 mA signal to a 3 psi to 15 psi pneumatic signal •Often used with control valves •Used as a bridge between 4 mA to 20 mA loop and 3 psi to 15 psi pneumatic technology •Typically operate from a 20 psi or greater pressure supply •Source 4 mA to 20 mA, verify/measure correct pressure output 4-20 mA current input Pressure output Supply pressure ~20 PSI Current input Pressure output Percent of span 4 mA 3 psi 0 % 8 mA 6 psi 25 % 12 mA 9 psi 50 % 16 mA 12 psi 75 % 20 mA 15 psi 100 %
  • 22. Testing control valves • Flow control, final control element • 4 mA to 20 mA or 3 psi to 15 psi input • Normally closed or open –Normally closed fails closed with loss of power –Normally open fails open with loss of power • Apply a 4 mA to 20 mA signal and check for operation per the applicable table below Normally Closed Normally Open Closed ClosedOpen Open Closed Open Pressure input Current output Percent of travel 3 psi 4 mA 0 % 6 psi 8 mA 25 % 9 psi 12 mA 50 % 12 psi 16 mA 75 % 15 psi 20 mA 100 % Pressure input Current output Percent of travel 3 psi 4 mA 0 % 6 psi 8 mA 25 % 9 psi 12 mA 50 % 12 psi 16 mA 75 % 15 psi 20 mA 100 %
  • 23. Testing HART control valves • Testing HART valves require simultaneous HART feedback, while energizing the valve and monitoring travel. • Underperforming valves can disrupt a process unexpectedly, leading to expensive unplanned downtime. • Even valves with no visible issues, may be contributing to lowered quality and higher cost. • Simple tools exist for quick verification of valve health to avoid some common issues. • Often control valves are critical components in safety & shutdown systems What can go wrong with a Control Valve? Mechanical Issues: Electrical Issues: Equipment Issues: Stiction Hysteresis Dead Band Stick-Slip Over/Under Travel PV Translation Control Power Loss Out of Tolerance Positioner Communication Transmitter Malfunction Under/Over-Sized Valves Nonlinearity Applications
  • 24. Review: Current loop devices and test methods • Transmitters –Apply input stimulus (temperature, pressure, etc) –Measure for correct 4 to 20 mA output –Use mA simulate for substitution testing • 24 V loop power supplies –Measure for correct voltage, substitution test to verify • I to P, 4 mA to 20 mA input, 3 psi to 15 psi output –Source 4 to 20 mA, verify/measure correct pressure output • Control valves –Source 4 mA to 20 mA, verify position indication –Use mA signal ramping to test for smooth operation • PLC, DCS, indicators, controllers, flow computers, and chart recorders analog inputs –Source 4 mA to 20 mA into the input and verify correct indication
  • 25. Special Offers • For a limited time only, Save $500 on Fluke 710 mA Loop Calibrator
  • 26. Questions or Comments? Email Nicole VanWert-Quinzi nvanwert@Transcat.com Transcat: 800-828-1470 www.Transcat.com For related product information, go to: www.transcat.com/brand/fluke-store