Understanding Arc Flash
Presented by
Eddie F. Jones, PE
Engineering Services
2
Engineering Services
3
Engineering Services
4
Engineering Services
5
Engineering Services
6
Five to 10 arc flash explosions occur in
electric equipment every day in the
United States. This number does not
include cases in which the victim is sent
to an ordinary hospital. Instead, these
incidents are so severe the victims
require treatment from a special burn
center.
Engineering Services
7
Type of faults
• Bolted Fault
Bolted faults are characterized by a solidly connected fault path
causing high levels of current to flow through this solid
connection.
• Arcing Faults
Arcing faults differ in the fact that the current actually flows
through ionized air causing an arc.
The major difference between these two types of faults is that
the energy in a bolted fault condition is dissipated in the faulted
equipment while an arcing fault releases energy out into the
surrounding enviroment
Engineering Services
8
What causes electrical arcing
• Inadvertent contact
• Loose connections
• Insulation failure
• Poorly maintained equipment
• Voltage transients
• Unsuccessful Short Circuit Interruption
• Animals (squirrels, snakes .. Etc)
Engineering Services
9
Why is arc flash dangerous?
An arc is a source of intense heat, light, sound and
pressure!
• North Carolina in August: 100o F (311K)
• Surface of the Sun: 8,540o F (5,000 K)
• Arc @ arc terminals: 35,540o F (20,000+ K)
Max. arc power = 1/2 x bolted fault kW
Heat transfer depends on:
Size of arc (arc power)
Duration of arc
Distance from arc (1/x^2)
Enclosure (“arc in a box” focuses heat in one direction)
Engineering Services
10
Physical Effects of Arc Blast
• Metal vapor and air expand very rapidly due to arc heating
• Pressure wave knocks worker away from arc
– Good: removes personnel from heat source
– Bad: removes personnel from ladder
• Pressure propels molten metal droplets out from arc source
– Hot enough to ignite clothing
• Structural damage to buildings
• Damaging sound pressure
– Eardrum rupture
– Blindness
– Lung damage
– Death!
Engineering Services
11
Engineering Services
12
Standards used to protect
workers from Arc-flash
hazards.
Engineering Services
13
“Covers electrical safety-related work
practices and procedures for employees who
work on or near exposed energized electrical
conductors or circuit parts in work places…”
“Switchboards, panelboards, industrial
control panels, and motor control centers ...
shall be field marked to warn qualified
persons of potential electric arc flash
hazards.”
“ The employer shall ensure that each
employee exposed to electric arcs shall not
wear clothing that could increase the injury
when exposed to these arcs.”
“This guide presents methods for the
calculation of arc-flash incident energy and
arc-flash boundaries in three-phase ac systems
to which workers may be exposed.”
Engineering Services
14
Safe operations
Equipment
(Product
Standards)
Analysis
Practices Training
OSHA (Workplace Safety)
NEC (Installation)
IEEE 1584
Calculations
OSHA Standards
NFPA 70E
Employer (Facility)
Employee
(Work, PPE)
Enforcement
by inspectors
Enforcement
by OSHA
Electrical Safety Program
Design for Safety Electrical Safety Program
Engineering Services
15
NEC 110.16
“Switchboards, panelboards, industrial control panels, and motor
control centers that are in other than dwelling occupancies and
are likely to require examination, adjustment, servicing, or
maintenance while energized shall be field marked to warn
qualified persons of potential electric arc flash hazards. The
marking shall be located so as to be clearly visible to qualified
persons before examination, adjustment, servicing, or
maintenance of the equipment.”
Warning for awareness, to prepare for future work
Field marked - not marked by manufacturer
No mention of values - only warning of hazard
Engineering Services
16
OSHA 29 CFR 1910.335
“Employees working in areas where there are potential
electrical hazards shall be provided with, and shall use,
electrical protective equipment that is appropriate for the
specific parts of the body to be protected and for the work
to be performed.”
Notice that OSHA does not specifically mention
calculations or NFPA 70E. However, since NFPA
70E is a recognized, published standard available
to the industry, OSHA will cite using requirements
of NFPA 70E.
Personal Protective Equipment
Engineering Services
17
OSHA 29 CFR 1910.333
• Safety related work practices shall be employed to prevent electric
shock or other injuries resulting from either direct or indirect
electrical contacts.”
• “Live parts to which an employee may be exposed shall be
deenergized before the employee works on or near them, unless
the employer can demonstrate that deenergizing introduces
additional or increased hazards or is infeasible.”
The fundamental requirement is to de-energize!
Working on energized equipment is always a risk!
Engineering Services
18
When is it acceptable to work on
energized equipment?
Examples of increased or additional hazards
Interruption of:
Life support systems
Emergency alarm systems
Hazardous location ventilation
Examples of unfeasibility:
Start-up testing
Trouble shooting diagnostics
Continuous process segment
Engineering Services
19
NFPA 70E 2-1.3.3
“Flash hazard analysis shall be done
before a person approaches any
exposed electrical conductor or circuit
part that has not been placed in an
electrically safe work condition.”
Engineering Services
20
Electrically Safe
The following steps must be taken to ensure an electrically safe work
condition.
• Find all possible sources of supply
• Open the disconnecting device for each source
• Where possible visually verify the device is open
• Apply lock-out/tag-out devices
• Test voltage on each conductor to verify that it is de-energized
• Apply grounding devices where stored energy or induced voltage could
exist or where de-energized parts could contact live parts
Remember personal protective equipment must be worn when
working within the flash protective boundary until the circuit is
verified to be de-energized.
Engineering Services
21
Incident energy
Incident energy:
• The amount of energy impressed on a surface, a certain distance
from the source, generated during an arc event.
• Incident energy is measured in calories/cm2 or Joules/cm2.
1.2 cal/cm2 is the minimum amount of Incident Energy to produce
second degree burns on human skin. The flash protection
boundary is the distance at which the incident energy equals 1.2
cal/cm2.
Engineering Services
22
Classes of Protective Clothing
Incident
Energy
(cal/cm2
)
Clothing
Class
Description ATPV
0-2 0 Untreated
Cotton
n/a
2-5 1 FR shirt and
pants
5-7
5-8 2A Cotton
Underwear +
Cl. 1
8-18
5-16 2B FR Underwear
+ Cl. 1
16-22
8-25 3 FR Coverall +
Cl. 2A
25-50
25-40 4 Double Layer
Switching Coat
+ Cl. 2A
40-60+
NFPA70E lists the
clothing that is
appropriate for each
hazard class.
ATPV - Arc thermal performance exposure value (cal/cm2)
Engineering Services
23
Hazard/Risk Category
Task Assumes Equipment is energized, and work is done
within Flash Boundary
Hazard/Risk
Category
V-rated
Gloves
V-rated
Tools
Panelboards or Switchboards rated >240V (with Molded Case or
Insulated case circuit breakers) - Notes 1 and 3
- - -
CB or fused switch operation with covers on 0 N N
CB or fused switch operation with covers off 1 N N
Work on energized parts, including voltage testing 2* Y Y
Note 1. 25kA short circuit current available, 0.03 sec (2 cycle) fault
clearing
Note 3. For < 10 kA short circuit current available, the Hazard/Risk
Category required may be reduced by one Number.
Engineering Services
24
Limits of approach
NFPA70E establishes
approach boundaries to
live parts for shock
protection for both
qualified and unqualified
personnel.
Voltage
(L-L)
Limited
Approach
(movable)
Limited
Approach
(fixed)
Restricted
Approach
Flash
Protection
< 300 V 10’ 3’ 6” Avoid
Contact
3’
300 – 750 V 10’ 3’ 6” 1’ 3’
750 – 2,000
V
10’ 4’ 2’ 4’
2,000 –
15,000 V
10’ 5’ 2’ 2” 16’
Engineering Services
25
IEEE 1584-2002
“IEEE Guide for Performing Arc-Flash Hazard Calculations”
• Incorporates results of extensive testing performed by several parties
• Provides tools to calculating incident arc-flash energy and protection
boundries.
• Does not replace NEC or 70E--instead, works with and alongside of
them
Engineering Services
26
What is an Arc flash Analysis?
“A study investigating a worker’s
potential exposure to arc flash
energy,
conducted for the purpose of
injury prevention
and the determination of safe
work practices
and appropriate levels of PPE.”
Engineering Services
27
Analysis Process
1 Collect system and installation data
2 Determine system modes of operation
3 Determine bolted fault current
4 Calculate arc fault current
5 Find protective device characteristic and arc duration
6 Select working distances
7 Calculate incident energy
8 Calculate flash protection boundary
9 Determine PPE (risk hazard) category
Engineering Services
28
Arc Flash Study Deliverables
• AFIE and resulting PPE levels
• Single-line diagram
• Short circuit duty assessment
• Time-current coordination settings
• Equipment labels (optional)
Engineering Services
29
Flash Hazard Analysis Table
Engineering Services
30
Can arc flash exposure be reduced?
• Design considerations
– Main circuit breakers
Especially on the load side of service entrance
transformers
– High resistance grounded systems
Limits the line to ground fault energy
– Performing Arc-flash analysis
Review circuit breaker settings (INST)
125E
2000KVA
3000A MAIN
SUB1B
LV 46.0 kA
LV X/R 8.2
MTRI-SUB1
1600A1 800A1 1200A2 800A
2 sets: 500
EQUIPCP
BUS-0031
LV 9.1 kA
LV X/R 1.9
Engineering Services
31
Breaker Settings Comparison
TX Inrush
2000 KVA
2 sets: 500
2000 KVA
125E
3000A MAIN
800A1
2 sets: 500
1 10 100 1K 10K
0.01
0.10
1
10
100
1000
CURRENT IN AMPERES
Case 3.tcc Ref. Voltage: 480 Current Scale x10^2 Ford Sharonville.drw
TIME
IN
SECONDS
TX Inrush
2000 KVA
2 sets: 500
2000 KVA
125E
3000A MAIN
800A1
2 sets: 500
1 10 100 1K 10K
0.01
0.10
1
10
100
1000
CURRENT IN AMPERES
Case 3.tcc Ref. Voltage: 480 Current Scale x10^2 Ford Sharonville.drw
TIME
IN
SECONDS
IA = 6K
IB = 9K
Fault clears in 8
seconds
Incident energy
= 718 cal/cm2
No FR class for IE
values this high
Fault clears in 0.1
second
Incident energy
= .97 cal/cm2
FR class 0
IA = 6K
IB = 9K
Engineering Services
32
Can arc flash exposure be reduced?
Maintenance considerations
• Direct replacements, reconditioning, retrofills
of older devices
– New, improved protective relays
– MasterPact clearing times
• Remote racking
• Arc Terminator for MV MetalClad s/g
• Arc resistant switchgear
• HVIR windows, remote thermal monitoring
– Thermographic imaging requires
• Equipment energized and serving normal loads
• Equipment open and visible
Engineering Services
33
Parting thought
Numerous injuries and deaths are caused each year by
arc-flash incidents. While arc-flash can not be completely
eliminated, there are many things that we can do to prevent
it. The single most important thing we can do to prevent
arc-flash incidents is to place the equipment in a “safe
working condition.” If it is more dangerous to turn the
equipment off workers must wear appropriate PPE.
Thank you for your time and attention
Understanding Arc Flash presentation engineering

More Related Content

PDF
Understanding Arc Flash
PDF
Why Test Series - Arc Flash Evaluations CS-00158
ZIP
Electrical Arc Flash Safety and Risk Management
PPT
Introduction to Arc Flash/Blast Electrical Hazards
PPTX
Arc Flash Solutions
PPTX
arcflashsolutions2-160226132648
PPTX
Electrical hazards
PDF
Safety In Electrical Jobs.pdf
Understanding Arc Flash
Why Test Series - Arc Flash Evaluations CS-00158
Electrical Arc Flash Safety and Risk Management
Introduction to Arc Flash/Blast Electrical Hazards
Arc Flash Solutions
arcflashsolutions2-160226132648
Electrical hazards
Safety In Electrical Jobs.pdf

Similar to Understanding Arc Flash presentation engineering (18)

PDF
Arc flash analysis, electrical safety and risk assessment
PDF
Arc flash in Industry
PPT
arc flash powerpoint safety powerpoint upload
DOCX
Arc flash
DOCX
Arc flash
DOCX
Arc flash q
PPT
Introduction to Arc Flash - Revisions to the NFPA 70E, Electrically Safe Wor...
PPTX
2015 nfpa 70 e changes
PPTX
487034682-electrical-safety-ppt-final-pptx.pptx
PDF
Lecture 2.pdf m m mm mn
PPT
Electrical hazards2 (1)
PPT
70 e ppt short 2012
PPT
6a_ELECTRIC SAFETY.ppt
PDF
Surge Protection
PPTX
Electrical Workplace Safety and Arc Flash Hazard Awareness - English.pptx
PPTX
Electrical Workplace Safety and Arc Flash Hazard Awareness - English.pptx
PDF
amrepresent
PPT
Electrical safety sample
Arc flash analysis, electrical safety and risk assessment
Arc flash in Industry
arc flash powerpoint safety powerpoint upload
Arc flash
Arc flash
Arc flash q
Introduction to Arc Flash - Revisions to the NFPA 70E, Electrically Safe Wor...
2015 nfpa 70 e changes
487034682-electrical-safety-ppt-final-pptx.pptx
Lecture 2.pdf m m mm mn
Electrical hazards2 (1)
70 e ppt short 2012
6a_ELECTRIC SAFETY.ppt
Surge Protection
Electrical Workplace Safety and Arc Flash Hazard Awareness - English.pptx
Electrical Workplace Safety and Arc Flash Hazard Awareness - English.pptx
amrepresent
Electrical safety sample
Ad

Recently uploaded (20)

PPTX
Infosys Presentation by1.Riyan Bagwan 2.Samadhan Naiknavare 3.Gaurav Shinde 4...
PPTX
OOP with Java - Java Introduction (Basics)
PPTX
Foundation to blockchain - A guide to Blockchain Tech
PPTX
Geodesy 1.pptx...............................................
PDF
Model Code of Practice - Construction Work - 21102022 .pdf
PPT
Project quality management in manufacturing
DOCX
573137875-Attendance-Management-System-original
PPTX
CARTOGRAPHY AND GEOINFORMATION VISUALIZATION chapter1 NPTE (2).pptx
PPTX
UNIT-1 - COAL BASED THERMAL POWER PLANTS
PPTX
Sustainable Sites - Green Building Construction
PPTX
Lecture Notes Electrical Wiring System Components
PDF
PPT on Performance Review to get promotions
PPTX
FINAL REVIEW FOR COPD DIANOSIS FOR PULMONARY DISEASE.pptx
PDF
TFEC-4-2020-Design-Guide-for-Timber-Roof-Trusses.pdf
PPT
CRASH COURSE IN ALTERNATIVE PLUMBING CLASS
PDF
composite construction of structures.pdf
PPTX
IOT PPTs Week 10 Lecture Material.pptx of NPTEL Smart Cities contd
PDF
R24 SURVEYING LAB MANUAL for civil enggi
PPTX
Internet of Things (IOT) - A guide to understanding
PDF
Digital Logic Computer Design lecture notes
Infosys Presentation by1.Riyan Bagwan 2.Samadhan Naiknavare 3.Gaurav Shinde 4...
OOP with Java - Java Introduction (Basics)
Foundation to blockchain - A guide to Blockchain Tech
Geodesy 1.pptx...............................................
Model Code of Practice - Construction Work - 21102022 .pdf
Project quality management in manufacturing
573137875-Attendance-Management-System-original
CARTOGRAPHY AND GEOINFORMATION VISUALIZATION chapter1 NPTE (2).pptx
UNIT-1 - COAL BASED THERMAL POWER PLANTS
Sustainable Sites - Green Building Construction
Lecture Notes Electrical Wiring System Components
PPT on Performance Review to get promotions
FINAL REVIEW FOR COPD DIANOSIS FOR PULMONARY DISEASE.pptx
TFEC-4-2020-Design-Guide-for-Timber-Roof-Trusses.pdf
CRASH COURSE IN ALTERNATIVE PLUMBING CLASS
composite construction of structures.pdf
IOT PPTs Week 10 Lecture Material.pptx of NPTEL Smart Cities contd
R24 SURVEYING LAB MANUAL for civil enggi
Internet of Things (IOT) - A guide to understanding
Digital Logic Computer Design lecture notes
Ad

Understanding Arc Flash presentation engineering

  • 1. Engineering Services 1 Understanding Arc Flash Presented by Eddie F. Jones, PE
  • 6. Engineering Services 6 Five to 10 arc flash explosions occur in electric equipment every day in the United States. This number does not include cases in which the victim is sent to an ordinary hospital. Instead, these incidents are so severe the victims require treatment from a special burn center.
  • 7. Engineering Services 7 Type of faults • Bolted Fault Bolted faults are characterized by a solidly connected fault path causing high levels of current to flow through this solid connection. • Arcing Faults Arcing faults differ in the fact that the current actually flows through ionized air causing an arc. The major difference between these two types of faults is that the energy in a bolted fault condition is dissipated in the faulted equipment while an arcing fault releases energy out into the surrounding enviroment
  • 8. Engineering Services 8 What causes electrical arcing • Inadvertent contact • Loose connections • Insulation failure • Poorly maintained equipment • Voltage transients • Unsuccessful Short Circuit Interruption • Animals (squirrels, snakes .. Etc)
  • 9. Engineering Services 9 Why is arc flash dangerous? An arc is a source of intense heat, light, sound and pressure! • North Carolina in August: 100o F (311K) • Surface of the Sun: 8,540o F (5,000 K) • Arc @ arc terminals: 35,540o F (20,000+ K) Max. arc power = 1/2 x bolted fault kW Heat transfer depends on: Size of arc (arc power) Duration of arc Distance from arc (1/x^2) Enclosure (“arc in a box” focuses heat in one direction)
  • 10. Engineering Services 10 Physical Effects of Arc Blast • Metal vapor and air expand very rapidly due to arc heating • Pressure wave knocks worker away from arc – Good: removes personnel from heat source – Bad: removes personnel from ladder • Pressure propels molten metal droplets out from arc source – Hot enough to ignite clothing • Structural damage to buildings • Damaging sound pressure – Eardrum rupture – Blindness – Lung damage – Death!
  • 12. Engineering Services 12 Standards used to protect workers from Arc-flash hazards.
  • 13. Engineering Services 13 “Covers electrical safety-related work practices and procedures for employees who work on or near exposed energized electrical conductors or circuit parts in work places…” “Switchboards, panelboards, industrial control panels, and motor control centers ... shall be field marked to warn qualified persons of potential electric arc flash hazards.” “ The employer shall ensure that each employee exposed to electric arcs shall not wear clothing that could increase the injury when exposed to these arcs.” “This guide presents methods for the calculation of arc-flash incident energy and arc-flash boundaries in three-phase ac systems to which workers may be exposed.”
  • 14. Engineering Services 14 Safe operations Equipment (Product Standards) Analysis Practices Training OSHA (Workplace Safety) NEC (Installation) IEEE 1584 Calculations OSHA Standards NFPA 70E Employer (Facility) Employee (Work, PPE) Enforcement by inspectors Enforcement by OSHA Electrical Safety Program Design for Safety Electrical Safety Program
  • 15. Engineering Services 15 NEC 110.16 “Switchboards, panelboards, industrial control panels, and motor control centers that are in other than dwelling occupancies and are likely to require examination, adjustment, servicing, or maintenance while energized shall be field marked to warn qualified persons of potential electric arc flash hazards. The marking shall be located so as to be clearly visible to qualified persons before examination, adjustment, servicing, or maintenance of the equipment.” Warning for awareness, to prepare for future work Field marked - not marked by manufacturer No mention of values - only warning of hazard
  • 16. Engineering Services 16 OSHA 29 CFR 1910.335 “Employees working in areas where there are potential electrical hazards shall be provided with, and shall use, electrical protective equipment that is appropriate for the specific parts of the body to be protected and for the work to be performed.” Notice that OSHA does not specifically mention calculations or NFPA 70E. However, since NFPA 70E is a recognized, published standard available to the industry, OSHA will cite using requirements of NFPA 70E. Personal Protective Equipment
  • 17. Engineering Services 17 OSHA 29 CFR 1910.333 • Safety related work practices shall be employed to prevent electric shock or other injuries resulting from either direct or indirect electrical contacts.” • “Live parts to which an employee may be exposed shall be deenergized before the employee works on or near them, unless the employer can demonstrate that deenergizing introduces additional or increased hazards or is infeasible.” The fundamental requirement is to de-energize! Working on energized equipment is always a risk!
  • 18. Engineering Services 18 When is it acceptable to work on energized equipment? Examples of increased or additional hazards Interruption of: Life support systems Emergency alarm systems Hazardous location ventilation Examples of unfeasibility: Start-up testing Trouble shooting diagnostics Continuous process segment
  • 19. Engineering Services 19 NFPA 70E 2-1.3.3 “Flash hazard analysis shall be done before a person approaches any exposed electrical conductor or circuit part that has not been placed in an electrically safe work condition.”
  • 20. Engineering Services 20 Electrically Safe The following steps must be taken to ensure an electrically safe work condition. • Find all possible sources of supply • Open the disconnecting device for each source • Where possible visually verify the device is open • Apply lock-out/tag-out devices • Test voltage on each conductor to verify that it is de-energized • Apply grounding devices where stored energy or induced voltage could exist or where de-energized parts could contact live parts Remember personal protective equipment must be worn when working within the flash protective boundary until the circuit is verified to be de-energized.
  • 21. Engineering Services 21 Incident energy Incident energy: • The amount of energy impressed on a surface, a certain distance from the source, generated during an arc event. • Incident energy is measured in calories/cm2 or Joules/cm2. 1.2 cal/cm2 is the minimum amount of Incident Energy to produce second degree burns on human skin. The flash protection boundary is the distance at which the incident energy equals 1.2 cal/cm2.
  • 22. Engineering Services 22 Classes of Protective Clothing Incident Energy (cal/cm2 ) Clothing Class Description ATPV 0-2 0 Untreated Cotton n/a 2-5 1 FR shirt and pants 5-7 5-8 2A Cotton Underwear + Cl. 1 8-18 5-16 2B FR Underwear + Cl. 1 16-22 8-25 3 FR Coverall + Cl. 2A 25-50 25-40 4 Double Layer Switching Coat + Cl. 2A 40-60+ NFPA70E lists the clothing that is appropriate for each hazard class. ATPV - Arc thermal performance exposure value (cal/cm2)
  • 23. Engineering Services 23 Hazard/Risk Category Task Assumes Equipment is energized, and work is done within Flash Boundary Hazard/Risk Category V-rated Gloves V-rated Tools Panelboards or Switchboards rated >240V (with Molded Case or Insulated case circuit breakers) - Notes 1 and 3 - - - CB or fused switch operation with covers on 0 N N CB or fused switch operation with covers off 1 N N Work on energized parts, including voltage testing 2* Y Y Note 1. 25kA short circuit current available, 0.03 sec (2 cycle) fault clearing Note 3. For < 10 kA short circuit current available, the Hazard/Risk Category required may be reduced by one Number.
  • 24. Engineering Services 24 Limits of approach NFPA70E establishes approach boundaries to live parts for shock protection for both qualified and unqualified personnel. Voltage (L-L) Limited Approach (movable) Limited Approach (fixed) Restricted Approach Flash Protection < 300 V 10’ 3’ 6” Avoid Contact 3’ 300 – 750 V 10’ 3’ 6” 1’ 3’ 750 – 2,000 V 10’ 4’ 2’ 4’ 2,000 – 15,000 V 10’ 5’ 2’ 2” 16’
  • 25. Engineering Services 25 IEEE 1584-2002 “IEEE Guide for Performing Arc-Flash Hazard Calculations” • Incorporates results of extensive testing performed by several parties • Provides tools to calculating incident arc-flash energy and protection boundries. • Does not replace NEC or 70E--instead, works with and alongside of them
  • 26. Engineering Services 26 What is an Arc flash Analysis? “A study investigating a worker’s potential exposure to arc flash energy, conducted for the purpose of injury prevention and the determination of safe work practices and appropriate levels of PPE.”
  • 27. Engineering Services 27 Analysis Process 1 Collect system and installation data 2 Determine system modes of operation 3 Determine bolted fault current 4 Calculate arc fault current 5 Find protective device characteristic and arc duration 6 Select working distances 7 Calculate incident energy 8 Calculate flash protection boundary 9 Determine PPE (risk hazard) category
  • 28. Engineering Services 28 Arc Flash Study Deliverables • AFIE and resulting PPE levels • Single-line diagram • Short circuit duty assessment • Time-current coordination settings • Equipment labels (optional)
  • 30. Engineering Services 30 Can arc flash exposure be reduced? • Design considerations – Main circuit breakers Especially on the load side of service entrance transformers – High resistance grounded systems Limits the line to ground fault energy – Performing Arc-flash analysis Review circuit breaker settings (INST) 125E 2000KVA 3000A MAIN SUB1B LV 46.0 kA LV X/R 8.2 MTRI-SUB1 1600A1 800A1 1200A2 800A 2 sets: 500 EQUIPCP BUS-0031 LV 9.1 kA LV X/R 1.9
  • 31. Engineering Services 31 Breaker Settings Comparison TX Inrush 2000 KVA 2 sets: 500 2000 KVA 125E 3000A MAIN 800A1 2 sets: 500 1 10 100 1K 10K 0.01 0.10 1 10 100 1000 CURRENT IN AMPERES Case 3.tcc Ref. Voltage: 480 Current Scale x10^2 Ford Sharonville.drw TIME IN SECONDS TX Inrush 2000 KVA 2 sets: 500 2000 KVA 125E 3000A MAIN 800A1 2 sets: 500 1 10 100 1K 10K 0.01 0.10 1 10 100 1000 CURRENT IN AMPERES Case 3.tcc Ref. Voltage: 480 Current Scale x10^2 Ford Sharonville.drw TIME IN SECONDS IA = 6K IB = 9K Fault clears in 8 seconds Incident energy = 718 cal/cm2 No FR class for IE values this high Fault clears in 0.1 second Incident energy = .97 cal/cm2 FR class 0 IA = 6K IB = 9K
  • 32. Engineering Services 32 Can arc flash exposure be reduced? Maintenance considerations • Direct replacements, reconditioning, retrofills of older devices – New, improved protective relays – MasterPact clearing times • Remote racking • Arc Terminator for MV MetalClad s/g • Arc resistant switchgear • HVIR windows, remote thermal monitoring – Thermographic imaging requires • Equipment energized and serving normal loads • Equipment open and visible
  • 33. Engineering Services 33 Parting thought Numerous injuries and deaths are caused each year by arc-flash incidents. While arc-flash can not be completely eliminated, there are many things that we can do to prevent it. The single most important thing we can do to prevent arc-flash incidents is to place the equipment in a “safe working condition.” If it is more dangerous to turn the equipment off workers must wear appropriate PPE. Thank you for your time and attention