• Introduction
• Reasons for constant frequency
• Methods of Load frequency control
• LFC problem in SingleArea Power System
• Load Frequency Control of TwoArea System
• Automatic Generation Control (AGC)
• In an electric power system, Load Frequency Control (LFC) is a
system to maintain reasonably uniform frequency, to divide the load
between the generators, and to control the tie-line interchange
schedules.
• The change in frequency is sensed when the rotor angle ∂ is
changed.
• The error signals are transformed into real power command signal,
which is sent to prime mover to call for an increment in the torque.
• The prime mover then brings change in the generator output by an
amount which will change the values of within the specified
tolerance.
• The speed of the alternating current motors depends on the frequency of the power
supply. There are situations where speed consistency is expected to be of high
order.
• The accuracy of the electric clocks are dependent on the frequency
of the supply.
• If the normal frequency is 50 Hertz and the system frequency falls below 47.5
Hertz or goes up above 52.5 Hertz then the blades of the turbine are likely to get
damaged so as to prevent the failing of the generator.
• Due to the subnormal frequency operation the blast of the ID and FD fans in the
power stations get reduced and thereby reduce the generation power in the thermal
plants.
Unit 2 Load Frequency  Control    ppt.ppt
• The load frequency control strategies have been suggested based on the
conventional linear Control theory. These controllers may be unsuitable in some
operating conditions due to the complexity of the power systems such as nonlinear
load characteristics and variable operating points.
• Under normal operating condition controller are set for small changes in load
demand without voltage and frequency exceeding the pre specified limits. If the
operating condition changes by any cause, the controller must be reset either
manually or automatically. The objective of load frequency controller is to exert
the control off frequency and at the same time real power exchange via outgoing
transmission line.
• The speed governor is the main primary tool for the load
frequency
control (LFC).
• Figure shows a schematic arrangement of a speed
governing system used on steam turbines to control the
output of the generator to maintain constant frequency.
• The speed governing system consists of the following parts
.
1) Speed governor
2) Linkage mechanism
3) Hydraulic amplifier
4) Speed changer
Unit 2 Load Frequency  Control    ppt.ppt
This is the heart of the system which senses the change in speed (frequency). As the
speed increases the fly balls move outwards and the point B on linkage mechanism
moves downwards. The reverse happens when the speed decreases.
2.Hydraulic amplifier
• It comprises a pilot valve and main piston Low power level pilot valve movement is
converted into high power level piston valve movement.
• This is necessary in order to open or close the steam valve against high pressure
steam.
• It provides a steady state power output setting for the turbine.
• Its downward movement opens the upper pilot valve so that more steam is admitted to the
turbine under steady conditions (hence more steady power output).
• The reverse happens for upward movement of speed changer.
3. Linkage mechanism
• ABC is a rigid link pivoted at B and CDE is another rigid link pivoted at This link
mechanism provides a movement to the control valve in proportion to change in
speed.
• It also provides a feedback from the steam valve movement
Model of Speed Governing System
• Assume that the system is initially operating under steady conditions—the
linkage mechanism stationary and pilot valve closed, steam valve opened by a
definite magnitude, turbine running at constant speed with turbine power output
balancing the generator load. Let the operating conditions be characterized by
• We shall obtain a linear incremental model around these operating conditions.
• Let the point A on the linkage mechanism be moved downwards by a small
amount ΔyA. It is a command which causes the turbine power output to change
and can therefore be written as
• where ΔPC is the commanded increase in power.
• The command signal ΔPC (i.e. ΔyE) sets into motion a sequence of events—the pilot
valve moves upwards, high pressure oil flows on to the top of the main piston moving it
downwards; the steam valve opening consequently increases, the turbine generator
speed increases,
i.e. the frequency goes up. Let us model these events mathematically.
• Two factors contribute to the movement of C:
….(1)
….(3)
• The movement ΔyD depending upon its sign opens one of the ports of the pilot valve
admitting high pressure oil into the cylinder thereby moving the main piston and
opening the steam valve by ΔyE. Certain justifiable simplifying assumptions, which
can be made at this stage, are:
• Inertial reaction forces of main piston and steam valve are negligible compared to
the forces exerted on the piston by high pressure oil.
• Because of (i) above, the rate of oil admitted to the cylinder is proportional to port
opening ΔyD.
• The volume of oil admitted to the cylinder is thus proportional to the time integral of
ΔyD,. The movement ΔyE is obtained by dividing the oil volume by the area of the
cross-section of the piston. Thus
….(4)
• It can be verified from the schematic diagram that a positive movement ΔyD causes negative
(upward) movement ΔyE accounting for the negative sign used in above Eq.
• Taking the Laplace transform of above Eqs. (2),(3), and (4) we get
• EliminatingΔYC(s) andΔYD(s), we can write
….(5)
….(6)
….(7)
• Where
• Equation (8) is represented in the form of a block diagram in Fig.
Turbine Model:
Let us now relate the dynamic response of a steam turbine in terms of changes in power
output to changes in steam valve opening ΔyE. Figure 8.4a shows a two stage steam
turbine with a reheat unit.
The dynamic response is largely influenced by two factors, (i) entrained steam between
the inlet steam valve and first stage of the turbine, (ii) the storage action in the reheater
which causes the output of the low pressure stage to lag behind that of the high pressure
stage.
Thus, the turbine transfer function is characterized by two time constants. For ease of
analysis it will be assumed here that the turbine can be modelled to have a single
equivalent time constant.
Figure 8.4b shows the transfer function model of a steam turbine. Typically the time
constant Tt lies in the range 0.2 to 2.5 sec.
Unit 2 Load Frequency  Control    ppt.ppt
Adjustment of Governor Characteristics
• The control of system frequency and load depends upon the
governor of the prime movers.
• The below figure shows the characteristics of the speed governor system
• For stable operation of generator ,the governors are designed to permitt the
speed to drop as the load is increased .
• Then slop of the curve represent the speed regulation R.
• Governors typically have a speed regulation of 5-6% from zero to full load.
Where
NL
=Steady state speed at No-
Load
FL =Steady state speed at full load
0
=Rated speed
If two or more alternators with droping govenor characteristics are connected to a
power system there will be unique frequency at which they will share a load change.
• Assme ,two generator units with droping characteristics as
shown in above figure.
• Let the initial frequency of both the unit is f with power output P1 and P2 when a
load increases to P it causes the units to slow down/.
• The governor increases the output until they reach a new common operating
frequency f.
• An extended power system can be divided into a number of load frequency control
areas interconnected by means of tie lines. Without loss of generality two area
case connected by tie-line is considered. The control objectives are as follows:
(1)Each control area as for as possible should supply its own load
demand and power transfer through tie line should be on mutual
agreement.
(2)Both control areas should controllable to the frequency control.
• A two area system consists of two single area systems connected
through a power line called tie-line. Each area feeds its user pool, and
the tie line allows electric power to flow between the areas, because
both areas as well as the power flow on the tie-line. For the same
reason, the control system of each area needs information about the
transient situation in both areas to bring the local frequency back to its
steady state value. Information about the local area is found in the tie
line power fluctuations. Therefore, the tie-line power is sensed, and
the resulting tie-line power signal is fed back into both areas. It is
conveniently assumed that each control area can be represented by an
equivalent turbine, generator and governor system.
Unit 2 Load Frequency  Control    ppt.ppt
• Sometimes, load on the system is increased suddenly then the
turbine speed drops before the governor can adjust the input of the
steam to the new load.
• As the change in the value of speed diminishes, the error signal
becomes smaller and the position of the governor get closer to the
point required to maintain the constant speed.
• One way to restore the speed or frequency to its nominal value is to
add an integrator on the way.
• As the load of the system changes continuously the generation is
adjusted automatically to restore the frequency to the nominal value.
This scheme is known as automatic generation control.
• In an interconnected system consisting of several pools, the role of
the AGC is to divide the load among the system, stations and
generators so as to achieve maximum economy and reasonably
uniform frequency.
Unit 2 Load Frequency  Control    ppt.ppt
• Introduction
• Importance of voltage control
• Methods of voltage control
• Shunt compensation
• Series capacitor
• Synchronous condenser
• Tap changing transformer
• Auto transformer tap changing
• Booster transformer
• Transmission of power from generating station to
consumers.
• Constant voltage for satisfactory operation.
• Variation cause unpredictable operation or mal
functioning.
• Cause : change in load at supply side.
• Load ,
voltage due
to
volta
ge drop in alternator synchronous impedence,
transmission impedence, transformer impedence,
feeders and distributors.
• Prescribe limits : +- 6% of declared voltage
• Lighting load :
Lamp characterisic is very sensitive to change in voltage.
• below limit 20%
• Above limit 50%
in illumination power.
in life of lamp.
• Induction motor :
• in voltage saturation of pole
• in voltage reduces starting torque.
• Distribution Transformer :
• Due to heating, rating reduces.
• Used at more than one point due to
• Desirable drop in transmission and distribution.
• Dissimilar load characteristics.
• Individual means of voltage control for each circuit.
• Devices used at
• Generating station
• Transformer station
• Feeders if drop exceeds the limit
1. Shunt compensation
2. Series capacitor
3. Synchronous condenser
4. Tap changing transformer
5. Auto transformer tap changing
 Shunt Reactor :
 Used to compensate effect line capacitance
 limit voltage rise on open circuit or light load
 increases effective ZC
 They are connected either:
 directly to the lines at the ends
 Tertiary windings easily switched as VAR vary.
 In long lines to overcome ferranti effect.
 Connected to bus bar without C.B for switching.
 Shunt Capacitor :
• Supply leading reactive power and boost the voltage
as loading of current reduces.
• Switching substation inductive load absorb
inductive current of lower P.F.
• They are connected either:
• H.V. bus
• Tertiary winding of transformers
• Advantage :
• low cost and flexibility of installation.
• Disadvantage :
• Q is proportional to (voltage)^2. So output reduces.
 Series capacitor :
Connected in series with line.
Used to reduce inductive reactance of line so reduction of
 I 2X loss
 characteristic impedance ZC
Reactive power produced increases with increasing power
transfer.
Application :
 improve power transfer capacity.
 voltage regulation
Unit 2 Load Frequency  Control    ppt.ppt
A synchronous machine running without a prime mover or a
mechanical load
Depending on field excitation, it can either absorb or generate VARs
With a voltage regulator, it can automatically adjust VAR to maintain
constant voltage
Started as an induction motor and then synchronized
Normally connected to tertiary windings of transformers
Unlike a SVC, a synchronous condenser has an internal voltage
Speed of response not as fast as that of an SVC
• Off load Tap changing transformer :
• Position of tap number of turns output voltage.
• Stud 1 : min value
• Stud 5 : max value
• Light load primary voltage = alternator voltages and movable arm is
placed at stud 1.
• Load drop so movement of stud.
• On load Tap changing transformer :
• widely used so no interruption of supply voltage
• Secondary divided into two parallel path so current divided.
• Tap changing operation is performed one after other.
• Disadvantages :
• Voltage surge due to high voltage drop.
• Num of tapings = 2 * voltage steps.
• Mid tapped auto transformer is used.
• Connected with one side of line, divided into two parts.
• Odd switches and even switches
• Normal operation no drop
• Tap changing high drop large circulating current flow
control by reactor.

More Related Content

PPTX
Speed Control Of DC Motor
PPTX
Multi terminal dc systems (mtdc)
PPT
EXCITATION SYSTEM.ppt
PPTX
Unit 2 Reactive Power Management
PPTX
Gcsc gto thyristor controlled series capacitor
PPTX
Braking methods of induction motor
PPTX
Automatic Generation Control
PPT
Ac voltage controller
Speed Control Of DC Motor
Multi terminal dc systems (mtdc)
EXCITATION SYSTEM.ppt
Unit 2 Reactive Power Management
Gcsc gto thyristor controlled series capacitor
Braking methods of induction motor
Automatic Generation Control
Ac voltage controller

What's hot (20)

PPTX
Traction Motors and Control
PPT
Dual converters (1)
PDF
Static relay
PPTX
Protection Of Generator
PPT
Induction motor three phase
DOC
Hvdc notes
PPTX
Pid controllers
PPTX
INTERLINE FLOW CONTROLLER
PPTX
Induction Motor Drives
PPTX
Switchgear and protection 1
PPTX
P, PI AND PID CONTROLLER
PPTX
Electromagnetic Protection (PART III)
PPTX
FACT devices
PPTX
Vector Control of AC Induction Motors
PPTX
MTDC SYSTEMS
PPTX
PPTX
Tachogenerator
PPTX
Input output , heat rate characteristics and Incremental cost
PPT
Three phase ac voltage controllers
Traction Motors and Control
Dual converters (1)
Static relay
Protection Of Generator
Induction motor three phase
Hvdc notes
Pid controllers
INTERLINE FLOW CONTROLLER
Induction Motor Drives
Switchgear and protection 1
P, PI AND PID CONTROLLER
Electromagnetic Protection (PART III)
FACT devices
Vector Control of AC Induction Motors
MTDC SYSTEMS
Tachogenerator
Input output , heat rate characteristics and Incremental cost
Three phase ac voltage controllers
Ad

Similar to Unit 2 Load Frequency Control ppt.ppt (20)

PPTX
LOAD FREQUENCY AND VOLTAGE GENERATION CONTROL
PPTX
speed governer characteristics and classfication
PPTX
Inter Connected Power System(Turbine Speed Governing Mechanism )
PPTX
Load Frequency Control of Two Area System
PPTX
Different method of frequency and voltage control
PPT
PPT V-F control.ppt
PPTX
Power System Control
PPTX
SPEED GOVERNOR SYSYTEM AND ITS DERIVATIONS
PPTX
UNIT-2-PPT- Real Power Frequency Control
PPT
Electric-Traction-Railways.ppt
PPTX
ICPS_170993109001
PPTX
Automatic Generation Control
PPTX
DC Electrical Machine Modeling and speed control
PPTX
load frequency control of two area
PPTX
frequency control in India by regulating remotely generation of indian power ...
PDF
IRJET- An Investigative Study of Generator-Load Tie-Line Model of Speed Gover...
PPSX
Electronic governor
PPTX
INTRODUCTION SLIDE ON ALFC LECTURES.pptx
PPTX
LOAD FREQUENCY CONTROL USING ELECTRIC VEICHLE SYSTEM IN INTERCONNECTED POWER ...
PPTX
PSOC Sudjdjdjdjjdjdjjdjdjehueueueuueueminar.pptx
LOAD FREQUENCY AND VOLTAGE GENERATION CONTROL
speed governer characteristics and classfication
Inter Connected Power System(Turbine Speed Governing Mechanism )
Load Frequency Control of Two Area System
Different method of frequency and voltage control
PPT V-F control.ppt
Power System Control
SPEED GOVERNOR SYSYTEM AND ITS DERIVATIONS
UNIT-2-PPT- Real Power Frequency Control
Electric-Traction-Railways.ppt
ICPS_170993109001
Automatic Generation Control
DC Electrical Machine Modeling and speed control
load frequency control of two area
frequency control in India by regulating remotely generation of indian power ...
IRJET- An Investigative Study of Generator-Load Tie-Line Model of Speed Gover...
Electronic governor
INTRODUCTION SLIDE ON ALFC LECTURES.pptx
LOAD FREQUENCY CONTROL USING ELECTRIC VEICHLE SYSTEM IN INTERCONNECTED POWER ...
PSOC Sudjdjdjdjjdjdjjdjdjehueueueuueueminar.pptx
Ad

More from Sri Ramakrishna Institute of Technology (10)

PPT
CO1 Power System Operation and Control BASICS .ppt
PPT
ELECTRIC VECHICLE ppt OCT 3 UNIT 2 (2).ppt
PPT
UNIT III PROTECTION OF TRANSFORMER OCTOBER 2 (2).ppt
PPT
UNIT III PROTECTION OF GENERATOR OCTOBER 2 (2).ppt
PPT
unit-v new CIRCUIT BREAKERS SEP 12 new.ppt
PPT
Basic principle and types Static Relays ppt
PPT
Basic principle of Numeric relay and static relay.ppt
PPT
Protection and Switch Gear Introduction Relay PPT ppt
PPT
Electric Vehicle CHARGING METHOD PPT.ppt
PPT
PSOC Computer Control Of Power system .ppt
CO1 Power System Operation and Control BASICS .ppt
ELECTRIC VECHICLE ppt OCT 3 UNIT 2 (2).ppt
UNIT III PROTECTION OF TRANSFORMER OCTOBER 2 (2).ppt
UNIT III PROTECTION OF GENERATOR OCTOBER 2 (2).ppt
unit-v new CIRCUIT BREAKERS SEP 12 new.ppt
Basic principle and types Static Relays ppt
Basic principle of Numeric relay and static relay.ppt
Protection and Switch Gear Introduction Relay PPT ppt
Electric Vehicle CHARGING METHOD PPT.ppt
PSOC Computer Control Of Power system .ppt

Recently uploaded (20)

PPTX
web development for engineering and engineering
DOCX
573137875-Attendance-Management-System-original
PPTX
KTU 2019 -S7-MCN 401 MODULE 2-VINAY.pptx
PDF
July 2025 - Top 10 Read Articles in International Journal of Software Enginee...
PDF
TFEC-4-2020-Design-Guide-for-Timber-Roof-Trusses.pdf
PPTX
MET 305 2019 SCHEME MODULE 2 COMPLETE.pptx
PDF
Operating System & Kernel Study Guide-1 - converted.pdf
PPTX
CYBER-CRIMES AND SECURITY A guide to understanding
DOCX
ASol_English-Language-Literature-Set-1-27-02-2023-converted.docx
PPTX
Welding lecture in detail for understanding
PDF
Well-logging-methods_new................
PPTX
bas. eng. economics group 4 presentation 1.pptx
PPTX
IOT PPTs Week 10 Lecture Material.pptx of NPTEL Smart Cities contd
PPT
Mechanical Engineering MATERIALS Selection
PPTX
Lecture Notes Electrical Wiring System Components
PDF
PPT on Performance Review to get promotions
PPTX
Engineering Ethics, Safety and Environment [Autosaved] (1).pptx
PPT
Project quality management in manufacturing
PDF
Automation-in-Manufacturing-Chapter-Introduction.pdf
PDF
Mitigating Risks through Effective Management for Enhancing Organizational Pe...
web development for engineering and engineering
573137875-Attendance-Management-System-original
KTU 2019 -S7-MCN 401 MODULE 2-VINAY.pptx
July 2025 - Top 10 Read Articles in International Journal of Software Enginee...
TFEC-4-2020-Design-Guide-for-Timber-Roof-Trusses.pdf
MET 305 2019 SCHEME MODULE 2 COMPLETE.pptx
Operating System & Kernel Study Guide-1 - converted.pdf
CYBER-CRIMES AND SECURITY A guide to understanding
ASol_English-Language-Literature-Set-1-27-02-2023-converted.docx
Welding lecture in detail for understanding
Well-logging-methods_new................
bas. eng. economics group 4 presentation 1.pptx
IOT PPTs Week 10 Lecture Material.pptx of NPTEL Smart Cities contd
Mechanical Engineering MATERIALS Selection
Lecture Notes Electrical Wiring System Components
PPT on Performance Review to get promotions
Engineering Ethics, Safety and Environment [Autosaved] (1).pptx
Project quality management in manufacturing
Automation-in-Manufacturing-Chapter-Introduction.pdf
Mitigating Risks through Effective Management for Enhancing Organizational Pe...

Unit 2 Load Frequency Control ppt.ppt

  • 1. • Introduction • Reasons for constant frequency • Methods of Load frequency control • LFC problem in SingleArea Power System • Load Frequency Control of TwoArea System • Automatic Generation Control (AGC)
  • 2. • In an electric power system, Load Frequency Control (LFC) is a system to maintain reasonably uniform frequency, to divide the load between the generators, and to control the tie-line interchange schedules. • The change in frequency is sensed when the rotor angle ∂ is changed. • The error signals are transformed into real power command signal, which is sent to prime mover to call for an increment in the torque. • The prime mover then brings change in the generator output by an amount which will change the values of within the specified tolerance.
  • 3. • The speed of the alternating current motors depends on the frequency of the power supply. There are situations where speed consistency is expected to be of high order. • The accuracy of the electric clocks are dependent on the frequency of the supply. • If the normal frequency is 50 Hertz and the system frequency falls below 47.5 Hertz or goes up above 52.5 Hertz then the blades of the turbine are likely to get damaged so as to prevent the failing of the generator. • Due to the subnormal frequency operation the blast of the ID and FD fans in the power stations get reduced and thereby reduce the generation power in the thermal plants.
  • 5. • The load frequency control strategies have been suggested based on the conventional linear Control theory. These controllers may be unsuitable in some operating conditions due to the complexity of the power systems such as nonlinear load characteristics and variable operating points. • Under normal operating condition controller are set for small changes in load demand without voltage and frequency exceeding the pre specified limits. If the operating condition changes by any cause, the controller must be reset either manually or automatically. The objective of load frequency controller is to exert the control off frequency and at the same time real power exchange via outgoing transmission line.
  • 6. • The speed governor is the main primary tool for the load frequency control (LFC). • Figure shows a schematic arrangement of a speed governing system used on steam turbines to control the output of the generator to maintain constant frequency. • The speed governing system consists of the following parts . 1) Speed governor 2) Linkage mechanism 3) Hydraulic amplifier 4) Speed changer
  • 8. This is the heart of the system which senses the change in speed (frequency). As the speed increases the fly balls move outwards and the point B on linkage mechanism moves downwards. The reverse happens when the speed decreases. 2.Hydraulic amplifier • It comprises a pilot valve and main piston Low power level pilot valve movement is converted into high power level piston valve movement. • This is necessary in order to open or close the steam valve against high pressure steam.
  • 9. • It provides a steady state power output setting for the turbine. • Its downward movement opens the upper pilot valve so that more steam is admitted to the turbine under steady conditions (hence more steady power output). • The reverse happens for upward movement of speed changer. 3. Linkage mechanism • ABC is a rigid link pivoted at B and CDE is another rigid link pivoted at This link mechanism provides a movement to the control valve in proportion to change in speed. • It also provides a feedback from the steam valve movement
  • 10. Model of Speed Governing System • Assume that the system is initially operating under steady conditions—the linkage mechanism stationary and pilot valve closed, steam valve opened by a definite magnitude, turbine running at constant speed with turbine power output balancing the generator load. Let the operating conditions be characterized by • We shall obtain a linear incremental model around these operating conditions. • Let the point A on the linkage mechanism be moved downwards by a small amount ΔyA. It is a command which causes the turbine power output to change and can therefore be written as
  • 11. • where ΔPC is the commanded increase in power. • The command signal ΔPC (i.e. ΔyE) sets into motion a sequence of events—the pilot valve moves upwards, high pressure oil flows on to the top of the main piston moving it downwards; the steam valve opening consequently increases, the turbine generator speed increases, i.e. the frequency goes up. Let us model these events mathematically. • Two factors contribute to the movement of C: ….(1) ….(3)
  • 12. • The movement ΔyD depending upon its sign opens one of the ports of the pilot valve admitting high pressure oil into the cylinder thereby moving the main piston and opening the steam valve by ΔyE. Certain justifiable simplifying assumptions, which can be made at this stage, are: • Inertial reaction forces of main piston and steam valve are negligible compared to the forces exerted on the piston by high pressure oil. • Because of (i) above, the rate of oil admitted to the cylinder is proportional to port opening ΔyD. • The volume of oil admitted to the cylinder is thus proportional to the time integral of ΔyD,. The movement ΔyE is obtained by dividing the oil volume by the area of the cross-section of the piston. Thus ….(4)
  • 13. • It can be verified from the schematic diagram that a positive movement ΔyD causes negative (upward) movement ΔyE accounting for the negative sign used in above Eq. • Taking the Laplace transform of above Eqs. (2),(3), and (4) we get • EliminatingΔYC(s) andΔYD(s), we can write ….(5) ….(6) ….(7)
  • 14. • Where • Equation (8) is represented in the form of a block diagram in Fig.
  • 15. Turbine Model: Let us now relate the dynamic response of a steam turbine in terms of changes in power output to changes in steam valve opening ΔyE. Figure 8.4a shows a two stage steam turbine with a reheat unit. The dynamic response is largely influenced by two factors, (i) entrained steam between the inlet steam valve and first stage of the turbine, (ii) the storage action in the reheater which causes the output of the low pressure stage to lag behind that of the high pressure stage. Thus, the turbine transfer function is characterized by two time constants. For ease of analysis it will be assumed here that the turbine can be modelled to have a single equivalent time constant. Figure 8.4b shows the transfer function model of a steam turbine. Typically the time constant Tt lies in the range 0.2 to 2.5 sec.
  • 17. Adjustment of Governor Characteristics • The control of system frequency and load depends upon the governor of the prime movers. • The below figure shows the characteristics of the speed governor system
  • 18. • For stable operation of generator ,the governors are designed to permitt the speed to drop as the load is increased . • Then slop of the curve represent the speed regulation R. • Governors typically have a speed regulation of 5-6% from zero to full load.
  • 19. Where NL =Steady state speed at No- Load FL =Steady state speed at full load 0 =Rated speed If two or more alternators with droping govenor characteristics are connected to a power system there will be unique frequency at which they will share a load change.
  • 20. • Assme ,two generator units with droping characteristics as shown in above figure. • Let the initial frequency of both the unit is f with power output P1 and P2 when a load increases to P it causes the units to slow down/. • The governor increases the output until they reach a new common operating frequency f.
  • 21. • An extended power system can be divided into a number of load frequency control areas interconnected by means of tie lines. Without loss of generality two area case connected by tie-line is considered. The control objectives are as follows: (1)Each control area as for as possible should supply its own load demand and power transfer through tie line should be on mutual agreement. (2)Both control areas should controllable to the frequency control.
  • 22. • A two area system consists of two single area systems connected through a power line called tie-line. Each area feeds its user pool, and the tie line allows electric power to flow between the areas, because both areas as well as the power flow on the tie-line. For the same reason, the control system of each area needs information about the transient situation in both areas to bring the local frequency back to its steady state value. Information about the local area is found in the tie line power fluctuations. Therefore, the tie-line power is sensed, and the resulting tie-line power signal is fed back into both areas. It is conveniently assumed that each control area can be represented by an equivalent turbine, generator and governor system.
  • 24. • Sometimes, load on the system is increased suddenly then the turbine speed drops before the governor can adjust the input of the steam to the new load. • As the change in the value of speed diminishes, the error signal becomes smaller and the position of the governor get closer to the point required to maintain the constant speed. • One way to restore the speed or frequency to its nominal value is to add an integrator on the way. • As the load of the system changes continuously the generation is adjusted automatically to restore the frequency to the nominal value. This scheme is known as automatic generation control. • In an interconnected system consisting of several pools, the role of the AGC is to divide the load among the system, stations and generators so as to achieve maximum economy and reasonably uniform frequency.
  • 26. • Introduction • Importance of voltage control • Methods of voltage control • Shunt compensation • Series capacitor • Synchronous condenser • Tap changing transformer • Auto transformer tap changing • Booster transformer
  • 27. • Transmission of power from generating station to consumers. • Constant voltage for satisfactory operation. • Variation cause unpredictable operation or mal functioning. • Cause : change in load at supply side. • Load , voltage due to volta ge drop in alternator synchronous impedence, transmission impedence, transformer impedence, feeders and distributors. • Prescribe limits : +- 6% of declared voltage
  • 28. • Lighting load : Lamp characterisic is very sensitive to change in voltage. • below limit 20% • Above limit 50% in illumination power. in life of lamp. • Induction motor : • in voltage saturation of pole • in voltage reduces starting torque. • Distribution Transformer : • Due to heating, rating reduces.
  • 29. • Used at more than one point due to • Desirable drop in transmission and distribution. • Dissimilar load characteristics. • Individual means of voltage control for each circuit. • Devices used at • Generating station • Transformer station • Feeders if drop exceeds the limit
  • 30. 1. Shunt compensation 2. Series capacitor 3. Synchronous condenser 4. Tap changing transformer 5. Auto transformer tap changing
  • 31.  Shunt Reactor :  Used to compensate effect line capacitance  limit voltage rise on open circuit or light load  increases effective ZC  They are connected either:  directly to the lines at the ends  Tertiary windings easily switched as VAR vary.  In long lines to overcome ferranti effect.  Connected to bus bar without C.B for switching.
  • 32.  Shunt Capacitor : • Supply leading reactive power and boost the voltage as loading of current reduces. • Switching substation inductive load absorb inductive current of lower P.F. • They are connected either: • H.V. bus • Tertiary winding of transformers • Advantage : • low cost and flexibility of installation. • Disadvantage : • Q is proportional to (voltage)^2. So output reduces.
  • 33.  Series capacitor : Connected in series with line. Used to reduce inductive reactance of line so reduction of  I 2X loss  characteristic impedance ZC Reactive power produced increases with increasing power transfer. Application :  improve power transfer capacity.  voltage regulation
  • 35. A synchronous machine running without a prime mover or a mechanical load Depending on field excitation, it can either absorb or generate VARs With a voltage regulator, it can automatically adjust VAR to maintain constant voltage Started as an induction motor and then synchronized Normally connected to tertiary windings of transformers Unlike a SVC, a synchronous condenser has an internal voltage Speed of response not as fast as that of an SVC
  • 36. • Off load Tap changing transformer : • Position of tap number of turns output voltage. • Stud 1 : min value • Stud 5 : max value • Light load primary voltage = alternator voltages and movable arm is placed at stud 1. • Load drop so movement of stud.
  • 37. • On load Tap changing transformer : • widely used so no interruption of supply voltage • Secondary divided into two parallel path so current divided. • Tap changing operation is performed one after other. • Disadvantages : • Voltage surge due to high voltage drop. • Num of tapings = 2 * voltage steps.
  • 38. • Mid tapped auto transformer is used. • Connected with one side of line, divided into two parts. • Odd switches and even switches • Normal operation no drop • Tap changing high drop large circulating current flow control by reactor.