2. - 1 -
………………………………………………………………… ENGLISH ……………………………………………………………………
Thank you for choosing Delta DVP-SS2 series PLCs. DVP-SS2 series PLCs include
one 12-point PLC, and two 14-point PLCs. A DVP-SS2 series PLC provides various
instructions, and the size of the program memory in it is 8k steps. It is able to connect to
all DVP-S series extension modules, including digital I/O (max. 480 I/O points) and
analog modules (for A/D, D/A conversion and temperature measurement). 4 groups of
high-speed (10kHz) pulse output satisfy all kinds of applications. DVP-SS2 is small in
size, and can be install easily. Users do not have to install any batteries in DVP-SS2
series PLCs. The PLC programs and the latched data are stored in the flash memories.
EN DVP-SS2 is an OPEN-TYPE device. It should be installed in a control cabinet
free of airborne dust, humidity, electric shock and vibration. To prevent
non-maintenance staff from operating DVP-SS2, or to prevent an accident from
damaging DVP-SS2, the control cabinet in which DVP-SS2 is installed should be
equipped with a safeguard. For example, the control cabinet in which DVP-SS2 is
installed can be unlocked with a special tool or key.
EN DO NOT connect AC power to any of I/O terminals, otherwise serious damage
may occur. Please check all wiring again before DVP-SS2 is powered up. After
DVP-SS2 is disconnected, Do NOT touch any terminals in a minute. Make sure
that the ground terminal on DVP-SS2 is correctly grounded in order to
prevent electromagnetic interference.
FR DVP-SS2 est un module OUVERT. Il doit être installé que dans une enceinte
protectrice (boitier, armoire, etc.) saine, dépourvue de poussière, d’humidité, de
vibrations et hors d’atteinte des chocs électriques. La protection doit éviter que
les personnes non habilitées à la maintenance puissent accéder à l’appareil (par
exemple, une clé ou un outil doivent être nécessaire pour ouvrir a protection).
FR Ne pas appliquer la tension secteur sur les bornes d’entrées/Sorties, ou l’appareil
DVP-SS2 pourra être endommagé. Merci de vérifier encore une fois le câblage
avant la mise sous tension du DVP-SS2. Lors de la déconnection de l’appareil,
ne pas toucher les connecteurs dans la minute suivante. Vérifier que la terre est
bien reliée au connecteur de terre afin d’éviter toute interférence
électromagnétique.
Product Profile
[ Figure 1 ]
25.20 60.00
EXTENSION
PORT
90.00
3.00
3.001
2
3
4
5
6
7
8
9
10
11
4
12
13
14
Unit: mm
1. POWER, RUN, ERROR indicator 8. Nameplate
2. RUN/STOP switch 9. Extension port
3. I/O port for program communication (RS-232) 10. DIN rail mounting slot (35mm)
4. DIN rail clip 11. Extension unit clip
5. I/O terminals 12. RS-485 communication port
6. I/O point indicator 13. Mounting rail for extension module
7. Mounting hole for extension module 14. DC power input
Electrical Specifications
Model
Item
DVP14SS211R DVP14SS211T DVP12SS211S
Power supply voltage
24VDC (-15% ~ 20%)
(with counter-connection protection on the polarity of DC input power)
DVPPS01(PS02): input 100-240VAC, output 24VDC/1A(PS02: 2A)
Inrush current Max. 7.5A@24VDC
3. - 2 -
Model
Item
DVP14SS211R DVP14SS211T DVP12SS211S
Fuse capacity 1.85A/30VDC, Polyswitch
Power consumption 1.8W 1.5W
Power protection With counter-connection protection on the polarity of DC input power
Insulation resistance > 5MΩ (all I/O point-to-ground: 500VDC)
Noise immunity
ESD (IEC 61131-2, IEC 61000-4-2): 8kV Air Discharge
EFT (IEC 61131-2, IEC 61000-4-4): Power Line: 2kV, Digital I/O: 1kV,
Analog & Communication I/O: 1kV
RS (IEC 61131-2, IEC 61000-4-3): 26MHz ~ 1GHz, 10V/m
Grounding
The diameter of grounding wire cannot be smaller than the wire
diameter of terminals L and N (All DVP units should be grounded
directly to the ground pole).
Operation / storage
Operation: 0°C ~ 55°C (temp.), 5 ~ 95% (humidity), Pollution degree2
Storage: -25°C ~ 70°C (temp.), 5 ~ 95% (humidity)
Vibration / shock
resistance
International standards: IEC61131-2, IEC 68-2-6 (TEST
Fc)/IEC61131-2 & IEC 68-2-27 (TEST Ea)
Weight (g) 97g 82.5g 90g
Input PointSpec.
Items 24VDC (-15% ~ 20%) single common port input
Input No. X0 ~ X3 X4 ~ X7
Input type DC (SINK or SOURCE)
Input Current (± 10%) 24VDC, 5mA
Input impedance 4.7kΩ
Max. frequency 20kHz 10kHz
OffOn > 15VDCAction
level OnOff < 5VDC
OffOn < 10μs < 20μsResponse
time OnOff < 20μs < 50μs
Filter time Adjustable within 0 ~ 20ms by D1020 (Default: 10ms)
Output PointSpec.
Items Relay Transistor
Output No. Y0 ~ Y5 Y0 ~ Y3 Y4, Y5
Max. frequency 1Hz 10kHz 1kHz
Working voltage 250VAC, < 30VDC 5 ~ 30VDC
#1
Resistive 1.5A/1 point (5A/COM) 0.5A/1 point (3A/COM)
Inductive
#2
15W (30VDC)Max. load
Lamp 20WDC/100WAC 2.5W (30VDC)
OffOn 20μs 100μsResponse
time OnOff
Approx. 10ms
30μs 100μs
#1: UP, ZP must work with external auxiliary power supply 24VDC (-15% ~ +20%), rated
consumption approx. 10mA/point.
#2: Life curves
Contact
Current(A)0.50.1 0.2
50
0.3 0.7 1 2
200
300
500
100
1000
2000
3000
Operation(X10)3
120VAC Resistive
30VDC Inductive(t=7ms)
240VAC Inductive(cos 0.4)ψ=
120VAC Inductive(cos =0.4)ψ
30VDC
Inductive
(t=40ms)
[ Figure 2 ]
4. - 3 -
I/O Configuration
Input Output I/O Configuration
Model
Point Type Point Type Relay
Transistor
(NPN)
Transistor
(PNP)
14SS211R Relay
14SS211T
6
Transistor
(NPN)
12SS211S
8
DC
(Sink Or
Source)
4
Transistor
(PNP)
S/S
X0
X1
X2
X5
X6
X7
Y0
Y1
Y2
Y3
Y4
Y5
X4
C0
C1
X3
S/S
X0
X1
X2
X5
X6
X7
ZP
Y0
Y1
Y4
Y5
X4
UP
Y3
X3
Y2
S/S
X0
X1
X2
X5
X6
X7
ZP
Y0
Y1
DA
X4
UP
Y3
X3
Y2
PWM
Note: The layout of output terminals on DVP-SS2 is different from that on DVP-SS.
Dimension & Installation
Please install the PLC in an enclosure with sufficient
space around it to allow heat dissipation, See [Figure 3].
Direct Mounting: Use M4 screw according to the
dimension of the product.
DIN Rail Mounting: When mounting the PLC to
35mm DIN rail, be sure to use the retaining clip to stop
any side-to-side movement of the PLC and reduce the
chance of wires being loose. The retaining clip is at
the bottom of the PLC. To secure the PLC to DIN rail,
pull down the clip, place it onto the rail and gently push
it up. To remove the PLC, pull the retaining clip down
with a flat screwdriver and gently remove the PLC
from DIN rail.
Wiring
Use 22-16AWG (1.5mm) single or multiple core wire on
I/O wiring terminals. See the figure in the right hand side
for its specification. PLC terminal screws should be
tightened to 1.90 kg-cm (1.65 in-lbs) and please use only
60/75ºC copper conductor.
22-16AWG
< 1.5mm
1. DO NOT wire empty terminal. DO NOT place the I/O signal cable in the same wiring
circuit.
2. DO NOT drop tiny metallic conductor into the PLC while screwing and wiring. Tear
off the sticker on the heat dissipation hole for preventing alien substances from
dropping in to ensure normal heat dissipation of the PLC.
Power Supply
The power input of DVP-SS2 is DC. When operating DVP-SS2, please note the
following points:
1. The power is connected to two terminals, 24VDC and 0V, and the range of power is
20.4 ~ 28.8VDC. If the power voltage is less than 20.4VDC, the PLC will stop running,
all outputs will go “Off”, and the ERROR indicator will start to blink continuously.
2. The power shutdown for less than 10ms will not affect the operation of the PLC.
However, the shutdown time that is too long or the drop of power voltage will stop the
operation of the PLC, and all outputs will go off. When the power returns to normal
status, the PLC will automatically resume the operation. (Please take care of the
latched auxiliary relays and registers inside the PLC when doing the programming).
Safety Wiring
Since DVP-SS2 is only compatible with DC power supply, Delta’s power supply modules
(DVPPS01/DVPPS02) are the suitable power supplies for DVP-SS2. We suggest you
install the protection circuit at the power supply terminal to protect DVPPS01 or
DVPPS02. See the figure below.
5. - 4 -
AC power supply: 100 ~ 240VAC, 50/60Hz Breaker
Emergency stop: This button cuts off the system power supply when accidental
emergency takes place.
Power indicator AC power supply load
Power supply circuit protection fuse (2A) DVPPS01/DVPPS02
DC power supply output: 24VDC, 500mA DVP-PLC (main processing unit)
Digital I/O module
Input Point Wiring
There are 2 types of DC inputs, SINK and SOURCE. (See the example below. For
detailed point configuration, please refer to the specification of each model.)
DC Signal IN – SINK mode
Input point loop equivalent circuit
DC Signal IN – SOURCE mode
Input point loop equivalent circuit
24G
+24V
S/S
X0
X1
[ Figure 5 ]
+24V
24G
S/S
X0
X1
[ Figure 6 ]
Output Point Wiring
1. DVP-SS2 has two output modules on it, relay and transistor. Be aware of the
connection of shared terminals when wiring output terminals.
2. Output terminals, Y0, Y1, and Y2, of relay models use C0 common port; Y3, Y4, and
Y5 use C1 common port. See [Figure 7]. When the output points are enabled, their
corresponding indicators on the front panel will be on.
3. The output terminals Y0~Y5 of the transistor (NPN) model are connected to the
common terminals UP and ZP. See [Figure 8a]. The output terminals Y0~Y3 on the
transistor (PNP) model are connected to the common terminals UP and ZP. See
[Figure 8b].
4. Isolation circuit: The optical coupler is used to isolate signals between the circuit
inside PLC and input modules.
6. - 5 -
Relay (R) output circuit wiring
DC power supply Emergency stop: Uses external switch
Fuse: Uses 5~10A fuse at the shared terminal of output contacts to protect the output circuit
Transient voltage suppressor (SB360 3A 60V): Extends the life span of contact.
1. Diode suppression of DC load: Used when in smaller power [Figure 10a]
2. Diode + Zener suppression of DC load: Used when in larger power and frequent On/Off
[Figure 10b]
Incandescent light (resistive load) AC power supply
Manually exclusive output: For example, Y3 and Y4 control the forward running and reverse
running of the motor, forming an interlock for the external circuit, together with the PLC
internal program, to ensure safe protection in case of any unexpected errors.
Absorber: Reduces the interference on AC load [Figure 11]
Transistor output circuit wiring
Transistor output (NPN) Transistor output (PNP)
[ Figure12 ] [ Figure 13 ]
VDC
+
Small er power
D
[ F ig ure 14a ]
D: 1N4001 diode or equi va lent com ponent
ZP
Y
UP
VDC
+
Smal ler power
D
[ F ig ure 15a ]
D: 1N4001 diode or equi valent com ponent
Y
UP
ZP
7. - 6 -
Transistor output (NPN) Transistor output (PNP)
ZD D
VDC
+
Larger power and
frequent on/off
ZD: 9V Z ener, 5W [ F ig ure 14b ]
D: 1N4001 diode or equi valent com ponent
ZP
Y
UP
ZDD
Larger power
and
frequent on/off
ZD: 9V Z ener, 5W [ F ig ure 15b ]
D: 1N4001 diode or equi valent com ponent
ZP
UP
VDC +
Y
VDC
+
DC power supply Emergency stop Circuit protection fuse
The output of the transistor model is “open collector”. If Y0/Y1 is set to pulse output, the
output current has to be bigger than 0.1A to ensure normal operation of the model.
1. Diode suppression: Used when in smaller power [Figure 14a] and [Figure 15a]
Diode + Zener suppression: Used when in larger power and frequent On/Off [Figure 14b]
and [Figure 15b]
Manually exclusive output: For example, Y2 and Y3 control the forward running and reverse
running of the motor, forming an interlock for the external circuit, together with the PLC
internal program, to ensure safe protection in case of any unexpected errors.
PWM DA output circuit wiring (Only for DVP-12SS211S)
Please refer to figure 1 below for more information about wiring.
Item Specifications
DA range 0~10VDC
Value range 0~100
Resolution*1 0.1V (1~9V)
Output impedance 2k
Minimum load 1.5k
DA
UP +
24VDC
ZP
+
V0
VR Rin
PWM
Y0
-
VR is connected to Rin in parallel.
The impedance is about 1.46 .
Load
[Figure 1]
D/A conversion time <70ms
*1: 1~9V is a linear area. The resolution is 0.1V. 0~1V and 9~10V are nonlinear areas. The
output probably can not reach the voltage set.
Please refer to the correction formula before you use the PWM DA output function.
Please refer to the explanation of PWM for
more information about setting the time unit
for the pulses output by Y0.
Set the pulse cycle to 100µs.
Set the duty cycle of a pulse to 50%.
M1002
SET M1116
M0
PWM D0 Y0
MOV K100 D2
MOV K50 D0
D2
Set M0 to ON. Adjust the variable resistor so
that V0 is 5V, as shown in the curve below.
D0數值
0 50
5V
100
10V
DA輸出
RS-485 Wiring
Master node
Slave node
Figure 17
D+ D- D+ D- D+ D-
3
1 2 2
3
Terminal resistor
Note: 1. Terminal resistors are suggested to be connected to master and the last slave with
resistor value of 120.
2. To ensure communication quality, please apply double shielded twisted pair cable
(20AWG) for wiring.
Value in D0
DA output
16. - 15 -
………………………………………….......………………… TÜRKÇE …………...……......………………………………………………
Delta’nın DVP-SS2 modelini seçtiğiniz için teşekkürler. DVP-SS2 PLC 8k program
hafızası ile çeşitli komutlar sunar ve üzerinde 14-nokta (8DI + 6DO) ve 12-nokta
(8DI+4DO) vardır. PLC’ye dijital giriş/çıkış modülleri (max. 480 giriş/çıkış nokta) ve
analog modüller (A/D, D/A dönüştürücü ve sıcaklık üniteleri) bağlanabilir. İki grup
yüksek-hızlı (10kHz) pulse çıkışı ve yeni 4-eksen interpolasyon komutları ile birçok
uygulama için tatmin edici çözümler sunar. DVP-SS2 ürünü küçük ölçüsüyle kurulumu
çok kolaydır. Kullanıcıların DVP-SS2 PLC'lere herhangi bir pil takması gerekmez. PLC
programları ve kalıcı veriler flash belleklerde saklanır.
Bu bilgi dökümanı sadece ürünün elektriksel özellikleri, genel fonksiyonları, kurulumu
ve bağlantısı ile ilgili bilgiler sağlar. Detaylı programlama ve DVP-SS2 uygulama
komutları ile ilgili lütfen “DVP-SS2 Operation Manual: Programming” dökümanını
inceleyiniz. Opsiyonel çevre birimleri ile ilgili lütfen kutunun içindeki ürünle birlikte
gelen bilgi dökümanını inceleyiniz.
Bu ürün AÇIK TİP bir PLC’dir. PLC ürünü toz, rutubet, elektrik şoku riski ve
titreşimden uzak yerlerde muhafaza edilmelidir. Ayrıca cihaza yetkili olmayan kişilerin
müdahale etmesini engelleyecek önlemler alınmalıdır. (Örneğin ürünün kurulduğu
panoya kilit konulması gibi). Aksi halde kullanıcılar ve/veya PLC zarar görebilir.
Giriş/Çıkış terminallerine kesinlikle AC besleme bağlamayınız. Aksi halde ürün zarar
görebilir. Enerji vermeden önce ürünün tüm bağlantılarını kontrol ediniz.
Elektromanyetik gürültüyü önlemek için topraklamanın düzgün yapıldığına emin
olunuz. Enerjili iken ürün terminallerine müdahale etmeyiniz.
Ürün Görünüşü
İngilizce (English) bölümünde Şekil 1’ye [Figure 1] bakınız. Birim: mm.
Elektriksel Özellikler
Model
Madde
DVP14SS211R DVP14SS211T DVP12SS211S
Besleme voltajı
24VDC (-15% ~ 20%)
(DC giriş besleme ters bağlantı koruması)
DVPPS01(PS02): giriş 100-240VAC, çıkış 24VDC/1A(PS02: 2A)
Sızıntı Akımı Maksimum 7.5A@24VDC
Sigorta Kapasitesi 1.85A/30VDC, Polyswitch
Güç Tüketimi 1.8W 1.5W
Besleme Koruma DC giriş besleme ters bağlantı koruması
Izolasyon direnci > 5MΩ (Tüm I/O nokta - ground: 500VDC)
Ses Bağışıklığı
ESD (IEC 61131-2, IEC 61000-4-2): 8kV Air Discharge
EFT (IEC 61131-2, IEC 61000-4-4): Power Line: 2kV, Digital I/O: 1kV,
Analog & Communication I/O: 1kV
RS (IEC 61131-2, IEC 61000-4-3): 26MHz ~ 1GHz, 10V/m
Topraklama
Topraklama kablosunun kesiti 24V - 0V terminalleri kabloları
kesitinden küçük olmamalıdır. (Tüm DVP ürünleri doğrudan ground
ucundan topraklanmalıdırlar).
Çalışma/Saklama
Çalışma: 0°C ~ 55°C (sıcaklık), 50 ~ 95% (rutubet), Kirlenme derece 2
Saklama: -25°C ~ 70°C (sıcaklık), 5 ~ 95% (rutubet)
Titreşim/Şok direnci
Uluslararası Standartlar: IEC61131-2, IEC 68-2-6 (TEST
Fc)/IEC61131-2 & IEC 68-2-27 (TEST Ea)
Ağırlık (g) 97g 82.5g 90g
Giriş NoktasıÖzellik.
Madde 24VDC (-15% ~ 20%) tek ortak uç girişi
Giriş No. X0 ~ X3 X4 ~ X7
Giriş Tipi DC (SINK veya SOURCE)
Giriş Akımı (± 10%) 24VDC, 5mA
Giriş Empedansı
impedance
4.7k Ohm
Maksimum frekans 20kHz 10kHz
OffOn > 15VDC
Aktif seviye
OnOff < 5VDC
OffOn < 10μs < 20usCevap
Zamanı OnOff < 20μs < 50us
Filtre zamanı D1020 datasından 0 ~ 20ms (Default: 10ms)
17. - 16 -
Çıkış NoktasıÖzellik
Madde Röle Transistor
Çıkış No. Y0 ~ Y5 Y1, Y3 Y4, Y5
Maksimum frekans 1Hz 10kHz 1kHz
Çalışma Voltajı 250VAC, < 30VDC 5 ~ 30VDC
#1
Rezistif 1.5A /1 nokta (5A/COM) 0.5A/1 nokta (3A/COM)
Endüktif
#2
15W (30VDC)
Maksimum
Yük
Lamba 20WDC/100WAC 2.5W (30VDC)
OffOn 20μs 100μsCevap
Zamanı OnOff
Yaklaşık 10ms
30μs 100μs
#1: UP, ZP harici 24VDC (-15% ~ +20%) güç kaynağı ile çalışır, güç tüketimi oranı yaklaşık
10mA/nokta.
#2: İngilizce (English) bölümünde Şekil 2’ye [Figure 2] bakınız.
I/O Konfigurasyon
Giriş Çıkış I/O konfigurasyon
Model
Nokta Tip Nokta Tip Röle Transistor
14SS211R Röle
14SS211T
8 6 Transistor
(NPN)
12SS211S 8
DC
(Sink veya
Source)
4
Transistor
(PNP)
İngilizce
(English)
bölümünde
bakınız
İngilizce
(English)
bölümünde
bakınız
Not: DVPSS2 üzerindeki çıkış terminallerinin yerleşim planı DVP-SS’de olduğundan
farklıdır.
Ölçüler & Kurulum
Lütfen PLC’nin kurulumunu yaparken ısı dağılımının verimli olması için çevresinde
gerekli boşluğun bırakıldığına emin olunuz.
Lütfen İngilizce (English) bölümünde Şekil 3’e [Figure 3] bakınız.
Doğrudan Montaj: Ürünün ölçülerine göre lütfen M4 vida kullanınız.
DIN Ray Montaj: PLC ürünü 35mm DIN rayına monte edileceği zaman, ürünün
hareket ederek kablo bağlantılarının zarar görmesini engellemek için sabitleyici klipsleri
kullanınız. Sabitleyici klipsler PLC’nin altında olup, PLC’yi DIN rayına sabitlemek için bu
klipsleri bastırınız. PLC’yi yerinden çıkarmak içinse ince tornavida yardımı ile önce bu
klipsleri açınız ve PLC’yi DIN rayından çekerek çıkartınız.
Bağlantı
1. PLC’nin I/O terminal bağlantılarını yapmak için 22-16AWG
(1.5mm) tek damarlı veya çok damarlı kablo kullanınız.
Kablo özellikleri yandaki şekilde gösterildiği gibi olmalıdır.
PLC terminal vidaları 1.90 kg-cm (1.65 in-lbs) oranında
sıkılmalı ve sadece bakır iletkenler kullanılmalıdır.
22-16AWG
< 1.5mm
2. Boş terminallere bağlantı yapmayınız ve I/O sinyal kabloları ile power kablolarını
ayrı kablo bloğundan bağlayınız.
3. PLC kablo bağlantılarını yaparken PLC’nin içine iletken parçacıklar düşürmeyiniz.
Bağlantıları tamamladıktan sonra ısı dağılımın sağlanabilmesi için küçük cisimlerin
PLC’nin içine düşmesini engelleyen koruyucu etiketleri çıkartınız.
Güç Kaynağı (Power Supply)
DVP-SS2 serisi ürünlerin besleme girişi DC’dir. DVP-SS2 serisi ürünleri kullanırken
aşağıdaki uyarılara dikkat ediniz:
1. Besleme, 24VDC ve 0V terminallerine bağlanmalı ve besleme voltajı 20.4 ~
28.8VDC aralığında olmalıdır. Eğer besleme voltajı 20.4VDC altına düşerse, PLC
çalışmayı durdurur, tüm çıkışları “OFF” olur ve ERROR indikatör sürekli flash yapar.
2. 10 ms altındaki enerji kesintisi PLC’nin çalışmasına etki etmeyecektir. Fakat daha
uzun sureli bir enerji kesintisi veya voltaj düşmesi durumunda PLC çalışması
duracak ve tüm çıkışlar OFF olacaktır. PLC’nin beslemesi normal duruma
döndüğünde, PLC otomatik olarak normal çalışmasına geri döner.
(PLC programlanacağı zaman içindeki kalıcı röle ve register’lerin kullanımına dikkat
ediniz).
Güvenli Bağlantı
DVP-SS2 ürünleri sadece DC voltaj ile beslenir. DELTA’nın güç kaynakları (DVPPS01 /
DVPPS02), DVP-SS2 PLC’lerin beslemesi için uygundur. DVPPS01 veya DVPPS02
ürünlerini korumak için power supply terminallerine koruyucu devre kurulması önerilir.
İngilizce (English) bölümünde Şekil 4’e [Figure 4] bakınız.
18. - 17 -
AC power supply:100 ~ 240VAC, 50/60Hz Devre kesici
Acil Stop: Acil durumda sistemin enerjisini kesmek için kullanılır.
Power indikatör AC power supply yük
Power supply devre koruma sigortası (2A) DVPPS01/DVPPS02
DC power supply çıkışı: 24VDC, 500mA DVP-PLC (Ana işlemci birimi)
Digital I/O modülü
Giriş Bağlantısı
2 çeşit DC giriş vardır, SINK veya SOURCE. İngilizce (English) bölümde Şekil 5’e
[Figure 5] ve Şekil 6’ya [Figure 6] bakınız.
Çıkış Bağlantısı
1. DVP-SS2 serisi ürünlerde 2 çeşit çıkış vardır. Röle ve Transistör (NPN/PNP). Çıkış
terminal bağlantılarını yaparken ortak terminallerin kullanımına dikkat ediniz. (COM).
2. Y0, Y1, ve Y2 çıkış terminalleri C0 ortak ucunu, Y3, Y4 ve Y5 çıkış terminalleri C1
ortak ucunu kullanır. İngilizce (English) bölümde Şekil 7’ye [Figure 7] bakınız. Çıkış
terminallerinden biri aktif olursa o çıkış terminaline karşılık gelen indicator ON olur.
3. Y0 ~Y5 transistör çıkış terminalli (NPN) modeller UP, ZP ortak uçlarını kullanır.
İngilizce (English) bölümde Şekil 8’a [Figure 8a] bakınız. Y0 ~Y3 transistör çıkış
terminalli (PNP) modeller UP, ZP ortak uçlarını kullanır. İngilizce (English) bölümde
Şekil 8’b [Figure 8b] bakınız.
4. İzolasyon devresi: PLC iç devreleri ve giriş modülleri arasını izole etmek için
optokuplör kullanılır.
Röle (R) çıkış devre bağlantısı
Bağlantı detayı için İngilizce (English) bölümde Şekil 9’a - Şekil 11’e [Figure 9] ~
[Figure 11] bakınız.
DC power supply Acil stop: Harici switch kullanır.
Sigorta: Çıkış devrelerini korumak için çıkışların ortak terminallerinde 5~10A sigorta kullanır.
Yüksek gerilim darbe koruyucu (SB360 3A 60V): Kontak ömrünü uzatmak için kullanılır.
1. DC yük diyot koruma: Düşük power olduğu zaman kullanılır. (İngilizce (English) bölümde
Şekil 10a’ya [Figure 10a] bakınız).
2. DC yük Diyot + Zener koruma: Yüksek power veya çok sık On/Off durumlarda kullanılır.
(İngilizce (English) bölümde Şekil 10b’ye [Figure 10b] bakınız)
Akkor Lamba (resistif yük) AC power supply
Manual tek çıkış: Örneğin, Y3 ve Y4 çıkışları motorun ileri ve geri çalışmasını kontrol etsin.
Çıkışların aynı anda çalışmasını ve beklenmeyen hataları önlemek için PLC programında
ve harici devre bağlantısında gerekli önlemler alınarak aynı anda sadece tek çıkışın
çalışması sağlanabilir.
Dalga Emici (Absorber): AC yükteki gürültüyü önlemek için kullanılır. (İngilizce (English)
bölümde Şekil 11’e [Figure 11] bakınız)
Transistör (T) çıkış devre bağlantısı
Bağlantı detayı için İngilizce (English) bölümde Şekil 12 ~ Şekil 15b’ye [Figure 12] ~
[Figure 15b] bakınız.
DC power supply Acil stop Devre koruma sigortası
Transistor çıkışlı modeler “açık kolektör(open collector)” dür. Eğer Y0/Y1 pulse çıkışı olarak
ayarlandıysa, normal çalışma için çıkış akımı 0.1A’den büyük olmalıdır.
1. Diyot koruma: Düşük power olduğu zaman kullanılır. (İngilizce (English) bölümde
Şekil 14a [Figure 14a]’ye ve Şekil 15a [Figure 15a]’ye bakınız.)
2. Diyot + Zener koruma: Yüksek power veya çok sık On/Off durumlarda kullanılır
(İngilizce (English) bölümde Şekil 14b [Figure 14b]’ye ve Şekil 15b [Figure 15b]’ye]
bakınız.)
Manual tek çıkış: Örneğin, Y2 ve Y3 çıkışları motorun ileri ve geri çalışmasını kontrol etsin.
Çıkışların aynı anda çalışmasını ve beklenmeyen hataları önlemek için PLC programında
ve harici devre bağlantısında gerekli önlemler alınarak aynı anda sadece tek çıkışın
çalışması sağlanabilir.
19. - 18 -
PWM DA çıkış devre bağlantısı (Sadece DVP-12SS211S içindir.)
Bağlantı detayı için İngilizce (English) bölümde Şekil 1’e [Figure 1] bakınız.
Nesne Özellikler
DA aralığı 0~10VDC
Değer aralığı 0~100
Çözünürlük*1 0.1V (1~9V)
Çıkış empedansı 2k
Minimum yük 1.5k
DA
UP +
24VDC
ZP
+
V0
VR Rin
PWM
Y0
-
VR is connected to Rin in parallel.
The impedance is about 1.46K .
Load
[Figure 1] D/A çevrim zamanı <70ms
(VR ile Rin paralel bağlıdır. Empedans yaklaşık 1.46kΩ.)
*1: 1~9V lineer alandır. Çözünürlük 0.1V. 0~1 ve 9~10V lineer olmayan alandır. Çıkış voltaj set
değerine ulaşamayacaktır.
PWM DA çıkış fonksiyonunu kullanmadan önce lütfen aşağıdaki düzeltme formülüne bakınız.
Lütfen Y0 pulse çıkışı zaman birimi ayarı
hakkında daha fazla bilgi için PWM
açıklamalarına bakınız.
Pulse periyodunu 100µs set ediniz.
Pulse görev periyodunu 50% set ediniz.
M1002
SET M1116
M0
PWM D0 Y0
MOV K100 D2
MOV K50 D0
D2 M0 set ediniz (ON). V0 çıkışı 5V olacak
şekilde değişken değerli direnci aşağıdaki
değişim eğrisine göre ayarlayınız.
D0數值
0 50
5V
100
10V
DA輸出
RS-485 Bağlantısı
Bağlantı detayı için İngilizce (English) bölümde Şekil 17’ye [Figure 17] bakınız.
○1 Master istasyon ○2 Slave istasyon
○3 Sonlandırma direnci
Not:
1. Sonlandırma direnci master ve son slave arasında 120Ω olacak şekilde bağlanılması önerilir.
2. Haberleşme kalitesini arttırmak için, lütfen bağlantıda double shield (çift ekranlı) twisted pair
(sarmal çiftli) kablo (20AWG) kullanınız.
D0 değeri
DA çıkışı