SlideShare a Scribd company logo
American Journal of Electrical Power and Energy Systems
2013; 2(2): 50-56
Published online March 10, 2013 (http://www.sciencepublishinggroup.com/j/epes)
doi: 10.11648/j.epes.20130202.14
Application of STATCOM to increase transient stability of
wind farm
Bouhadouza Boubekeur, Ahmed Gherbi, Hacene Mellah
Department of Electrical Engineering, Sétif-1 University, Algeria
Email address:
bouhadouza_b@yahoo.fr (B. Bouhadouza), gherbi_a@yahoo.fr (A. Gherbi), has.mel@gmail.com (H. Mellah)
To cite this article:
Bouhadouza Boubekeur, Ahmed Gherbi, Hacene Mellah. Application of STATCOM to Increase Transient Stability of Wind Farm,
American Journal of Electrical Power and Energy Systems. Vol. 2, No. 2, 2013, pp. 50-56. doi: 10.11648/j.epes.20130202.14
Abstract: In this paper we interested to the study the necessary of Facts to increase the transient stability on the presence
of faults and the integration of new renewable source, like wind energy, these lasts make the electrical grid operate in a new
conditions, the STATCOM is one of the important Facts element, It provides the desired reactive-power generation and
absorption entirely by means of electronic processing of the voltage and current waveforms in a voltage source converter
(VSC). This function is identical to the synchronous condenser with rotating mass. In present work we propose a transient
stability improvement using STATCOM under faults, in the first time we study the transient stability with and without
STATCOM for clearly his advantages. In the second time we know the relation between the reactive power injecting by a
STATCOM and the critical clearing time, some simulation results are given, commented and discussed.
Keywords: Transient Stability, Reactive Power, FACTS, STATCOM, Wind Power, CCT
1. Introduction
There is now general acceptance that the burning of fos-
sil fuels is having a significant influence on the global cli-
mate. Effective mitigation of climate change will require
deep reductions in greenhouse gas emissions, with UK
estimates of a 60–80% cut being necessary by 2050 [1],
Still purer with the nuclear power, this last leaves behind
dangerous wastes for thousands of years and risks contami-
nation of land, air, and water; the catastrophe of Japan is
not far[2], to avoid the problems of the pollution, the ener-
gy policy decision states that the objective is to facilitate a
change to an ecologically sustainable energy production
system such as wind power [3], but the major problem is
how associate the wind power stations to the grid with
assure the linking conditions[4]. In addition, now a day’s
power transmission and distribution systems face increas-
ing demands for more power, better quality and higher
reliability at lower cost, as well as low environmental effect.
Under these conditions, transmission networks are called
upon to operate at high transmission levels, and thus power
engineers have had to confront some major operating prob-
lems such as transient stability, damping of oscillations and
voltage regulation etc [5], in this work we interest to the
transient stability, this last indicates the capability of the
power system to maintain synchronism when subjected to a
severe transient disturbances such as fault on heavily
loaded lines, loss of a large load etc [6].Generator excita-
tion controller with only excitation control can improve
transient stability for minor faults but it is not sufficient to
maintain stability of system for large faults occur near to
generator terminals [6]. Researchers worked on other solu-
tion and found that flexible AC transmission systems
(FACTS) are one of the most prominent solution [7], [8].
The objective principal to use FACTS technology for the
operators of the electric power is to have an opportunity for
the control of the power flow and by increasing the capaci-
ties usable of these lines under the normal conditions. The
parameter which controls the operation of transmission of
energy in a line such as the impedances series and shunts,
running, tension and phase angle is controlled by utilizing
FACTS controllers. FACTS devices increases power han-
dling capacity of the line and improve transient stability as
well as damping performance of the power system [7], [8].
According to the specialized literature we find several
types of FACTS [6-11], in our work we are limited to the
study a great disturbance, so the FACTS element used for
reactive power compensation both assuring the low cost
and high efficiency is STATCOM.
The static synchronous compensators (STATCOM) con-
sist of shunt connected voltage source converter through
coupling transformer with the transmission line. STAT-
American Journal of Electrical Power and Energy Systems 2013, 2(2): 50-56 51
COM can control voltage magnitude and, to a small extent,
the phase angle in a very short time and therefore, has abili-
ty to improve the system [7], [8].
2. Wind Turbine Model
2.1. Squirrel Cage Induction Generator
The fixed speed wind generator systems have been used
with a multiple-stage gearbox and a SCIG directly con-
nected to the grid through a transformer [11].
The well-known advantages of SCIG are it is robust,
easy and relatively cheap for mass production [11], electri-
cally fairly simple devices consisting of an aerodynamic
rotor driving a low-speed shaft, a gearbox, a high-speed
shaft and an induction generator [12].
The gearbox is needed, because the optimal rotor and
generator speed ranges are different, we find also a pole-
changeable SCIG has been used in some commercial wind
turbines; it does not provide continuous speed variations
[11]. The generator is directly grid coupled. Therefore,
rotor speed variations are very small, because the only
speed variations that can occur are changes in the rotor
slip[13], because the operating slip variation is generally
less than 1%, this type of wind generation is normally re-
ferred to as fixed speed [12].
A SCIG consumes reactive power. Therefore, in case of
large wind turbines and/or weak grids, often capacitors are
added to generate the induction generator magnetizing
current, thus improving the power factor of the system as a
whole [13].
The power extracted from the wind needs to be limited,
because otherwise the generator could be overloaded or the
pullout torque could be exceeded, leading to rotor speed
instability. In this concept, this is often done by using the
stall effect. This means that the rotor geometry is designed
in such a way that its aerodynamic properties make the
rotor efficiency decrease in high wind speeds, thus limiting
the power extracted from the wind and preventing the gene-
rator from being damaged and the rotor speed from becom-
ing unstable [13], so the operating condition of a squirrel-
cage induction generator, used in fixed-speed turbines, is
dictated by the mechanical input power and the voltage at
the generator terminals. This type of generator cannot con-
trol bus bar voltages by itself controlling the reactive power
exchange with the network. Additional reactive power
compensation equipment, often fixed shunt-connected
capacitors, is normally fitted [12]; this system concept is
also known as the 'Danish concept' and is depicted in Fig 1
[13].
The slip is generally considered positive in the motor op-
eration mode and negative in the generator mode. In both
operation modes, higher rotor slips result in higher current
in the rotor and higher electromechanical power conversion.
If the machine is operated at slips greater than unity by
turning it backwards, it absorbs power without delivering
anything out i.e. it works as a brake. The power in this case
is converted into I heat loss in the rotor conductor that
needs to be dissipated [14].
Fig. 1 shows the torque-slip characteristic of the induc-
tion machine in the generating mode. If the generator is
loaded at constant load torque only 1 is stable. The
loading limit of the generator i.e. the maximum torque it
can support is called the breakdown torque and represented
in the Fig.1 as If the generator is loaded under a con-
stant torque above , it will become unstable and stall,
draw excessive current and destroy itself thermally if not
properly protected [14].
Figure 1. Torque versus slip characteristic of an induction generator [14].
2.2. Modeling for Fixed - Speed Wind Turbines
The modeling of wind turbine plays an important role in
the building of stability concept. Every research recently
uses grid model, wind turbine model and wind speed model
as a foundation. The specific simulation approach used to
study the dynamics of large power systems is reduced-order
modeling of wind turbine. This model uses several assump-
tions and gives the models the various subsystems of each
of the recent wind turbine types as presents at the Fig.2 [14].
Figure 2. Generator structure of fixed-speed wind turbine model [6].
We use Matlab to modeling the wind turbine system in
two main blocks: rotor model and generator model.
2.2.1. Rotor Model
The traditional rotor model in wind turbine simulation is
base on the well known equation which gives the relation-
ship between the power extracted from wind and wind
speed [14]:
-0.2 -0.6 -0.8 -1-0.4
0
P2P1
Ns Speed
Slip perunit
Tmax
2 Ns
TL Load Torque
52 Bouhadouza Boubekeur et al.: Application of STATCOM to increase transient stability of wind farm
2
).,(
3
wwt
pvpwt
vA
CPCP
ρ
βλ== (1)
Where C is the power coefficient of wind turbine (C is
the function of the blade pitch angle and the tip-speed
ratio); is the air density; is the swept area; is the
wind speed. The tip-speed ratio .is defined as:
v
Rwwt .
=λ (2)
Where w is mechanical angular velocity of wind tur-
bine blades; R is radius of wind turbine blades. The numer-
ical method of C is in Ref [15].
, 0.5176
!!"
#$
% 0.4β % 5( e
*+,
-$ . 0.0068 (3)
Where
01 2
3
045.567
%
5.589
7843
:
;3
(4)
There is always an optimum tip speed ratio λ= corres-
ponding to the maximum power coefficient of wind turbine
C >?@ for any pitch angleβ. The β 0 without considering
wind turbine status at extreme wind speed.
The output torque of wind turbine is [4]:
AB
CDE
(5)
The relation betweenC , β and λ is shown in Fig .3.
Figure 3. Aerodynamic power coefficient variation against tip speed
ratio and pitch angle .
The maximum value of C ( 0.48) is achieved
for 0 degree and for F 8.1.
To extract the maximum power generated, we must fix
the advance report F is the maximum power
cient .
2.2.2.Generator Model
In real wind power market, three types of wind power
system for large WTs exist. The first type is fixed-speed
wind power (SCIG), directly connected to the grid. The
second one is a variable speed wind system using a DFIG
or SCIG. The third type is also a variable speed WT, PMSG
[16].
The IG space vector model is generally composed of
three sets of equations: voltage equations, flux linkage
equations, and motion equation. The voltage equations for
the stator and rotor of the generator in the arbitrary refer-
ence frame are given by [17]:







++=
+−=
qs
s
dsqssqs
ds
s
qsdssds
dt
d
w
iRv
dt
d
w
iRv
ϕϕ
ϕϕ
1
1
(6)







=++=
=+−=
0
1
.
0
1
.
qr
s
drqrrqr
dr
s
qrdrrdr
dt
d
w
siRv
dt
d
w
siRv
ϕϕ
ϕϕ
(7)
The electrical torque is given by this equation after sev-
eral converted steps:
)..( dsqrqsdrme iiiiLT += (8)
J
TT
dt
dw emr −
= (9)
The power flow studies in the IG are represented in
Fig .4 [14].
Figure 4. Power flow and losses in an IG.
3. Statcom
A STATCOM is a controlled reactive-power source. It
provides the desired reactive-power generation and absorp-
tion entirely by means of electronic processing of the vol-
tage and current waveforms in a voltage source converter
(VSC). This function is identical to the synchronous con-
denser with rotating mass, but its response time is extreme-
ly faster than of the synchronous condenser. This rapidity is
very effective to increase transient stability, to enhance
voltage support, and to damp low frequency oscillation for
the transmission system [5].
The schematic representation of the STATCOM and its
equivalent circuit are shown in Fig 5.
Figure 5. STATCOM, VSC connected to the AC network via a shunt
transformer.
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
0
0.1
0.2
0.3
0.4
0.5
0.6
X: 8.1
Y: 0.48
lamda
Cp
B=0°
B=5°
B=10°
B=15°
B=20°
American Journal of Electrical Power and Energy Systems 2013, 2(2): 50-56 53
The STATCOM has the ability to either generate or ab-
sorb reactive power by suitable control of the inverted
voltage|IJK| L MJK, with respect to the AC voltage on the
high-voltage side of the STATCOM transformer, say node
l,| N| L MN.
In an ideal STATCOM, with no active power loss in-
volved, the following reactive power equation yields useful
insight into how the reactive power exchange with the AC
system is achieved.
2
2
cos( )l l vR
vR l vR
vR vR
l l vR
vR
v v v
Q
x x
v v v
x
θ θ= − −
−
=
Where θP θQR for the case of a lossless STATCOM;
If |vP| T |vQR| then QQR becomes positive and the
STATCOM absorbs reactive power. On the other hand, QQR
becomes negative if |vP| L |vQR| and the STATCOM gene-
rates reactive power.
In power flow studies the STATCOM may be
represented in the same way as a synchronous condenser,
which in most cases is the model of a synchronous genera-
tor with zero active power generation. It is adjusts the vol-
tage source magnitude and phase angle using Newton’s
algorithm to satisfy a specified voltage magnitude at the
point of connection with the AC network as presents at the
Fig .5.
)sin*(cos vRvRvRvR jvv θθ +=
It should be pointed out that maximum and minimum
limits will exist for |vQR| which are a function of the
STATCOM. Capacitor rating. On the other hand, θQR can
take any value between 0 and 2π radians but in practice it
will keep close to θP [18].
STATCOM is capable of providing capacitive reactive
power for network with a very low voltage level
near0.15pu. It also is able to generate its maximum capa-
citive power independent of network voltage. This capabili-
ty will be very beneficial in time of a fault or voltage col-
lapse or other restrictive phenomena, as presents at the Fig
6 [10].
Figure 6. Voltage current characteristic of STATCOM.
4. Simulation Results
The proposed test system has a wind farm connected to a
network of 6 bus bars; the type of generators is an IG. Un-
der normal operating conditions, the wind farm provide
9MW, the bank condenser used for offer a reactive power
to the IG ,as presents at the following Fig .7.
Figure 7. Test system.
The first objective of this paper is to evaluate the specific
needs of the system to restore to its initial state as quickly
as possible after fault clearing.
4.1. Without STATCOM
The effect of a three phase short circuit fault at the load
bus is studied. The ground fault is initiated at t 15s and
cleared at t 16s. The system is studied under different
conditions at the load bus as chosen below.
Fig 8 and Fig 9 shows the active and reactive power at
the load bus, we can see the active power curve reached
8.7MW in transient state operation and return near to zero
in the steady state mode even with the presence of the fault,
however we find a peak in the reactive power curve at the
time of the application fault and stabilized at -1Mvar.
Fig 10 and 11 shows the active and reactive power of
each wind turbine.
It is clear according to these results that the active and
reactive power of wind farm are disconnected before the
appearance of fault, because the insufficient of the excita-
tion condenser of generator, and the wind farm protection
systems, however the reactive power gives a negative value
because the presence of the condenser.
Figure 8. Active power at bus 6.
0 5 10 15 20
-2
0
2
4
6
8
10
Temps [S]
lapuissanceactiveaujbB6[mw]
PJB6
54 Bouhadouza Boubekeur et al.: Application of STATCOM to increase transient stability of wind farm
Figure 9. Reactive power at bus 6.
Figure 10. Active power of wind farm.
Figure 11. Reactive power of wind farm.
4.2. With STATACOM
According to the previous simulation results, we added
the STATCOM at bus 6 for view the STATCOM effects.
Fig 12 and 13 shows the active and reactive power at the
load bus, we can note that in the both curves the two pow-
ers also stabilized faster with less oscillation compared with
the preceding case in the transient state and even after the
fault, however fig 14 and 15 shows the active and reactive
power for each wind turbine.
According to the simulation results, the curves presented
above shows the importance of the compensation when the
wind farm recovers its operation after the fault and takes its
stability with some oscillation by the intervention of
STATCOM at bus bar 6.
Figure 12. Active power at bus 6.
Figure 12. Active power at bus 6.
Figure 13. Reactive power at bus 6.
0 5 10 15 20
-2
0
2
4
6
8
10
Temps [S]
lespuissancesréactivesaujbB6[mvar]
QJB6
0 5 10 15 20
-0.5
0
0.5
1
1.5
2
2.5
3
3.5
Temps [S]
lapuissanceactivedewindturbine[mw]
P1
P2
P3
0 5 10 15 20
-1
0
1
2
3
4
5
6
Temps [S]
lapuissanceréactivedewindturbine[mvar]
Q1
Q2
Q3
0 5 10 15 20
-2
0
2
4
6
8
10
12
Temps [S]
lapuissanceactiveaujbB6[mw]
P JB6
0 5 10 15 20
-2
0
2
4
6
8
10
12
14
16
Temps [S]
lespuissancesréactivesaujbB6[mvar]
Q JB6
0 5 10 15 20
-2
0
2
4
6
8
10
12
14
16
Temps [S]
lespuissancesréactivesaujbB6[mvar]
Q JB6
American Journal of Electrical Power and Energy Systems 2013, 2(2): 50-56 55
Figure 14. Active power of Wind Farm.
Figure 15. Reactive power of Wind farm.
4.3. Transient Stability
In this section, the following evaluation index is used to
show the impact of grid-connected wind farms of IG type
on the transient stability test system.
Critical clearance time (CCT) of faults is generally con-
sidered as the best measurement of severity of a contingen-
cy and thus widely used for ranking contingencies in ac-
cordance with their severity; in addition CCT is defined as
the longest allowed fault clearance time without losing
stability [4]. In our studies, the CCT is employed as a tran-
sient stability index to evaluate the test system; we use a
different value of reactive power injecting by a STATCOM
for controller the CCT.
Fig 16 shows CCT for several values of STATCOM, we
illustrate that the relation between the reactive power in-
jecting by a STATCOM and the CCT is nearly a linear.
Figure 16. Critical time for several values of STATCOM.
5. Conclusions
The increasing penetration of renewable energy sources
in the grid, high demands, caused destabilized the electrical
network, so the researchers must be finding and master a
new techniques for produced more power, better quality
and higher reliability at lower cost. In first section a global
description of system was presented, for each its compo-
nent a brief presentation are given, modeled and simulated.
In the second section, the dynamics of the grid-
connected wind farm is compared with and without the
presence of STATCOM under fault, our test network con-
tain three wind farm each wind farm has two equal wind
turbine, according to the simulation results, it clearly illu-
strates the need of STATCOM improvement when the wind
farm recovers its operation after the fault and takes its sta-
bility and do not leave the wind farm disconnect in the
insufficient of the excitation condenser case. In the last
section, a several successive simulation are executed for
understand the relation between the STATCOM dimension
and the CCT.
References
[1] AL. Olimpo, J. Nick, E. Janaka, C. Phill and H Mike, “Wind
Energy Generation Modelling and Control,” John Wiley &
Sons, Ltd 2009.
[2] H. Mellah and K. E. Hemsas, “Design and Analysis of an
External-Rotor Internal-Stator Doubly Fed Induction Gene-
rator for Small Wind Turbine Application by Fem,” Interna-
tional Journal of Renewable and Sustainable Energy. vol. 2,
no. 1, pp. 1-11, 2013.
[3] A. Petersson, "Analysis Modeling and Control of Doubly-
Fed Induction Generators for Wind Turbines,” PhD thesis,
Chalmers university of technology, GOteborg, Sweden 2005.
[4] B .BOUHADOUZA, “Amélioration de la Stabilité
Transitoire des Fermes Eoliennes par l’utilisation des
STATCOM,” magister theses of Setif university, Algeria,
2011.
[5] A. Pahade and N. Saxena, “Transient stability improvement
by using shunt FACT device (STATCOM) with Reference
Voltage Compensation (RVC) control scheme,” International
Journal of Electrical, Electronics and Computer Engineering,
vol. 2, pp.7-12, 2013.
[6] S. Chauhan, V. Chopra, S. Singh, “Transient Stability Im-
provement of Two Machine System using Fuzzy Controlled
STATCOM,” International Journal of Innovative Technolo-
gy and Exploring Engineering, vol. 2,pp. 52-56, March 2013.
[7] V. K. Chandrakar, A. G. Kothari, “Comparison of RBFN
based STATCOM, SSSC and UPFC Controllers for Tran-
sient Stability improvement,” Power Systems Conference
and Exposition, PSCE '06, pp. 784 – 791, IEEE PES 2006.
[8] M. Mohammad Hussaini, R. Anita, "The Study of Dynamic
Performance of Wind Farms with the Application Trends in
Engineering,” International Journal of Recent Trends in En-
gineering, vol. 2, pp. 158-160, 2009
[9] P. Kumkratug, “The Effect of STATCOM on Inter-Area
5 10 15 20
-0.5
0
0.5
1
1.5
2
2.5
3
3.5
4
4.5
Temps [S]
lapuissanceactivedewindturbine[mw]
P1
P2
P3
5 10 15 20
-2
-1
0
1
2
3
4
5
Temps [S]
lapuissanceréactivedewindturbine[mvar]
Q1
Q2
Q3
12 14 16 18 20 22 24
1
1.5
2
2.5
3
3.5
4
4.5
5
5.5
6
Q STATCOM (MVAr)
CCT(msec)
CCT
56 Bouhadouza Boubekeur et al.: Application of STATCOM to increase transient stability of wind farm
Power System Stability Improvement,” IEEE computer so-
ciety conference, Second UKSIM European Symposium on
Computer Modeling and Simulation, pp. 359 – 363, 2008.
[10] X. Zhang, C. Rehtanz and B. Pal, “Flexible AC Transmis-
sion Systems: Modelling and Control,” Publisher: Springer,
2006.
[11] H. Li, Z. Chen, "Overview of different wind generator sys-
tems and their comparisons,” IET, Renewable Power Gener-
ation, vol. 2, pp. 123–138, 2008.
[12] A. Olimpo, J. Nick, E. Janaka, C. Phill and H Mike, “Wind
Energy Generation Modelling and Control, John Wiley &
Sons, Ltd 2009.
[13] J.G. Slootweg, S. de Haan, H. Polinder, W. L. Kling, “Mod-
eling wind turbines in power system dynamics simulations,”
Power Engineering Society Summer Meeting, Vol. 1, pp. 22
– 26, IEEE, 2001.
[14] M. Huong Nguyen, T. K. Saha, “Dynamic simulation for
wind farm in a large power system,” Power Engineering
Conference, AUPEC '08. Australasian Universities, pp. 1 – 6,
IEEE, 2008.
[15] L. Shenghu , L. Zhengkai , H. Xinjie , J. Shusen, “Dynamic
equivalence to induction generators and wind turbines for
power system stability analysis,” 2nd IEEE International
Symposium on Power Electronics for Distributed Genera-
tion Systems (PEDG), pp. 887 – 892, IEEE 2010.
[16] H. Mellah, K. E. Hemsas, “Simulations Analysis with Com-
parative Study of a PMSG Performances for Small WT Ap-
plication by FEM,” International Journal of Energy Engi-
neering, vol.3, no 2, pp. 55-64, 2013.
[17] B. wu, Y. Lang, N. Zargari, S. Kouro, “power conversion
and control of wind energy systems,” IEEE press, wiley,
Canada 2010.
[18] E.Acha, V.G.Agelidis, O.Anaya-lara, T.J.E.Miller, “power
Electronic Control in Electrical Systems", Newnes. A divi-
sion of reed educational and professional publishing ltd,
2002.
[19] M. A. Kamarposhti, M. Alinezhad, “Comparison of SVC
and STATCOM in Static Voltage Stability Margin En-
hancement", International Journal of Electrical Power and
Energy Systems Engineering, 2010.

More Related Content

PDF
G010234652
PDF
Stabilization and Frequency Regulation in Microgrid by Controlling Pitch Angle
PDF
Welcome to International Journal of Engineering Research and Development (IJERD)
PDF
Load Frequency Control of DFIG-isolated and Grid Connected Mode
PDF
Px7301 power electronics for renewable energy systems
PDF
Commanding Doubly-Fed Induction Generator (DFIG) to Decouple Active and React...
PDF
Stability Improvement in Grid Connected Multi Area System using ANFIS Based S...
PDF
The transient stability analysis of wind turbines interconected to grid under...
G010234652
Stabilization and Frequency Regulation in Microgrid by Controlling Pitch Angle
Welcome to International Journal of Engineering Research and Development (IJERD)
Load Frequency Control of DFIG-isolated and Grid Connected Mode
Px7301 power electronics for renewable energy systems
Commanding Doubly-Fed Induction Generator (DFIG) to Decouple Active and React...
Stability Improvement in Grid Connected Multi Area System using ANFIS Based S...
The transient stability analysis of wind turbines interconected to grid under...

What's hot (20)

PPTX
Open-End-Winding Permanent Magnet Synchonous Generator for Wind Energy Conver...
PDF
Online efficiency optimization of IPMSM for electric vehicles
PDF
Comparison of solar based closed loop DC-DC converter using PID and ANN contr...
PDF
Analysis of PMSG in Wind Integration using T Source Inverter with Simple Boos...
PDF
Grid connected pv system using 9 level flying capacitor multilevel inverter
PDF
Cy36602610
PDF
IRJET- Decoupled Control Technique of DFIG with Dual PWM Converters for Wind ...
PDF
Aircraft Electrical Power Generation & Distribution System Units Through an A...
PDF
Ka3617341739
PDF
DFIG control of WECS using indirect matrix converter
PDF
Impacts of Photovoltaic Distributed Generation Location and Size on Distribut...
PDF
Wind-Turbine Asynchronous Generator Synchronous Condenser with Excitation in ...
PDF
Microgrid stability and control modes
PDF
Improving Light-Load Efficiency by Eliminating Interaction Effect in the Grid...
PDF
Advanced Control of Wind Electric Pumping System for Isolated Areas Application
PDF
R36100108
PDF
40220140505006
PDF
An intelligent based fault-tolerant system 2018
PDF
MSPWM Based Implementation of Novel 5-level Inverter with Photovoltaic System
PPTX
Magnitude and frequency control of grid connected doubly fed IG based synchro...
Open-End-Winding Permanent Magnet Synchonous Generator for Wind Energy Conver...
Online efficiency optimization of IPMSM for electric vehicles
Comparison of solar based closed loop DC-DC converter using PID and ANN contr...
Analysis of PMSG in Wind Integration using T Source Inverter with Simple Boos...
Grid connected pv system using 9 level flying capacitor multilevel inverter
Cy36602610
IRJET- Decoupled Control Technique of DFIG with Dual PWM Converters for Wind ...
Aircraft Electrical Power Generation & Distribution System Units Through an A...
Ka3617341739
DFIG control of WECS using indirect matrix converter
Impacts of Photovoltaic Distributed Generation Location and Size on Distribut...
Wind-Turbine Asynchronous Generator Synchronous Condenser with Excitation in ...
Microgrid stability and control modes
Improving Light-Load Efficiency by Eliminating Interaction Effect in the Grid...
Advanced Control of Wind Electric Pumping System for Isolated Areas Application
R36100108
40220140505006
An intelligent based fault-tolerant system 2018
MSPWM Based Implementation of Novel 5-level Inverter with Photovoltaic System
Magnitude and frequency control of grid connected doubly fed IG based synchro...
Ad

Viewers also liked (12)

PDF
APPLICATION OF STATCOM to IMPROVED DYNAMIC PERFORMANCE OF POWER SYSTEM
PDF
Ethical Hacking
DOCX
Biometrics
PPTX
Presentation on ethical hacking
PPTX
Power quality using statcom
PPTX
implementation of statcom and reactive power compensation
PPTX
Reactive power compensation using statcom
PPTX
Enhancement of power quality in distribution system using d statcom
PPTX
POWER QUALITY IMPROVEMENT IN A PV DISTRIBUTION SYSTEM BY USING D-STATCOM
PPTX
statcom
PPT
DOCX
Statcom
APPLICATION OF STATCOM to IMPROVED DYNAMIC PERFORMANCE OF POWER SYSTEM
Ethical Hacking
Biometrics
Presentation on ethical hacking
Power quality using statcom
implementation of statcom and reactive power compensation
Reactive power compensation using statcom
Enhancement of power quality in distribution system using d statcom
POWER QUALITY IMPROVEMENT IN A PV DISTRIBUTION SYSTEM BY USING D-STATCOM
statcom
Statcom
Ad

Similar to Application of statcom to increase transient stability of wind farm (20)

PDF
Ijetr021123
PDF
Dynamic_Analysis_of_Grid_Connected_Wind_Farms_Using_ATP.pdf
PDF
Flc based statcom for a dfig driven wind turbine to enhance voltage stability
PDF
Flc based statcom for a dfig driven wind turbine to enhance voltage stability
PDF
Voltage Stabilization of a Wind Turbine with STATCOM Using Intelligent Contro...
PDF
Voltage stability enhancement for large scale squirrel cage induction generat...
PDF
STATCOM Based Wind Energy System by using Hybrid Fuzzy Logic Controller
PDF
Voltage Compensation in Wind Power System using STATCOM Controlled by Soft Co...
PDF
Performance Improvement of a Grid Connected Wind Farm System
PDF
Integration of a Wind Turbine Based Doubly Fed Induction Generator Using STAT...
PDF
TCSC AND SVC OPTIMAL LOCATION TO IMPROVE THE PERFORMANCE OF POWER SYSTEM WITH...
PPTX
grid power quality improvement and battery energy storage in wind energy systems
PPTX
SPARC_Course_IIT_D_DH_WTG_Modeling_March_2021_VV.pptx
PDF
Review on stability analysis of grid connected wind power generating system1
PDF
Review on stability analysis of grid connected wind power generating system1
PDF
K010516873
PDF
journal publishing, how to publish research paper, Call For research paper, i...
Ijetr021123
Dynamic_Analysis_of_Grid_Connected_Wind_Farms_Using_ATP.pdf
Flc based statcom for a dfig driven wind turbine to enhance voltage stability
Flc based statcom for a dfig driven wind turbine to enhance voltage stability
Voltage Stabilization of a Wind Turbine with STATCOM Using Intelligent Contro...
Voltage stability enhancement for large scale squirrel cage induction generat...
STATCOM Based Wind Energy System by using Hybrid Fuzzy Logic Controller
Voltage Compensation in Wind Power System using STATCOM Controlled by Soft Co...
Performance Improvement of a Grid Connected Wind Farm System
Integration of a Wind Turbine Based Doubly Fed Induction Generator Using STAT...
TCSC AND SVC OPTIMAL LOCATION TO IMPROVE THE PERFORMANCE OF POWER SYSTEM WITH...
grid power quality improvement and battery energy storage in wind energy systems
SPARC_Course_IIT_D_DH_WTG_Modeling_March_2021_VV.pptx
Review on stability analysis of grid connected wind power generating system1
Review on stability analysis of grid connected wind power generating system1
K010516873
journal publishing, how to publish research paper, Call For research paper, i...

More from Mellah Hacene (20)

PDF
1901.08661
PDF
Elk 26-6-32-1711-330
PDF
Commande par gradins d'un convertisseur multiniveau asymétrique à structure c...
PDF
22057 44311-1-pb
PDF
96 manuscript-579-1-10-20210211
PDF
Cascade forward neural network based on resilient backpropagation for simulta...
PDF
Miucc 2021 list_of_reviewers
PDF
2021 miucc committees
PDF
Power transformer faults diagnosis using undestructive methods and ann for dg...
PDF
Adaptive maximum power point tracking using neural networks for a photovoltai...
PDF
International conference on mechanical engineering and applied mechanics[icme...
PDF
MATHEMATICAL MODEL OF WIND TURBINE IN GRID-OFF SYSTEM
PDF
SIMULATION OF A MATHEMATICAL MODEL OF A WIND TURBINE
PPTX
Multiphysics Modeling of Induction Machines_Jd'12 pres
PPTX
4th INTERNATIONAL CONFERENCE ON ELECTRICAL ENGINEERING.,Icee'12
PPTX
7th International Conference on Electrical Engineering 8- 10 October 2012, Ce...
PDF
Stochastic Estimation Methods for Induction Motor Transient Thermal Monitorin...
PDF
Design and analysis of an external rotor internal-stator doubly fed induction...
PDF
الفصل الثالث عمليات في الوندوز
PDF
Article jd2
1901.08661
Elk 26-6-32-1711-330
Commande par gradins d'un convertisseur multiniveau asymétrique à structure c...
22057 44311-1-pb
96 manuscript-579-1-10-20210211
Cascade forward neural network based on resilient backpropagation for simulta...
Miucc 2021 list_of_reviewers
2021 miucc committees
Power transformer faults diagnosis using undestructive methods and ann for dg...
Adaptive maximum power point tracking using neural networks for a photovoltai...
International conference on mechanical engineering and applied mechanics[icme...
MATHEMATICAL MODEL OF WIND TURBINE IN GRID-OFF SYSTEM
SIMULATION OF A MATHEMATICAL MODEL OF A WIND TURBINE
Multiphysics Modeling of Induction Machines_Jd'12 pres
4th INTERNATIONAL CONFERENCE ON ELECTRICAL ENGINEERING.,Icee'12
7th International Conference on Electrical Engineering 8- 10 October 2012, Ce...
Stochastic Estimation Methods for Induction Motor Transient Thermal Monitorin...
Design and analysis of an external rotor internal-stator doubly fed induction...
الفصل الثالث عمليات في الوندوز
Article jd2

Recently uploaded (20)

PDF
The CXO Playbook 2025 – Future-Ready Strategies for C-Suite Leaders Cerebrai...
PDF
keyrequirementskkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkk
PDF
TFEC-4-2020-Design-Guide-for-Timber-Roof-Trusses.pdf
PPTX
Infosys Presentation by1.Riyan Bagwan 2.Samadhan Naiknavare 3.Gaurav Shinde 4...
PPTX
bas. eng. economics group 4 presentation 1.pptx
PDF
Digital Logic Computer Design lecture notes
PPTX
Recipes for Real Time Voice AI WebRTC, SLMs and Open Source Software.pptx
PPTX
CYBER-CRIMES AND SECURITY A guide to understanding
PDF
Mitigating Risks through Effective Management for Enhancing Organizational Pe...
PPT
CRASH COURSE IN ALTERNATIVE PLUMBING CLASS
PDF
BMEC211 - INTRODUCTION TO MECHATRONICS-1.pdf
PDF
Enhancing Cyber Defense Against Zero-Day Attacks using Ensemble Neural Networks
PDF
Embodied AI: Ushering in the Next Era of Intelligent Systems
PDF
Well-logging-methods_new................
PPTX
UNIT-1 - COAL BASED THERMAL POWER PLANTS
PPTX
web development for engineering and engineering
PDF
Model Code of Practice - Construction Work - 21102022 .pdf
PPTX
IOT PPTs Week 10 Lecture Material.pptx of NPTEL Smart Cities contd
PPTX
FINAL REVIEW FOR COPD DIANOSIS FOR PULMONARY DISEASE.pptx
PPTX
OOP with Java - Java Introduction (Basics)
The CXO Playbook 2025 – Future-Ready Strategies for C-Suite Leaders Cerebrai...
keyrequirementskkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkk
TFEC-4-2020-Design-Guide-for-Timber-Roof-Trusses.pdf
Infosys Presentation by1.Riyan Bagwan 2.Samadhan Naiknavare 3.Gaurav Shinde 4...
bas. eng. economics group 4 presentation 1.pptx
Digital Logic Computer Design lecture notes
Recipes for Real Time Voice AI WebRTC, SLMs and Open Source Software.pptx
CYBER-CRIMES AND SECURITY A guide to understanding
Mitigating Risks through Effective Management for Enhancing Organizational Pe...
CRASH COURSE IN ALTERNATIVE PLUMBING CLASS
BMEC211 - INTRODUCTION TO MECHATRONICS-1.pdf
Enhancing Cyber Defense Against Zero-Day Attacks using Ensemble Neural Networks
Embodied AI: Ushering in the Next Era of Intelligent Systems
Well-logging-methods_new................
UNIT-1 - COAL BASED THERMAL POWER PLANTS
web development for engineering and engineering
Model Code of Practice - Construction Work - 21102022 .pdf
IOT PPTs Week 10 Lecture Material.pptx of NPTEL Smart Cities contd
FINAL REVIEW FOR COPD DIANOSIS FOR PULMONARY DISEASE.pptx
OOP with Java - Java Introduction (Basics)

Application of statcom to increase transient stability of wind farm

  • 1. American Journal of Electrical Power and Energy Systems 2013; 2(2): 50-56 Published online March 10, 2013 (http://www.sciencepublishinggroup.com/j/epes) doi: 10.11648/j.epes.20130202.14 Application of STATCOM to increase transient stability of wind farm Bouhadouza Boubekeur, Ahmed Gherbi, Hacene Mellah Department of Electrical Engineering, Sétif-1 University, Algeria Email address: bouhadouza_b@yahoo.fr (B. Bouhadouza), gherbi_a@yahoo.fr (A. Gherbi), has.mel@gmail.com (H. Mellah) To cite this article: Bouhadouza Boubekeur, Ahmed Gherbi, Hacene Mellah. Application of STATCOM to Increase Transient Stability of Wind Farm, American Journal of Electrical Power and Energy Systems. Vol. 2, No. 2, 2013, pp. 50-56. doi: 10.11648/j.epes.20130202.14 Abstract: In this paper we interested to the study the necessary of Facts to increase the transient stability on the presence of faults and the integration of new renewable source, like wind energy, these lasts make the electrical grid operate in a new conditions, the STATCOM is one of the important Facts element, It provides the desired reactive-power generation and absorption entirely by means of electronic processing of the voltage and current waveforms in a voltage source converter (VSC). This function is identical to the synchronous condenser with rotating mass. In present work we propose a transient stability improvement using STATCOM under faults, in the first time we study the transient stability with and without STATCOM for clearly his advantages. In the second time we know the relation between the reactive power injecting by a STATCOM and the critical clearing time, some simulation results are given, commented and discussed. Keywords: Transient Stability, Reactive Power, FACTS, STATCOM, Wind Power, CCT 1. Introduction There is now general acceptance that the burning of fos- sil fuels is having a significant influence on the global cli- mate. Effective mitigation of climate change will require deep reductions in greenhouse gas emissions, with UK estimates of a 60–80% cut being necessary by 2050 [1], Still purer with the nuclear power, this last leaves behind dangerous wastes for thousands of years and risks contami- nation of land, air, and water; the catastrophe of Japan is not far[2], to avoid the problems of the pollution, the ener- gy policy decision states that the objective is to facilitate a change to an ecologically sustainable energy production system such as wind power [3], but the major problem is how associate the wind power stations to the grid with assure the linking conditions[4]. In addition, now a day’s power transmission and distribution systems face increas- ing demands for more power, better quality and higher reliability at lower cost, as well as low environmental effect. Under these conditions, transmission networks are called upon to operate at high transmission levels, and thus power engineers have had to confront some major operating prob- lems such as transient stability, damping of oscillations and voltage regulation etc [5], in this work we interest to the transient stability, this last indicates the capability of the power system to maintain synchronism when subjected to a severe transient disturbances such as fault on heavily loaded lines, loss of a large load etc [6].Generator excita- tion controller with only excitation control can improve transient stability for minor faults but it is not sufficient to maintain stability of system for large faults occur near to generator terminals [6]. Researchers worked on other solu- tion and found that flexible AC transmission systems (FACTS) are one of the most prominent solution [7], [8]. The objective principal to use FACTS technology for the operators of the electric power is to have an opportunity for the control of the power flow and by increasing the capaci- ties usable of these lines under the normal conditions. The parameter which controls the operation of transmission of energy in a line such as the impedances series and shunts, running, tension and phase angle is controlled by utilizing FACTS controllers. FACTS devices increases power han- dling capacity of the line and improve transient stability as well as damping performance of the power system [7], [8]. According to the specialized literature we find several types of FACTS [6-11], in our work we are limited to the study a great disturbance, so the FACTS element used for reactive power compensation both assuring the low cost and high efficiency is STATCOM. The static synchronous compensators (STATCOM) con- sist of shunt connected voltage source converter through coupling transformer with the transmission line. STAT-
  • 2. American Journal of Electrical Power and Energy Systems 2013, 2(2): 50-56 51 COM can control voltage magnitude and, to a small extent, the phase angle in a very short time and therefore, has abili- ty to improve the system [7], [8]. 2. Wind Turbine Model 2.1. Squirrel Cage Induction Generator The fixed speed wind generator systems have been used with a multiple-stage gearbox and a SCIG directly con- nected to the grid through a transformer [11]. The well-known advantages of SCIG are it is robust, easy and relatively cheap for mass production [11], electri- cally fairly simple devices consisting of an aerodynamic rotor driving a low-speed shaft, a gearbox, a high-speed shaft and an induction generator [12]. The gearbox is needed, because the optimal rotor and generator speed ranges are different, we find also a pole- changeable SCIG has been used in some commercial wind turbines; it does not provide continuous speed variations [11]. The generator is directly grid coupled. Therefore, rotor speed variations are very small, because the only speed variations that can occur are changes in the rotor slip[13], because the operating slip variation is generally less than 1%, this type of wind generation is normally re- ferred to as fixed speed [12]. A SCIG consumes reactive power. Therefore, in case of large wind turbines and/or weak grids, often capacitors are added to generate the induction generator magnetizing current, thus improving the power factor of the system as a whole [13]. The power extracted from the wind needs to be limited, because otherwise the generator could be overloaded or the pullout torque could be exceeded, leading to rotor speed instability. In this concept, this is often done by using the stall effect. This means that the rotor geometry is designed in such a way that its aerodynamic properties make the rotor efficiency decrease in high wind speeds, thus limiting the power extracted from the wind and preventing the gene- rator from being damaged and the rotor speed from becom- ing unstable [13], so the operating condition of a squirrel- cage induction generator, used in fixed-speed turbines, is dictated by the mechanical input power and the voltage at the generator terminals. This type of generator cannot con- trol bus bar voltages by itself controlling the reactive power exchange with the network. Additional reactive power compensation equipment, often fixed shunt-connected capacitors, is normally fitted [12]; this system concept is also known as the 'Danish concept' and is depicted in Fig 1 [13]. The slip is generally considered positive in the motor op- eration mode and negative in the generator mode. In both operation modes, higher rotor slips result in higher current in the rotor and higher electromechanical power conversion. If the machine is operated at slips greater than unity by turning it backwards, it absorbs power without delivering anything out i.e. it works as a brake. The power in this case is converted into I heat loss in the rotor conductor that needs to be dissipated [14]. Fig. 1 shows the torque-slip characteristic of the induc- tion machine in the generating mode. If the generator is loaded at constant load torque only 1 is stable. The loading limit of the generator i.e. the maximum torque it can support is called the breakdown torque and represented in the Fig.1 as If the generator is loaded under a con- stant torque above , it will become unstable and stall, draw excessive current and destroy itself thermally if not properly protected [14]. Figure 1. Torque versus slip characteristic of an induction generator [14]. 2.2. Modeling for Fixed - Speed Wind Turbines The modeling of wind turbine plays an important role in the building of stability concept. Every research recently uses grid model, wind turbine model and wind speed model as a foundation. The specific simulation approach used to study the dynamics of large power systems is reduced-order modeling of wind turbine. This model uses several assump- tions and gives the models the various subsystems of each of the recent wind turbine types as presents at the Fig.2 [14]. Figure 2. Generator structure of fixed-speed wind turbine model [6]. We use Matlab to modeling the wind turbine system in two main blocks: rotor model and generator model. 2.2.1. Rotor Model The traditional rotor model in wind turbine simulation is base on the well known equation which gives the relation- ship between the power extracted from wind and wind speed [14]: -0.2 -0.6 -0.8 -1-0.4 0 P2P1 Ns Speed Slip perunit Tmax 2 Ns TL Load Torque
  • 3. 52 Bouhadouza Boubekeur et al.: Application of STATCOM to increase transient stability of wind farm 2 ).,( 3 wwt pvpwt vA CPCP ρ βλ== (1) Where C is the power coefficient of wind turbine (C is the function of the blade pitch angle and the tip-speed ratio); is the air density; is the swept area; is the wind speed. The tip-speed ratio .is defined as: v Rwwt . =λ (2) Where w is mechanical angular velocity of wind tur- bine blades; R is radius of wind turbine blades. The numer- ical method of C is in Ref [15]. , 0.5176 !!" #$ % 0.4β % 5( e *+, -$ . 0.0068 (3) Where 01 2 3 045.567 % 5.589 7843 : ;3 (4) There is always an optimum tip speed ratio λ= corres- ponding to the maximum power coefficient of wind turbine C >?@ for any pitch angleβ. The β 0 without considering wind turbine status at extreme wind speed. The output torque of wind turbine is [4]: AB CDE (5) The relation betweenC , β and λ is shown in Fig .3. Figure 3. Aerodynamic power coefficient variation against tip speed ratio and pitch angle . The maximum value of C ( 0.48) is achieved for 0 degree and for F 8.1. To extract the maximum power generated, we must fix the advance report F is the maximum power cient . 2.2.2.Generator Model In real wind power market, three types of wind power system for large WTs exist. The first type is fixed-speed wind power (SCIG), directly connected to the grid. The second one is a variable speed wind system using a DFIG or SCIG. The third type is also a variable speed WT, PMSG [16]. The IG space vector model is generally composed of three sets of equations: voltage equations, flux linkage equations, and motion equation. The voltage equations for the stator and rotor of the generator in the arbitrary refer- ence frame are given by [17]:        ++= +−= qs s dsqssqs ds s qsdssds dt d w iRv dt d w iRv ϕϕ ϕϕ 1 1 (6)        =++= =+−= 0 1 . 0 1 . qr s drqrrqr dr s qrdrrdr dt d w siRv dt d w siRv ϕϕ ϕϕ (7) The electrical torque is given by this equation after sev- eral converted steps: )..( dsqrqsdrme iiiiLT += (8) J TT dt dw emr − = (9) The power flow studies in the IG are represented in Fig .4 [14]. Figure 4. Power flow and losses in an IG. 3. Statcom A STATCOM is a controlled reactive-power source. It provides the desired reactive-power generation and absorp- tion entirely by means of electronic processing of the vol- tage and current waveforms in a voltage source converter (VSC). This function is identical to the synchronous con- denser with rotating mass, but its response time is extreme- ly faster than of the synchronous condenser. This rapidity is very effective to increase transient stability, to enhance voltage support, and to damp low frequency oscillation for the transmission system [5]. The schematic representation of the STATCOM and its equivalent circuit are shown in Fig 5. Figure 5. STATCOM, VSC connected to the AC network via a shunt transformer. 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 0 0.1 0.2 0.3 0.4 0.5 0.6 X: 8.1 Y: 0.48 lamda Cp B=0° B=5° B=10° B=15° B=20°
  • 4. American Journal of Electrical Power and Energy Systems 2013, 2(2): 50-56 53 The STATCOM has the ability to either generate or ab- sorb reactive power by suitable control of the inverted voltage|IJK| L MJK, with respect to the AC voltage on the high-voltage side of the STATCOM transformer, say node l,| N| L MN. In an ideal STATCOM, with no active power loss in- volved, the following reactive power equation yields useful insight into how the reactive power exchange with the AC system is achieved. 2 2 cos( )l l vR vR l vR vR vR l l vR vR v v v Q x x v v v x θ θ= − − − = Where θP θQR for the case of a lossless STATCOM; If |vP| T |vQR| then QQR becomes positive and the STATCOM absorbs reactive power. On the other hand, QQR becomes negative if |vP| L |vQR| and the STATCOM gene- rates reactive power. In power flow studies the STATCOM may be represented in the same way as a synchronous condenser, which in most cases is the model of a synchronous genera- tor with zero active power generation. It is adjusts the vol- tage source magnitude and phase angle using Newton’s algorithm to satisfy a specified voltage magnitude at the point of connection with the AC network as presents at the Fig .5. )sin*(cos vRvRvRvR jvv θθ += It should be pointed out that maximum and minimum limits will exist for |vQR| which are a function of the STATCOM. Capacitor rating. On the other hand, θQR can take any value between 0 and 2π radians but in practice it will keep close to θP [18]. STATCOM is capable of providing capacitive reactive power for network with a very low voltage level near0.15pu. It also is able to generate its maximum capa- citive power independent of network voltage. This capabili- ty will be very beneficial in time of a fault or voltage col- lapse or other restrictive phenomena, as presents at the Fig 6 [10]. Figure 6. Voltage current characteristic of STATCOM. 4. Simulation Results The proposed test system has a wind farm connected to a network of 6 bus bars; the type of generators is an IG. Un- der normal operating conditions, the wind farm provide 9MW, the bank condenser used for offer a reactive power to the IG ,as presents at the following Fig .7. Figure 7. Test system. The first objective of this paper is to evaluate the specific needs of the system to restore to its initial state as quickly as possible after fault clearing. 4.1. Without STATCOM The effect of a three phase short circuit fault at the load bus is studied. The ground fault is initiated at t 15s and cleared at t 16s. The system is studied under different conditions at the load bus as chosen below. Fig 8 and Fig 9 shows the active and reactive power at the load bus, we can see the active power curve reached 8.7MW in transient state operation and return near to zero in the steady state mode even with the presence of the fault, however we find a peak in the reactive power curve at the time of the application fault and stabilized at -1Mvar. Fig 10 and 11 shows the active and reactive power of each wind turbine. It is clear according to these results that the active and reactive power of wind farm are disconnected before the appearance of fault, because the insufficient of the excita- tion condenser of generator, and the wind farm protection systems, however the reactive power gives a negative value because the presence of the condenser. Figure 8. Active power at bus 6. 0 5 10 15 20 -2 0 2 4 6 8 10 Temps [S] lapuissanceactiveaujbB6[mw] PJB6
  • 5. 54 Bouhadouza Boubekeur et al.: Application of STATCOM to increase transient stability of wind farm Figure 9. Reactive power at bus 6. Figure 10. Active power of wind farm. Figure 11. Reactive power of wind farm. 4.2. With STATACOM According to the previous simulation results, we added the STATCOM at bus 6 for view the STATCOM effects. Fig 12 and 13 shows the active and reactive power at the load bus, we can note that in the both curves the two pow- ers also stabilized faster with less oscillation compared with the preceding case in the transient state and even after the fault, however fig 14 and 15 shows the active and reactive power for each wind turbine. According to the simulation results, the curves presented above shows the importance of the compensation when the wind farm recovers its operation after the fault and takes its stability with some oscillation by the intervention of STATCOM at bus bar 6. Figure 12. Active power at bus 6. Figure 12. Active power at bus 6. Figure 13. Reactive power at bus 6. 0 5 10 15 20 -2 0 2 4 6 8 10 Temps [S] lespuissancesréactivesaujbB6[mvar] QJB6 0 5 10 15 20 -0.5 0 0.5 1 1.5 2 2.5 3 3.5 Temps [S] lapuissanceactivedewindturbine[mw] P1 P2 P3 0 5 10 15 20 -1 0 1 2 3 4 5 6 Temps [S] lapuissanceréactivedewindturbine[mvar] Q1 Q2 Q3 0 5 10 15 20 -2 0 2 4 6 8 10 12 Temps [S] lapuissanceactiveaujbB6[mw] P JB6 0 5 10 15 20 -2 0 2 4 6 8 10 12 14 16 Temps [S] lespuissancesréactivesaujbB6[mvar] Q JB6 0 5 10 15 20 -2 0 2 4 6 8 10 12 14 16 Temps [S] lespuissancesréactivesaujbB6[mvar] Q JB6
  • 6. American Journal of Electrical Power and Energy Systems 2013, 2(2): 50-56 55 Figure 14. Active power of Wind Farm. Figure 15. Reactive power of Wind farm. 4.3. Transient Stability In this section, the following evaluation index is used to show the impact of grid-connected wind farms of IG type on the transient stability test system. Critical clearance time (CCT) of faults is generally con- sidered as the best measurement of severity of a contingen- cy and thus widely used for ranking contingencies in ac- cordance with their severity; in addition CCT is defined as the longest allowed fault clearance time without losing stability [4]. In our studies, the CCT is employed as a tran- sient stability index to evaluate the test system; we use a different value of reactive power injecting by a STATCOM for controller the CCT. Fig 16 shows CCT for several values of STATCOM, we illustrate that the relation between the reactive power in- jecting by a STATCOM and the CCT is nearly a linear. Figure 16. Critical time for several values of STATCOM. 5. Conclusions The increasing penetration of renewable energy sources in the grid, high demands, caused destabilized the electrical network, so the researchers must be finding and master a new techniques for produced more power, better quality and higher reliability at lower cost. In first section a global description of system was presented, for each its compo- nent a brief presentation are given, modeled and simulated. In the second section, the dynamics of the grid- connected wind farm is compared with and without the presence of STATCOM under fault, our test network con- tain three wind farm each wind farm has two equal wind turbine, according to the simulation results, it clearly illu- strates the need of STATCOM improvement when the wind farm recovers its operation after the fault and takes its sta- bility and do not leave the wind farm disconnect in the insufficient of the excitation condenser case. In the last section, a several successive simulation are executed for understand the relation between the STATCOM dimension and the CCT. References [1] AL. Olimpo, J. Nick, E. Janaka, C. Phill and H Mike, “Wind Energy Generation Modelling and Control,” John Wiley & Sons, Ltd 2009. [2] H. Mellah and K. E. Hemsas, “Design and Analysis of an External-Rotor Internal-Stator Doubly Fed Induction Gene- rator for Small Wind Turbine Application by Fem,” Interna- tional Journal of Renewable and Sustainable Energy. vol. 2, no. 1, pp. 1-11, 2013. [3] A. Petersson, "Analysis Modeling and Control of Doubly- Fed Induction Generators for Wind Turbines,” PhD thesis, Chalmers university of technology, GOteborg, Sweden 2005. [4] B .BOUHADOUZA, “Amélioration de la Stabilité Transitoire des Fermes Eoliennes par l’utilisation des STATCOM,” magister theses of Setif university, Algeria, 2011. [5] A. Pahade and N. Saxena, “Transient stability improvement by using shunt FACT device (STATCOM) with Reference Voltage Compensation (RVC) control scheme,” International Journal of Electrical, Electronics and Computer Engineering, vol. 2, pp.7-12, 2013. [6] S. Chauhan, V. Chopra, S. Singh, “Transient Stability Im- provement of Two Machine System using Fuzzy Controlled STATCOM,” International Journal of Innovative Technolo- gy and Exploring Engineering, vol. 2,pp. 52-56, March 2013. [7] V. K. Chandrakar, A. G. Kothari, “Comparison of RBFN based STATCOM, SSSC and UPFC Controllers for Tran- sient Stability improvement,” Power Systems Conference and Exposition, PSCE '06, pp. 784 – 791, IEEE PES 2006. [8] M. Mohammad Hussaini, R. Anita, "The Study of Dynamic Performance of Wind Farms with the Application Trends in Engineering,” International Journal of Recent Trends in En- gineering, vol. 2, pp. 158-160, 2009 [9] P. Kumkratug, “The Effect of STATCOM on Inter-Area 5 10 15 20 -0.5 0 0.5 1 1.5 2 2.5 3 3.5 4 4.5 Temps [S] lapuissanceactivedewindturbine[mw] P1 P2 P3 5 10 15 20 -2 -1 0 1 2 3 4 5 Temps [S] lapuissanceréactivedewindturbine[mvar] Q1 Q2 Q3 12 14 16 18 20 22 24 1 1.5 2 2.5 3 3.5 4 4.5 5 5.5 6 Q STATCOM (MVAr) CCT(msec) CCT
  • 7. 56 Bouhadouza Boubekeur et al.: Application of STATCOM to increase transient stability of wind farm Power System Stability Improvement,” IEEE computer so- ciety conference, Second UKSIM European Symposium on Computer Modeling and Simulation, pp. 359 – 363, 2008. [10] X. Zhang, C. Rehtanz and B. Pal, “Flexible AC Transmis- sion Systems: Modelling and Control,” Publisher: Springer, 2006. [11] H. Li, Z. Chen, "Overview of different wind generator sys- tems and their comparisons,” IET, Renewable Power Gener- ation, vol. 2, pp. 123–138, 2008. [12] A. Olimpo, J. Nick, E. Janaka, C. Phill and H Mike, “Wind Energy Generation Modelling and Control, John Wiley & Sons, Ltd 2009. [13] J.G. Slootweg, S. de Haan, H. Polinder, W. L. Kling, “Mod- eling wind turbines in power system dynamics simulations,” Power Engineering Society Summer Meeting, Vol. 1, pp. 22 – 26, IEEE, 2001. [14] M. Huong Nguyen, T. K. Saha, “Dynamic simulation for wind farm in a large power system,” Power Engineering Conference, AUPEC '08. Australasian Universities, pp. 1 – 6, IEEE, 2008. [15] L. Shenghu , L. Zhengkai , H. Xinjie , J. Shusen, “Dynamic equivalence to induction generators and wind turbines for power system stability analysis,” 2nd IEEE International Symposium on Power Electronics for Distributed Genera- tion Systems (PEDG), pp. 887 – 892, IEEE 2010. [16] H. Mellah, K. E. Hemsas, “Simulations Analysis with Com- parative Study of a PMSG Performances for Small WT Ap- plication by FEM,” International Journal of Energy Engi- neering, vol.3, no 2, pp. 55-64, 2013. [17] B. wu, Y. Lang, N. Zargari, S. Kouro, “power conversion and control of wind energy systems,” IEEE press, wiley, Canada 2010. [18] E.Acha, V.G.Agelidis, O.Anaya-lara, T.J.E.Miller, “power Electronic Control in Electrical Systems", Newnes. A divi- sion of reed educational and professional publishing ltd, 2002. [19] M. A. Kamarposhti, M. Alinezhad, “Comparison of SVC and STATCOM in Static Voltage Stability Margin En- hancement", International Journal of Electrical Power and Energy Systems Engineering, 2010.