SlideShare a Scribd company logo
AIR CONDITIONING and VENTILATION SYSTEMS
NME 515
Heating, Ventilating, and Air
Conditioning
ANALYSIS and DESIGN
Engr. Charlton Inao, ME
TESDA TVET NC Level 3 RAC-CRE Certified
17/19/2020 Eng Charlton Inao
Space Heat Load
Engr. Charlton Inao, ME
TESDA TVET NC Level 3 RAC-
CRE Certified
2
Reference: Heating, Ventilating, and Air Conditioning
ANALYSIS and DESIGN by FC Mc Quiston and JD Parker
7/19/2020 Eng Charlton Inao
Space Heat Load
3
There are two kinds of heat losses: (1) the heat
transmitted through the walls, ceiling, floor, glass, or
other surfaces and (2) the heat required to warm
outdoor air entering the space. Transient analyses are
often used to study the actual energy requirements of a
structure in simulation studies. In such cases solar
effects and internal heat gains are taken into account.
7/19/2020 Eng Charlton Inao
7-1 OUTDOOR DESIGN CONDITIONS
4
The outdoor design temperature should generally be
the 97
1
2
percent value as specified by ASHRAE Energy
Standards. If the structure is of lightweight construction
(low heat capacity), is poorly insulated. or has
considerable glass or space temperature control is
critical, however, the 99 percent values should be
considered. The designer must remember that should
the outdoor temperature fall below the design value for
some extended period, the indoor temperature may do
likewise.
7/19/2020 Eng Charlton Inao
7-2 INDOOR DESIGN CONDITIONS
5
The indoor design temperature should be kept relatively
low so that the heating equipment will not be oversized.
A design temperature of 70 F or 22 C is commonly used
with relative humidity less than or equal to 30 percent.
7/19/2020 Eng Charlton Inao
7-2 INDOOR DESIGN CONDITIONS
6
Even properly sized equipment operates under partial
load. at reduced efficiency, most of the time; therefore,
any oversizing aggravates this condition and lowers the
overall system efficiency. The temperature in an
unheated space is needed to compute· the heat loss
and may be estimated by assuming steady-state heat
transfer and making an energy balance on the space.
7/19/2020 Eng Charlton Inao
7-2 INDOOR DESIGN CONDITIONS
7
EXAMPLE 7-1
Estimate the temperature in the crawl space of Fig. 7-1.
The conductance for the floor is 0.20 Btu/(hr-ft2-F)
including the air film on each side. The conductance for
the foundation wall including the insulation and inside
and outside air film resistances is 0.12 Btu/(hr-ft2-F).
Assume an indoor temperature of 70 F and an outdoor
temperature of 10 Fat a location where the degree days
are about 3000. The building dimensions are 50 × 75 ft.
7/19/2020 Eng Charlton Inao
7-2 INDOOR DESIGN CONDITIONS
87/19/2020 Eng Charlton Inao
7-2 INDOOR DESIGN CONDITIONS
9
SOLUTION
The first step is to make an energy balance on the crawl
space. Heat will be gained through the floor and heat
will be lost through the foundation wall and through the
ground around the perimeter much like a floor slab.
7/19/2020 Eng Charlton Inao
7-2 INDOOR DESIGN CONDITIONS
10
SOLUTION
Infiltration of outdoor air will also represent a heat loss
but that will be neglected in this example.
7/19/2020 Eng Charlton Inao
7-2 INDOOR DESIGN CONDITIONS
117/19/2020 Eng Charlton Inao
7-2 INDOOR DESIGN CONDITIONS
12
Now the area of the floor is 50 × 75 = 3750 ft2 and
assuming that the foundation wall averages a height of
2 ft, the area of the foundation wall is 2 (2 × 50) + (2
× 75) = 500 ft2. The perimeter of the building is (2 ×
50) + (2 × 75) = 250 ft. Referring to Table 5-12, the
heat-loss coefficient is estimated to be 0.8 Btu/(hr-ft-F).
Then
7/19/2020 Eng Charlton Inao
7-2 INDOOR DESIGN CONDITIONS
13
Now the area of the floor is 50 × 75 = 3750 ft2 and
assuming that the foundation wall averages a height of
2 ft, the area of the foundation wall is 2 (2 × 50) + (2
× 75) = 500 ft2. The perimeter of the building is (2 ×
50) + (2 × 75) = 250 ft. Referring to Table 5-12, the
heat-loss coefficient is estimated to be 0.8 Btu/(hr-ft-F).
Then
7/19/2020 Eng Charlton Inao
7-2 INDOOR DESIGN CONDITIONS
14
If the infiltration had been considered, the crawl-space
temperature would be lower. Many crawl spaces are
ventilated to prevent moisture problems. and infiltration
would be significant even when the vents are closed.
7/19/2020 Eng Charlton Inao
7-2 INDOOR DESIGN CONDITIONS
15
EXAMPLE 7-2
Estimate the temperature in the unheated room shown
in Fig. 7-2. The structure is built on a slab. The exterior
walls of the unheated room have an- overall heat-
transfer coefficient- of 0.2 Btu/(hr-ft2-F), the ceiling-
attic-roof combination has an overall coefficient of 0.07
Btu/(hr-ft2-F), and the interior walls have an overall
coefficient of 0.06 Btu/(hr-ft2-F). Inside and outdoor
design temperatures are 72 F and - 5 F, respectively.
7/19/2020 Eng Charlton Inao
7-2 INDOOR DESIGN CONDITIONS
16
SOLUTION
The heat transferred from the heated to the unheated
room has a single path, neglecting the door, and may
be represented as
7/19/2020 Eng Charlton Inao
7-2 INDOOR DESIGN CONDITIONS
17
SOLUTION
The heat transferred from the unheated room to the
outdoor air has parallel paths through the ceiling and
walls (neglecting the door and floor):
7/19/2020 Eng Charlton Inao
7-2 INDOOR DESIGN CONDITIONS
18
SOLUTION
The heat loss to the floor can be neglected because of
the anticipated low temperature in the room. Equation
7-2 may be written
where
7/19/2020 Eng Charlton Inao
7-2 INDOOR DESIGN CONDITIONS
197/19/2020 Eng Charlton Inao
7-2 INDOOR DESIGN CONDITIONS
20
By combining Eqs. 7-1 and 7-3. we obtain
7/19/2020 Eng Charlton Inao
7-2 INDOOR DESIGN CONDITIONS
21
Then from Eq. 7-6
The assumption of negligible heat transfer through the
slab is justified by the result.
7/19/2020 Eng Charlton Inao
7-3 TRANSMISSION HEAT LOSSES
22
The heat transferred through walls, ceiling, roof,
window glass, floors, and doors is all sensible heat
transfer, referred to as transmission heat loss and
computed from
7/19/2020 Eng Charlton Inao
7-4 INFILTRATION
23
All structures have some air leakage or infiltration. This
means a heat loss because the cold dry outdoor air
must be heated to the inside design temperature and
moisture must be added to increase the humidity to the
design value. The sensible heat required (to increase
the temperature) is given by
7/19/2020 Eng Charlton Inao
7-4 INFILTRATION
24
Infiltration is usually estimated on the basis of volume
flow rate at outdoor conditions. Equation 7-8 then
becomes
7/19/2020 Eng Charlton Inao
7-4 INFILTRATION
25
The latent heat required to humidify the air is given by
7/19/2020 Eng Charlton Inao
7-4 INFILTRATION
26
In terms of volume flow rate of air, Eq. 7-9 becomes
7/19/2020 Eng Charlton Inao
7-4 INFILTRATION
27
Various methods are used in estimating air infiltration in
building structures. In one method the estimate is
based on the characteristics of the windows, walls, and
doors and the pressure difference between inside and
outside. This is known as the crack method because of
the cracks around window sash and doors. The other
approach is the air-change method which is based on
an assumed number of air changes per hour based on
experience.
7/19/2020 Eng Charlton Inao
Air-change Method
28
Experienced engineers will often simply make an
assumption of the number of air-changes per hour
(ACH) that a building will experience based on their
appraisal of the building type, construction, and use.
The range will usually be from 0.5 ACH (very low) to
2.0 ACH (very high). The infiltration rate is related to
ACH and space volume as follows:
7/19/2020 Eng Charlton Inao
Air-change Method
297/19/2020 Eng Charlton Inao
Crack Method
30
Outdoor air infiltrates the indoor space through cracks
around doors, windows, lighting fixtures, and joints
between walls and floor and even through the building
material itself.
7/19/2020 Eng Charlton Inao
Crack Method
31
The pressure difference of Eq. 7-11 results from three
different effects:
All of the pressure differences are positive when each
causes flow of air to the inside of the building.
7/19/2020 Eng Charlton Inao
Crack Method
327/19/2020 Eng Charlton Inao
Crack Method
33
The pressure difference due to the wind results from an
increase or decrease in air velocity and is described by
7/19/2020 Eng Charlton Inao
Crack Method
347/19/2020 Eng Charlton Inao
Crack Method
35
Finally, Eq. 7-13a may be written
7/19/2020 Eng Charlton Inao
Crack Method
367/19/2020 Eng Charlton Inao
Crack Method
37
When larger openings predominate in the lower
portion of the building, the neutral pressure
level will be lowered., Similarly, the neutral
pressure level will be raised by larger openings
in the upper portion of the building. Normally
the larger openings will occur in the lower part
of the building because of doors.
7/19/2020 Eng Charlton Inao
Crack Method
38
The theoretical pressure difference with no internal
separations is given by
7/19/2020 Eng Charlton Inao
Crack Method
39
The floors in a conventional building offer resistance to
vertical air flow. Furthermore, this resistance varies
depending on how stairwells and elevator shafts are
sealed. When the resistance can be assumed equal for
each floor, a single correction, called the draft
coefficient, can be used to relate the actual pressure
difference ∆Ps, to the theoretical value ∆Pst:
7/19/2020 Eng Charlton Inao
Crack Method
40
The flow of air from floor to floor causes a decrease in
pressure at each floor; therefore, ∆Ps will be less than
∆Pst and Cd is less than one. Using the draft coefficient,
Eq. 7-15 becomes
7/19/2020 Eng Charlton Inao
Crack Method
417/19/2020 Eng Charlton Inao
Crack
Method
427/19/2020 Eng Charlton Inao
Crack
Method
437/19/2020 Eng Charlton Inao
• Calculation Aids
44
The use of storm sash and storm doors is common. The
addition of a storm sash with crack length and a K value
equal to the prime window reduces infiltration by about
35 percent.
7/19/2020 Eng Charlton Inao
• Calculation Aids
45
Single-bank doors open directly into the space;
however, there may be two or more doors at one
location.
Vestibule-type doors are best characterized as two
doors in series so as to form an air lock between them.
These doors often appear as two pairs of doors in
series, which amounts to two vestibule-type doors.
7/19/2020 Eng Charlton Inao
• Calculation Aids
467/19/2020 Eng Charlton Inao
• Calculation Aids
477/19/2020 Eng Charlton Inao
• Calculation Aids
487/19/2020 Eng Charlton Inao
• Calculation Aids
497/19/2020 Eng Charlton Inao
• Calculation Aids
507/19/2020 Eng Charlton Inao
• Calculation Aids
517/19/2020 Eng Charlton Inao
• Calculation Aids
527/19/2020 Eng Charlton Inao
• Calculation Aids
53
EXAMPLE 7-3
A 12-story office building is 120 ft tall with plan
dimensions of 120 × 80 ft. The structure is of
conventional curtain wan construction with all windows
fixed in place. There are double vestibule-type doors on
all four sides. Under winter design conditions, a wind of
15 mph blows normal to one of the long dimensions.
Estimate the pressure differences for all walls for the
first and twelfth floors. Consider only wind and stack
effects. The indoor-outdoor temperature difference is 60
F.
7/19/2020 Eng Charlton Inao
• Calculation Aids
54
SOLUTION
The pressure difference for each effect must first be computed
and then combined to find the total. First consider the wind:
Equation 7-13b expresses the wind pressure difference where
the pressure coefficients may be obtained from Fig. 7-5 for a
normal wind. Then using standard sea level density:
7/19/2020 Eng Charlton Inao
• Calculation Aids
55
SOLUTION
The wind effect will be assumed constant with respect
to height.
7/19/2020 Eng Charlton Inao
• Calculation Aids
56
SOLUTION
Then for the first floor, h = 50 ft and
7/19/2020 Eng Charlton Inao
• Calculation Aids
57
SOLUTION
For the twelfth floor, h = 70 ft and
7/19/2020 Eng Charlton Inao
• Calculation Aids
58
SOLUTION
The negative sign indicates that the pressure is greater
inside the building than on the outside. The pressure
differences may now be summarized for each side
where ∆P = (∆Pw + ∆Ps) in. wg.
7/19/2020 Eng Charlton Inao
• Calculation Aids
59
These results show that air will tend to infiltrate on
most floors on the windward wall. Infiltration will occur
on about the lower four floors on the leeward wall. All
other surfaces will have exfiltration.
7/19/2020 Eng Charlton Inao
• Calculation Aids
60
EXAMPLE 7-4
Estimate the infiltration rate for the leeward doors of
Example 7-3. The doors have
1
8
-in. cracks and the traffic
rate is low except at 5:00 P.M., when the traffic rate is
350 people per hour per door for a short time.
7/19/2020 Eng Charlton Inao
• Calculation Aids
61
SOLUTION
This problem is solved in two steps to account for crack
leakage and infiltration due to traffic. For the design
condition, the effect of traffic is negligible; however, it is
of interest to compute this component for 5:00 P.M.
Figure 7-9 pertains to crack leakage for commercial
swinging doors.
7/19/2020 Eng Charlton Inao
• Calculation Aids
62
SOLUTION
For a pressure difference of 0.041 in. wg. and
1
8
-in.
cracks, the leakage rate is 8 cfm/ft. The crack length for
standard double swinging doors is
7/19/2020 Eng Charlton Inao
• Calculation Aids
63
SOLUTION
Vestibule-type doors will tend to decrease the
infiltration rate somewhat like storm sash or a storm
door. Assume a 30 percent reduction; then
7/19/2020 Eng Charlton Inao
• Calculation Aids
64
SOLUTION
Figures 7-10 and 7-11 are used to estimate the
infiltration due to traffic. The traffic coefficient C is read
from Fig. 7-11 for 350 people per hour and for
vestibule-type doors at 5000. Then, from Fig. 1-10 at a
pressure difference of 0.041 in. wg,
7/19/2020 Eng Charlton Inao
• Calculation Aids
65
SOLUTION
A part of the crack leakage should be added to this;
however, this is somewhat academic. Care should be
exercised in including the traffic infiltration in the design
heat load. It will usually be a short-term effect.
7/19/2020 Eng Charlton Inao
• Calculation Aids
66
EXAMPLE 7-5
Estimate the leakage rate for the twelfth floor of the
building in Example 1-3. Neglect the roof.
7/19/2020 Eng Charlton Inao
• Calculation Aids
67
SOLUTION
Referring to the pressure differences computed in
Example 7-3, it is obvious that the leakage will be from
the inside out on the twelfth floor. Therefore, a great
deal of air must be entering the space from the
stairwells and elevator shafts. Because the twelfth floor
has no movable openings, except to the roof, all
leakage is assumed to be through the walls. Figure 7-8
gives data for this case where K = 0.66 for conventional
construction
7/19/2020 Eng Charlton Inao
• Calculation Aids
68
SOLUTION
7/19/2020 Eng Charlton Inao
• Calculation Aids
69
SOLUTION
where the negative sign indicates that the flow is from
the inside out. The net leakage flow of 630 cfm entered
the building at other locations where the heat loss
should be assigned.
7/19/2020 Eng Charlton Inao
• Calculation Aids
70
EXAMPLE 7-6
A single-story building is oriented so that a 15-mph
wind approaches 45 degrees to the windward sides.
There are 120 ft of crack: for the windows and 20 ft of
crack for a door on the windward side. The sides have
130 ft of window cracks and 18 ft of door crack. All
windows and doors are average fitting. Estimate the
infiltration.
7/19/2020 Eng Charlton Inao
• Calculation Aids
71
SOLUTION
The major portion of the infiltration for this kind of
building will be through the cracks. It is approximately
true that air will enter on the sides and flow out with
most of the heat loss imposed on the rooms where the
air enters. As suggested, we will use double the total
crack length and assume that most of the air leaves
through the ceiling area with a pressure difference
computed for a quartering wind on the windward side.
Using Eq. 7-13b, Fig. 7-4, and Table 7-1.
7/19/2020 Eng Charlton Inao
• Calculation Aids
72
SOLUTION
where standard sea level air density bas been used.
From Tables 7-2 and 7-3. the K factor for the windows
and doors is read as 2.0. Then from Fig. 7-3, the
leakage per foot of crack is
7/19/2020 Eng Charlton Inao
• Calculation Aids
73
SOLUTION
and the total infiltration for the space is
7/19/2020 Eng Charlton Inao
7-5 HEAT LOSSES FROM AIR DUCTS
74
The losses of a duct system can be considerable when
the ducts are not in the conditioned space. Proper
insulation will reduce these losses but cannot
completely eliminate them. The loss may be estimated
using die following relation:
7/19/2020 Eng Charlton Inao
7-5 HEAT LOSSES FROM AIR DUCTS
75
EXAMPLE 7-7
Estimate the heat loss from 1000 cfm of air at 120 Ft
flowing in a l6-in. duct 25 ft in length. The duct has 1
in. of fibrous glass insulation and the overall coefficient
is 0.2 Btu/(hr-ft2-F). The environment temperature is 12
F.
7/19/2020 Eng Charlton Inao
7-5 HEAT LOSSES FROM AIR DUCTS
76
SOLUTION
Equation 7-18 will be used to estimate the heat loss
assuming that the mean temperature difference is given
approximately by
7/19/2020 Eng Charlton Inao
7-5 HEAT LOSSES FROM AIR DUCTS
77
SOLUTION
The surface area of the duct is
7/19/2020 Eng Charlton Inao
7-5 HEAT LOSSES FROM AIR DUCTS
78
SOLUTION
The temperature of the air leaving the duct may be
computed from
7/19/2020 Eng Charlton Inao
7-5 HEAT LOSSES FROM AIR DUCTS
79
SOLUTION
Although insulation and surface drastically reduces the
heat loss, the magnitude of the temperature difference
and surface area must be considered in each case.
7/19/2020 Eng Charlton Inao
7-6 AUXILLARY HEAT SOURCES
80
The heat energy supplied by people, lights, motors, and
machinery may be estimated. but any actual allowance
for these heat sources requires careful consideration.
People may not occupy certain spaces in the evenings,
or weekends, and during other periods, but these
spaces must generally be heated to a reasonably
comfortable temperature prior to occupancy.
7/19/2020 Eng Charlton Inao
7-6 AUXILLARY HEAT SOURCES
817/19/2020 Eng Charlton Inao
7-7 INTERMITTENTLY HEATED
STRUCTURES
82
When a structure is not heated on a continuous basis,
the beating equipment capacity may have to be
enlarged to assure that the temperature can be raised
to a comfortable level within a reasonable period of
time. The heat capacity of the building and occupant
comfort are important factors when considering the use
of intermittent beating.
7/19/2020 Eng Charlton Inao
7-8 SUPPLY AIR FOR SPACE HEATING
83
There are many cases when the air quantity is
conveniently computed from
7/19/2020 Eng Charlton Inao
7-8 SUPPLY AIR FOR SPACE HEATING
84
Obviously, the air quantity for each room should be
apportioned according to the heating load for that
space. Then
7/19/2020 Eng Charlton Inao
PROBLEMS
85
7-1. Select an indoor design relative humidity for structures located
in the cities given below. Assume an indoor design dry bulb
temperature from Table C-L. Windows in the building are double
glass. aluminum frame with thermal break. Other external surfaces
are well insulated.
(a) Sioux City, Iowa
(b) Atlanta, Georgia
(c) Syracuse, New York
(d) Denver, Colorado
(e) San Francisco. California
(f) Bismarck, North Dakota
(g) Rapid City, South Dakota7/19/2020 Eng Charlton Inao
PROBLEMS
86
7-2. Estimate the temperature in the crawl space of a
building with floor plan dimensions of 30 ×60 ft. The
concrete foundation has an average height of 2 ft and
the wall is 6-in. thick. Use winter design conditions for
Oklahoma City, Oklahoma.
7/19/2020 Eng Charlton Inao
PROBLEMS
87
7-3. Estimate the temperature in the knee space shown
in Fig. 7-12. The roof is equivalent to 0.5 in. (25 mm) of
wood on 2 × 6-in. rafters on 24-in. (0.6-01) centers.
The walls are 2 × 4-in. studs on 16-in., (0.4-m) centers
with 3.5 in. (90 mm) of insulation. The joist spaces all
have 6 in. (150 mm) of insulation. Inside and outside
temperatures are 70 F (21 C) and 10 F (-12 C).
7/19/2020 Eng Charlton Inao
PROBLEMS
887/19/2020 Eng Charlton Inao
PROBLEMS
89
7-4. Consider the knee space shown in Fig. 7-12. The
vertical dimension is 8 ft, the horizontal dimension is 3
ft. and the space is 20 ft long. The walls and roof
surrounding the space all have an overall heat-transfer
coefficient of about 0.09 Btu/(hr-ft2-F). Assuming an
outdoor temperature of 2 F and an indoor temperature
of 68 F, make a recommendation concerning the
placement of water pipes in the knee space.
7/19/2020 Eng Charlton Inao
PROBLEMS
90
7-5. Estimate the temperature in an unheated basement
that is completely below ground level with heated space
above. Assume no insulation and dimension of 20 × 20
× 7 ft. The basement is located in Lincoln, Nebraska.
Use standard design conditions.
7/19/2020 Eng Charlton Inao
PROBLEMS
91
7-6. Rework Example 7-1 assuming that the crawl space
experiences an infiltration rate of 0.25 air changes per
hour.
7/19/2020 Eng Charlton Inao
PROBLEMS
92
7-7. Rework Example 7-2 assuming an infiltration rate
of 0.2 air changes per hour.
7/19/2020 Eng Charlton Inao
PROBLEMS
93
7-8. A large single-story business office is fitted with
nine loose-fitting, double-hung woodsash windows 3 ft
wide by 6 ft high. If the outside wind is 15 mph at a
temperature of -10 F, what is the percent reduction in
sensible heat loss if the windows are weather stripped?
Assume an inside temperature of 70 F. Base your
solution on a quartering wind.
7/19/2020 Eng Charlton Inao
PROBLEMS
94
7-9. Using the crack method compute the infiltration for
a tight-fitting swinging door that is used occasionally.
The door bas dimensions of 0.9 × 2.0 m and is on the
windward side of a bouse exposed to a 9 m/s wind.
Neglect internal pressurization and stack effect.
7/19/2020 Eng Charlton Inao
PROBLEMS
95
7-10. A room in a single-story building has two 3 × 5-ft
wood, double-hung windows of average fit that are not
weather stripped. The wind is 20 mph and normal to
the wall with negligible pressurization of the room. Find
the infiltration rate assuming that the entire crack is
admitting air.
7/19/2020 Eng Charlton Inao
PROBLEMS
96
7-11. Compute the design infiltration rate and beat gain
for the bouse described in Problem 7-16 assuming an
orientation normal to a is 15 mph wind. The windows
and doors are tight fitting.
7/19/2020 Eng Charlton Inao
PROBLEMS
97
7-12. Refer to Example 7-3. (a) Estimate the total
pressure difference for each wall for the third and ninth
floors. (b) Using design conditions for Denver, Colorado,
estimate the heat load due to infiltration for the third
floors and ninth floors.
7/19/2020 Eng Charlton Inao
PROBLEMS
98
7-13. Refer to Examples 7-3 and 7-4. (a) Estimate the
infiltration rates for the windward and side doors for a
low traffic rate. (b) Estimate the curtain wall infiltration
for the first floor. (c) Compute the heat load due to
infiltration for the first floor if the building is located in
Cleveland. Ohio.
7/19/2020 Eng Charlton Inao
PROBLEMS
99
7-14. A 20-story office building has plan dimensions of 100 × 60 ft
and is oriented-at 45 degrees to a 20 mph wind. All windows are
fixed in place. There are double vestibule-type swinging doors on
the 6O-ft walls. The walls are average curtain wall construction and
the doors have about i-in. cracks. (a) Compute the pressure
differences for each wall due to wind and stack effect for the first,
fifth, fifteenth, and twentieth floors. (b) Plot pressure difference
versus height for each wall and estimate which surfaces have
infiltration and exfiltration. (c) Compute the total infiltration rate for
the first floor assuming a very low traffic rate. Compute the
infiltration rate for the fifteenth floor. (e) Compute the infiltration
rate for the twentieth floor. Neglect any leakage through the roof.
7/19/2020 Eng Charlton Inao
PROBLEMS
100
7-15. Refer to Problem 7-14. (a) Compute the heat gain due to
infiltration for the first floor with the building located in Dallas,
Texas. (b) Compute the heat gain due to infiltration for the
fifteenth floor. (c) what is the heat gain due to infiltration for the
twentieth floor?
7/19/2020 Eng Charlton Inao
PROBLEMS
101
7-17. Rework Problem 7-16 for Lincoln, Nebraska. Include
infiltration in the analysis.
7/19/2020 Eng Charlton Inao
PROBLEMS
102
7-18. Consider a building located in Syracuse, New York. Using
ASHRAE Standard recommendations, compute the transmission
loss for (a) a wall like Table 5-7a, case 2, which is 3 × 4 m with a
window of 1 m2 area, (b) a single pane window with aluminum
frame and no thermal break, (c) a roof-ceiling combination that is
like Table 5-7b, case 1, with an area of 16 m2.
7/19/2020 Eng Charlton Inao
PROBLEMS
1037/19/2020 Eng Charlton Inao
PROBLEMS
1047/19/2020 Eng Charlton Inao
PROBLEMS
105
7-20. A small commercial building has a computed heat
load of 200,000 Btu/hr sensible and 25,000 Btu/hr
latent. Assuming a 50 F temperature rise for the heating
unit, compute the quantity of air to be supplied by the
unit using the following methods: (a) Use a
psychrometric chart with room conditions of 70F and 30
percent relative humidity. (b) Calculate the air quantity
based on the sensible heat transfer.
7/19/2020 Eng Charlton Inao

More Related Content

PDF
Fan and blowers (mech 326)
DOCX
Refrigeration system 2
PDF
Hydro electric power plant
PDF
Chapter_3.pdf
PPTX
Heat conduction through a plane wall
DOC
Calculation of Turbine Efficiency
PDF
Chapter 6 Psychrometry & Air-Conditioning
PDF
Solucionario faires
Fan and blowers (mech 326)
Refrigeration system 2
Hydro electric power plant
Chapter_3.pdf
Heat conduction through a plane wall
Calculation of Turbine Efficiency
Chapter 6 Psychrometry & Air-Conditioning
Solucionario faires

What's hot (20)

PPT
HVAC Cooling Load Calculation
PPT
Referigeration
PDF
Heat & Mass Balance in Cement Plant
PPT
Air compressor
PDF
Boiler design-calculation 3
PDF
[W f stoecker]_refrigeration_and_a_ir_conditioning_(book_zz.org)
DOC
Time value of money 2
PDF
cooling load calculations Hostel Building
PDF
Determination of vacuum pump operational efficiency
PDF
Cooling tower calculation (1) (1)
PDF
AC 6Ed.pdf
PDF
steady heat transfer between two large parallel plates
PPT
Se prod thermo_examples_mst
PDF
Refrigeration system 2
PDF
Solutions Manual for Contemporary Engineering Economics 5th Edition by Park
PDF
Gas Compressor Calculations Tutorial
PDF
Statics Mechanics of Materials 4th Edition Hibbeler Solutions Manual
PPT
Psychrometry and air conditioning
HVAC Cooling Load Calculation
Referigeration
Heat & Mass Balance in Cement Plant
Air compressor
Boiler design-calculation 3
[W f stoecker]_refrigeration_and_a_ir_conditioning_(book_zz.org)
Time value of money 2
cooling load calculations Hostel Building
Determination of vacuum pump operational efficiency
Cooling tower calculation (1) (1)
AC 6Ed.pdf
steady heat transfer between two large parallel plates
Se prod thermo_examples_mst
Refrigeration system 2
Solutions Manual for Contemporary Engineering Economics 5th Edition by Park
Gas Compressor Calculations Tutorial
Statics Mechanics of Materials 4th Edition Hibbeler Solutions Manual
Psychrometry and air conditioning
Ad

Similar to Chap5 space heat load calculations (20)

PDF
Heat Load Calculation
PDF
Heat Loss Due to Thermal Bridges in a Foundation with Floor Heating (abstract)
PDF
Textbook chapter 2 air conditioning systems
PDF
Heat Load Calculation
PDF
[ME-20249]Complex Engineering RAC file.pdf
PDF
Computational fluid dynamic analysis of solar chimney design
PDF
Estimation of HVAC energy saving potential in San Diego apartment units throu...
PPTX
HVAC Mini project review.pptx
PDF
Ventilation Analysis
PDF
Low Energy Office Proposal
PDF
Ijetr011821
PDF
Passive cooling-measures-for-murbs
PDF
IRJET- Air Conditioning Ceiling Fan by using Thermoelectric Module
PDF
NYC Large Building Model Case Study_Final
PPTX
Cooling Load Calculations and vapour compression
PDF
IRJET- Developing a New Model of Existing Split Air Conditioner
PDF
Mohamed Zedan - State of The Art in the Use of Thermal Insulation in Building
PPT
The 2030 Challenge & Current Energy Efficient Housing
PDF
Comparison of Cooling Load Calculations by using Theoretical Analysis and E 2...
PPT
Building And Energy Code Pres
Heat Load Calculation
Heat Loss Due to Thermal Bridges in a Foundation with Floor Heating (abstract)
Textbook chapter 2 air conditioning systems
Heat Load Calculation
[ME-20249]Complex Engineering RAC file.pdf
Computational fluid dynamic analysis of solar chimney design
Estimation of HVAC energy saving potential in San Diego apartment units throu...
HVAC Mini project review.pptx
Ventilation Analysis
Low Energy Office Proposal
Ijetr011821
Passive cooling-measures-for-murbs
IRJET- Air Conditioning Ceiling Fan by using Thermoelectric Module
NYC Large Building Model Case Study_Final
Cooling Load Calculations and vapour compression
IRJET- Developing a New Model of Existing Split Air Conditioner
Mohamed Zedan - State of The Art in the Use of Thermal Insulation in Building
The 2030 Challenge & Current Energy Efficient Housing
Comparison of Cooling Load Calculations by using Theoretical Analysis and E 2...
Building And Energy Code Pres
Ad

More from Charlton Inao (20)

PPTX
Fundametals of HVAC Refrigeration and Airconditioning
PPTX
Technopreneurship 1.4 team formation
PPT
Coolers and chillers for HVAC
PDF
Basic dryer for HVAC
PPTX
Comfort cooling july 23
PPT
Cooling towers july 23
PDF
Chap4 solar radiation in HVAC
PPTX
fUNDAMENTALS OF hvac
PPTX
technopreneurship
PPTX
Nme 515 air conditioning and ventilation systems for submission
PDF
Ched cmo 2018 2019 bsme curriculum and syllabus
PDF
Nme 516 industrial processes for canvas
PDF
Nme 3107 technopreneurship for canvas june 17
PPTX
Robotics ch 4 robot dynamics
PPTX
Week 5 1 pe 3032 modeling of electromechanical and thermal nonlinearities
PDF
MECHATRONICS LAB Final report feb 7
PPTX
Pe 4030 ch 2 sensors and transducers part 2 flow level temp light oct 7, 2016
PPT
Ansys flat top cylinder with fillet 35 mpa 12 25 version 2
PPT
Wk 6 part 2 non linearites and non linearization april 05
PPT
Pe 4030 ch 2 sensors and transducers part 1 final sept 20 2016
Fundametals of HVAC Refrigeration and Airconditioning
Technopreneurship 1.4 team formation
Coolers and chillers for HVAC
Basic dryer for HVAC
Comfort cooling july 23
Cooling towers july 23
Chap4 solar radiation in HVAC
fUNDAMENTALS OF hvac
technopreneurship
Nme 515 air conditioning and ventilation systems for submission
Ched cmo 2018 2019 bsme curriculum and syllabus
Nme 516 industrial processes for canvas
Nme 3107 technopreneurship for canvas june 17
Robotics ch 4 robot dynamics
Week 5 1 pe 3032 modeling of electromechanical and thermal nonlinearities
MECHATRONICS LAB Final report feb 7
Pe 4030 ch 2 sensors and transducers part 2 flow level temp light oct 7, 2016
Ansys flat top cylinder with fillet 35 mpa 12 25 version 2
Wk 6 part 2 non linearites and non linearization april 05
Pe 4030 ch 2 sensors and transducers part 1 final sept 20 2016

Recently uploaded (20)

PPTX
UNIT - 3 Total quality Management .pptx
PPT
Introduction, IoT Design Methodology, Case Study on IoT System for Weather Mo...
PDF
SMART SIGNAL TIMING FOR URBAN INTERSECTIONS USING REAL-TIME VEHICLE DETECTI...
PDF
Enhancing Cyber Defense Against Zero-Day Attacks using Ensemble Neural Networks
PDF
UNIT no 1 INTRODUCTION TO DBMS NOTES.pdf
PDF
R24 SURVEYING LAB MANUAL for civil enggi
PPTX
Nature of X-rays, X- Ray Equipment, Fluoroscopy
PDF
null (2) bgfbg bfgb bfgb fbfg bfbgf b.pdf
PPT
Total quality management ppt for engineering students
PDF
Integrating Fractal Dimension and Time Series Analysis for Optimized Hyperspe...
PPTX
6ME3A-Unit-II-Sensors and Actuators_Handouts.pptx
PPTX
UNIT 4 Total Quality Management .pptx
PPTX
Current and future trends in Computer Vision.pptx
PPTX
Safety Seminar civil to be ensured for safe working.
PDF
keyrequirementskkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkk
PDF
The CXO Playbook 2025 – Future-Ready Strategies for C-Suite Leaders Cerebrai...
PPT
A5_DistSysCh1.ppt_INTRODUCTION TO DISTRIBUTED SYSTEMS
PDF
86236642-Electric-Loco-Shed.pdf jfkduklg
PPTX
CURRICULAM DESIGN engineering FOR CSE 2025.pptx
PPT
INTRODUCTION -Data Warehousing and Mining-M.Tech- VTU.ppt
UNIT - 3 Total quality Management .pptx
Introduction, IoT Design Methodology, Case Study on IoT System for Weather Mo...
SMART SIGNAL TIMING FOR URBAN INTERSECTIONS USING REAL-TIME VEHICLE DETECTI...
Enhancing Cyber Defense Against Zero-Day Attacks using Ensemble Neural Networks
UNIT no 1 INTRODUCTION TO DBMS NOTES.pdf
R24 SURVEYING LAB MANUAL for civil enggi
Nature of X-rays, X- Ray Equipment, Fluoroscopy
null (2) bgfbg bfgb bfgb fbfg bfbgf b.pdf
Total quality management ppt for engineering students
Integrating Fractal Dimension and Time Series Analysis for Optimized Hyperspe...
6ME3A-Unit-II-Sensors and Actuators_Handouts.pptx
UNIT 4 Total Quality Management .pptx
Current and future trends in Computer Vision.pptx
Safety Seminar civil to be ensured for safe working.
keyrequirementskkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkk
The CXO Playbook 2025 – Future-Ready Strategies for C-Suite Leaders Cerebrai...
A5_DistSysCh1.ppt_INTRODUCTION TO DISTRIBUTED SYSTEMS
86236642-Electric-Loco-Shed.pdf jfkduklg
CURRICULAM DESIGN engineering FOR CSE 2025.pptx
INTRODUCTION -Data Warehousing and Mining-M.Tech- VTU.ppt

Chap5 space heat load calculations

  • 1. AIR CONDITIONING and VENTILATION SYSTEMS NME 515 Heating, Ventilating, and Air Conditioning ANALYSIS and DESIGN Engr. Charlton Inao, ME TESDA TVET NC Level 3 RAC-CRE Certified 17/19/2020 Eng Charlton Inao
  • 2. Space Heat Load Engr. Charlton Inao, ME TESDA TVET NC Level 3 RAC- CRE Certified 2 Reference: Heating, Ventilating, and Air Conditioning ANALYSIS and DESIGN by FC Mc Quiston and JD Parker 7/19/2020 Eng Charlton Inao
  • 3. Space Heat Load 3 There are two kinds of heat losses: (1) the heat transmitted through the walls, ceiling, floor, glass, or other surfaces and (2) the heat required to warm outdoor air entering the space. Transient analyses are often used to study the actual energy requirements of a structure in simulation studies. In such cases solar effects and internal heat gains are taken into account. 7/19/2020 Eng Charlton Inao
  • 4. 7-1 OUTDOOR DESIGN CONDITIONS 4 The outdoor design temperature should generally be the 97 1 2 percent value as specified by ASHRAE Energy Standards. If the structure is of lightweight construction (low heat capacity), is poorly insulated. or has considerable glass or space temperature control is critical, however, the 99 percent values should be considered. The designer must remember that should the outdoor temperature fall below the design value for some extended period, the indoor temperature may do likewise. 7/19/2020 Eng Charlton Inao
  • 5. 7-2 INDOOR DESIGN CONDITIONS 5 The indoor design temperature should be kept relatively low so that the heating equipment will not be oversized. A design temperature of 70 F or 22 C is commonly used with relative humidity less than or equal to 30 percent. 7/19/2020 Eng Charlton Inao
  • 6. 7-2 INDOOR DESIGN CONDITIONS 6 Even properly sized equipment operates under partial load. at reduced efficiency, most of the time; therefore, any oversizing aggravates this condition and lowers the overall system efficiency. The temperature in an unheated space is needed to compute· the heat loss and may be estimated by assuming steady-state heat transfer and making an energy balance on the space. 7/19/2020 Eng Charlton Inao
  • 7. 7-2 INDOOR DESIGN CONDITIONS 7 EXAMPLE 7-1 Estimate the temperature in the crawl space of Fig. 7-1. The conductance for the floor is 0.20 Btu/(hr-ft2-F) including the air film on each side. The conductance for the foundation wall including the insulation and inside and outside air film resistances is 0.12 Btu/(hr-ft2-F). Assume an indoor temperature of 70 F and an outdoor temperature of 10 Fat a location where the degree days are about 3000. The building dimensions are 50 × 75 ft. 7/19/2020 Eng Charlton Inao
  • 8. 7-2 INDOOR DESIGN CONDITIONS 87/19/2020 Eng Charlton Inao
  • 9. 7-2 INDOOR DESIGN CONDITIONS 9 SOLUTION The first step is to make an energy balance on the crawl space. Heat will be gained through the floor and heat will be lost through the foundation wall and through the ground around the perimeter much like a floor slab. 7/19/2020 Eng Charlton Inao
  • 10. 7-2 INDOOR DESIGN CONDITIONS 10 SOLUTION Infiltration of outdoor air will also represent a heat loss but that will be neglected in this example. 7/19/2020 Eng Charlton Inao
  • 11. 7-2 INDOOR DESIGN CONDITIONS 117/19/2020 Eng Charlton Inao
  • 12. 7-2 INDOOR DESIGN CONDITIONS 12 Now the area of the floor is 50 × 75 = 3750 ft2 and assuming that the foundation wall averages a height of 2 ft, the area of the foundation wall is 2 (2 × 50) + (2 × 75) = 500 ft2. The perimeter of the building is (2 × 50) + (2 × 75) = 250 ft. Referring to Table 5-12, the heat-loss coefficient is estimated to be 0.8 Btu/(hr-ft-F). Then 7/19/2020 Eng Charlton Inao
  • 13. 7-2 INDOOR DESIGN CONDITIONS 13 Now the area of the floor is 50 × 75 = 3750 ft2 and assuming that the foundation wall averages a height of 2 ft, the area of the foundation wall is 2 (2 × 50) + (2 × 75) = 500 ft2. The perimeter of the building is (2 × 50) + (2 × 75) = 250 ft. Referring to Table 5-12, the heat-loss coefficient is estimated to be 0.8 Btu/(hr-ft-F). Then 7/19/2020 Eng Charlton Inao
  • 14. 7-2 INDOOR DESIGN CONDITIONS 14 If the infiltration had been considered, the crawl-space temperature would be lower. Many crawl spaces are ventilated to prevent moisture problems. and infiltration would be significant even when the vents are closed. 7/19/2020 Eng Charlton Inao
  • 15. 7-2 INDOOR DESIGN CONDITIONS 15 EXAMPLE 7-2 Estimate the temperature in the unheated room shown in Fig. 7-2. The structure is built on a slab. The exterior walls of the unheated room have an- overall heat- transfer coefficient- of 0.2 Btu/(hr-ft2-F), the ceiling- attic-roof combination has an overall coefficient of 0.07 Btu/(hr-ft2-F), and the interior walls have an overall coefficient of 0.06 Btu/(hr-ft2-F). Inside and outdoor design temperatures are 72 F and - 5 F, respectively. 7/19/2020 Eng Charlton Inao
  • 16. 7-2 INDOOR DESIGN CONDITIONS 16 SOLUTION The heat transferred from the heated to the unheated room has a single path, neglecting the door, and may be represented as 7/19/2020 Eng Charlton Inao
  • 17. 7-2 INDOOR DESIGN CONDITIONS 17 SOLUTION The heat transferred from the unheated room to the outdoor air has parallel paths through the ceiling and walls (neglecting the door and floor): 7/19/2020 Eng Charlton Inao
  • 18. 7-2 INDOOR DESIGN CONDITIONS 18 SOLUTION The heat loss to the floor can be neglected because of the anticipated low temperature in the room. Equation 7-2 may be written where 7/19/2020 Eng Charlton Inao
  • 19. 7-2 INDOOR DESIGN CONDITIONS 197/19/2020 Eng Charlton Inao
  • 20. 7-2 INDOOR DESIGN CONDITIONS 20 By combining Eqs. 7-1 and 7-3. we obtain 7/19/2020 Eng Charlton Inao
  • 21. 7-2 INDOOR DESIGN CONDITIONS 21 Then from Eq. 7-6 The assumption of negligible heat transfer through the slab is justified by the result. 7/19/2020 Eng Charlton Inao
  • 22. 7-3 TRANSMISSION HEAT LOSSES 22 The heat transferred through walls, ceiling, roof, window glass, floors, and doors is all sensible heat transfer, referred to as transmission heat loss and computed from 7/19/2020 Eng Charlton Inao
  • 23. 7-4 INFILTRATION 23 All structures have some air leakage or infiltration. This means a heat loss because the cold dry outdoor air must be heated to the inside design temperature and moisture must be added to increase the humidity to the design value. The sensible heat required (to increase the temperature) is given by 7/19/2020 Eng Charlton Inao
  • 24. 7-4 INFILTRATION 24 Infiltration is usually estimated on the basis of volume flow rate at outdoor conditions. Equation 7-8 then becomes 7/19/2020 Eng Charlton Inao
  • 25. 7-4 INFILTRATION 25 The latent heat required to humidify the air is given by 7/19/2020 Eng Charlton Inao
  • 26. 7-4 INFILTRATION 26 In terms of volume flow rate of air, Eq. 7-9 becomes 7/19/2020 Eng Charlton Inao
  • 27. 7-4 INFILTRATION 27 Various methods are used in estimating air infiltration in building structures. In one method the estimate is based on the characteristics of the windows, walls, and doors and the pressure difference between inside and outside. This is known as the crack method because of the cracks around window sash and doors. The other approach is the air-change method which is based on an assumed number of air changes per hour based on experience. 7/19/2020 Eng Charlton Inao
  • 28. Air-change Method 28 Experienced engineers will often simply make an assumption of the number of air-changes per hour (ACH) that a building will experience based on their appraisal of the building type, construction, and use. The range will usually be from 0.5 ACH (very low) to 2.0 ACH (very high). The infiltration rate is related to ACH and space volume as follows: 7/19/2020 Eng Charlton Inao
  • 30. Crack Method 30 Outdoor air infiltrates the indoor space through cracks around doors, windows, lighting fixtures, and joints between walls and floor and even through the building material itself. 7/19/2020 Eng Charlton Inao
  • 31. Crack Method 31 The pressure difference of Eq. 7-11 results from three different effects: All of the pressure differences are positive when each causes flow of air to the inside of the building. 7/19/2020 Eng Charlton Inao
  • 33. Crack Method 33 The pressure difference due to the wind results from an increase or decrease in air velocity and is described by 7/19/2020 Eng Charlton Inao
  • 35. Crack Method 35 Finally, Eq. 7-13a may be written 7/19/2020 Eng Charlton Inao
  • 37. Crack Method 37 When larger openings predominate in the lower portion of the building, the neutral pressure level will be lowered., Similarly, the neutral pressure level will be raised by larger openings in the upper portion of the building. Normally the larger openings will occur in the lower part of the building because of doors. 7/19/2020 Eng Charlton Inao
  • 38. Crack Method 38 The theoretical pressure difference with no internal separations is given by 7/19/2020 Eng Charlton Inao
  • 39. Crack Method 39 The floors in a conventional building offer resistance to vertical air flow. Furthermore, this resistance varies depending on how stairwells and elevator shafts are sealed. When the resistance can be assumed equal for each floor, a single correction, called the draft coefficient, can be used to relate the actual pressure difference ∆Ps, to the theoretical value ∆Pst: 7/19/2020 Eng Charlton Inao
  • 40. Crack Method 40 The flow of air from floor to floor causes a decrease in pressure at each floor; therefore, ∆Ps will be less than ∆Pst and Cd is less than one. Using the draft coefficient, Eq. 7-15 becomes 7/19/2020 Eng Charlton Inao
  • 44. • Calculation Aids 44 The use of storm sash and storm doors is common. The addition of a storm sash with crack length and a K value equal to the prime window reduces infiltration by about 35 percent. 7/19/2020 Eng Charlton Inao
  • 45. • Calculation Aids 45 Single-bank doors open directly into the space; however, there may be two or more doors at one location. Vestibule-type doors are best characterized as two doors in series so as to form an air lock between them. These doors often appear as two pairs of doors in series, which amounts to two vestibule-type doors. 7/19/2020 Eng Charlton Inao
  • 46. • Calculation Aids 467/19/2020 Eng Charlton Inao
  • 47. • Calculation Aids 477/19/2020 Eng Charlton Inao
  • 48. • Calculation Aids 487/19/2020 Eng Charlton Inao
  • 49. • Calculation Aids 497/19/2020 Eng Charlton Inao
  • 50. • Calculation Aids 507/19/2020 Eng Charlton Inao
  • 51. • Calculation Aids 517/19/2020 Eng Charlton Inao
  • 52. • Calculation Aids 527/19/2020 Eng Charlton Inao
  • 53. • Calculation Aids 53 EXAMPLE 7-3 A 12-story office building is 120 ft tall with plan dimensions of 120 × 80 ft. The structure is of conventional curtain wan construction with all windows fixed in place. There are double vestibule-type doors on all four sides. Under winter design conditions, a wind of 15 mph blows normal to one of the long dimensions. Estimate the pressure differences for all walls for the first and twelfth floors. Consider only wind and stack effects. The indoor-outdoor temperature difference is 60 F. 7/19/2020 Eng Charlton Inao
  • 54. • Calculation Aids 54 SOLUTION The pressure difference for each effect must first be computed and then combined to find the total. First consider the wind: Equation 7-13b expresses the wind pressure difference where the pressure coefficients may be obtained from Fig. 7-5 for a normal wind. Then using standard sea level density: 7/19/2020 Eng Charlton Inao
  • 55. • Calculation Aids 55 SOLUTION The wind effect will be assumed constant with respect to height. 7/19/2020 Eng Charlton Inao
  • 56. • Calculation Aids 56 SOLUTION Then for the first floor, h = 50 ft and 7/19/2020 Eng Charlton Inao
  • 57. • Calculation Aids 57 SOLUTION For the twelfth floor, h = 70 ft and 7/19/2020 Eng Charlton Inao
  • 58. • Calculation Aids 58 SOLUTION The negative sign indicates that the pressure is greater inside the building than on the outside. The pressure differences may now be summarized for each side where ∆P = (∆Pw + ∆Ps) in. wg. 7/19/2020 Eng Charlton Inao
  • 59. • Calculation Aids 59 These results show that air will tend to infiltrate on most floors on the windward wall. Infiltration will occur on about the lower four floors on the leeward wall. All other surfaces will have exfiltration. 7/19/2020 Eng Charlton Inao
  • 60. • Calculation Aids 60 EXAMPLE 7-4 Estimate the infiltration rate for the leeward doors of Example 7-3. The doors have 1 8 -in. cracks and the traffic rate is low except at 5:00 P.M., when the traffic rate is 350 people per hour per door for a short time. 7/19/2020 Eng Charlton Inao
  • 61. • Calculation Aids 61 SOLUTION This problem is solved in two steps to account for crack leakage and infiltration due to traffic. For the design condition, the effect of traffic is negligible; however, it is of interest to compute this component for 5:00 P.M. Figure 7-9 pertains to crack leakage for commercial swinging doors. 7/19/2020 Eng Charlton Inao
  • 62. • Calculation Aids 62 SOLUTION For a pressure difference of 0.041 in. wg. and 1 8 -in. cracks, the leakage rate is 8 cfm/ft. The crack length for standard double swinging doors is 7/19/2020 Eng Charlton Inao
  • 63. • Calculation Aids 63 SOLUTION Vestibule-type doors will tend to decrease the infiltration rate somewhat like storm sash or a storm door. Assume a 30 percent reduction; then 7/19/2020 Eng Charlton Inao
  • 64. • Calculation Aids 64 SOLUTION Figures 7-10 and 7-11 are used to estimate the infiltration due to traffic. The traffic coefficient C is read from Fig. 7-11 for 350 people per hour and for vestibule-type doors at 5000. Then, from Fig. 1-10 at a pressure difference of 0.041 in. wg, 7/19/2020 Eng Charlton Inao
  • 65. • Calculation Aids 65 SOLUTION A part of the crack leakage should be added to this; however, this is somewhat academic. Care should be exercised in including the traffic infiltration in the design heat load. It will usually be a short-term effect. 7/19/2020 Eng Charlton Inao
  • 66. • Calculation Aids 66 EXAMPLE 7-5 Estimate the leakage rate for the twelfth floor of the building in Example 1-3. Neglect the roof. 7/19/2020 Eng Charlton Inao
  • 67. • Calculation Aids 67 SOLUTION Referring to the pressure differences computed in Example 7-3, it is obvious that the leakage will be from the inside out on the twelfth floor. Therefore, a great deal of air must be entering the space from the stairwells and elevator shafts. Because the twelfth floor has no movable openings, except to the roof, all leakage is assumed to be through the walls. Figure 7-8 gives data for this case where K = 0.66 for conventional construction 7/19/2020 Eng Charlton Inao
  • 69. • Calculation Aids 69 SOLUTION where the negative sign indicates that the flow is from the inside out. The net leakage flow of 630 cfm entered the building at other locations where the heat loss should be assigned. 7/19/2020 Eng Charlton Inao
  • 70. • Calculation Aids 70 EXAMPLE 7-6 A single-story building is oriented so that a 15-mph wind approaches 45 degrees to the windward sides. There are 120 ft of crack: for the windows and 20 ft of crack for a door on the windward side. The sides have 130 ft of window cracks and 18 ft of door crack. All windows and doors are average fitting. Estimate the infiltration. 7/19/2020 Eng Charlton Inao
  • 71. • Calculation Aids 71 SOLUTION The major portion of the infiltration for this kind of building will be through the cracks. It is approximately true that air will enter on the sides and flow out with most of the heat loss imposed on the rooms where the air enters. As suggested, we will use double the total crack length and assume that most of the air leaves through the ceiling area with a pressure difference computed for a quartering wind on the windward side. Using Eq. 7-13b, Fig. 7-4, and Table 7-1. 7/19/2020 Eng Charlton Inao
  • 72. • Calculation Aids 72 SOLUTION where standard sea level air density bas been used. From Tables 7-2 and 7-3. the K factor for the windows and doors is read as 2.0. Then from Fig. 7-3, the leakage per foot of crack is 7/19/2020 Eng Charlton Inao
  • 73. • Calculation Aids 73 SOLUTION and the total infiltration for the space is 7/19/2020 Eng Charlton Inao
  • 74. 7-5 HEAT LOSSES FROM AIR DUCTS 74 The losses of a duct system can be considerable when the ducts are not in the conditioned space. Proper insulation will reduce these losses but cannot completely eliminate them. The loss may be estimated using die following relation: 7/19/2020 Eng Charlton Inao
  • 75. 7-5 HEAT LOSSES FROM AIR DUCTS 75 EXAMPLE 7-7 Estimate the heat loss from 1000 cfm of air at 120 Ft flowing in a l6-in. duct 25 ft in length. The duct has 1 in. of fibrous glass insulation and the overall coefficient is 0.2 Btu/(hr-ft2-F). The environment temperature is 12 F. 7/19/2020 Eng Charlton Inao
  • 76. 7-5 HEAT LOSSES FROM AIR DUCTS 76 SOLUTION Equation 7-18 will be used to estimate the heat loss assuming that the mean temperature difference is given approximately by 7/19/2020 Eng Charlton Inao
  • 77. 7-5 HEAT LOSSES FROM AIR DUCTS 77 SOLUTION The surface area of the duct is 7/19/2020 Eng Charlton Inao
  • 78. 7-5 HEAT LOSSES FROM AIR DUCTS 78 SOLUTION The temperature of the air leaving the duct may be computed from 7/19/2020 Eng Charlton Inao
  • 79. 7-5 HEAT LOSSES FROM AIR DUCTS 79 SOLUTION Although insulation and surface drastically reduces the heat loss, the magnitude of the temperature difference and surface area must be considered in each case. 7/19/2020 Eng Charlton Inao
  • 80. 7-6 AUXILLARY HEAT SOURCES 80 The heat energy supplied by people, lights, motors, and machinery may be estimated. but any actual allowance for these heat sources requires careful consideration. People may not occupy certain spaces in the evenings, or weekends, and during other periods, but these spaces must generally be heated to a reasonably comfortable temperature prior to occupancy. 7/19/2020 Eng Charlton Inao
  • 81. 7-6 AUXILLARY HEAT SOURCES 817/19/2020 Eng Charlton Inao
  • 82. 7-7 INTERMITTENTLY HEATED STRUCTURES 82 When a structure is not heated on a continuous basis, the beating equipment capacity may have to be enlarged to assure that the temperature can be raised to a comfortable level within a reasonable period of time. The heat capacity of the building and occupant comfort are important factors when considering the use of intermittent beating. 7/19/2020 Eng Charlton Inao
  • 83. 7-8 SUPPLY AIR FOR SPACE HEATING 83 There are many cases when the air quantity is conveniently computed from 7/19/2020 Eng Charlton Inao
  • 84. 7-8 SUPPLY AIR FOR SPACE HEATING 84 Obviously, the air quantity for each room should be apportioned according to the heating load for that space. Then 7/19/2020 Eng Charlton Inao
  • 85. PROBLEMS 85 7-1. Select an indoor design relative humidity for structures located in the cities given below. Assume an indoor design dry bulb temperature from Table C-L. Windows in the building are double glass. aluminum frame with thermal break. Other external surfaces are well insulated. (a) Sioux City, Iowa (b) Atlanta, Georgia (c) Syracuse, New York (d) Denver, Colorado (e) San Francisco. California (f) Bismarck, North Dakota (g) Rapid City, South Dakota7/19/2020 Eng Charlton Inao
  • 86. PROBLEMS 86 7-2. Estimate the temperature in the crawl space of a building with floor plan dimensions of 30 ×60 ft. The concrete foundation has an average height of 2 ft and the wall is 6-in. thick. Use winter design conditions for Oklahoma City, Oklahoma. 7/19/2020 Eng Charlton Inao
  • 87. PROBLEMS 87 7-3. Estimate the temperature in the knee space shown in Fig. 7-12. The roof is equivalent to 0.5 in. (25 mm) of wood on 2 × 6-in. rafters on 24-in. (0.6-01) centers. The walls are 2 × 4-in. studs on 16-in., (0.4-m) centers with 3.5 in. (90 mm) of insulation. The joist spaces all have 6 in. (150 mm) of insulation. Inside and outside temperatures are 70 F (21 C) and 10 F (-12 C). 7/19/2020 Eng Charlton Inao
  • 89. PROBLEMS 89 7-4. Consider the knee space shown in Fig. 7-12. The vertical dimension is 8 ft, the horizontal dimension is 3 ft. and the space is 20 ft long. The walls and roof surrounding the space all have an overall heat-transfer coefficient of about 0.09 Btu/(hr-ft2-F). Assuming an outdoor temperature of 2 F and an indoor temperature of 68 F, make a recommendation concerning the placement of water pipes in the knee space. 7/19/2020 Eng Charlton Inao
  • 90. PROBLEMS 90 7-5. Estimate the temperature in an unheated basement that is completely below ground level with heated space above. Assume no insulation and dimension of 20 × 20 × 7 ft. The basement is located in Lincoln, Nebraska. Use standard design conditions. 7/19/2020 Eng Charlton Inao
  • 91. PROBLEMS 91 7-6. Rework Example 7-1 assuming that the crawl space experiences an infiltration rate of 0.25 air changes per hour. 7/19/2020 Eng Charlton Inao
  • 92. PROBLEMS 92 7-7. Rework Example 7-2 assuming an infiltration rate of 0.2 air changes per hour. 7/19/2020 Eng Charlton Inao
  • 93. PROBLEMS 93 7-8. A large single-story business office is fitted with nine loose-fitting, double-hung woodsash windows 3 ft wide by 6 ft high. If the outside wind is 15 mph at a temperature of -10 F, what is the percent reduction in sensible heat loss if the windows are weather stripped? Assume an inside temperature of 70 F. Base your solution on a quartering wind. 7/19/2020 Eng Charlton Inao
  • 94. PROBLEMS 94 7-9. Using the crack method compute the infiltration for a tight-fitting swinging door that is used occasionally. The door bas dimensions of 0.9 × 2.0 m and is on the windward side of a bouse exposed to a 9 m/s wind. Neglect internal pressurization and stack effect. 7/19/2020 Eng Charlton Inao
  • 95. PROBLEMS 95 7-10. A room in a single-story building has two 3 × 5-ft wood, double-hung windows of average fit that are not weather stripped. The wind is 20 mph and normal to the wall with negligible pressurization of the room. Find the infiltration rate assuming that the entire crack is admitting air. 7/19/2020 Eng Charlton Inao
  • 96. PROBLEMS 96 7-11. Compute the design infiltration rate and beat gain for the bouse described in Problem 7-16 assuming an orientation normal to a is 15 mph wind. The windows and doors are tight fitting. 7/19/2020 Eng Charlton Inao
  • 97. PROBLEMS 97 7-12. Refer to Example 7-3. (a) Estimate the total pressure difference for each wall for the third and ninth floors. (b) Using design conditions for Denver, Colorado, estimate the heat load due to infiltration for the third floors and ninth floors. 7/19/2020 Eng Charlton Inao
  • 98. PROBLEMS 98 7-13. Refer to Examples 7-3 and 7-4. (a) Estimate the infiltration rates for the windward and side doors for a low traffic rate. (b) Estimate the curtain wall infiltration for the first floor. (c) Compute the heat load due to infiltration for the first floor if the building is located in Cleveland. Ohio. 7/19/2020 Eng Charlton Inao
  • 99. PROBLEMS 99 7-14. A 20-story office building has plan dimensions of 100 × 60 ft and is oriented-at 45 degrees to a 20 mph wind. All windows are fixed in place. There are double vestibule-type swinging doors on the 6O-ft walls. The walls are average curtain wall construction and the doors have about i-in. cracks. (a) Compute the pressure differences for each wall due to wind and stack effect for the first, fifth, fifteenth, and twentieth floors. (b) Plot pressure difference versus height for each wall and estimate which surfaces have infiltration and exfiltration. (c) Compute the total infiltration rate for the first floor assuming a very low traffic rate. Compute the infiltration rate for the fifteenth floor. (e) Compute the infiltration rate for the twentieth floor. Neglect any leakage through the roof. 7/19/2020 Eng Charlton Inao
  • 100. PROBLEMS 100 7-15. Refer to Problem 7-14. (a) Compute the heat gain due to infiltration for the first floor with the building located in Dallas, Texas. (b) Compute the heat gain due to infiltration for the fifteenth floor. (c) what is the heat gain due to infiltration for the twentieth floor? 7/19/2020 Eng Charlton Inao
  • 101. PROBLEMS 101 7-17. Rework Problem 7-16 for Lincoln, Nebraska. Include infiltration in the analysis. 7/19/2020 Eng Charlton Inao
  • 102. PROBLEMS 102 7-18. Consider a building located in Syracuse, New York. Using ASHRAE Standard recommendations, compute the transmission loss for (a) a wall like Table 5-7a, case 2, which is 3 × 4 m with a window of 1 m2 area, (b) a single pane window with aluminum frame and no thermal break, (c) a roof-ceiling combination that is like Table 5-7b, case 1, with an area of 16 m2. 7/19/2020 Eng Charlton Inao
  • 105. PROBLEMS 105 7-20. A small commercial building has a computed heat load of 200,000 Btu/hr sensible and 25,000 Btu/hr latent. Assuming a 50 F temperature rise for the heating unit, compute the quantity of air to be supplied by the unit using the following methods: (a) Use a psychrometric chart with room conditions of 70F and 30 percent relative humidity. (b) Calculate the air quantity based on the sensible heat transfer. 7/19/2020 Eng Charlton Inao