ME 425 – Heating Load Calculation

Heating Load Calculation

ME 425
Air Conditioning System Design
Keith E. Elder, P.E.

Heating Load Calculation
The heating load calculation begins with the
determination of heat loss through a variety
of building envelope components and
situations.
Walls
Windows
Exposed Floors
Basement Walls
Infiltration
Duct Loss

Roofs
Doors
Slab-on-Grade Floors
Basement Floors
Ventilation
Building Pickup

1
ME 425 – Heating Load Calculation

The Heat Loss Equation
q = Uo x A ( Ti - To )
Where:
Uo = the overall heat transfer
coefficient, Btu/hr/ft2/°F
A = the surface area, ft2
Ti = the indoor design temperature, °F
To = the outdoor design temperature, °F

Heat Loss Equation Assumptions
Steady State Conditions
No Thermal Storage
Heat Transfer is Instantaneous

One-Dimensional Parallel "Heat Flow"
Thermally Homogeneous Construction
Construction Anomalies can be Accounted for by
Transmission “Weighting” Corrections
Heat flow path “ignores” temperature variations
due to construction anomalies

2
ME 425 – Heating Load Calculation

Solving the Heat Loss Equation
Area Takeoffs (from plans with est. zoning)
Design Temperatures (‘05F28 CD & Std. 55)
Assembly U-factors, Uo:
Uo
= 1/ RTotal
RTotal

=

R1 + R2 + Rn + ...

R1, R2 and Rn represent the thermal resistance of each of
the elements in the path of the "heat flow.”
Properties of typical construction materials can be found
in Table 3 of ‘05F25.

Construction Material Properties

3
ME 425 – Heating Load Calculation

Air Film Properties
From ’05F25.2

Air Gap Properties
From ’05F25.4

4
ME 425 – Heating Load Calculation

Wall with no Framing Elements
What is the U-factor of a 3-1/2 inch wall
composed of 4 inch brick, R-11
insulation and 5/8 inch gypboard?
Outside Air Film
4" Brick
R-11 Batt Insulation
5/8" Gypboard
Inside Air Film

Ri
0.17
0.40
11.00
0.56
0.68

Total R =

12.81

Uo = 1/R
= 1/12.81
= 0.078

Btu
Hr-SF-deg F

Correcting for Cavity Depth
The R-value of batt insulation is rated by
manufacturers for predetermined depths.
Corrections must be made to calculations for
installation in non-standard cavities.
TABLE 20-A
R-Value of Fiberglass Batts Compressed within Various Depth Cavities
Insulation R-Value at Standard Thickness
R-Value
Standard Thickness
Nominal
Actual
Lumber Depth of
Cavity,
Sizes,
Inches
Inches
2 x 12
11-1/4
2 x 10
9-1/4
2x8
7-1/4
2x6
5-1/2
2x4
3-1/2
2x3
2-1/2
2x2
1-1/2"
2x1
3/4"

38
30
12" 9-½ "

22
21
19
15
13
11
8
5
6-¾ " 5-½ " 6-¼ " 3-½ " 3-5/8" 3-½ " 2-½ " 1-½ "

3
¾"

Insulation R-Values when Installed in a Confined Cavity

37
32
27
------

-30
26
21
-----

---20
14
----

---21
-----

---18
13
----

----15
----

----13
9.8
6.3
--

----11
-6.0
--

------5.7
--

------5.0
3.2

-------3.0

5
ME 425 – Heating Load Calculation

Correcting for Wood Framing
What is the U-factor of the previous
example if the wall is framed with
Douglas Fir studs spaced 16" on-center.
Outside Air Film
4" Brick
R-11 Batt Insulation
3-1/2" Fir Stud
5/8" Gypboard
Inside Air Film

Through
Insulation
0.17
0.40

Through
16" OC Stud
0.17
0.40

11.0
0.56
0.68

3.50
0.56
0.68

Total R =

12.81

5.31

Uo

=

0.078

0.188

Uavg

= 0.20 x 0.188 + 0.80 x 0.078
=

0.100

Btu/(hr-S.F.-F)

What About Metal Studs?
Transmission “weighting”
is not appropriate if the
conductivity of the
penetration exceeds that
of the layer being
penetrated by more than
an order of magnitude.
Isotherms

6
ME 425 – Heating Load Calculation

Correcting for Metal Studs
ASHRAE Standard 90.1 Correction Factors
Size of
Members
2x4
2x4
2x6
2x6

Framing
16 in. O.C.
24 in. O.C.
16 in. O.C.
24 in. O.C

Insulation Correction
R-Value Factor, Fc
R-11
0.50
R-11
0.60
R-19
0.40
R-19
0.45

Using Metal Stud Factors
What is the heat loss of the wall in the
first example if the wall is framed with 31/2" metal studs spaced 16" on-center?
Ri
Outside Air Film
0.17
4" Brick
0.40
R-11 + Mtl. Stud (11.0 x 0.50) = 5.50
0.56
5/8" Gypboard
0.68
Inside Air Film
Total R =
Uo

= 1/7.31 =

7.31
0.137

Btu
Hr-SF-deg F

7
ME 425 – Heating Load Calculation

ASHRAE Window Performance
Because of
conductive
spacers,
frames & new
coatings
available,
window Ufactors cannot
be calculated
accurately.

ASHRAE Window Performance
Reasonable estimates can be found in
Table 4, ‘05F31.8.

8
ME 425 – Heating Load Calculation

ASHRAE Window U-factors

ASHRAE Window U-factors

9
ME 425 – Heating Load Calculation

Door U-Factors
Door U-factors
can be found in
Table 4,
‘05F31.11.

Floors on Grade
qslab = F2 x Perimeter x ∆T

10
ME 425 – Heating Load Calculation

Floors on Grade - F2 Factors

Infiltration
The uncontrolled inward air leakage
through cracks and interstices in any
building element and around windows
and doors of a building, caused by the
pressure effects of wind and/or the
effect of differences in the
outdoor/indoor air density.
qinfiltration = 0.018Q∆T
Q = air flow due to infiltration, ft3/hr

11
ME 425 – Heating Load Calculation

Infiltration Estimates
From the 1972 Fundamentals Manual:
Number of Air
Changes Taking
Kind of Room or Building
Place per Hour
Rooms with no windows or exterior doors
1/2
Rooms with windows/exterior doors on one side
1
Rooms with windows/exterior doors on two sides
1-1/2
Rooms with windows/exterior doors on three sides
2
Entrance Halls
2
Note: Values may be reduced by 1/3 if windows & doors
weatherstripped

In-Class Heating Load Exercise
What is the heat loss for a Seattle office space 12
feet deep by 50 feet long, with 10 foot ceilings and
floor-to-floor spacing of 12 feet? The office zone is
located on the third floor of a five story building. The
wall is constructed of 6 inch concrete, with R-11
batt insulation installed between metal studs 16
inch on-center, and 5/8 inch gypsum board. The
window is insulated 1/4 inch glass with 1/2 inch air
space and composes 40 percent of the gross wall
area. The window framing is metal and has no
thermal break.

12
ME 425 – Heating Load Calculation

Building & Space Sketch

50’

12’
10’

12’

Section Sketch
Outside Air Film
6 Inch Concrete
R-11 Batt Insulation
between mtl studs 16” O.C.
5/8 Inch Sheet Rock
Inside Air Film
Total R =
Uwall

=

13

More Related Content

PDF
HVAC Design Project
PPTX
Heating and cooling load of a building
PPSX
AIR CONDITIONING LOAD CALCULATIONS PRESENTATIONS by EVRAJU
PDF
12 Cooling Load Calculations
PPTX
Load estimation in Air Conditioning
PDF
Cooling load estimation
PDF
Cooling load calculations
PDF
Cooling load problems
HVAC Design Project
Heating and cooling load of a building
AIR CONDITIONING LOAD CALCULATIONS PRESENTATIONS by EVRAJU
12 Cooling Load Calculations
Load estimation in Air Conditioning
Cooling load estimation
Cooling load calculations
Cooling load problems

What's hot (20)

PPT
HVAC Cooling Load Calculation
PPTX
Air distribution Product
PDF
Cooling and heating load calculations tide load4z
PDF
Basics of HVAC - Part 1 (Heating Ventilation Air Conditioning)
PPT
HVAC Fundamentals
PPTX
PPTX
Chiller water systems
PPTX
Air Conditioning & Hvac Systems
PPTX
HVAC Basics
PDF
VRF system presentation !
PPTX
Hvac - presentation (Air conditioning presentation)
PPT
PPT
Hvac presentation for beginers
PPTX
HVAC introduction
PPTX
Air Conditioning Systems in Refrigeration and Air Conditioning
PPT
Hvac Presentation
PPTX
Hvac duct design
PPTX
Chilled water systems
PDF
Variable refrigerant flow systems
HVAC Cooling Load Calculation
Air distribution Product
Cooling and heating load calculations tide load4z
Basics of HVAC - Part 1 (Heating Ventilation Air Conditioning)
HVAC Fundamentals
Chiller water systems
Air Conditioning & Hvac Systems
HVAC Basics
VRF system presentation !
Hvac - presentation (Air conditioning presentation)
Hvac presentation for beginers
HVAC introduction
Air Conditioning Systems in Refrigeration and Air Conditioning
Hvac Presentation
Hvac duct design
Chilled water systems
Variable refrigerant flow systems
Ad

Similar to Heat Load Calculation (20)

PPS
Thermal Performance
PPT
4A Group 8 - Problem Set #2
PPT
thermal conductivity.ppt
PPT
04_thermal.ppt
PPT
Heat Transfer.ppt
PDF
Ht analysis of conduction through wall OEP
PPT
Assignment2
PPT
4a group4 edited
PPT
4a Group4
PDF
Jim Malek - insulation, performance & certification
PDF
duct thermal Insulation hvac standard.pdf
PDF
HEAT AND MASS TRANSFER Question Bank.pdf
PPT
Part two audio demonstration
PPT
9. Lec-14 Overall Heat transfer coefficient.ppt
PDF
ECONOMIC INSULATION FOR INDUSTRIAL PIPING
PPT
4B group 4
PDF
HEAT LOAD EDITED.pdf
PPT
Group4 4 Ch E B
PPT
Thermal Insulation System for energy efficient buildings
PDF
Zmr heating load calculation
Thermal Performance
4A Group 8 - Problem Set #2
thermal conductivity.ppt
04_thermal.ppt
Heat Transfer.ppt
Ht analysis of conduction through wall OEP
Assignment2
4a group4 edited
4a Group4
Jim Malek - insulation, performance & certification
duct thermal Insulation hvac standard.pdf
HEAT AND MASS TRANSFER Question Bank.pdf
Part two audio demonstration
9. Lec-14 Overall Heat transfer coefficient.ppt
ECONOMIC INSULATION FOR INDUSTRIAL PIPING
4B group 4
HEAT LOAD EDITED.pdf
Group4 4 Ch E B
Thermal Insulation System for energy efficient buildings
Zmr heating load calculation
Ad

Recently uploaded (20)

PDF
Nidhal Samdaie CV - International Business Consultant
PPTX
ICG2025_ICG 6th steering committee 30-8-24.pptx
DOCX
Business Management - unit 1 and 2
PDF
Stem Cell Market Report | Trends, Growth & Forecast 2025-2034
PDF
Dr. Enrique Segura Ense Group - A Self-Made Entrepreneur And Executive
PDF
COST SHEET- Tender and Quotation unit 2.pdf
PDF
How to Get Funding for Your Trucking Business
PPTX
HR Introduction Slide (1).pptx on hr intro
PDF
Unit 1 Cost Accounting - Cost sheet
PDF
Reconciliation AND MEMORANDUM RECONCILATION
PPTX
job Avenue by vinith.pptxvnbvnvnvbnvbnbmnbmbh
PDF
SIMNET Inc – 2023’s Most Trusted IT Services & Solution Provider
PDF
Katrina Stoneking: Shaking Up the Alcohol Beverage Industry
PPTX
Business Ethics - An introduction and its overview.pptx
PPTX
Lecture (1)-Introduction.pptx business communication
DOCX
unit 2 cost accounting- Tender and Quotation & Reconciliation Statement
PPTX
AI-assistance in Knowledge Collection and Curation supporting Safe and Sustai...
PPT
340036916-American-Literature-Literary-Period-Overview.ppt
PDF
Ôn tập tiếng anh trong kinh doanh nâng cao
PPTX
Probability Distribution, binomial distribution, poisson distribution
Nidhal Samdaie CV - International Business Consultant
ICG2025_ICG 6th steering committee 30-8-24.pptx
Business Management - unit 1 and 2
Stem Cell Market Report | Trends, Growth & Forecast 2025-2034
Dr. Enrique Segura Ense Group - A Self-Made Entrepreneur And Executive
COST SHEET- Tender and Quotation unit 2.pdf
How to Get Funding for Your Trucking Business
HR Introduction Slide (1).pptx on hr intro
Unit 1 Cost Accounting - Cost sheet
Reconciliation AND MEMORANDUM RECONCILATION
job Avenue by vinith.pptxvnbvnvnvbnvbnbmnbmbh
SIMNET Inc – 2023’s Most Trusted IT Services & Solution Provider
Katrina Stoneking: Shaking Up the Alcohol Beverage Industry
Business Ethics - An introduction and its overview.pptx
Lecture (1)-Introduction.pptx business communication
unit 2 cost accounting- Tender and Quotation & Reconciliation Statement
AI-assistance in Knowledge Collection and Curation supporting Safe and Sustai...
340036916-American-Literature-Literary-Period-Overview.ppt
Ôn tập tiếng anh trong kinh doanh nâng cao
Probability Distribution, binomial distribution, poisson distribution

Heat Load Calculation

  • 1. ME 425 – Heating Load Calculation Heating Load Calculation ME 425 Air Conditioning System Design Keith E. Elder, P.E. Heating Load Calculation The heating load calculation begins with the determination of heat loss through a variety of building envelope components and situations. Walls Windows Exposed Floors Basement Walls Infiltration Duct Loss Roofs Doors Slab-on-Grade Floors Basement Floors Ventilation Building Pickup 1
  • 2. ME 425 – Heating Load Calculation The Heat Loss Equation q = Uo x A ( Ti - To ) Where: Uo = the overall heat transfer coefficient, Btu/hr/ft2/°F A = the surface area, ft2 Ti = the indoor design temperature, °F To = the outdoor design temperature, °F Heat Loss Equation Assumptions Steady State Conditions No Thermal Storage Heat Transfer is Instantaneous One-Dimensional Parallel "Heat Flow" Thermally Homogeneous Construction Construction Anomalies can be Accounted for by Transmission “Weighting” Corrections Heat flow path “ignores” temperature variations due to construction anomalies 2
  • 3. ME 425 – Heating Load Calculation Solving the Heat Loss Equation Area Takeoffs (from plans with est. zoning) Design Temperatures (‘05F28 CD & Std. 55) Assembly U-factors, Uo: Uo = 1/ RTotal RTotal = R1 + R2 + Rn + ... R1, R2 and Rn represent the thermal resistance of each of the elements in the path of the "heat flow.” Properties of typical construction materials can be found in Table 3 of ‘05F25. Construction Material Properties 3
  • 4. ME 425 – Heating Load Calculation Air Film Properties From ’05F25.2 Air Gap Properties From ’05F25.4 4
  • 5. ME 425 – Heating Load Calculation Wall with no Framing Elements What is the U-factor of a 3-1/2 inch wall composed of 4 inch brick, R-11 insulation and 5/8 inch gypboard? Outside Air Film 4" Brick R-11 Batt Insulation 5/8" Gypboard Inside Air Film Ri 0.17 0.40 11.00 0.56 0.68 Total R = 12.81 Uo = 1/R = 1/12.81 = 0.078 Btu Hr-SF-deg F Correcting for Cavity Depth The R-value of batt insulation is rated by manufacturers for predetermined depths. Corrections must be made to calculations for installation in non-standard cavities. TABLE 20-A R-Value of Fiberglass Batts Compressed within Various Depth Cavities Insulation R-Value at Standard Thickness R-Value Standard Thickness Nominal Actual Lumber Depth of Cavity, Sizes, Inches Inches 2 x 12 11-1/4 2 x 10 9-1/4 2x8 7-1/4 2x6 5-1/2 2x4 3-1/2 2x3 2-1/2 2x2 1-1/2" 2x1 3/4" 38 30 12" 9-½ " 22 21 19 15 13 11 8 5 6-¾ " 5-½ " 6-¼ " 3-½ " 3-5/8" 3-½ " 2-½ " 1-½ " 3 ¾" Insulation R-Values when Installed in a Confined Cavity 37 32 27 ------ -30 26 21 ----- ---20 14 ---- ---21 ----- ---18 13 ---- ----15 ---- ----13 9.8 6.3 -- ----11 -6.0 -- ------5.7 -- ------5.0 3.2 -------3.0 5
  • 6. ME 425 – Heating Load Calculation Correcting for Wood Framing What is the U-factor of the previous example if the wall is framed with Douglas Fir studs spaced 16" on-center. Outside Air Film 4" Brick R-11 Batt Insulation 3-1/2" Fir Stud 5/8" Gypboard Inside Air Film Through Insulation 0.17 0.40 Through 16" OC Stud 0.17 0.40 11.0 0.56 0.68 3.50 0.56 0.68 Total R = 12.81 5.31 Uo = 0.078 0.188 Uavg = 0.20 x 0.188 + 0.80 x 0.078 = 0.100 Btu/(hr-S.F.-F) What About Metal Studs? Transmission “weighting” is not appropriate if the conductivity of the penetration exceeds that of the layer being penetrated by more than an order of magnitude. Isotherms 6
  • 7. ME 425 – Heating Load Calculation Correcting for Metal Studs ASHRAE Standard 90.1 Correction Factors Size of Members 2x4 2x4 2x6 2x6 Framing 16 in. O.C. 24 in. O.C. 16 in. O.C. 24 in. O.C Insulation Correction R-Value Factor, Fc R-11 0.50 R-11 0.60 R-19 0.40 R-19 0.45 Using Metal Stud Factors What is the heat loss of the wall in the first example if the wall is framed with 31/2" metal studs spaced 16" on-center? Ri Outside Air Film 0.17 4" Brick 0.40 R-11 + Mtl. Stud (11.0 x 0.50) = 5.50 0.56 5/8" Gypboard 0.68 Inside Air Film Total R = Uo = 1/7.31 = 7.31 0.137 Btu Hr-SF-deg F 7
  • 8. ME 425 – Heating Load Calculation ASHRAE Window Performance Because of conductive spacers, frames & new coatings available, window Ufactors cannot be calculated accurately. ASHRAE Window Performance Reasonable estimates can be found in Table 4, ‘05F31.8. 8
  • 9. ME 425 – Heating Load Calculation ASHRAE Window U-factors ASHRAE Window U-factors 9
  • 10. ME 425 – Heating Load Calculation Door U-Factors Door U-factors can be found in Table 4, ‘05F31.11. Floors on Grade qslab = F2 x Perimeter x ∆T 10
  • 11. ME 425 – Heating Load Calculation Floors on Grade - F2 Factors Infiltration The uncontrolled inward air leakage through cracks and interstices in any building element and around windows and doors of a building, caused by the pressure effects of wind and/or the effect of differences in the outdoor/indoor air density. qinfiltration = 0.018Q∆T Q = air flow due to infiltration, ft3/hr 11
  • 12. ME 425 – Heating Load Calculation Infiltration Estimates From the 1972 Fundamentals Manual: Number of Air Changes Taking Kind of Room or Building Place per Hour Rooms with no windows or exterior doors 1/2 Rooms with windows/exterior doors on one side 1 Rooms with windows/exterior doors on two sides 1-1/2 Rooms with windows/exterior doors on three sides 2 Entrance Halls 2 Note: Values may be reduced by 1/3 if windows & doors weatherstripped In-Class Heating Load Exercise What is the heat loss for a Seattle office space 12 feet deep by 50 feet long, with 10 foot ceilings and floor-to-floor spacing of 12 feet? The office zone is located on the third floor of a five story building. The wall is constructed of 6 inch concrete, with R-11 batt insulation installed between metal studs 16 inch on-center, and 5/8 inch gypsum board. The window is insulated 1/4 inch glass with 1/2 inch air space and composes 40 percent of the gross wall area. The window framing is metal and has no thermal break. 12
  • 13. ME 425 – Heating Load Calculation Building & Space Sketch 50’ 12’ 10’ 12’ Section Sketch Outside Air Film 6 Inch Concrete R-11 Batt Insulation between mtl studs 16” O.C. 5/8 Inch Sheet Rock Inside Air Film Total R = Uwall = 13