SlideShare a Scribd company logo
International Journal of Electrical and Computer Engineering (IJECE)
Vol. 8, No. 1, February 2018, pp. 76~86
ISSN: 2088-8708, DOI: 10.11591/ijece.v8i1.pp76-86  76
Journal homepage: http://iaescore.com/journals/index.php/IJECE
Coordination of Adaptive Neuro Fuzzy Inference System
(ANFIS) and Type-2 Fuzzy Logic System-Power System
Stabilizer (T2FLS-PSS) to Improve a Large-scale Power System
Stability
Agung B. Muljono1
, I. M. Ginarsa2
, I. M. A. Nrartha3
, A. Dharma4
1,2,3
Department of Electrical Engineering, University of Mataram, NTB, Indonesia
4
Department of Electrical Engineering, Udayana University, Bali, Indonesia
Article Info ABSTRACT
Article history:
Received Sep 15, 2017
Revised Dec 30, 2017
Accepted Jan 14, 2018
Intelligent control included ANFIS and type-2 fuzzy (T2FLS) controllers
grown-up rapidly and these controllers are applied successfully in power
system control. Meanwhile, small signal stability problem appear in a large-
scale power system (LSPS) due to load fluctuation. If this problem persists,
and can not be solved, it will develop blackout on the LSPS. How to improve
the LSPS stability due to load fluctuation is done in this research by
coordinating of PSS based on ANFIS and T2FLS. The ANFIS parameters are
obtained automatically by training process. Meanwhile, the T2FLS
parameters are determined based on the knowledge that obtained from the
ANFIS parameters. Input membership function (MF) of the ANFIS is 5
Gaussian MFs. On the other hand, input MF of the T2FLS is 3 Gaussian
MFs. Results show that the T2FLS-PSS is able to maintain the stability by
decreasing peak overshoot for rotor speed and angle. The T2FLS-PSS makes
the settling time is shorter for rotor speed and angle on local mode oscillation
as well as on inter-area oscillation than conventional/ ANFIS-PSS. Also, the
T2FLS-PSS gives better performance than the other PSS when tested on
single disturbance and multiple disturbances.
Keyword:
ANFIS
Large-scale
PSS
Stability improvement
T2FLS
Copyright © 2018 Institute of Advanced Engineering and Science.
All rights reserved.
Corresponding Author:
Agung B. Muljono,
Dept. of Electrical Engineering,
University of Mataram,
Jln. Majapahit No. 62 Mataram, NTB, Indonesia.
+62 370 636 755
Email: agungbm@unram.ac.id
1. INTRODUCTION
Controller based on artificial intelligent is the research topic interest in recent year. Because the
intelligent control has learning ability to improve its performance from the environment where the controller
is applied. The spreading of intelligent control exists on some fields such as: Electrical and electronic
engineering, and computer science such as: Fuzzy controller is used to enhance photovoltaic generator power
quality by maintaining the MPPT tracking on low voltage side of DC/DC boost converter. The MPPT-fuzzy
controller is able to maintain voltage profile and current total harmonic distortion (THD) [1]. The
performance of fuzzy controller is compared to the PI controller on two inverter fed to control six-phase
permanent magnet synchronous machine (PMSM) operated as a motor. The simulation results show that the
fuzzy controller are more robust, quick response on high starting torque and more effective the PI
controller [2]. Support vector machine (SVM) method is used to classify a large-scale power system transient
stability. The SVM method gives a better result than multi-layer perceptron-neural network (MLP-NN)
Int J Elec & Comp Eng ISSN: 2088-8708 
Coordination of Adaptive Neuro Fuzzy Inference System (ANFIS) and Type-2 Fuzzy …. (Agung B. Muljono)
77
method [3]. Adaptive neuro-fuzzy inference system (ANFIS) controllers have been implemented in
3-machine 9-bus power systems. Where, the ANFIS controllers are able to maintain the dynamic stability of
the multimachine power systems significantly [4], [5]. Neural network controller is used as a feedback
control to improve the dynamic performance of single synchronous machine connected to infinite bus [6].
Adaptive fuzzy rule-based PSS [7] and fuzzy logic PSS [8], [9] are also successful applied to maintain
dynamic stability of a power system. Meanwhile, Type-2 fuzzy logic system (T2FLS) is applied to
coordination of excitation and governor systems [10]. In [11], the T2FLS is used as a PSS and tuning of its
parameter is optimized by differential evolution algorithm to cover the uncertainty of disturbances. An
indirect adaptive T2FLS-PSS is implemented to damp out of the low frequency oscillation on different
operating condition of a power system [12].
While, power system companies that serve consumers on a wide-area continuously with standard
quality assurance and without interruption. Some generation units such as: Hydro, thermal, nuclear and gas
power plants are connected to bulk power systems via interconnecting transmission line including high
voltage direct current (HVDC) system. On the other hand, almost of consumers are located in city areas such
as: Trade/commercial and official complex areas, suburban area, industrial area and residential area. Analysis
of a large-scale power system (LSPS) network is usually very complicated and difficult. The simplifying
scheme should be done to resolve this complicated network problem. In this research, the LSPS is divide into
three parts of small operation areas [13]. In operation time, imbalance of energy in respective synchronous
machine makes the rotor machine oscillate due to load fluctuation at one or some load buses. When the rotor
machines are oscillate continuously without any control scheme, this situation can cause the LSPS going into
instability problem.
To cover this rotor oscillation problem, power system stabilizer (PSS) is proposed at excitation
system of synchronous machine to damp the rotor oscillation. Where, local mode stability of a pump storage
power plant is significantly improved by using the PSS [14]. Furthermore, performance of a conventional
PSS is maintained by using additional or auxiliary loop [15]. PSS based on optimal and sub-optimal linear
quadratic regulator design are proposed to improve stability of power system. In this design, only speed
deviation and PSS states are considered as the inputs, while the coupling gain between machines are
neglected [16]. The function of conventional control is instead by the neural network, fuzzy or neuro-fuzzy
controls. Proportional integral and derivative-static var compensator based on recurrent neural network is
applied to control chaos and voltage collapse in a power system. This control scheme is able to suppress
chaos and voltage collapse in power systems [17]. Adaptive critic design based (ADC) neuro-fuzzy controller
is applied to control the static compensator in a LSPS. It is shown that the ADC neuro-fuzzy controller is
more effective than PI controller in responding to small disturbance and short circuit fault [18]. Also, a
Mamdani fuzzy controller is applied to hardware implementation to static compensator in a LSPS [19]. The
ANFIS-based composite controller-SVC and PID-loop are applied to control chaos and voltage collapse and
to regulate the voltage at load bus with loading fluctuation [20], [21]. Also, the ANFIS controller is tried to
maintain dynamic response of HVDC system [22] and to protect the HVDC devices from the short
circuit [23]. Furthermore, ANFIS power system stabilizer (PSS) has been applied to improve the stability of
single machine based on feedback linearization [24].
According to wide range usability and previous research of the ANFIS and T2FLS applications in
power system. We aim to evaluate the control strategy of ANFIS and T2FLS-based power system stabilizer
to improve stability of a large-scale power system in this research. Where, the ANFIS method is used in this
research because the ANFIS is able to train from time-series data. Parameters of ANFIS controller are
obtained by training processes in off-line mode. The parameters of ANFIS controller are adjusted
automatically during the training processes using data training. The data training is obtained by simulating
the system equipped with conventional PSS and load capacity of the LSPS is varied. Meanwhile, T2FLS
method is used in this research because the T2FLS is able to cover the input, membership function, and
output with uncertainty. Also, T2FLS membership function and rules are designed based on the knowledge
of the designer. The paper is organized as follows: Stability of a power system is described in Section 2.
Design of ANFIS and T2FLS-based power system stabilizer is explained in Section 3. Next, result and
discussion are presented in Section 4. And, the conclusion is provided in the last section.
2. POWER SYSTEM STABILITY
Stability is defined as the ability of power system to cover the disturbance at normal operation the
effort to maintain the power system going to steady state after the disturbance is disappeared. Dynamical
behavior of a single machine connected to infinite bus is depended on interaction of turbine, generator, also
the controller characteristic such as governor and excitation systems. Dynamical of a single machine
formulas in linear model are as follows [25] :
 ISSN: 2088-8708
Int J Elec & Comp Eng, Vol. 8, No. 1, February 2018 : 76 – 86
78
̇ (1)
̇ (2)
A large-scale power system (LSPS) consists of two or more local power system areas. Topology of
existing LSPS usually follows the geographic surfaces. Which is the local area is connected to the other by
transmission line to form the LSPS. The LSPS in this research is taken from Padiyar [26]. This system
consist of 39 buses and 10 machines. Furthermore, the system was simplified to Area I, Area II and Area III,
and shown in Figure 1. The Machine-1 (M1) at Bus 1 was treated as a reference bus. Furthermore, the speed
and angle rotor deviation was taken as zero values, respectively.
Figure 1. A large-scale power system
Power system stabilizer (PSS) provides additional damping to rotor oscillation of machine by
regulating its excitation system through an additional stabilizing signal. The PSS produces an electrical
torque component in phase with the rotor speed deviation to provide the additional damping torque. The PSS
is very important to improve stability of overall power systems. Since the PSS is to introduce a damping
torque component, a logical signal to use for regulating excitation system of machine is rotor speed deviation.
And, output of the PSS is the additional voltage compensation that feeding to the excitation system.
Conventional PSS consist of gain, washout and phase compensation blocks. The gain block determines the
amount of damping introduce by the PSS. The signal washout block serves as a high frequency filter, with
the time constant T. The phase compensation block provides appropriate phase lead characteristic to
compensate the phase lag between exciter input and generator (air-gap) electrical torque.
3. DESAIN OF PSS BASED ON ARTIFICIAL INTELLIGENT
3.1. PSS based on ANFIS Controller
An adaptive neuro-fuzzy inference system or adaptive network-based fuzzy inference system
(ANFIS) is a kind of artificial neural network that is based on Takagi–Sugeno fuzzy inference system. Since
it integrates both neural networks and fuzzy logic principles, it has potential to capture the benefits of both
models in a single framework. Its inference system corresponds to a set of fuzzy IF-THEN rules that have
learning capability to approximate nonlinear functions.
Hence, ANFIS is considered to be a universal estimator. The ANFIS consists of premise and
consequence parameters. The ANFIS function is same as the fuzzy rule based on Sugeno algorithm. So, both
the parameters are obtained by off-line learning processes with least squares estimation (LSE) and back-
propagation algorithms. At forward step, the parameters are identified by using LSE method. And, at
backward step the parameters are maintained by using gradient descent optimization. Suppose that the
Int J Elec & Comp Eng ISSN: 2088-8708 
Coordination of Adaptive Neuro Fuzzy Inference System (ANFIS) and Type-2 Fuzzy …. (Agung B. Muljono)
79
ANFIS network has 2 (two) inputs x, y and an output O, with 2 (two) rules based on first-order fuzzy model
Sugeno [27]:
(3)
Output of the ANFIS-network is formulated follow:
∑ ∑
∑
(4)
The ANFIS-based PSS is designed by some learning processes in off-line mode. Data training that
used for this learning process were obtained by simulating the conventional PSS. To obtain the data training,
the LSPS is equipped by conventional PSS. The result of the training stage was the ANFIS-based PSS and
this PSS was applied to replace the conventional PSS. And, the ANFIS-based PSS membership function for
rotor speed deviation is illustrated in Figure 2.
Figure 2. Membership function for input ANFIS of 3
3.2. PSS based on Type-2 Fuzzy Logic System (T2FLS) Controller
Type-2 fuzzy system is a class of fuzzy logic system which the antecedent or consequent
membership functions are type-2 fuzzy sets. The concept of a type-2 fuzzy set is defined as an extension of
the concept of an ordinary set (henceforth call a type-1 fuzzy set). The structure of a T2FLS is quite similar
to a T1FLS. The difference is that on the antecedent and/or consequent sets of the T2FLS are type-2 and each
rule output set is a type-2 also. The T2FLS consist of five parts such as [28], [29]: Fuzzifier, rule base,
inference engine, type reducer and defuzzifier parts. Block diagram of type-2 FLS and membership function
of input 3 are shown in Figure 3(a) and Figure 3(b), respectively.
Figure 3. PSS based on the type-2 logic fuzzy system
 ISSN: 2088-8708
Int J Elec & Comp Eng, Vol. 8, No. 1, February 2018 : 76 – 86
80
a. Fuzzifier
The fuzzifier maps a crisp input vector with n input fuzzy sets. Singleton type-2 fuzzy input sets ( ̃ )
are considered in this research. Where, in the singleton fuzzification, the input fuzzy set has only a single
point of non-zero membership. So, the ̃ is a T2 fuzzy singleton if = 1 for = and ̃ = 0 for
all , ( ).
b. Rule base
For an interval type-2 fuzzy logic system (IT2FLS), the j-th is written as follows:
If is and,..., If is Then is (5)
where the are antecedent type-2 sets, y  Y is the output and are the consequent T2 sets. This rule
represents a T2 fuzzy relation between the input and the output space on the FLS.
c. Fuzzy Inference
For the IT2FLS, product operation is considered to implement with minimum or t-norm, the firing
interval V j
of the j-th rule is an interval type-2 set, which is determined by its left most point and right most
point and :
[ ] [ ] (6)
where X0
is the instantaneous value of X. The firing interval bounds for the j-th rule of an IT2FLS with n
inputs and are written as follows:
∏ (7)
∏ (8)
d. Type Reduction
Type reduction process aims to change the T-2 output of inference system to a type-1 set. Where,
center of sets (COS) type reduction method is considered in this research. This method is more effective
computation than other methods and requires less time computation. The COS method is written as follows:
∑
∑
(9)
where is the interval set determined by two end points and , [ ] is the
type-2 interval consequent set and, [ ] is the firing interval.
e. Defuzzification
Next, the type reduced set is determined by its left most point and right most point
. Using the center of gravity, the defuzzified crisp output is given by
(10)
In this research we use Matlab/Simulink toolbox to generate the type-2 fuzzy logic system that provided by
Taskin and Kumbasar [30], [31].
4. RESULT AND DISCUSSION
Three PSS types are applied to improve the stability of a large-scale power system in this research.
The simulation procedure are as follows: The Machine-2 (M2) is equipped by ANFIS-PSS. While, the
Machine-3 (M3), Machine-7 (M7) and Machine-9 (M9) are equipped by conventional, ANFIS and T2FLS-
PSS. The responses are observed on 3 and 3 for local mode oscillation. Also, the responses are observed
Int J Elec & Comp Eng ISSN: 2088-8708 
Coordination of Adaptive Neuro Fuzzy Inference System (ANFIS) and Type-2 Fuzzy …. (Agung B. Muljono)
81
on 7, 9, 7 and 9 for inter-area mode oscillation. The proposed PSS is implemented using the
Matlab/Simulink [32] on an Intel Core 2 Duo E6550 @ 2.33 GHz PC computer.
4.1. Performance of Respective PSS on a Single Disturbance
First Scenario, PSS(s) based on ANFIS and Fuzzy type-2 are evaluated by forcing a single step
mechanical disturbance on Machine-2 at 0.1 pu. When the system was disturbed and simulation results were
observed on the Figure 4, Figure 5 and Figure 6. Also, the result is listed in Table 1.
Figure 4. Stability improvement on (a) 3 and (b)
3 when forced by a single disturbance
Figure 5. Enhancement of the (a) 7 and (b) 7
responses using T2FLS-PSS
Figure 4(a) and Table 1 show the peak overshoot (Po) of the rotor speed deviation (3) was
obtained at the values of 20.14, 21.42 and 19.85103
pu for the T2FLS-PSS, ANFIS-PSS and CONV-
PSS, respectively. In this result, the settling time was achieved at the times of 5.25, 5.72 and 5.97 s,
respectively. Figure 4(b) and Table 1 are responses for rotor angle deviation of M3. It is shown that the peak
overshoot was achieved at the values of 35.94, 35.56 and 35.53 for the T2FLS-PSS, ANFIS-PSS and
CONV-PSS, respectively. The steady state of rotor angle deviation was achieved at the value of 19.52. The
settling time was achieved at the times of 5.62, 5.89 and 6.44 s for the T2FLS-PSS, ANFIS-PSS and
CONV-PSS.
Figure 5(a) and Table 1 are the responses of the rotor speed deviation (7) when the respective
PSS(s) are applied to a large-scale power system. It is shown that the peak overshoot was achieved at the
values of 2.17, 3.59 and 5.57103
pu for the T2FLS-PSS, ANFIS-PSS and CONV-PSS, respectively.
The settling time was obtained at the times of 5.31, 5.83 and 6.55 s for the T2FLS-PSS, ANFIS-PSS and
CONV-PSS. It is shown that the responses of the ANFIS-PSS and CONV-PSS are still oscillated. The
improvement of the rotor angle deviation (7) is shown in Figure 5(b) and listed in Table 1. The T2FLS-
PSS gave the peak overshoot at the value of 8.48 and the settling time at time of 5.46 s. Meanwhile, the
ANFIS-PSS and CONV-PSS gave peak overshoot at the values of 10.25 and 10.23, respectively. The
settling time of the ANFIS-PSS and CONV-PSS was obtained at the times of 6.09 and 6.65 s. Steady state of
the rotor angle was achieved at the value of 6.39 for the T2FLS-PSS, and 5.98 for the ANFIS- and
CONV-PSS.
From Figure 6(a) and Table 1 we see that peak overshoot of the T2FLS-PSS was achieved at the
value of 6.53103
pu for the rotor speed deviation (9). On the other hand, the peak overshoot of the
ANFIS-PSS and CONV-PSS were achieved at the values of 6.65 and 7.09103
pu. The settling time was
obtained at the times of 5.24, 5.74 and 5.98 s, respectively. Furthermore, the responses for the rotor angle
deviation (9) is shown in Figure 6(b) and listed in Table 1.
Simulation result on the First Scenario shows that the T2FLS-PSS is able to improve stability by
observing the rotor speed and angle deviation. The T2FLS-PSS gives peak overshoot smaller than the
ANFIS/CONV-PSS for both rotor speed and angle. Also, the settling time of the T2FLS-PSS is shorter than
the other PSS(s) as well as for the local mode oscillation as well as inter-area mode oscillation.
 ISSN: 2088-8708
Int J Elec & Comp Eng, Vol. 8, No. 1, February 2018 : 76 – 86
82
Figure 6. Performance of respective PSS for the (a) 9 and (b) 9 responses
Table 1. Performance of conventional, ANFIS and T2FLS-PSS to improve stability of a LSPS
PSS-type
3 3
Peak overshoot
[Po]
Settling time Po [tst] Ss
× (−10−3
)(pu) [tst] (s) () (s) ()
CONV-PSS 19.85 5.97 34.53 6.44
ANFIS-PSS 21.42 5.72 35.56 5.89 19.52
T2FLS-PSS 20.14 5.25 35.94 5.62
7 7
CONV-PSS 19.85 5.97 34.53 6.44
ANFIS-PSS 21.42 5.72 35.56 5.89 19.52
T2FLS-PSS 20.14 5.25 35.94 5.62
9 9
CONV-PSS 19.85 5.97 34.53 6.44
ANFIS-PSS 21.42 5.72 35.56 5.89 19.52
T2FLS-PSS 20.14 5.25 35.94 5.62
4.2. Evaluation of Respective PSS on Multiple Disturbances
Second Scenario, we also evaluate the respective PSS(s) by forcing 2 (two) mechanical disturbances
to the Machine-2 sequentially on 0.08 and 0.09 pu at 0.0 and 8.0 s. Stability improvement of M3, M7 and M9
is observed on dynamic responses of rotor speed and angle deviation. These dynamic responses are shown in
Figure 7, Figure 8 and Figure 9. Also, the responses of respective PSS(s) are listed in Table 2.
Figure 7(a) and Table 2 show the dynamic response of the CONV-PSS oscillated with amplitude
between 11.23 and 4.60103
pu. Then, this amplitude was decreased until the response achieved steady
state at time more than 15.0 s. Dynamic response of the ANFIS-PSS also oscillated with amplitude at the
values between 9.75 and 3.19103
pu. On the other hand, dynamic response of T2FLS-PSS went to first
swing and this response increased rapidly to zero (nominal speed). This response was able to achieved steady
state at 4.51 and 12.17 s for first and second disturbances, respectively. Peak overshoot of the T2FLS-PSS for
the second disturbance was achieved at the value of 6.52103
pu. The rotor angle (3) responses of the all
PSS(s) are almost similar. The peak overshoot (Po1) of the T2FLS-PSS, ANFIS-PSS and CONV-PSS were
achieved at the values of 21.34, 21.32 and 21.83, respectively. Next, the rotor angle (3) achieved Po2
at the values of 40.30, 40.32 and 41.23 for the T2FLS-PSS, ANFIS-PSS and CONV-PSS. And, these
responses achieved steady state at around 36.04 and 36.20. This 3 response is shown in Figure 7(b).
The performances of the all PSS(s) are listed in Table 2.
Figure 8(a) and Table 2 show the dynamic response of rotor speed deviation (7) when equipped
by the CONV-PSS. This response oscillated with amplitude between 1.81 and 0.65103
pu. Then, this
amplitude was decreased until the the response achieved steady state at time of more than 15.0 s. Dynamic
response of the ANFIS-PSS also oscillated with amplitude at the values between 2.33 and 0.64103
pu.
(b).
Int J Elec & Comp Eng ISSN: 2088-8708 
Coordination of Adaptive Neuro Fuzzy Inference System (ANFIS) and Type-2 Fuzzy …. (Agung B. Muljono)
83
Meanwhile, the dynamic response of T2FLS-PSS was not oscillated and this response was able to achieved
steady state at 4.48 and 12.15 s for first and second disturbances, respectively. Peak overshoot of the T2FLS-
PSS for the second disturbance Po2 was achieved at the value of 1.12103
pu.
The rotor angle (7) for the T2FLS-PSS, ANFIS-PSS and CONV-PSS achieved the peak overshoot
Po1 at the value of 6.68, 6.38 and 6.41. Furthermore, the rotor angle Po2 was achieved at the values of
12.45, 12.10 and 12.27, respectively. And, the steady state was achieved at around 11.46 and 11.06
for the all PSS. The 7 response is shown in Figure 8(b) and listed in Table 2.
Figure 7. Responses of the (a) 3 and (b) 3 forced
by multiple disturbances
Figure 8. Performance of the respective PSS on (a)
7 and (b) 7
Dynamic responses of (9) for the respective PSS are shown in Figure 9(a) and Table 2.
Oscillation occurred on the CONV-PSS response with amplitude between 4.74 and 3.42103
pu. This
response was decreased and achieved the settling time at more than 8 s (tst1) and 15 s (tst2), for first and
second disturbances, respectively. The oscillation also appeared on the ANFIS-PSS response with amplitude
at the values between 4.46 and 1.13103
pu. But, the amplitude of the ANFIS-PSS response is less than the
amplitude of the CONV-PSS response. Moreover, the rotor speed (9) that system equipped by the T2FLS-
PSS achieved peak overshoot at the values of 2.02 (Po1) and 2.30103
(Po2) pu. Response of T2FLS-PSS
is better than the other PSS(s).
Figure 9. Enhancement stability of the (a) 9 and (b) 9 by using the T2FLS-PSS
 ISSN: 2088-8708
Int J Elec & Comp Eng, Vol. 8, No. 1, February 2018 : 76 – 86
84
The rotor angle (9) for the T2FLS-PSS, ANFIS-PSS and CONV-PSS achieved the peak overshoot
(Po1) at the values of 10.04, 9.75 and 9.71. Again, when the second disturbance was disturbed, the peak
overshoot of the T2FLS-PSS, ANFIS-PSS and CONV-PSS was achieved at the values of 18.68, 18.41 and
18.43, respectively. Settling time (tst1) for the T2FLS-PSS, ANFIS-PSS and CONV-PSS was achieved at
the times of 4.24, 4.32 and 5.44 s. Next, the settling time (tst2) was achieved at the times of 12.11, 12.29 and
13.07 s. Steady state (Ss1) was achieved at the value of 5.78 for the T2FLS-PSS, and at the value of 5.39
for the ANFIS-PSS and CONV-PSS. Finally, the steady state (Ss2) was achieved at values of 16.65, 16.51
and 16.50 for the T2FLS-PSS, ANFIS-PSS and CONV-PSS, respectively. The performance of respective
PSS(s) on (9) response are shown in Figure 9(b) and Table 2. The simulation results of this paper are in-
line with the simulation results in [16] that the settling time of the PSS responses in multimachine system are
around 5.0 s.
Table 2. Performance of respective PSS on second disturbance at 0.09 pu and 8.0 s
PSS-type
3 3
Po1 Po2 tst1 tst2 Po1 Po2 tst1 tst2 Ss1 Ss2
×[−10−3
] (pu) (s) −() (s) −()
CONV-PSS 10.12 11.23 >8.0 >15.0 21.83 41.23 7.8 14.9 17.71 36.2
ANFIS-PSS 8.03 9.75 4.85 12.49 21.26 40.32 4.82 12.47 17.65 36.12
T2FLS-PSS 6.52 7.86 4.51 12.17 21.34 40.30 4.79 12.36 17.52 36.04
7 7
CONV-PSS 1.81 2.09 >8.0 >15.0 6.41 12.27 5.43 13.15 5.39 11.06
ANFIS-PSS 2.33 2.43 4.81 12.47 6.38 12.10 4.51 12.38 5.39 11.06
T2FLS-PSS 1.01 1.12 4.48 12.15 6.68 12.45 4.32 12.14 5.78 11.46
9 9
CONV-PSS 4.74 5.45 >8.0 >15.0 9.71 18.43 5.41 13.07 5.39 16.50
ANFIS-PSS 4.46 4.74 4.75 12.39 9.75 18.61 4.32 12.29 5.39 16.51
T2FLS-PSS 2.02 2.3 4.36 11.97 10.04 18.68 4.24 12.11 5.78 16.65
5. CONCLUSION
The coordination of ANFIS-PSS and T2FLS-PSS are evaluated on a large-scale power system
(LSPS). The design of PSS based on ANFIS and T2FLS are also explored in-depth in this research. On
designing process, the ANFIS-PSS parameters are obtained automatically through learning stage. All the data
that used in the learning stage are obtained by simulating the LSPS equipped by conventional PSS (CONV-
PSS) with varied load capacity. The learning processes are conducted in off-line mode. Meanwhile, the
T2FLS parameters are determined by design based on the knowledge of the designer. The proposed PSS(s)
are tested by using two scenarios in order to validity of the model. In First Scenario, the system is forcing by
a single mechanical disturbance on the Machine-2. The simulation results are observed on the rotor speed and
angle of the Machine-3 (M3) for mode local oscillation, and Machine-7 (M7) and Machine-9 (M9) for mode
inter-area oscillation. The simulation results are as follows: The settling time of the rotor speed (Δ3) and
angle Δ3 are obtained at the times of 5.25 and 5.62 s, respectively, for T2FLS-PSS. The steady state values
for the Δ3 responses of all the PSS(s) are obtained at −19.52
. When multiple disturbances are forced to the
system, responses of the T2FLS-PSS are as follows: The settling time are obtained at 4.51 s (tst1) and 12.17 s
(tst2) for the Δ3. The settling time are obtained at 4.79 s (tst1) and 12.36 s (tst2) for the Δ3. The steady state
values are obtained at −17.52 (Ss1) and −36.04 (Ss2). The evaluation on inter-area mode oscillation (Area II
and III) is obtained as follows: The (Δ7) and Δ7 are obtained at the times of 5.31 and 5.46 s for the T2FLS-
PSS. The steady state values for the Δ7 responses of the T2FLS-PSS is obtained at 6.39. The (Δ9) and Δ9
are obtained at the times of 5.24 and 5.43 s for the T2FLS-PSS. The evaluation is also conducted on multiple
disturbances. In this scenario, responses of the CONV-PSS and ANFIS-PSS oscillated in a few second.
Meanwhile, the T2FLS response for the (Δ3) achieved the settling time at times of 4.70 and 12.36 s for the
first and second disturbances, respectively. The peak overshoot (Po1 and Po2) are achieved at the values of
−6.52 and −7.86× 10−3
pu. It is concluded that the T2FLS-PSS gives better responses than the other PSS.
Where, peak overshoot of the T2FLS-PSS less than the other PSS and the settling time also shorter than the
other PSS.
ACKNOWLEDGEMENTS
The authors would like to thank to the Directorat General of Higher Education (DGHE) the
Research, Technology and Higher Education Ministry, Republic of Indonesia to financial support through
Int J Elec & Comp Eng ISSN: 2088-8708 
Coordination of Adaptive Neuro Fuzzy Inference System (ANFIS) and Type-2 Fuzzy …. (Agung B. Muljono)
85
Hibah Penelitian Fundamental 2015-2016. Also, the authors thank to the colleagues and students at Power
System Laboratory, University of Mataram for well cooperation during this research was done.
REFERENCES
[1] Amirullah and A. Kiswantono, “Power Quality Enhancement of Integration Photovoltaic Generator to Grid under
Variable Solar Irradiance Level MPPT-Fuzzy”, International Journal in Electrical and Computer Engineering
(IJECE), Vol. 6. No. 6. pp. 2629-2642, 2016.
[2] A.S. Tomer and S.P. Dubey, “Response Based Comparative Analysis of Two Inverter Fed Six Phase PMSM Drive
by using PI and Fuzzy Logic Controller”, International Journal in Electrical and Computer Engineering (IJECE),
Vol. 6. No. 6. pp. 2643-2657, 2016.
[3] L.S. Moulin, et al., “Support Vector Machines for Transient Stability Analysis of Large-scale Power Systems,”
IEEE Trans. on Power Syst., vol. 19, no. 2, 2004.
[4] A.B. Muljono, et al., “Dynamic Stability Improvement using ANFIS-based Power System Stabilizer in a
Multimachine Power System (in Bahasa Indonesia),” Proc. of SENTIA, Polinema Malang, vol. 7, pp. B16-B21,
2015.
[5] A.B. Muljono, et al., “Dynamic Stability Improvement of Multimachine Power System using ANFIS-based Power
System Stabilizer,” TELKOMNIKA (Telecommunication Computing Electronics and Control), vol. 7, pp. 1170-
1178, 2015.
[6] M.H. Al-Qatamin, “An Optimal State Feedback Controller Based Neural Networks for Synchronous Generators,”
International Journal in Electrical and Computer Engineering (IJECE), Vol. 3 No. 4, pp. 561-567, 2013.
[7] T. Hussein and A. Shamekh, “Adaptive Rule-base Fuzzy Power System Stabilizer for a Multi-machine System,”
Proc. of the MED Conf., pp.1415-1419, 2013.
[8] M. Kushwaha and R. Khare, “Dynamic Stability Enhancement of Power System using Fuzzy Logic Based Power
System Stabilizer,” Proc. of Int. Conf. on ICPEC, pp. 213-219, 2013.
[9] B. Shah, “Comparative Study of Conventional and Fuzzy Based Power System Stabilizer,” Proc. of Int. Conf. on
CSNT, IEEE, pp. 547-551, 2013.
[10] F.M. Adjeroud, et al., “A Coordinated Genetic Based Type-2 Fuzzy Stabilizer for Conventional and
Superconducting Generators,” Electric Power Systems Research, vol. 129, pp. 51-61, 2015.
[11] Z. Sun, et al., “Optimal Tuning of Type-2 Fuzzy Logic Power System Stabilizer Based on Differential Evolution
Algorithm,” IJEPES, vol. 62, pp. 19-28, 2014.
[12] S. Kamel, et al., “An Indirect Adaptive Type-2 Fuzzy Sliding Mode PSS Design to Damp Power System
Oscillations,” Proc. of Int. Conf. on Modeling, Identification and Control, Tunisia, 2015.
[13] K.F. Zhang and X.Z. Dai, “Structural Analysis of Large-scale Power Systems”, Mathematica Problem in
Engineering,Hindawi Pub., 2012.
[14] Y.Y. Hsu and C.C. Su, “Application of Power System Stabilizer on a System with Pumped Storage plant,” IEEE
Trans. on Power Syst., vol. 3, no. 1, 1988.
[15] M. Saidy and F.M. Hughes, “Performance Improvement of a Conventional Power System Stabilizer,” Elect. Power
and Energy Syst., vol. 17 no. 5, 1995.
[16] J. Talaq, “Optimal Power System Stabilizers for Multi Machine Systems,” IJEPES, vol. 43, pp. 793-803, 2012.
[17] I.M. Ginarsa, et al., “Controlling Chaos and Voltage Collapse using Layered Recurrent Network-based PID-SVC in
Power Systems,” TELKOMNIKA (Telecommunication Computing Electronics and Control), vol. 11, pp. 451-462,
no. 3, 2013.
[18] S. Mohagheghi, et al., “Adaptive Critic Design Based on Neuro-fuzzy Controller for a Static Compensator in a
Multimachine Power System”, IEEE Trans. on Power Syst., vol. 21, no. 4, 2006.
[19] S. Mohagheghi, et al., “Hardware Implementation of a Mamdani Fuzzy Logic Controller for a Static Compensator
in a Multimachine Power System,” IEEE Trans. on Industry App., vol. 45, no. 4, 2009.
[20] I.M. Ginarsa, et al., “Controlling Chaos and Voltage Collapse using an ANFIS-based Composite Controller-static
Var Compensator in Power Systems,” IJEPES, vol. 46, pp. 79-88, 2013.
[21] I.M. Ginarsa, et al., “Improvement of Transient Voltage Responses using an Additional PID-loop on an
ANFISbased Composite Controller-SVC (CC-SVC) to Control Chaos and voltage Collapse in Power Systems,”
IEEJ Trans. on Power and Energy (Section B), vol. 131, no. 10, pp. 836-848, 2011.
[22] I.M. Ginarsa, et al., “Regulation of 12-pulse Rectifier Converter using ANFIS-based Controller in a HVDC
Transmission System”, in Integrated Sci-Tech: The Interdisciplinary Research Approach, vol. 1, chapt. 6, UPT
Perpustakaan UNILA Lampung, pp. 44-53, 2015.
[23] N. Bawane, et al., “ANFIS Based Control and Fault Detection of HVDC Converter,” HAIT Journal of Science and
Engineering B, vol. 2, no. 5-6, pp. 673-689, 2011.
[24] I.M. Ginarsa and O. Zebua, “Stability Improvement of Single Machine using ANFIS-PSS Based on
Feedbacklinearization,” TELKOMNIKA (Telecommunication Computing Electronics and Control), vol. 12, no. 2,
2014.
[25] P. Kundur, Power System Stability and Control, EPRI McGraw-Hill. New York, 1994.
[26] K.R. Padiyar, Power System Dynamic Stability and Control, John Wiley and Sons (Asia) Pte Ltd, Singapore,1994.
[27] J.-S.R. Jang, et al., Neuro-fuzzy and Soft Computing: A Computational Approach to Learning and Machine
Intelligence, Prentice-Hall International, Inc., USA, 1997.
[28] N.N. Karnik, et al., “Type-2 Fuzzy Logic Systems,” IEEE Trans. on Fuzzy Syst., vol. 7, no. 6, 1999.
 ISSN: 2088-8708
Int J Elec & Comp Eng, Vol. 8, No. 1, February 2018 : 76 – 86
86
[29] O. Castillo and P. Melin, “Recent Advances in Interval Type-2 Fuzzy Systems”, pp. 7-12. Springer, Heidelberg,
2012.
[30] A. Taskin and T. Kumbasar, “An Open Source Matlab/Simulink Toolbox for Interval Type-2 Fuzzy Logic System,”
IEEE Symp. Series on Computational Intelligence, Cape Town, South Africa, 2015.
[31] A. Taskin and T. Kumbasar, Matlab/Simulink Toolbox for Interval Type-2 Fuzzy Logic Systems,
http://web.itu.edu.tr/kumbasart/type2fuzzy.htm, access on 20 Sept. 2016, 20:10 pm.
[32] Matlab, MATLAB Version 8.0 (2013a), The Matworks Inc (2013).
BIOGRAPHIES OF AUTHORS
Agung B. Muljono was born in Purwodadi, Grobogan, Central Java Indonesia, on February 1971.
He received in B.Eng, and M.Eng in electrical engineering from Malang Institute of Technology
(1996) and Gadjah Mada University (2000) Indonesia, respectively. Since 1998 he was a lecturer
at electrical engineering, Mataram University. His research interests are power system
transmission and distribution, power system dynamic and stability, artificial intelligent application
in power systems, energy planning and distributed generation (DG) in power systems. He was an
active author and co-author research papers in national and international journal.
I M. Ginarsa was born in Darmasaba, Badung Regency, Bali Indonesia, on March 1970. He
received in B.Eng, M.Eng and Ph.D in electrical eng. from Udayana Univ. (1997), Gadjah Mada
Univ. (2001) and Sepuluh Nopember Institute of Tech. (2012), Indonesia. Since 1999 he was a
lecturer at Electrical engineering, Mataram University. In 2010 he was a member of Electric Power
System Laboratory, Kumamoto Univ. Japan as a research student. His research interests are power
system dynamic and stability, nonlinear dynamic in power system, voltage stability and control,
artificial intelligent application in power systems. His works have been presented in international
seminars. He was an active author and co-author in this field that his research papers have been
published in national and international journals. He was served a invited reviewer on national and
international publications
I M.A. Nrartha was born in Denpasar, Bali Indonesia, on April 1973. He received in B.Eng and
M.Eng in electrical eng. from Sepuluh Nopember Institute of Tech. (1997) and Gadjah Mada
Univ.(2001). Since 1999 he was a lecturer at Electrical engineering, Mataram University. His
research interests are power system dynamic and stability, transmission and distribution,
optimization, power quality and artificial intelligent application in power systems. He was an
active author and co-author research papers in national and international journal
A. Dharma was born in Denpasar, Bali Indonesia, on August 1964. He received in B.Eng, M.Eng
and Ph.D in electrical eng. from Sepuluh Nopember Institute of Tech, in 1990, 2001 and, 2006 and
2014, respectively. Since 1990 he was a lecturer at Electrical engineering, Udayana University. His
research interests are power system engineering, power generation, renewable energy technology
and application of artificial intelligent for load forecasting. He was an active author and co-author
research papers in national and international journal.

More Related Content

PDF
IRJET- Fuzzy Control Scheme for Damping of Oscillations in Multi Machine Powe...
PDF
DFIG wind turbine under unbalanced power system conditions using adaptive fuz...
PDF
D1072535
PDF
Low Frequency Oscillations Damping by UPFC with GAPOD and GADC-voltage regulator
PDF
Transient Stability Analysis with SSSC and UPFC in Multi-Machine Power System...
PDF
Static Sustenance of Power System Stability Using FLC Based UPFC in SMIB Powe...
PDF
International Journal of Engineering Research and Development
PDF
International Journal of Engineering Research and Development
IRJET- Fuzzy Control Scheme for Damping of Oscillations in Multi Machine Powe...
DFIG wind turbine under unbalanced power system conditions using adaptive fuz...
D1072535
Low Frequency Oscillations Damping by UPFC with GAPOD and GADC-voltage regulator
Transient Stability Analysis with SSSC and UPFC in Multi-Machine Power System...
Static Sustenance of Power System Stability Using FLC Based UPFC in SMIB Powe...
International Journal of Engineering Research and Development
International Journal of Engineering Research and Development

What's hot (18)

PDF
Starting of induction motor fed with stand-alone DFIG
PDF
Transient Stability Evaluation of the Power Generation under a Blackout Condi...
PDF
Transient response improvement of direct current using supplementary control ...
PPTX
V fuzzy logic applications to electrical systems
PDF
Energy storage systems control methods in micro grids Class-30, Subject: Di...
PDF
Effects of the Droop Speed Governor and Automatic Generation Control AGC on G...
PDF
Multi-machine transient stability by using static synchronous series compensator
PDF
Modelling, Simulation and Performance Analysis of A Variable Frequency Drive...
PDF
C1081826
PDF
Ijeet 06 08_005
PDF
Fi34989995
PDF
01 13sep 8450 9994-1-ed on-line assessment (edit lafi)
PDF
Enhanced Torque Control and Reduced Switching Frequency in Direct Torque Cont...
PDF
40220140505006
PDF
Transient Stability Assessment and Enhancement in Power System
PDF
G43013539
PDF
Comparative Performance Study for Closed Loop Operation of an Adjustable Spee...
PDF
Motor Command and Supervision Using the Magnetic Components of the Insulation...
Starting of induction motor fed with stand-alone DFIG
Transient Stability Evaluation of the Power Generation under a Blackout Condi...
Transient response improvement of direct current using supplementary control ...
V fuzzy logic applications to electrical systems
Energy storage systems control methods in micro grids Class-30, Subject: Di...
Effects of the Droop Speed Governor and Automatic Generation Control AGC on G...
Multi-machine transient stability by using static synchronous series compensator
Modelling, Simulation and Performance Analysis of A Variable Frequency Drive...
C1081826
Ijeet 06 08_005
Fi34989995
01 13sep 8450 9994-1-ed on-line assessment (edit lafi)
Enhanced Torque Control and Reduced Switching Frequency in Direct Torque Cont...
40220140505006
Transient Stability Assessment and Enhancement in Power System
G43013539
Comparative Performance Study for Closed Loop Operation of an Adjustable Spee...
Motor Command and Supervision Using the Magnetic Components of the Insulation...
Ad

Similar to Coordination of Adaptive Neuro Fuzzy Inference System (ANFIS) and Type-2 Fuzzy Logic System-Power System Stabilizer (T2FLS-PSS) to Improve a Large-scale Power System Stability (20)

PDF
Ks2418141819
PDF
Adaptive Neuro Fuzzy Controller Based Power System Stabilizer for Damping of ...
PDF
IRJET- Comparative Study on Angular Position and Angular Speed in 36 Rules of...
PDF
IRJET- Static Analysis of a RC Framed 20 Storey Structure using ETABS
PDF
Stabilization Of Power System Using Artificial Intelligence Based System
PDF
Comparative Analysis of Power System Stabilizer using Artificial Intelligence...
PDF
International Journal of Fuzzy Logic Systems (IJFLS)
PDF
International Journal of Engineering Research and Development
PDF
Stability enhancement of power system
PDF
STABILITY ENHANCEMENT OF POWER SYSTEM USING TYPE-2 FUZZY LOGIC POWER SYSTEM S...
PDF
DESIGN OF MPSS AND TCSC DAMPING CONTROLLERS IN MULTI- MACHINE POWER SYSTEM U...
PDF
Voltage Stability analysis by using SVC With Fuzzy Logic Controller in Multi ...
PDF
Neural Network-Based Stabilizer for the Improvement of Power System Dynamic P...
PDF
report on the Governing control and excitation control for stability of power...
PDF
report on the GOVERNING CONTROL AND EXCITATION CONTROL FOR STABILITY OF POWER...
PDF
Power system stabilisation based on ga anfis in generators
PDF
Br4301389395
PDF
Comparison of Different Design Methods for Power System Stabilizer Design - A...
PDF
Development of Power System Stabilizer Using Modern Optimization Approach
PDF
A review on SVC control for power system stability with and without auxiliary...
Ks2418141819
Adaptive Neuro Fuzzy Controller Based Power System Stabilizer for Damping of ...
IRJET- Comparative Study on Angular Position and Angular Speed in 36 Rules of...
IRJET- Static Analysis of a RC Framed 20 Storey Structure using ETABS
Stabilization Of Power System Using Artificial Intelligence Based System
Comparative Analysis of Power System Stabilizer using Artificial Intelligence...
International Journal of Fuzzy Logic Systems (IJFLS)
International Journal of Engineering Research and Development
Stability enhancement of power system
STABILITY ENHANCEMENT OF POWER SYSTEM USING TYPE-2 FUZZY LOGIC POWER SYSTEM S...
DESIGN OF MPSS AND TCSC DAMPING CONTROLLERS IN MULTI- MACHINE POWER SYSTEM U...
Voltage Stability analysis by using SVC With Fuzzy Logic Controller in Multi ...
Neural Network-Based Stabilizer for the Improvement of Power System Dynamic P...
report on the Governing control and excitation control for stability of power...
report on the GOVERNING CONTROL AND EXCITATION CONTROL FOR STABILITY OF POWER...
Power system stabilisation based on ga anfis in generators
Br4301389395
Comparison of Different Design Methods for Power System Stabilizer Design - A...
Development of Power System Stabilizer Using Modern Optimization Approach
A review on SVC control for power system stability with and without auxiliary...
Ad

More from IJECEIAES (20)

PDF
Redefining brain tumor segmentation: a cutting-edge convolutional neural netw...
PDF
Embedded machine learning-based road conditions and driving behavior monitoring
PDF
Advanced control scheme of doubly fed induction generator for wind turbine us...
PDF
Neural network optimizer of proportional-integral-differential controller par...
PDF
An improved modulation technique suitable for a three level flying capacitor ...
PDF
A review on features and methods of potential fishing zone
PDF
Electrical signal interference minimization using appropriate core material f...
PDF
Electric vehicle and photovoltaic advanced roles in enhancing the financial p...
PDF
Bibliometric analysis highlighting the role of women in addressing climate ch...
PDF
Voltage and frequency control of microgrid in presence of micro-turbine inter...
PDF
Enhancing battery system identification: nonlinear autoregressive modeling fo...
PDF
Smart grid deployment: from a bibliometric analysis to a survey
PDF
Use of analytical hierarchy process for selecting and prioritizing islanding ...
PDF
Enhancing of single-stage grid-connected photovoltaic system using fuzzy logi...
PDF
Enhancing photovoltaic system maximum power point tracking with fuzzy logic-b...
PDF
Adaptive synchronous sliding control for a robot manipulator based on neural ...
PDF
Remote field-programmable gate array laboratory for signal acquisition and de...
PDF
Detecting and resolving feature envy through automated machine learning and m...
PDF
Smart monitoring technique for solar cell systems using internet of things ba...
PDF
An efficient security framework for intrusion detection and prevention in int...
Redefining brain tumor segmentation: a cutting-edge convolutional neural netw...
Embedded machine learning-based road conditions and driving behavior monitoring
Advanced control scheme of doubly fed induction generator for wind turbine us...
Neural network optimizer of proportional-integral-differential controller par...
An improved modulation technique suitable for a three level flying capacitor ...
A review on features and methods of potential fishing zone
Electrical signal interference minimization using appropriate core material f...
Electric vehicle and photovoltaic advanced roles in enhancing the financial p...
Bibliometric analysis highlighting the role of women in addressing climate ch...
Voltage and frequency control of microgrid in presence of micro-turbine inter...
Enhancing battery system identification: nonlinear autoregressive modeling fo...
Smart grid deployment: from a bibliometric analysis to a survey
Use of analytical hierarchy process for selecting and prioritizing islanding ...
Enhancing of single-stage grid-connected photovoltaic system using fuzzy logi...
Enhancing photovoltaic system maximum power point tracking with fuzzy logic-b...
Adaptive synchronous sliding control for a robot manipulator based on neural ...
Remote field-programmable gate array laboratory for signal acquisition and de...
Detecting and resolving feature envy through automated machine learning and m...
Smart monitoring technique for solar cell systems using internet of things ba...
An efficient security framework for intrusion detection and prevention in int...

Recently uploaded (20)

PPTX
M Tech Sem 1 Civil Engineering Environmental Sciences.pptx
PPTX
Infosys Presentation by1.Riyan Bagwan 2.Samadhan Naiknavare 3.Gaurav Shinde 4...
PPTX
Engineering Ethics, Safety and Environment [Autosaved] (1).pptx
PDF
Digital Logic Computer Design lecture notes
PPT
Mechanical Engineering MATERIALS Selection
PDF
composite construction of structures.pdf
PDF
Model Code of Practice - Construction Work - 21102022 .pdf
PPTX
CYBER-CRIMES AND SECURITY A guide to understanding
PPTX
CH1 Production IntroductoryConcepts.pptx
PDF
TFEC-4-2020-Design-Guide-for-Timber-Roof-Trusses.pdf
DOCX
573137875-Attendance-Management-System-original
PPTX
CARTOGRAPHY AND GEOINFORMATION VISUALIZATION chapter1 NPTE (2).pptx
PPTX
Recipes for Real Time Voice AI WebRTC, SLMs and Open Source Software.pptx
PDF
The CXO Playbook 2025 – Future-Ready Strategies for C-Suite Leaders Cerebrai...
PDF
R24 SURVEYING LAB MANUAL for civil enggi
PDF
Operating System & Kernel Study Guide-1 - converted.pdf
PPTX
bas. eng. economics group 4 presentation 1.pptx
PDF
Mohammad Mahdi Farshadian CV - Prospective PhD Student 2026
PDF
Enhancing Cyber Defense Against Zero-Day Attacks using Ensemble Neural Networks
PPTX
Internet of Things (IOT) - A guide to understanding
M Tech Sem 1 Civil Engineering Environmental Sciences.pptx
Infosys Presentation by1.Riyan Bagwan 2.Samadhan Naiknavare 3.Gaurav Shinde 4...
Engineering Ethics, Safety and Environment [Autosaved] (1).pptx
Digital Logic Computer Design lecture notes
Mechanical Engineering MATERIALS Selection
composite construction of structures.pdf
Model Code of Practice - Construction Work - 21102022 .pdf
CYBER-CRIMES AND SECURITY A guide to understanding
CH1 Production IntroductoryConcepts.pptx
TFEC-4-2020-Design-Guide-for-Timber-Roof-Trusses.pdf
573137875-Attendance-Management-System-original
CARTOGRAPHY AND GEOINFORMATION VISUALIZATION chapter1 NPTE (2).pptx
Recipes for Real Time Voice AI WebRTC, SLMs and Open Source Software.pptx
The CXO Playbook 2025 – Future-Ready Strategies for C-Suite Leaders Cerebrai...
R24 SURVEYING LAB MANUAL for civil enggi
Operating System & Kernel Study Guide-1 - converted.pdf
bas. eng. economics group 4 presentation 1.pptx
Mohammad Mahdi Farshadian CV - Prospective PhD Student 2026
Enhancing Cyber Defense Against Zero-Day Attacks using Ensemble Neural Networks
Internet of Things (IOT) - A guide to understanding

Coordination of Adaptive Neuro Fuzzy Inference System (ANFIS) and Type-2 Fuzzy Logic System-Power System Stabilizer (T2FLS-PSS) to Improve a Large-scale Power System Stability

  • 1. International Journal of Electrical and Computer Engineering (IJECE) Vol. 8, No. 1, February 2018, pp. 76~86 ISSN: 2088-8708, DOI: 10.11591/ijece.v8i1.pp76-86  76 Journal homepage: http://iaescore.com/journals/index.php/IJECE Coordination of Adaptive Neuro Fuzzy Inference System (ANFIS) and Type-2 Fuzzy Logic System-Power System Stabilizer (T2FLS-PSS) to Improve a Large-scale Power System Stability Agung B. Muljono1 , I. M. Ginarsa2 , I. M. A. Nrartha3 , A. Dharma4 1,2,3 Department of Electrical Engineering, University of Mataram, NTB, Indonesia 4 Department of Electrical Engineering, Udayana University, Bali, Indonesia Article Info ABSTRACT Article history: Received Sep 15, 2017 Revised Dec 30, 2017 Accepted Jan 14, 2018 Intelligent control included ANFIS and type-2 fuzzy (T2FLS) controllers grown-up rapidly and these controllers are applied successfully in power system control. Meanwhile, small signal stability problem appear in a large- scale power system (LSPS) due to load fluctuation. If this problem persists, and can not be solved, it will develop blackout on the LSPS. How to improve the LSPS stability due to load fluctuation is done in this research by coordinating of PSS based on ANFIS and T2FLS. The ANFIS parameters are obtained automatically by training process. Meanwhile, the T2FLS parameters are determined based on the knowledge that obtained from the ANFIS parameters. Input membership function (MF) of the ANFIS is 5 Gaussian MFs. On the other hand, input MF of the T2FLS is 3 Gaussian MFs. Results show that the T2FLS-PSS is able to maintain the stability by decreasing peak overshoot for rotor speed and angle. The T2FLS-PSS makes the settling time is shorter for rotor speed and angle on local mode oscillation as well as on inter-area oscillation than conventional/ ANFIS-PSS. Also, the T2FLS-PSS gives better performance than the other PSS when tested on single disturbance and multiple disturbances. Keyword: ANFIS Large-scale PSS Stability improvement T2FLS Copyright © 2018 Institute of Advanced Engineering and Science. All rights reserved. Corresponding Author: Agung B. Muljono, Dept. of Electrical Engineering, University of Mataram, Jln. Majapahit No. 62 Mataram, NTB, Indonesia. +62 370 636 755 Email: agungbm@unram.ac.id 1. INTRODUCTION Controller based on artificial intelligent is the research topic interest in recent year. Because the intelligent control has learning ability to improve its performance from the environment where the controller is applied. The spreading of intelligent control exists on some fields such as: Electrical and electronic engineering, and computer science such as: Fuzzy controller is used to enhance photovoltaic generator power quality by maintaining the MPPT tracking on low voltage side of DC/DC boost converter. The MPPT-fuzzy controller is able to maintain voltage profile and current total harmonic distortion (THD) [1]. The performance of fuzzy controller is compared to the PI controller on two inverter fed to control six-phase permanent magnet synchronous machine (PMSM) operated as a motor. The simulation results show that the fuzzy controller are more robust, quick response on high starting torque and more effective the PI controller [2]. Support vector machine (SVM) method is used to classify a large-scale power system transient stability. The SVM method gives a better result than multi-layer perceptron-neural network (MLP-NN)
  • 2. Int J Elec & Comp Eng ISSN: 2088-8708  Coordination of Adaptive Neuro Fuzzy Inference System (ANFIS) and Type-2 Fuzzy …. (Agung B. Muljono) 77 method [3]. Adaptive neuro-fuzzy inference system (ANFIS) controllers have been implemented in 3-machine 9-bus power systems. Where, the ANFIS controllers are able to maintain the dynamic stability of the multimachine power systems significantly [4], [5]. Neural network controller is used as a feedback control to improve the dynamic performance of single synchronous machine connected to infinite bus [6]. Adaptive fuzzy rule-based PSS [7] and fuzzy logic PSS [8], [9] are also successful applied to maintain dynamic stability of a power system. Meanwhile, Type-2 fuzzy logic system (T2FLS) is applied to coordination of excitation and governor systems [10]. In [11], the T2FLS is used as a PSS and tuning of its parameter is optimized by differential evolution algorithm to cover the uncertainty of disturbances. An indirect adaptive T2FLS-PSS is implemented to damp out of the low frequency oscillation on different operating condition of a power system [12]. While, power system companies that serve consumers on a wide-area continuously with standard quality assurance and without interruption. Some generation units such as: Hydro, thermal, nuclear and gas power plants are connected to bulk power systems via interconnecting transmission line including high voltage direct current (HVDC) system. On the other hand, almost of consumers are located in city areas such as: Trade/commercial and official complex areas, suburban area, industrial area and residential area. Analysis of a large-scale power system (LSPS) network is usually very complicated and difficult. The simplifying scheme should be done to resolve this complicated network problem. In this research, the LSPS is divide into three parts of small operation areas [13]. In operation time, imbalance of energy in respective synchronous machine makes the rotor machine oscillate due to load fluctuation at one or some load buses. When the rotor machines are oscillate continuously without any control scheme, this situation can cause the LSPS going into instability problem. To cover this rotor oscillation problem, power system stabilizer (PSS) is proposed at excitation system of synchronous machine to damp the rotor oscillation. Where, local mode stability of a pump storage power plant is significantly improved by using the PSS [14]. Furthermore, performance of a conventional PSS is maintained by using additional or auxiliary loop [15]. PSS based on optimal and sub-optimal linear quadratic regulator design are proposed to improve stability of power system. In this design, only speed deviation and PSS states are considered as the inputs, while the coupling gain between machines are neglected [16]. The function of conventional control is instead by the neural network, fuzzy or neuro-fuzzy controls. Proportional integral and derivative-static var compensator based on recurrent neural network is applied to control chaos and voltage collapse in a power system. This control scheme is able to suppress chaos and voltage collapse in power systems [17]. Adaptive critic design based (ADC) neuro-fuzzy controller is applied to control the static compensator in a LSPS. It is shown that the ADC neuro-fuzzy controller is more effective than PI controller in responding to small disturbance and short circuit fault [18]. Also, a Mamdani fuzzy controller is applied to hardware implementation to static compensator in a LSPS [19]. The ANFIS-based composite controller-SVC and PID-loop are applied to control chaos and voltage collapse and to regulate the voltage at load bus with loading fluctuation [20], [21]. Also, the ANFIS controller is tried to maintain dynamic response of HVDC system [22] and to protect the HVDC devices from the short circuit [23]. Furthermore, ANFIS power system stabilizer (PSS) has been applied to improve the stability of single machine based on feedback linearization [24]. According to wide range usability and previous research of the ANFIS and T2FLS applications in power system. We aim to evaluate the control strategy of ANFIS and T2FLS-based power system stabilizer to improve stability of a large-scale power system in this research. Where, the ANFIS method is used in this research because the ANFIS is able to train from time-series data. Parameters of ANFIS controller are obtained by training processes in off-line mode. The parameters of ANFIS controller are adjusted automatically during the training processes using data training. The data training is obtained by simulating the system equipped with conventional PSS and load capacity of the LSPS is varied. Meanwhile, T2FLS method is used in this research because the T2FLS is able to cover the input, membership function, and output with uncertainty. Also, T2FLS membership function and rules are designed based on the knowledge of the designer. The paper is organized as follows: Stability of a power system is described in Section 2. Design of ANFIS and T2FLS-based power system stabilizer is explained in Section 3. Next, result and discussion are presented in Section 4. And, the conclusion is provided in the last section. 2. POWER SYSTEM STABILITY Stability is defined as the ability of power system to cover the disturbance at normal operation the effort to maintain the power system going to steady state after the disturbance is disappeared. Dynamical behavior of a single machine connected to infinite bus is depended on interaction of turbine, generator, also the controller characteristic such as governor and excitation systems. Dynamical of a single machine formulas in linear model are as follows [25] :
  • 3.  ISSN: 2088-8708 Int J Elec & Comp Eng, Vol. 8, No. 1, February 2018 : 76 – 86 78 ̇ (1) ̇ (2) A large-scale power system (LSPS) consists of two or more local power system areas. Topology of existing LSPS usually follows the geographic surfaces. Which is the local area is connected to the other by transmission line to form the LSPS. The LSPS in this research is taken from Padiyar [26]. This system consist of 39 buses and 10 machines. Furthermore, the system was simplified to Area I, Area II and Area III, and shown in Figure 1. The Machine-1 (M1) at Bus 1 was treated as a reference bus. Furthermore, the speed and angle rotor deviation was taken as zero values, respectively. Figure 1. A large-scale power system Power system stabilizer (PSS) provides additional damping to rotor oscillation of machine by regulating its excitation system through an additional stabilizing signal. The PSS produces an electrical torque component in phase with the rotor speed deviation to provide the additional damping torque. The PSS is very important to improve stability of overall power systems. Since the PSS is to introduce a damping torque component, a logical signal to use for regulating excitation system of machine is rotor speed deviation. And, output of the PSS is the additional voltage compensation that feeding to the excitation system. Conventional PSS consist of gain, washout and phase compensation blocks. The gain block determines the amount of damping introduce by the PSS. The signal washout block serves as a high frequency filter, with the time constant T. The phase compensation block provides appropriate phase lead characteristic to compensate the phase lag between exciter input and generator (air-gap) electrical torque. 3. DESAIN OF PSS BASED ON ARTIFICIAL INTELLIGENT 3.1. PSS based on ANFIS Controller An adaptive neuro-fuzzy inference system or adaptive network-based fuzzy inference system (ANFIS) is a kind of artificial neural network that is based on Takagi–Sugeno fuzzy inference system. Since it integrates both neural networks and fuzzy logic principles, it has potential to capture the benefits of both models in a single framework. Its inference system corresponds to a set of fuzzy IF-THEN rules that have learning capability to approximate nonlinear functions. Hence, ANFIS is considered to be a universal estimator. The ANFIS consists of premise and consequence parameters. The ANFIS function is same as the fuzzy rule based on Sugeno algorithm. So, both the parameters are obtained by off-line learning processes with least squares estimation (LSE) and back- propagation algorithms. At forward step, the parameters are identified by using LSE method. And, at backward step the parameters are maintained by using gradient descent optimization. Suppose that the
  • 4. Int J Elec & Comp Eng ISSN: 2088-8708  Coordination of Adaptive Neuro Fuzzy Inference System (ANFIS) and Type-2 Fuzzy …. (Agung B. Muljono) 79 ANFIS network has 2 (two) inputs x, y and an output O, with 2 (two) rules based on first-order fuzzy model Sugeno [27]: (3) Output of the ANFIS-network is formulated follow: ∑ ∑ ∑ (4) The ANFIS-based PSS is designed by some learning processes in off-line mode. Data training that used for this learning process were obtained by simulating the conventional PSS. To obtain the data training, the LSPS is equipped by conventional PSS. The result of the training stage was the ANFIS-based PSS and this PSS was applied to replace the conventional PSS. And, the ANFIS-based PSS membership function for rotor speed deviation is illustrated in Figure 2. Figure 2. Membership function for input ANFIS of 3 3.2. PSS based on Type-2 Fuzzy Logic System (T2FLS) Controller Type-2 fuzzy system is a class of fuzzy logic system which the antecedent or consequent membership functions are type-2 fuzzy sets. The concept of a type-2 fuzzy set is defined as an extension of the concept of an ordinary set (henceforth call a type-1 fuzzy set). The structure of a T2FLS is quite similar to a T1FLS. The difference is that on the antecedent and/or consequent sets of the T2FLS are type-2 and each rule output set is a type-2 also. The T2FLS consist of five parts such as [28], [29]: Fuzzifier, rule base, inference engine, type reducer and defuzzifier parts. Block diagram of type-2 FLS and membership function of input 3 are shown in Figure 3(a) and Figure 3(b), respectively. Figure 3. PSS based on the type-2 logic fuzzy system
  • 5.  ISSN: 2088-8708 Int J Elec & Comp Eng, Vol. 8, No. 1, February 2018 : 76 – 86 80 a. Fuzzifier The fuzzifier maps a crisp input vector with n input fuzzy sets. Singleton type-2 fuzzy input sets ( ̃ ) are considered in this research. Where, in the singleton fuzzification, the input fuzzy set has only a single point of non-zero membership. So, the ̃ is a T2 fuzzy singleton if = 1 for = and ̃ = 0 for all , ( ). b. Rule base For an interval type-2 fuzzy logic system (IT2FLS), the j-th is written as follows: If is and,..., If is Then is (5) where the are antecedent type-2 sets, y  Y is the output and are the consequent T2 sets. This rule represents a T2 fuzzy relation between the input and the output space on the FLS. c. Fuzzy Inference For the IT2FLS, product operation is considered to implement with minimum or t-norm, the firing interval V j of the j-th rule is an interval type-2 set, which is determined by its left most point and right most point and : [ ] [ ] (6) where X0 is the instantaneous value of X. The firing interval bounds for the j-th rule of an IT2FLS with n inputs and are written as follows: ∏ (7) ∏ (8) d. Type Reduction Type reduction process aims to change the T-2 output of inference system to a type-1 set. Where, center of sets (COS) type reduction method is considered in this research. This method is more effective computation than other methods and requires less time computation. The COS method is written as follows: ∑ ∑ (9) where is the interval set determined by two end points and , [ ] is the type-2 interval consequent set and, [ ] is the firing interval. e. Defuzzification Next, the type reduced set is determined by its left most point and right most point . Using the center of gravity, the defuzzified crisp output is given by (10) In this research we use Matlab/Simulink toolbox to generate the type-2 fuzzy logic system that provided by Taskin and Kumbasar [30], [31]. 4. RESULT AND DISCUSSION Three PSS types are applied to improve the stability of a large-scale power system in this research. The simulation procedure are as follows: The Machine-2 (M2) is equipped by ANFIS-PSS. While, the Machine-3 (M3), Machine-7 (M7) and Machine-9 (M9) are equipped by conventional, ANFIS and T2FLS- PSS. The responses are observed on 3 and 3 for local mode oscillation. Also, the responses are observed
  • 6. Int J Elec & Comp Eng ISSN: 2088-8708  Coordination of Adaptive Neuro Fuzzy Inference System (ANFIS) and Type-2 Fuzzy …. (Agung B. Muljono) 81 on 7, 9, 7 and 9 for inter-area mode oscillation. The proposed PSS is implemented using the Matlab/Simulink [32] on an Intel Core 2 Duo E6550 @ 2.33 GHz PC computer. 4.1. Performance of Respective PSS on a Single Disturbance First Scenario, PSS(s) based on ANFIS and Fuzzy type-2 are evaluated by forcing a single step mechanical disturbance on Machine-2 at 0.1 pu. When the system was disturbed and simulation results were observed on the Figure 4, Figure 5 and Figure 6. Also, the result is listed in Table 1. Figure 4. Stability improvement on (a) 3 and (b) 3 when forced by a single disturbance Figure 5. Enhancement of the (a) 7 and (b) 7 responses using T2FLS-PSS Figure 4(a) and Table 1 show the peak overshoot (Po) of the rotor speed deviation (3) was obtained at the values of 20.14, 21.42 and 19.85103 pu for the T2FLS-PSS, ANFIS-PSS and CONV- PSS, respectively. In this result, the settling time was achieved at the times of 5.25, 5.72 and 5.97 s, respectively. Figure 4(b) and Table 1 are responses for rotor angle deviation of M3. It is shown that the peak overshoot was achieved at the values of 35.94, 35.56 and 35.53 for the T2FLS-PSS, ANFIS-PSS and CONV-PSS, respectively. The steady state of rotor angle deviation was achieved at the value of 19.52. The settling time was achieved at the times of 5.62, 5.89 and 6.44 s for the T2FLS-PSS, ANFIS-PSS and CONV-PSS. Figure 5(a) and Table 1 are the responses of the rotor speed deviation (7) when the respective PSS(s) are applied to a large-scale power system. It is shown that the peak overshoot was achieved at the values of 2.17, 3.59 and 5.57103 pu for the T2FLS-PSS, ANFIS-PSS and CONV-PSS, respectively. The settling time was obtained at the times of 5.31, 5.83 and 6.55 s for the T2FLS-PSS, ANFIS-PSS and CONV-PSS. It is shown that the responses of the ANFIS-PSS and CONV-PSS are still oscillated. The improvement of the rotor angle deviation (7) is shown in Figure 5(b) and listed in Table 1. The T2FLS- PSS gave the peak overshoot at the value of 8.48 and the settling time at time of 5.46 s. Meanwhile, the ANFIS-PSS and CONV-PSS gave peak overshoot at the values of 10.25 and 10.23, respectively. The settling time of the ANFIS-PSS and CONV-PSS was obtained at the times of 6.09 and 6.65 s. Steady state of the rotor angle was achieved at the value of 6.39 for the T2FLS-PSS, and 5.98 for the ANFIS- and CONV-PSS. From Figure 6(a) and Table 1 we see that peak overshoot of the T2FLS-PSS was achieved at the value of 6.53103 pu for the rotor speed deviation (9). On the other hand, the peak overshoot of the ANFIS-PSS and CONV-PSS were achieved at the values of 6.65 and 7.09103 pu. The settling time was obtained at the times of 5.24, 5.74 and 5.98 s, respectively. Furthermore, the responses for the rotor angle deviation (9) is shown in Figure 6(b) and listed in Table 1. Simulation result on the First Scenario shows that the T2FLS-PSS is able to improve stability by observing the rotor speed and angle deviation. The T2FLS-PSS gives peak overshoot smaller than the ANFIS/CONV-PSS for both rotor speed and angle. Also, the settling time of the T2FLS-PSS is shorter than the other PSS(s) as well as for the local mode oscillation as well as inter-area mode oscillation.
  • 7.  ISSN: 2088-8708 Int J Elec & Comp Eng, Vol. 8, No. 1, February 2018 : 76 – 86 82 Figure 6. Performance of respective PSS for the (a) 9 and (b) 9 responses Table 1. Performance of conventional, ANFIS and T2FLS-PSS to improve stability of a LSPS PSS-type 3 3 Peak overshoot [Po] Settling time Po [tst] Ss × (−10−3 )(pu) [tst] (s) () (s) () CONV-PSS 19.85 5.97 34.53 6.44 ANFIS-PSS 21.42 5.72 35.56 5.89 19.52 T2FLS-PSS 20.14 5.25 35.94 5.62 7 7 CONV-PSS 19.85 5.97 34.53 6.44 ANFIS-PSS 21.42 5.72 35.56 5.89 19.52 T2FLS-PSS 20.14 5.25 35.94 5.62 9 9 CONV-PSS 19.85 5.97 34.53 6.44 ANFIS-PSS 21.42 5.72 35.56 5.89 19.52 T2FLS-PSS 20.14 5.25 35.94 5.62 4.2. Evaluation of Respective PSS on Multiple Disturbances Second Scenario, we also evaluate the respective PSS(s) by forcing 2 (two) mechanical disturbances to the Machine-2 sequentially on 0.08 and 0.09 pu at 0.0 and 8.0 s. Stability improvement of M3, M7 and M9 is observed on dynamic responses of rotor speed and angle deviation. These dynamic responses are shown in Figure 7, Figure 8 and Figure 9. Also, the responses of respective PSS(s) are listed in Table 2. Figure 7(a) and Table 2 show the dynamic response of the CONV-PSS oscillated with amplitude between 11.23 and 4.60103 pu. Then, this amplitude was decreased until the response achieved steady state at time more than 15.0 s. Dynamic response of the ANFIS-PSS also oscillated with amplitude at the values between 9.75 and 3.19103 pu. On the other hand, dynamic response of T2FLS-PSS went to first swing and this response increased rapidly to zero (nominal speed). This response was able to achieved steady state at 4.51 and 12.17 s for first and second disturbances, respectively. Peak overshoot of the T2FLS-PSS for the second disturbance was achieved at the value of 6.52103 pu. The rotor angle (3) responses of the all PSS(s) are almost similar. The peak overshoot (Po1) of the T2FLS-PSS, ANFIS-PSS and CONV-PSS were achieved at the values of 21.34, 21.32 and 21.83, respectively. Next, the rotor angle (3) achieved Po2 at the values of 40.30, 40.32 and 41.23 for the T2FLS-PSS, ANFIS-PSS and CONV-PSS. And, these responses achieved steady state at around 36.04 and 36.20. This 3 response is shown in Figure 7(b). The performances of the all PSS(s) are listed in Table 2. Figure 8(a) and Table 2 show the dynamic response of rotor speed deviation (7) when equipped by the CONV-PSS. This response oscillated with amplitude between 1.81 and 0.65103 pu. Then, this amplitude was decreased until the the response achieved steady state at time of more than 15.0 s. Dynamic response of the ANFIS-PSS also oscillated with amplitude at the values between 2.33 and 0.64103 pu. (b).
  • 8. Int J Elec & Comp Eng ISSN: 2088-8708  Coordination of Adaptive Neuro Fuzzy Inference System (ANFIS) and Type-2 Fuzzy …. (Agung B. Muljono) 83 Meanwhile, the dynamic response of T2FLS-PSS was not oscillated and this response was able to achieved steady state at 4.48 and 12.15 s for first and second disturbances, respectively. Peak overshoot of the T2FLS- PSS for the second disturbance Po2 was achieved at the value of 1.12103 pu. The rotor angle (7) for the T2FLS-PSS, ANFIS-PSS and CONV-PSS achieved the peak overshoot Po1 at the value of 6.68, 6.38 and 6.41. Furthermore, the rotor angle Po2 was achieved at the values of 12.45, 12.10 and 12.27, respectively. And, the steady state was achieved at around 11.46 and 11.06 for the all PSS. The 7 response is shown in Figure 8(b) and listed in Table 2. Figure 7. Responses of the (a) 3 and (b) 3 forced by multiple disturbances Figure 8. Performance of the respective PSS on (a) 7 and (b) 7 Dynamic responses of (9) for the respective PSS are shown in Figure 9(a) and Table 2. Oscillation occurred on the CONV-PSS response with amplitude between 4.74 and 3.42103 pu. This response was decreased and achieved the settling time at more than 8 s (tst1) and 15 s (tst2), for first and second disturbances, respectively. The oscillation also appeared on the ANFIS-PSS response with amplitude at the values between 4.46 and 1.13103 pu. But, the amplitude of the ANFIS-PSS response is less than the amplitude of the CONV-PSS response. Moreover, the rotor speed (9) that system equipped by the T2FLS- PSS achieved peak overshoot at the values of 2.02 (Po1) and 2.30103 (Po2) pu. Response of T2FLS-PSS is better than the other PSS(s). Figure 9. Enhancement stability of the (a) 9 and (b) 9 by using the T2FLS-PSS
  • 9.  ISSN: 2088-8708 Int J Elec & Comp Eng, Vol. 8, No. 1, February 2018 : 76 – 86 84 The rotor angle (9) for the T2FLS-PSS, ANFIS-PSS and CONV-PSS achieved the peak overshoot (Po1) at the values of 10.04, 9.75 and 9.71. Again, when the second disturbance was disturbed, the peak overshoot of the T2FLS-PSS, ANFIS-PSS and CONV-PSS was achieved at the values of 18.68, 18.41 and 18.43, respectively. Settling time (tst1) for the T2FLS-PSS, ANFIS-PSS and CONV-PSS was achieved at the times of 4.24, 4.32 and 5.44 s. Next, the settling time (tst2) was achieved at the times of 12.11, 12.29 and 13.07 s. Steady state (Ss1) was achieved at the value of 5.78 for the T2FLS-PSS, and at the value of 5.39 for the ANFIS-PSS and CONV-PSS. Finally, the steady state (Ss2) was achieved at values of 16.65, 16.51 and 16.50 for the T2FLS-PSS, ANFIS-PSS and CONV-PSS, respectively. The performance of respective PSS(s) on (9) response are shown in Figure 9(b) and Table 2. The simulation results of this paper are in- line with the simulation results in [16] that the settling time of the PSS responses in multimachine system are around 5.0 s. Table 2. Performance of respective PSS on second disturbance at 0.09 pu and 8.0 s PSS-type 3 3 Po1 Po2 tst1 tst2 Po1 Po2 tst1 tst2 Ss1 Ss2 ×[−10−3 ] (pu) (s) −() (s) −() CONV-PSS 10.12 11.23 >8.0 >15.0 21.83 41.23 7.8 14.9 17.71 36.2 ANFIS-PSS 8.03 9.75 4.85 12.49 21.26 40.32 4.82 12.47 17.65 36.12 T2FLS-PSS 6.52 7.86 4.51 12.17 21.34 40.30 4.79 12.36 17.52 36.04 7 7 CONV-PSS 1.81 2.09 >8.0 >15.0 6.41 12.27 5.43 13.15 5.39 11.06 ANFIS-PSS 2.33 2.43 4.81 12.47 6.38 12.10 4.51 12.38 5.39 11.06 T2FLS-PSS 1.01 1.12 4.48 12.15 6.68 12.45 4.32 12.14 5.78 11.46 9 9 CONV-PSS 4.74 5.45 >8.0 >15.0 9.71 18.43 5.41 13.07 5.39 16.50 ANFIS-PSS 4.46 4.74 4.75 12.39 9.75 18.61 4.32 12.29 5.39 16.51 T2FLS-PSS 2.02 2.3 4.36 11.97 10.04 18.68 4.24 12.11 5.78 16.65 5. CONCLUSION The coordination of ANFIS-PSS and T2FLS-PSS are evaluated on a large-scale power system (LSPS). The design of PSS based on ANFIS and T2FLS are also explored in-depth in this research. On designing process, the ANFIS-PSS parameters are obtained automatically through learning stage. All the data that used in the learning stage are obtained by simulating the LSPS equipped by conventional PSS (CONV- PSS) with varied load capacity. The learning processes are conducted in off-line mode. Meanwhile, the T2FLS parameters are determined by design based on the knowledge of the designer. The proposed PSS(s) are tested by using two scenarios in order to validity of the model. In First Scenario, the system is forcing by a single mechanical disturbance on the Machine-2. The simulation results are observed on the rotor speed and angle of the Machine-3 (M3) for mode local oscillation, and Machine-7 (M7) and Machine-9 (M9) for mode inter-area oscillation. The simulation results are as follows: The settling time of the rotor speed (Δ3) and angle Δ3 are obtained at the times of 5.25 and 5.62 s, respectively, for T2FLS-PSS. The steady state values for the Δ3 responses of all the PSS(s) are obtained at −19.52 . When multiple disturbances are forced to the system, responses of the T2FLS-PSS are as follows: The settling time are obtained at 4.51 s (tst1) and 12.17 s (tst2) for the Δ3. The settling time are obtained at 4.79 s (tst1) and 12.36 s (tst2) for the Δ3. The steady state values are obtained at −17.52 (Ss1) and −36.04 (Ss2). The evaluation on inter-area mode oscillation (Area II and III) is obtained as follows: The (Δ7) and Δ7 are obtained at the times of 5.31 and 5.46 s for the T2FLS- PSS. The steady state values for the Δ7 responses of the T2FLS-PSS is obtained at 6.39. The (Δ9) and Δ9 are obtained at the times of 5.24 and 5.43 s for the T2FLS-PSS. The evaluation is also conducted on multiple disturbances. In this scenario, responses of the CONV-PSS and ANFIS-PSS oscillated in a few second. Meanwhile, the T2FLS response for the (Δ3) achieved the settling time at times of 4.70 and 12.36 s for the first and second disturbances, respectively. The peak overshoot (Po1 and Po2) are achieved at the values of −6.52 and −7.86× 10−3 pu. It is concluded that the T2FLS-PSS gives better responses than the other PSS. Where, peak overshoot of the T2FLS-PSS less than the other PSS and the settling time also shorter than the other PSS. ACKNOWLEDGEMENTS The authors would like to thank to the Directorat General of Higher Education (DGHE) the Research, Technology and Higher Education Ministry, Republic of Indonesia to financial support through
  • 10. Int J Elec & Comp Eng ISSN: 2088-8708  Coordination of Adaptive Neuro Fuzzy Inference System (ANFIS) and Type-2 Fuzzy …. (Agung B. Muljono) 85 Hibah Penelitian Fundamental 2015-2016. Also, the authors thank to the colleagues and students at Power System Laboratory, University of Mataram for well cooperation during this research was done. REFERENCES [1] Amirullah and A. Kiswantono, “Power Quality Enhancement of Integration Photovoltaic Generator to Grid under Variable Solar Irradiance Level MPPT-Fuzzy”, International Journal in Electrical and Computer Engineering (IJECE), Vol. 6. No. 6. pp. 2629-2642, 2016. [2] A.S. Tomer and S.P. Dubey, “Response Based Comparative Analysis of Two Inverter Fed Six Phase PMSM Drive by using PI and Fuzzy Logic Controller”, International Journal in Electrical and Computer Engineering (IJECE), Vol. 6. No. 6. pp. 2643-2657, 2016. [3] L.S. Moulin, et al., “Support Vector Machines for Transient Stability Analysis of Large-scale Power Systems,” IEEE Trans. on Power Syst., vol. 19, no. 2, 2004. [4] A.B. Muljono, et al., “Dynamic Stability Improvement using ANFIS-based Power System Stabilizer in a Multimachine Power System (in Bahasa Indonesia),” Proc. of SENTIA, Polinema Malang, vol. 7, pp. B16-B21, 2015. [5] A.B. Muljono, et al., “Dynamic Stability Improvement of Multimachine Power System using ANFIS-based Power System Stabilizer,” TELKOMNIKA (Telecommunication Computing Electronics and Control), vol. 7, pp. 1170- 1178, 2015. [6] M.H. Al-Qatamin, “An Optimal State Feedback Controller Based Neural Networks for Synchronous Generators,” International Journal in Electrical and Computer Engineering (IJECE), Vol. 3 No. 4, pp. 561-567, 2013. [7] T. Hussein and A. Shamekh, “Adaptive Rule-base Fuzzy Power System Stabilizer for a Multi-machine System,” Proc. of the MED Conf., pp.1415-1419, 2013. [8] M. Kushwaha and R. Khare, “Dynamic Stability Enhancement of Power System using Fuzzy Logic Based Power System Stabilizer,” Proc. of Int. Conf. on ICPEC, pp. 213-219, 2013. [9] B. Shah, “Comparative Study of Conventional and Fuzzy Based Power System Stabilizer,” Proc. of Int. Conf. on CSNT, IEEE, pp. 547-551, 2013. [10] F.M. Adjeroud, et al., “A Coordinated Genetic Based Type-2 Fuzzy Stabilizer for Conventional and Superconducting Generators,” Electric Power Systems Research, vol. 129, pp. 51-61, 2015. [11] Z. Sun, et al., “Optimal Tuning of Type-2 Fuzzy Logic Power System Stabilizer Based on Differential Evolution Algorithm,” IJEPES, vol. 62, pp. 19-28, 2014. [12] S. Kamel, et al., “An Indirect Adaptive Type-2 Fuzzy Sliding Mode PSS Design to Damp Power System Oscillations,” Proc. of Int. Conf. on Modeling, Identification and Control, Tunisia, 2015. [13] K.F. Zhang and X.Z. Dai, “Structural Analysis of Large-scale Power Systems”, Mathematica Problem in Engineering,Hindawi Pub., 2012. [14] Y.Y. Hsu and C.C. Su, “Application of Power System Stabilizer on a System with Pumped Storage plant,” IEEE Trans. on Power Syst., vol. 3, no. 1, 1988. [15] M. Saidy and F.M. Hughes, “Performance Improvement of a Conventional Power System Stabilizer,” Elect. Power and Energy Syst., vol. 17 no. 5, 1995. [16] J. Talaq, “Optimal Power System Stabilizers for Multi Machine Systems,” IJEPES, vol. 43, pp. 793-803, 2012. [17] I.M. Ginarsa, et al., “Controlling Chaos and Voltage Collapse using Layered Recurrent Network-based PID-SVC in Power Systems,” TELKOMNIKA (Telecommunication Computing Electronics and Control), vol. 11, pp. 451-462, no. 3, 2013. [18] S. Mohagheghi, et al., “Adaptive Critic Design Based on Neuro-fuzzy Controller for a Static Compensator in a Multimachine Power System”, IEEE Trans. on Power Syst., vol. 21, no. 4, 2006. [19] S. Mohagheghi, et al., “Hardware Implementation of a Mamdani Fuzzy Logic Controller for a Static Compensator in a Multimachine Power System,” IEEE Trans. on Industry App., vol. 45, no. 4, 2009. [20] I.M. Ginarsa, et al., “Controlling Chaos and Voltage Collapse using an ANFIS-based Composite Controller-static Var Compensator in Power Systems,” IJEPES, vol. 46, pp. 79-88, 2013. [21] I.M. Ginarsa, et al., “Improvement of Transient Voltage Responses using an Additional PID-loop on an ANFISbased Composite Controller-SVC (CC-SVC) to Control Chaos and voltage Collapse in Power Systems,” IEEJ Trans. on Power and Energy (Section B), vol. 131, no. 10, pp. 836-848, 2011. [22] I.M. Ginarsa, et al., “Regulation of 12-pulse Rectifier Converter using ANFIS-based Controller in a HVDC Transmission System”, in Integrated Sci-Tech: The Interdisciplinary Research Approach, vol. 1, chapt. 6, UPT Perpustakaan UNILA Lampung, pp. 44-53, 2015. [23] N. Bawane, et al., “ANFIS Based Control and Fault Detection of HVDC Converter,” HAIT Journal of Science and Engineering B, vol. 2, no. 5-6, pp. 673-689, 2011. [24] I.M. Ginarsa and O. Zebua, “Stability Improvement of Single Machine using ANFIS-PSS Based on Feedbacklinearization,” TELKOMNIKA (Telecommunication Computing Electronics and Control), vol. 12, no. 2, 2014. [25] P. Kundur, Power System Stability and Control, EPRI McGraw-Hill. New York, 1994. [26] K.R. Padiyar, Power System Dynamic Stability and Control, John Wiley and Sons (Asia) Pte Ltd, Singapore,1994. [27] J.-S.R. Jang, et al., Neuro-fuzzy and Soft Computing: A Computational Approach to Learning and Machine Intelligence, Prentice-Hall International, Inc., USA, 1997. [28] N.N. Karnik, et al., “Type-2 Fuzzy Logic Systems,” IEEE Trans. on Fuzzy Syst., vol. 7, no. 6, 1999.
  • 11.  ISSN: 2088-8708 Int J Elec & Comp Eng, Vol. 8, No. 1, February 2018 : 76 – 86 86 [29] O. Castillo and P. Melin, “Recent Advances in Interval Type-2 Fuzzy Systems”, pp. 7-12. Springer, Heidelberg, 2012. [30] A. Taskin and T. Kumbasar, “An Open Source Matlab/Simulink Toolbox for Interval Type-2 Fuzzy Logic System,” IEEE Symp. Series on Computational Intelligence, Cape Town, South Africa, 2015. [31] A. Taskin and T. Kumbasar, Matlab/Simulink Toolbox for Interval Type-2 Fuzzy Logic Systems, http://web.itu.edu.tr/kumbasart/type2fuzzy.htm, access on 20 Sept. 2016, 20:10 pm. [32] Matlab, MATLAB Version 8.0 (2013a), The Matworks Inc (2013). BIOGRAPHIES OF AUTHORS Agung B. Muljono was born in Purwodadi, Grobogan, Central Java Indonesia, on February 1971. He received in B.Eng, and M.Eng in electrical engineering from Malang Institute of Technology (1996) and Gadjah Mada University (2000) Indonesia, respectively. Since 1998 he was a lecturer at electrical engineering, Mataram University. His research interests are power system transmission and distribution, power system dynamic and stability, artificial intelligent application in power systems, energy planning and distributed generation (DG) in power systems. He was an active author and co-author research papers in national and international journal. I M. Ginarsa was born in Darmasaba, Badung Regency, Bali Indonesia, on March 1970. He received in B.Eng, M.Eng and Ph.D in electrical eng. from Udayana Univ. (1997), Gadjah Mada Univ. (2001) and Sepuluh Nopember Institute of Tech. (2012), Indonesia. Since 1999 he was a lecturer at Electrical engineering, Mataram University. In 2010 he was a member of Electric Power System Laboratory, Kumamoto Univ. Japan as a research student. His research interests are power system dynamic and stability, nonlinear dynamic in power system, voltage stability and control, artificial intelligent application in power systems. His works have been presented in international seminars. He was an active author and co-author in this field that his research papers have been published in national and international journals. He was served a invited reviewer on national and international publications I M.A. Nrartha was born in Denpasar, Bali Indonesia, on April 1973. He received in B.Eng and M.Eng in electrical eng. from Sepuluh Nopember Institute of Tech. (1997) and Gadjah Mada Univ.(2001). Since 1999 he was a lecturer at Electrical engineering, Mataram University. His research interests are power system dynamic and stability, transmission and distribution, optimization, power quality and artificial intelligent application in power systems. He was an active author and co-author research papers in national and international journal A. Dharma was born in Denpasar, Bali Indonesia, on August 1964. He received in B.Eng, M.Eng and Ph.D in electrical eng. from Sepuluh Nopember Institute of Tech, in 1990, 2001 and, 2006 and 2014, respectively. Since 1990 he was a lecturer at Electrical engineering, Udayana University. His research interests are power system engineering, power generation, renewable energy technology and application of artificial intelligent for load forecasting. He was an active author and co-author research papers in national and international journal.