42U Confidential   ©2008 42U All rights reserved  Slide  Data Center Measurement  – Building An ROI Baseline August 22, 2008 ________________________________
Overview Big Picture Why Measure What to Measure How To Measure Visualization Primer Case Study Summary Q&A 42U Confidential   ©2008 42U All rights reserved  Slide
Why Measure Service Level Agreement (SLA) Information Technology Infrastructure Library (ITIL) Total Cost of Ownership (TCO) Actual Versus Designed Stranded Capacity “ Can’t Manage What You Can’t Measure” 42U Confidential   ©2008 42U All rights reserved  Slide
Energy Cost Projection 42U Confidential   ©2008 42U All rights reserved  Slide  Source: Aperture, Greener Pastures for Your Data Center
Energy Benchmark Established Benchmark Enables Comparison 42U Confidential   ©2008 42U All rights reserved  Slide  Source: The Green Grid
Energy Consumers 70% of Power Consumption Goes to the Infrastructure  Over Twice that of the IT Equipment 42U Confidential   ©2008 42U All rights reserved  Slide  Source: The Green Grid, Guidelines  for Energy-Efficient Datacenters
What To Measure Power Temperature Air Pressure Humidity Water Flow & Temperature 42U Confidential   ©2008 42U All rights reserved  Slide
Best Practice Opportunities Chilled Water Fans 42U Confidential   ©2008 42U All rights reserved  Slide  Source: Accenture Data Center Energy Forecast Report, July11, 2008
How To Measure Level of Precision Alternatives Point In Time Ongoing Real-Time Modeling Tool Requirements 42U Confidential   ©2008 42U All rights reserved  Slide
Visualization Tools System Admins Network Admins Data Center Managers 42U Confidential   ©2008 42U All rights reserved  Slide
Real-Time Imaging 42U Confidential   ©2008 42U All rights reserved  Slide
Real-Time Imaging 42U Confidential   ©2008 42U All rights reserved  Slide
CFD Visualization Computational Fluid Dynamics (CFD) 42U Confidential   ©2008 42U All rights reserved  Slide
Case Study Lawrence Berkeley National Lab Continued Increase in Demand Data Center Capacity ~2011 Strategic Imperative on Efficiency Study Results Improve Airflow Virtualization Water Cooling 42U Confidential   ©2008 42U All rights reserved  Slide
Efficiency Measurement Life-Cycle TM 42U Confidential   ©2008 42U All rights reserved  Slide  Reconfiguration Measurement Points Measurement Object Database Security Hardware Configuration & Testing Network Configuration & Testing Sensor Installation Software Installation Network Verification Data Collection Analysis System Management Facilities Data IT Infrastructure Data IT Equipment Data Integration Requirements Survey Planning Installation Measurement
Wireless Sensor Network 42U Confidential   ©2008 42U All rights reserved  Slide
Confirmation of Fundamentals Impact of a Single Blanking Panel Consistent Results For Floor Leaks Tile Arrangement Top of rack Middle of rack 42U Confidential   ©2008 42U All rights reserved  Slide
Floor Tile Tuning One Day Time Investment 24 Converted from Perforated to Solid 6 Converted from High- to Low- Flow 4 Converted from Low- to High- Flow Before After 42U Confidential   ©2008 42U All rights reserved  Slide
Results of Tuning Real-Time Verification Eliminates Guesswork Under-Floor Pressure Rack-Top Temperatures 42U Confidential   ©2008 42U All rights reserved  Slide
Air Flow Tuning 42U Confidential   ©2008 42U All rights reserved  Slide
Measureable Correlations Real-Time Feedback Enhanced Knowledge of Data Center Redundancy Characteristics Under-Floor Pressure Rack-Top Temperatures 42U Confidential   ©2008 42U All rights reserved  Slide
Summary Planning What To Measure How To Measure Interpreting Results Efficiency Improvement Plan Rank By ROI 42U Confidential   ©2008 42U All rights reserved  Slide
Q&A 42U Confidential   ©2008 42U All rights reserved  Slide  For More Information Contact Your 42U Data Center Efficiency Consultant: 1-800-638-2638 or  www.42U.com For a Copy of Today’s Presentation Email: [email_address] Thank You

More Related Content

PPT
Data Center Energy Efficiency Best Practices
PPT
Data Center Server Rack Strategies
PPTX
The Data Center in Real Time: Monitoring Tools Overview & Demo
PPTX
Duke Energy - Case Study
PPTX
Fusing Material and Data Science
PDF
Energy Management Strategies for Operational Excellence @ ARC's 2011 Industry...
PPTX
DigitalClone Live Product Update
PPTX
Datacenter power optimization
Data Center Energy Efficiency Best Practices
Data Center Server Rack Strategies
The Data Center in Real Time: Monitoring Tools Overview & Demo
Duke Energy - Case Study
Fusing Material and Data Science
Energy Management Strategies for Operational Excellence @ ARC's 2011 Industry...
DigitalClone Live Product Update
Datacenter power optimization

What's hot (17)

PDF
Beyond Big Data: Harnessing the Industrial Internet for Wind Power
PDF
PDF
alspa_solution_overview_brochure
PPTX
Drivetrain Modeling
PDF
Future of IIoT Predictive Maintenance Study
PDF
1530 sulimov
PPTX
DigitalClone for Engineering Supporting Business Initiatives of Rotorcraft OE...
PPTX
Improving your PUE while consolidating into an existing live data center
PPT
Fire suppression systems Full aisle containment and cooling
PPTX
REWITEC Additives to Extend Gearbox Life
PPTX
Transforming data into sustained energy performance
PPTX
Essential elements of data center operations
PDF
Comprehensive Energy Management Strategy
PPTX
Predictive Maintenance for Oil and Gas
PPSX
Coppertree Energy Metering and Dashboards
PDF
Equota Pitch Deck EN 2015
PPTX
The economics of reducing the cost of energy by 13% revenues
Beyond Big Data: Harnessing the Industrial Internet for Wind Power
alspa_solution_overview_brochure
Drivetrain Modeling
Future of IIoT Predictive Maintenance Study
1530 sulimov
DigitalClone for Engineering Supporting Business Initiatives of Rotorcraft OE...
Improving your PUE while consolidating into an existing live data center
Fire suppression systems Full aisle containment and cooling
REWITEC Additives to Extend Gearbox Life
Transforming data into sustained energy performance
Essential elements of data center operations
Comprehensive Energy Management Strategy
Predictive Maintenance for Oil and Gas
Coppertree Energy Metering and Dashboards
Equota Pitch Deck EN 2015
The economics of reducing the cost of energy by 13% revenues
Ad

Viewers also liked (13)

PDF
Introduction to Objects - building Measurement Systems
PDF
Building Your Content Marketing Measurement Program From The Ground Up
PPTX
Social Bakers EngageX: Building Measurement Frameworks - 1000heads
PDF
Pr news pr measurement- building a foundation in metrics
PPTX
Implementing Mobile Number Portability (MNP) in Africa: Kenyan Case Study
PDF
Building a Digital Measurement Plan - PSE Web 2013
PPTX
Advance building measurement NRM 2
PDF
Sem 2 bs1 telecommunication r1
PPTX
An introduction to SOC (Security Operation Center)
PDF
Breeching Inlet
PPTX
Dry riser system
PDF
Fire safety-in-high-rise-apartment-buildings
PPTX
Project planning and project work plan
Introduction to Objects - building Measurement Systems
Building Your Content Marketing Measurement Program From The Ground Up
Social Bakers EngageX: Building Measurement Frameworks - 1000heads
Pr news pr measurement- building a foundation in metrics
Implementing Mobile Number Portability (MNP) in Africa: Kenyan Case Study
Building a Digital Measurement Plan - PSE Web 2013
Advance building measurement NRM 2
Sem 2 bs1 telecommunication r1
An introduction to SOC (Security Operation Center)
Breeching Inlet
Dry riser system
Fire safety-in-high-rise-apartment-buildings
Project planning and project work plan
Ad

Similar to Data Center Measurement (20)

PPT
Data Center Cooling Strategies
PPT
Data Center Power Strategies
PPT
Data Center Energy Efficiency Leadership
PPT
Data Center Optimization Best Practices
PPTX
Data Center Optimization with Avocent MergePoint Infrastructure Explorer (AMIE)
PPT
How green standards are changing data center design and operations
PPTX
Power Usage Effectiveness (PUE): Status & Directions. By K. Winkler
PPT
PUE Reconsidered - AFCOM (MI), July 2009
PPTX
Detechtion - Sales Presentation (2-27-23)(1).pptx
PPTX
How green standards are changing data center design and operations
PPTX
Presentation---17-Nov-22 1.pptx
PPTX
SpecFlow Executable Specifications
PPTX
Retrofit, build, or go cloud/colo? Choosing your best direction
PPTX
Retrofit, build, or go cloud/colo? Choosing your best direction
PDF
Datacenter Strategy, Design, and Build
PPTX
Ejecución de sizer para SimpliVity Partners
PPTX
Supermicro and The Green Grid (TGG)
PPT
Data Center PUE Reconsidered
PPT
ch28-software-reengineering.ppt
PDF
MMSys'21 - Multi-access edge computing for adaptive bitrate video streaming
Data Center Cooling Strategies
Data Center Power Strategies
Data Center Energy Efficiency Leadership
Data Center Optimization Best Practices
Data Center Optimization with Avocent MergePoint Infrastructure Explorer (AMIE)
How green standards are changing data center design and operations
Power Usage Effectiveness (PUE): Status & Directions. By K. Winkler
PUE Reconsidered - AFCOM (MI), July 2009
Detechtion - Sales Presentation (2-27-23)(1).pptx
How green standards are changing data center design and operations
Presentation---17-Nov-22 1.pptx
SpecFlow Executable Specifications
Retrofit, build, or go cloud/colo? Choosing your best direction
Retrofit, build, or go cloud/colo? Choosing your best direction
Datacenter Strategy, Design, and Build
Ejecución de sizer para SimpliVity Partners
Supermicro and The Green Grid (TGG)
Data Center PUE Reconsidered
ch28-software-reengineering.ppt
MMSys'21 - Multi-access edge computing for adaptive bitrate video streaming

More from 42U Data Center Solutions (20)

PDF
What is the Goal of Server Rack Accessories
PDF
What is the Goal of Data Center Security
PDF
What is the Goal of Power Distribution
PDF
What is the Goal of Data Center Racks & Enclosures
PDF
What is the Goal of High Performance KVM Switch Solutions
PDF
What is the Goal of Integrated Data Center Solutions
PDF
What is the Goal of Digital Signage
PDF
What is the Goal of Data Center Containment
PDF
What is the Goal of Data Center Cooling
PDF
What is the Goal of Data Center Airflow Management
PDF
What is the Goal of Technical Furniture
PDF
UPS Solutions for the Next Generation Data Center with Jen
PDF
KVM Solutions for the Next Generation Data Center with Jen
PDF
High Density Cooling Solutions for the Next Generation Data Center with Jen
PDF
DCIM & Monitoring Solutions for the Next Generation Data Center with Jen
PDF
Power & Cooling Solutions for the Next Generation Data Center with Jen
PPT
Uncovering the Myths Behind Remote Power
PPT
Eliminating Data Center Hot Spots
PPT
Data Center Cooling Study on Liquid Cooling
PPT
Hot Aisle & Cold Aisle Containment Solutions & Case Studies
What is the Goal of Server Rack Accessories
What is the Goal of Data Center Security
What is the Goal of Power Distribution
What is the Goal of Data Center Racks & Enclosures
What is the Goal of High Performance KVM Switch Solutions
What is the Goal of Integrated Data Center Solutions
What is the Goal of Digital Signage
What is the Goal of Data Center Containment
What is the Goal of Data Center Cooling
What is the Goal of Data Center Airflow Management
What is the Goal of Technical Furniture
UPS Solutions for the Next Generation Data Center with Jen
KVM Solutions for the Next Generation Data Center with Jen
High Density Cooling Solutions for the Next Generation Data Center with Jen
DCIM & Monitoring Solutions for the Next Generation Data Center with Jen
Power & Cooling Solutions for the Next Generation Data Center with Jen
Uncovering the Myths Behind Remote Power
Eliminating Data Center Hot Spots
Data Center Cooling Study on Liquid Cooling
Hot Aisle & Cold Aisle Containment Solutions & Case Studies

Recently uploaded (20)

PPTX
SOPHOS-XG Firewall Administrator PPT.pptx
PDF
Encapsulation theory and applications.pdf
PDF
NewMind AI Weekly Chronicles - August'25-Week II
PPTX
1. Introduction to Computer Programming.pptx
PDF
Build a system with the filesystem maintained by OSTree @ COSCUP 2025
PDF
Spectral efficient network and resource selection model in 5G networks
PDF
Reach Out and Touch Someone: Haptics and Empathic Computing
PDF
Video forgery: An extensive analysis of inter-and intra-frame manipulation al...
PDF
Blue Purple Modern Animated Computer Science Presentation.pdf.pdf
PDF
Mushroom cultivation and it's methods.pdf
PPT
Teaching material agriculture food technology
PDF
A comparative analysis of optical character recognition models for extracting...
PDF
MIND Revenue Release Quarter 2 2025 Press Release
PPTX
OMC Textile Division Presentation 2021.pptx
PPTX
Programs and apps: productivity, graphics, security and other tools
PDF
Agricultural_Statistics_at_a_Glance_2022_0.pdf
PDF
Advanced methodologies resolving dimensionality complications for autism neur...
PPTX
TechTalks-8-2019-Service-Management-ITIL-Refresh-ITIL-4-Framework-Supports-Ou...
PPTX
TLE Review Electricity (Electricity).pptx
PDF
Accuracy of neural networks in brain wave diagnosis of schizophrenia
SOPHOS-XG Firewall Administrator PPT.pptx
Encapsulation theory and applications.pdf
NewMind AI Weekly Chronicles - August'25-Week II
1. Introduction to Computer Programming.pptx
Build a system with the filesystem maintained by OSTree @ COSCUP 2025
Spectral efficient network and resource selection model in 5G networks
Reach Out and Touch Someone: Haptics and Empathic Computing
Video forgery: An extensive analysis of inter-and intra-frame manipulation al...
Blue Purple Modern Animated Computer Science Presentation.pdf.pdf
Mushroom cultivation and it's methods.pdf
Teaching material agriculture food technology
A comparative analysis of optical character recognition models for extracting...
MIND Revenue Release Quarter 2 2025 Press Release
OMC Textile Division Presentation 2021.pptx
Programs and apps: productivity, graphics, security and other tools
Agricultural_Statistics_at_a_Glance_2022_0.pdf
Advanced methodologies resolving dimensionality complications for autism neur...
TechTalks-8-2019-Service-Management-ITIL-Refresh-ITIL-4-Framework-Supports-Ou...
TLE Review Electricity (Electricity).pptx
Accuracy of neural networks in brain wave diagnosis of schizophrenia

Data Center Measurement

  • 1. 42U Confidential ©2008 42U All rights reserved Slide Data Center Measurement – Building An ROI Baseline August 22, 2008 ________________________________
  • 2. Overview Big Picture Why Measure What to Measure How To Measure Visualization Primer Case Study Summary Q&A 42U Confidential ©2008 42U All rights reserved Slide
  • 3. Why Measure Service Level Agreement (SLA) Information Technology Infrastructure Library (ITIL) Total Cost of Ownership (TCO) Actual Versus Designed Stranded Capacity “ Can’t Manage What You Can’t Measure” 42U Confidential ©2008 42U All rights reserved Slide
  • 4. Energy Cost Projection 42U Confidential ©2008 42U All rights reserved Slide Source: Aperture, Greener Pastures for Your Data Center
  • 5. Energy Benchmark Established Benchmark Enables Comparison 42U Confidential ©2008 42U All rights reserved Slide Source: The Green Grid
  • 6. Energy Consumers 70% of Power Consumption Goes to the Infrastructure Over Twice that of the IT Equipment 42U Confidential ©2008 42U All rights reserved Slide Source: The Green Grid, Guidelines for Energy-Efficient Datacenters
  • 7. What To Measure Power Temperature Air Pressure Humidity Water Flow & Temperature 42U Confidential ©2008 42U All rights reserved Slide
  • 8. Best Practice Opportunities Chilled Water Fans 42U Confidential ©2008 42U All rights reserved Slide Source: Accenture Data Center Energy Forecast Report, July11, 2008
  • 9. How To Measure Level of Precision Alternatives Point In Time Ongoing Real-Time Modeling Tool Requirements 42U Confidential ©2008 42U All rights reserved Slide
  • 10. Visualization Tools System Admins Network Admins Data Center Managers 42U Confidential ©2008 42U All rights reserved Slide
  • 11. Real-Time Imaging 42U Confidential ©2008 42U All rights reserved Slide
  • 12. Real-Time Imaging 42U Confidential ©2008 42U All rights reserved Slide
  • 13. CFD Visualization Computational Fluid Dynamics (CFD) 42U Confidential ©2008 42U All rights reserved Slide
  • 14. Case Study Lawrence Berkeley National Lab Continued Increase in Demand Data Center Capacity ~2011 Strategic Imperative on Efficiency Study Results Improve Airflow Virtualization Water Cooling 42U Confidential ©2008 42U All rights reserved Slide
  • 15. Efficiency Measurement Life-Cycle TM 42U Confidential ©2008 42U All rights reserved Slide Reconfiguration Measurement Points Measurement Object Database Security Hardware Configuration & Testing Network Configuration & Testing Sensor Installation Software Installation Network Verification Data Collection Analysis System Management Facilities Data IT Infrastructure Data IT Equipment Data Integration Requirements Survey Planning Installation Measurement
  • 16. Wireless Sensor Network 42U Confidential ©2008 42U All rights reserved Slide
  • 17. Confirmation of Fundamentals Impact of a Single Blanking Panel Consistent Results For Floor Leaks Tile Arrangement Top of rack Middle of rack 42U Confidential ©2008 42U All rights reserved Slide
  • 18. Floor Tile Tuning One Day Time Investment 24 Converted from Perforated to Solid 6 Converted from High- to Low- Flow 4 Converted from Low- to High- Flow Before After 42U Confidential ©2008 42U All rights reserved Slide
  • 19. Results of Tuning Real-Time Verification Eliminates Guesswork Under-Floor Pressure Rack-Top Temperatures 42U Confidential ©2008 42U All rights reserved Slide
  • 20. Air Flow Tuning 42U Confidential ©2008 42U All rights reserved Slide
  • 21. Measureable Correlations Real-Time Feedback Enhanced Knowledge of Data Center Redundancy Characteristics Under-Floor Pressure Rack-Top Temperatures 42U Confidential ©2008 42U All rights reserved Slide
  • 22. Summary Planning What To Measure How To Measure Interpreting Results Efficiency Improvement Plan Rank By ROI 42U Confidential ©2008 42U All rights reserved Slide
  • 23. Q&A 42U Confidential ©2008 42U All rights reserved Slide For More Information Contact Your 42U Data Center Efficiency Consultant: 1-800-638-2638 or www.42U.com For a Copy of Today’s Presentation Email: [email_address] Thank You

Editor's Notes

  • #4: Provides actual data that can be used in data center design and management tools. Create a roadmap Ensuring you’re not exposed to SLA failures??? Ensuring compliance with your ITIL compliance in areas such as supplying appropriate capacities, as opposed to sufficient capacities. More deeply, business analysis best practices, as defined in the Business Analysis Body of Knowledge (BABOK), define the techniques and ITIL v3 where the focus is on the life cycle approach. Ineffective business analysis costs U.S. businesses at least $30B every year. Improving the precision of the Total Cost of Ownership calculation to be used for informed planning. As-configured is not typically the actual experience. Blockages and inefficiencies degrade the actual performance. Identifying stranded capacities that are opportunities for efficiency improvement programs. Gartner recently reported findings (RN-G00153396) that included strong recommendations that IT improve their efficiency by first measuring their energy efficiency losses. Gartner describes operational maturity as moving from chaos through reactivity, proactive services to generation of business value. One of the first steps to take to move closer to and to maintain IT business value is to measure your data center against a meaningful benchmark, such as power usage effectiveness (PUE). Stratavia recently produced an excellent whitepaper describing this process. A measurement initiative can be the basis for a more broad greening initiative that generates considerable savings, frees budget for other efforts and contributes to corporate environmental initiatives. (need green corporate story). The Department of Energy (DOE) will soon release DC Pro, a tool that can be used to calculate data center infrastructure efficiency (DCiE) as well as provide recommendations for improvement.
  • #5: The A and B projections are for improvements in server technology efficiency.
  • #6: Power Usage Effectiveness is an established benchmark that can be used to compare your data center efficiency to the national average as well as others in your industry. Power use efficiency is an alternative use of the acronym. EPA uses the term EER, energy efficiency ratio, in their recent study.
  • #9: The largest opportunities for efficiency gains from upgrading to best practices are in the area of chilled water and fans. Air and Water side economizers are two best practice approaches that will reduce chiller expenses.
  • #10: You need to target the meaningful level of precision that is cost effective. You can do some gross calculations using room-level data, but that will not yield sufficiently actionable results. Conversely, measuring down to the device level is typically not cost effective; very nice information to have, but in most cases it’s not required. The most effective level is at the rack. Depending on the volatility of your data center you can decide to have a point-in-time assessment, establish an ongoing monitoring environment or invest in real-time monitoring technology. It has been our experience that data centers are rarely static environments, but some purpose-built data centers do have sufficiently low volatility that a point in time measurement approach is the most cost effective approach. The cost and availability of real-time monitoring technology has improved dramatically and is now to the point that it is a very cost effective alternative. It is important to note that there can be value in having device-level data. It can identify unusual airflow requirements, power consumption characteristics of a device, as well as more accurate assessments of the effect of rack configuration changes. In general, this level of detail does require a mature IT environment where change history and inventory management data is maintained. Another factor to consider when determining your measurement instrumentation plan is your need for data to use in a modeling tool that can predict the results of changes before you make the changes. This brings us to an important topic, visualization…
  • #11: systems & network administrators have tools for visualization useful for debugging, benchmarking, capacity planning, forensics data center managers have comparatively poor visualization tools
  • #13: … and now for an illustration of the power of visualization.
  • #14: Computational Fluid Dynamics
  • #15: Several decades old ~5000 sq ft 18” raised floors ~.5MW total power consumption Combination of clusters and business systems clusters account for almost all new demand Unusual cooling system 7 down-shot CRACs for under-floor supply supplementary overhead supply (chiller coil + fans) Starting summer of 2007, IT began a data center efficiency effort In collaboration with researchers in EETD, we perform a series of engineering studies documenting electrical, mechanical systems measuring loads & capacities; performing CFD calculating efficiency identifying opportunities for improvement deploying wireless sensor system (more later) The data center was overcooled but this is the norm Abundant low-hanging fruit simultaneous humidification & dehumidification blanking panels missing excessive number of perforated floor tiles air-flow pathologies (mixing, short-circuiting) The data center was relatively efficient! none of the clusters backed by UPS
  • #17: We installed a wireless sensor net from SynapSense 200 monitoring points temperature, humidity, under-floor pressure, current For the first time, we have a detailed understanding of environmental conditions in the data center real-time and historical graphs underlying database
  • #18: effect of adding one 12” blanking panel to the middle of a rack conventional wisdom is correct: blanking panes are essential other data center clichés also borne out eliminate leaks in floor manage floor tile permeability
  • #19: Feedback on floor-tile tuning in the course of one day 24 perforated floor tiles removed 6 floor tiles converted from high- to low-flow 4 floor tiles converted from low- to high-flow
  • #20: Feedback on floor-tile tuning: with instrumentation, we can observe results in real time when airflow is restricted, under-floor pressure increases rack-top temperatures decrease without monitoring and visualization, this process is guesswork how many tiles to remove?
  • #21: Visualizing impact of site modifications Graphing impact of major maintenance (redirection of overhead cold air supply underfloor) on air pressure in some areas, under-floor pressure increased by almost 50% impact varies according to distance from new air supply
  • #22: Visualizing impact of maintenance: each CRAC turned off in turn, for service hot spots monitored during maintenance two-fold benefit real-time feedback enhanced knowledge of data center redundancy characteristics provisionally turn off one or more CRAC units?
  • #23: Get electrical, mechanical studies Find engineering firms with data center experience Consider instrumenting your data center to enhance visibility Eat your spinach (blanking panels, leaks) Take advantage of outstanding, free PG&E Pacific Energy Center classes (state-wide) Keep an eye on emerging technologies (flywheel UPS, rack-level cooling)