This document describes a proposed override control system that uses two anti-reset windup controllers, a common actuator, and pre-filter and post-filter to limit an override variable without overshoot. The standard override control system uses a min/max selector that can cause overshoot. The proposed system instead uses a post-filter and limiter to define the desired limit and set-point for the override variable. Simulation results demonstrate that the proposed system can limit the override variable without overshoot, which is an improvement over the standard approach. An experiment on a laboratory thermal plant confirms the effectiveness of the proposed solution.