SlideShare a Scribd company logo
MINISTRY OF EDUCATION OF YOUTHS
AND SPORTS
INSTITUTE OF TECHNOLOGY OF CAMBODIA
DEPARTMENT OF INDUSTRIALAND MECHANICAL
FINAL YEAR THESIS
Tittle: Designing, Installation and Testing of VRF System
Students : TITH Sopheara and VENG Socheat
Specialty : Mechanical engineering
Advisor : Mr. KHOUN Rithymean
Academic Year : 2016- 2017
1
Contents
I. General Introduction
II. Definition
III. Panasonic VRF system
IV. Load calculation
V. Selection
VI. VRF system installation
VII. Testing and Commissioning
VIII.Conclusion
2
I. General Introduction
 Presentation of Internship
•From: 20 February to 20 May 2017
•Company: Comin Khmere
•Position : MVAC trainee
•Project: TK Royal One (Cambodia)
3
II. Definition
4
What is VRF systems?
• Variable refrigerant flow vary the flow of refrigerant to
indoor units based on demand. There are 2 types of VRF
system, heat pump and heat recovery system.
What is VRF Heat pump ?
• VRF heat pump provide heating or cooling but not
simultaneous heating and cooling
5
II. Definition
What is VRF heat recovery?
• VRF heat recovery can operate simultaneous in
heating or cooling mode.
6
II. Definition
Variable refrigerant flow (VRF) is an air-conditioning system
configuration where there is one outdoor unit and multiple
indoor units.
III. Panasonic VRF System
7
III. Panasonic VRF System
1. Outdoor unit
The outdoor unit of VRF
system, sometimes called the
outside unit or condenser.
8
(Carin, 2016)
III. Panasonic VRF System
DC twin rotary compressor:
The component of compressor are:
1. Electric motor
2. Compression mechanism
3. Accumulator
The compressor is the heart of the
refrigeration cycle.
9
(Bhatia, 2014)
III.Panasonic VRF System
a. 2-WAY Mini-FSV LE1 Series
 Use for cooling or heating mode only
Capacity range from 4HP to 6HP
COP: 4.21 in case of 4 HP
 Cooling operation possible up to 46 °C
And low as -20 °C for heating mode
 Max connectable 9 units with length 150m
10
(Hiong, 2016-2017)
III.Panasonic VRF System
b. 2-WAY FSV-EX ME2 Series
 Use for cooling or heating mode only
 Capacity range from 8HP to 80HP
 Operation temperature as high as 52°C
for cooling and as low as -20 °C for
heating mode
 Max connectable 64 units with max
length 1,000m
11
(Hiong, 2016-2017)
III.Panasonic VRF System
c. 3-WAY FSV MF2 Series
 Using for simultaneous heating and cooling
 Capacity range from 8HP to 42HP
 Temperature operation as high as 46°C for
cooling and as low as -20 for heating
 Max connectable 52 units with pipe length
up to 500m
12
(Hiong, 2016-2017)
III.Panasonic VRF System
2. Indoor unit
There are many types of indoor units such as:
• F2 type : Cooling Capacity 2.2kW to 16kW
• M1 type : Cooling Capacity 2.2kW up to 5.6kW
• Z1 type : Cooling Capacity 2.2kW to 7.3kW
• E2 type : Cooling Capacity 18kW to 28kW
13
III.Panasonic VRF System
2. Indoor unit
• E1 type : Cooling Capacity 7.3kW to 28kW
• U1 type : 4-way cassette, Cooling Capacity 2.2kW to 16kW
• Y2 type : 4-way mini cassette, Cooling Capacity 2.2kW to 5.6kW
• L1 type : 2-way cassette, Cooling Capacity 2.2kW to 7.3kW
• D1 type : 1-way cassette, Cooling Capacity 2.8kW to 7.3kW
• P1 type : Floor standing, Cooling Capacity 2.2kW to 7.3kW
14
IV.Load Calculation
 Feature of the Building TK Royal One
15http://www.cambodiancondos.com/condo-developments/tk-royal-one/
IV. Load Calculation
1. Estimate Method
Q = S . R
• Q: Total heat load [Btu.h-1]or [W]
• S: room area [m2]
• R: The rate of cooling [Btu.h-1.m-2]
Calculation total heating load for TKR1 “ Reception
room’’ which has S = 62.4 m2
• R = 900 Btu.h-1.m-2
Thus, Q = 56160 Btu.h−1 =16.45kW
16
Another room calculate by Estimate method
Items Type of Room
AREA Ratio Cooling Capacity
m² Btu/h.m2 kW Btu/h
1 Conference Hall 265.45 1200 93.36 318540
2 Break Room 49.07 750 10.78 36802
3 Coffee Shop 73.6 1300 28.04 95680
4 Financial Office 98.14 850 24.48 83419
5 Hall 35.5 700 7.28 24850
6 Office 56.5 850 14.07 48025
7 Meeting Room 31.95 900 8.40 28755
8 Service Counter 36.8 1300 14.02 47840
9 Shop 87.7 800 20.56 70160
10 Toilet 38 500 5.56 19000
17
IV. Load Calculation
2. Manual Method
The Manual Method is the method used to calculate the cooling load
of the building space with minimum errors.
Total heating load:
QT = QS + QL [W]
oTotal sensitive loads
QS = QStr+ QSRm+QSRv+QSoc+QSecl+QSequip
oTotal latent loads
QL= QLr+ QLoc+QLequip
18
IV.Load Calculation
Calculation heating load for TKR1 “ Reception Area’’
oTotal sensitive loads
QS = 14445.26 W
oTotal latent loads
QL = 1197.58W
Total heating load:
QT= 14445.26 W + 1197.58W = 15642.84 W = 15.64 kW
19
IV.Load Calculation
Verify the cooling capacity coefficient R [Btu/h.m2]:
• Manul method: R= 53367Btu.h−1 / 62.4 m2 = 855 Btu.h−1
• Estimate method: R = 900 Btu.h−1
From the calculation above by manual method, we see that
error of cooling rate approximate 5 % compared to
estimation method
20
V. Selection
1. Selection indoor unit
The total cooling load required is 109.8 kW
21(Hiong, 2016-2017)
V. Selection
The characteristic of outdoor unit model U-40ME2R8
are:
• Cooling capacity 113 kW
• Using with power supply 400/415 V/3-phase/50 Hz
• Electrical rating for cooling option: 57.3 A
• Refrigerant amount at shipment: 22.0 kg
• Air flowrate: 48600 m3 h-1
22
V. Selection
2. Selection indoor unit
 For Conference Hall of TKR1:
The requirement of cooling load is 93.36 kW.
Catalogue of model mid static duct E1 type chosen that
Its cooling capacity from 7.3 kW to 28 kW.
E1 type is a kind of saving energy, the power input
45% less (compared to H1 type)
4 of S-224ME1E5 were chosen: Cooling capacity 4 ×
22.4kW = 89.6kW
23
V. Selection
24
(Hiong, 2016-2017)
VI.VRF System Installation
1. Air duct installation
25
2. Indoor unit installation
VI.VRF System Installation
3. Copper pipe installation
26
VI.VRF System Installation
4. Drainage water pipe installation
27
VI.VRF System Installation
5. Outdoor unit installation
28
VII. Testing and Commissioning
Before we start operation VRF, we have to:
1. Test refrigerant pipe
2. Adding refrigerant
3. Check at main power on
4. Testing and commissioning
29
30
1. Test refrigerant pipe
a. Check for any leakage in the
refrigerant piping
b. Perform vacuum drying to
remove all moisture
• Keeping the valve of the outdoor
unit closed
• If the specified amount of
refrigerant cannot be charged, fully
open the valves of the outdoor unit
at liquid and gas sides, operate the
air conditioner in COOL mode
31
2. Adding refrigerant
Check on the outdoor unit
Check on the setting indoor unit
32
3. Check at main power on
a. Check ON the rotary switches of
outdoor unit
b. Check ON the setting indoor unit
• Incoming supply for outdoor phrase sequence for 3 phases,
Incoming Voltage (380~415V).
• Incoming voltage for Indoor 220~240V and ensure power supply all
Indoor unit is turn "ON".
• Once all the setting is set and check, then start addressing the system
by short-circuit pin CN-30
33
4. Testing and commissioning
34
 Start addressing the system by short-circuit pin CN-30
Laptop - Window 7 professional – 32
or 64 bits operation system
 Normal USB Printer
Wire
 Panasonic Flash Writer – 8F000900210 / Part Code – 6233214375
 To be purchase from Panasonic
(Oudom, 2017)
35
a. Indoor fan speed and temperature.
OUTDOOR Screen
INDOOR Screen
b. Outdoor Compressor temperature,
Gas temperature and etc.
 After the result have to be printed out by manufacture and to be attached in
Testing and Commissioning form for VRF recording.
(Oudom, 2017)
VIII. Conclusion
• The calculation cooling load by estimation and manual
seem a litter bit difference value. The selection of the
systems that suitable for reception area and conference
hall is outdoor unit model U-40ME2R8 which maximum
cooling capacity is 113 kW.
• To get the best result of VRF system, we have to
understand about plan and condition for installation of
indoor unit, outdoor unit, air duct, copper pipe, and
drainage water pipe.
• VRF testing and commissioning is a part which we use
the method statement to carry on indoor unit, outdoor unit
operation after installation.
36
Thank You For Your
Attention !
Q & A
37
Thank you for your
attention!!!
Question?

More Related Content

PPTX
VRF II VRV
PDF
VRF system presentation !
PDF
Dc inverter vrf installation instructions and Tips
PPT
Chiller-vs-vrf.ppt
PPTX
HVAC Systems- A Complete Guide
DOCX
Data Center Site survey document
DOC
Project Report On Data Center Management
VRF II VRV
VRF system presentation !
Dc inverter vrf installation instructions and Tips
Chiller-vs-vrf.ppt
HVAC Systems- A Complete Guide
Data Center Site survey document
Project Report On Data Center Management

What's hot (20)

PPTX
VARIABLE REFRIGERANT FLOW(VRF) ppt
PPTX
Water Chilled Airconditioning
PDF
Comparison between Systems
PPT
AIR CONDITIONING SYSTEM DESINGING
PPTX
Duct Design & Air distribution
PPTX
HVAC Sysems & AHU
PPTX
Air conditioning system
PDF
Blue star package units
PPTX
Cooling Systems - Chiller Technologies
PPTX
Smoke extraction in buildings
PDF
Introduction to VRF
PPTX
Hvac - presentation (Air conditioning presentation)
PPTX
HVAC PPT.pptx
PDF
Chiller ppt
PPTX
VARIABLE REFRIGERATE FLOW
PPTX
Hvac duct design
PPTX
Basic Component of HVAC(compressor)
PPTX
HVAC - by Anoushka Aggarwal
PPTX
Air distribution Product
VARIABLE REFRIGERANT FLOW(VRF) ppt
Water Chilled Airconditioning
Comparison between Systems
AIR CONDITIONING SYSTEM DESINGING
Duct Design & Air distribution
HVAC Sysems & AHU
Air conditioning system
Blue star package units
Cooling Systems - Chiller Technologies
Smoke extraction in buildings
Introduction to VRF
Hvac - presentation (Air conditioning presentation)
HVAC PPT.pptx
Chiller ppt
VARIABLE REFRIGERATE FLOW
Hvac duct design
Basic Component of HVAC(compressor)
HVAC - by Anoushka Aggarwal
Air distribution Product
Ad

Similar to Design, Installation and Testing of the VRF System (20)

PDF
PRESENTATION AIRWELL VRF 2014 GB
PDF
Compact Automotive Thermoelectric Generator with Embedded Heat Pipes for Ther...
PDF
Frenic hvac catalog
PDF
Design HVAC System for Hospital
PDF
Catalog Biến tần Frenic-HVAC (Fuji Electric)
PDF
Fuji tu dong hoa catalog frenic-hvac-dienhathe.org
PDF
[ME-20249]Complex Engineering RAC file.pdf
DOCX
Experimentation on heat pipe and cfd analysis for performance enhancement
DOCX
Experimentation on heat pipe and cfd analysis for performance enhancement
PDF
IRJET- Enhancement of COP of Vapor Compression Refrigeration Cycle using CFD
PPTX
Different types of HVAC systems in a Hospital.pptx
PDF
Crac precision climate_control_units_for_data_centres
PDF
IRJET- Air Conditioning Ceiling Fan by using Thermoelectric Module
PPTX
High Efficiency Solutions EEV & Monitoring Systems
PDF
Inlet Air Cooling system from Ikeuchi Improve gas Turbine efficiency
PPTX
AETEG Presentation.pptx
PDF
Technical specification EEE
PDF
Training Seminar - Standards, Heat Tracing Options & Application Optimization...
PDF
Rittal - Re-Cooling - Chiller Ürünleri
PDF
Eta a series reflow oven
PRESENTATION AIRWELL VRF 2014 GB
Compact Automotive Thermoelectric Generator with Embedded Heat Pipes for Ther...
Frenic hvac catalog
Design HVAC System for Hospital
Catalog Biến tần Frenic-HVAC (Fuji Electric)
Fuji tu dong hoa catalog frenic-hvac-dienhathe.org
[ME-20249]Complex Engineering RAC file.pdf
Experimentation on heat pipe and cfd analysis for performance enhancement
Experimentation on heat pipe and cfd analysis for performance enhancement
IRJET- Enhancement of COP of Vapor Compression Refrigeration Cycle using CFD
Different types of HVAC systems in a Hospital.pptx
Crac precision climate_control_units_for_data_centres
IRJET- Air Conditioning Ceiling Fan by using Thermoelectric Module
High Efficiency Solutions EEV & Monitoring Systems
Inlet Air Cooling system from Ikeuchi Improve gas Turbine efficiency
AETEG Presentation.pptx
Technical specification EEE
Training Seminar - Standards, Heat Tracing Options & Application Optimization...
Rittal - Re-Cooling - Chiller Ürünleri
Eta a series reflow oven
Ad

Recently uploaded (20)

PPTX
IOT PPTs Week 10 Lecture Material.pptx of NPTEL Smart Cities contd
PPTX
UNIT 4 Total Quality Management .pptx
PDF
Evaluating the Democratization of the Turkish Armed Forces from a Normative P...
PPTX
OOP with Java - Java Introduction (Basics)
PDF
Model Code of Practice - Construction Work - 21102022 .pdf
PPTX
M Tech Sem 1 Civil Engineering Environmental Sciences.pptx
PDF
SM_6th-Sem__Cse_Internet-of-Things.pdf IOT
PPTX
CARTOGRAPHY AND GEOINFORMATION VISUALIZATION chapter1 NPTE (2).pptx
PPTX
Construction Project Organization Group 2.pptx
PPT
CRASH COURSE IN ALTERNATIVE PLUMBING CLASS
PDF
BMEC211 - INTRODUCTION TO MECHATRONICS-1.pdf
PPTX
MET 305 2019 SCHEME MODULE 2 COMPLETE.pptx
PPTX
Lecture Notes Electrical Wiring System Components
PPTX
Infosys Presentation by1.Riyan Bagwan 2.Samadhan Naiknavare 3.Gaurav Shinde 4...
PDF
July 2025 - Top 10 Read Articles in International Journal of Software Enginee...
PPTX
UNIT-1 - COAL BASED THERMAL POWER PLANTS
PDF
Mitigating Risks through Effective Management for Enhancing Organizational Pe...
PPTX
web development for engineering and engineering
PPTX
KTU 2019 -S7-MCN 401 MODULE 2-VINAY.pptx
PDF
Embodied AI: Ushering in the Next Era of Intelligent Systems
IOT PPTs Week 10 Lecture Material.pptx of NPTEL Smart Cities contd
UNIT 4 Total Quality Management .pptx
Evaluating the Democratization of the Turkish Armed Forces from a Normative P...
OOP with Java - Java Introduction (Basics)
Model Code of Practice - Construction Work - 21102022 .pdf
M Tech Sem 1 Civil Engineering Environmental Sciences.pptx
SM_6th-Sem__Cse_Internet-of-Things.pdf IOT
CARTOGRAPHY AND GEOINFORMATION VISUALIZATION chapter1 NPTE (2).pptx
Construction Project Organization Group 2.pptx
CRASH COURSE IN ALTERNATIVE PLUMBING CLASS
BMEC211 - INTRODUCTION TO MECHATRONICS-1.pdf
MET 305 2019 SCHEME MODULE 2 COMPLETE.pptx
Lecture Notes Electrical Wiring System Components
Infosys Presentation by1.Riyan Bagwan 2.Samadhan Naiknavare 3.Gaurav Shinde 4...
July 2025 - Top 10 Read Articles in International Journal of Software Enginee...
UNIT-1 - COAL BASED THERMAL POWER PLANTS
Mitigating Risks through Effective Management for Enhancing Organizational Pe...
web development for engineering and engineering
KTU 2019 -S7-MCN 401 MODULE 2-VINAY.pptx
Embodied AI: Ushering in the Next Era of Intelligent Systems

Design, Installation and Testing of the VRF System

  • 1. MINISTRY OF EDUCATION OF YOUTHS AND SPORTS INSTITUTE OF TECHNOLOGY OF CAMBODIA DEPARTMENT OF INDUSTRIALAND MECHANICAL FINAL YEAR THESIS Tittle: Designing, Installation and Testing of VRF System Students : TITH Sopheara and VENG Socheat Specialty : Mechanical engineering Advisor : Mr. KHOUN Rithymean Academic Year : 2016- 2017 1
  • 2. Contents I. General Introduction II. Definition III. Panasonic VRF system IV. Load calculation V. Selection VI. VRF system installation VII. Testing and Commissioning VIII.Conclusion 2
  • 3. I. General Introduction  Presentation of Internship •From: 20 February to 20 May 2017 •Company: Comin Khmere •Position : MVAC trainee •Project: TK Royal One (Cambodia) 3
  • 4. II. Definition 4 What is VRF systems? • Variable refrigerant flow vary the flow of refrigerant to indoor units based on demand. There are 2 types of VRF system, heat pump and heat recovery system.
  • 5. What is VRF Heat pump ? • VRF heat pump provide heating or cooling but not simultaneous heating and cooling 5 II. Definition
  • 6. What is VRF heat recovery? • VRF heat recovery can operate simultaneous in heating or cooling mode. 6 II. Definition
  • 7. Variable refrigerant flow (VRF) is an air-conditioning system configuration where there is one outdoor unit and multiple indoor units. III. Panasonic VRF System 7
  • 8. III. Panasonic VRF System 1. Outdoor unit The outdoor unit of VRF system, sometimes called the outside unit or condenser. 8 (Carin, 2016)
  • 9. III. Panasonic VRF System DC twin rotary compressor: The component of compressor are: 1. Electric motor 2. Compression mechanism 3. Accumulator The compressor is the heart of the refrigeration cycle. 9 (Bhatia, 2014)
  • 10. III.Panasonic VRF System a. 2-WAY Mini-FSV LE1 Series  Use for cooling or heating mode only Capacity range from 4HP to 6HP COP: 4.21 in case of 4 HP  Cooling operation possible up to 46 °C And low as -20 °C for heating mode  Max connectable 9 units with length 150m 10 (Hiong, 2016-2017)
  • 11. III.Panasonic VRF System b. 2-WAY FSV-EX ME2 Series  Use for cooling or heating mode only  Capacity range from 8HP to 80HP  Operation temperature as high as 52°C for cooling and as low as -20 °C for heating mode  Max connectable 64 units with max length 1,000m 11 (Hiong, 2016-2017)
  • 12. III.Panasonic VRF System c. 3-WAY FSV MF2 Series  Using for simultaneous heating and cooling  Capacity range from 8HP to 42HP  Temperature operation as high as 46°C for cooling and as low as -20 for heating  Max connectable 52 units with pipe length up to 500m 12 (Hiong, 2016-2017)
  • 13. III.Panasonic VRF System 2. Indoor unit There are many types of indoor units such as: • F2 type : Cooling Capacity 2.2kW to 16kW • M1 type : Cooling Capacity 2.2kW up to 5.6kW • Z1 type : Cooling Capacity 2.2kW to 7.3kW • E2 type : Cooling Capacity 18kW to 28kW 13
  • 14. III.Panasonic VRF System 2. Indoor unit • E1 type : Cooling Capacity 7.3kW to 28kW • U1 type : 4-way cassette, Cooling Capacity 2.2kW to 16kW • Y2 type : 4-way mini cassette, Cooling Capacity 2.2kW to 5.6kW • L1 type : 2-way cassette, Cooling Capacity 2.2kW to 7.3kW • D1 type : 1-way cassette, Cooling Capacity 2.8kW to 7.3kW • P1 type : Floor standing, Cooling Capacity 2.2kW to 7.3kW 14
  • 15. IV.Load Calculation  Feature of the Building TK Royal One 15http://www.cambodiancondos.com/condo-developments/tk-royal-one/
  • 16. IV. Load Calculation 1. Estimate Method Q = S . R • Q: Total heat load [Btu.h-1]or [W] • S: room area [m2] • R: The rate of cooling [Btu.h-1.m-2] Calculation total heating load for TKR1 “ Reception room’’ which has S = 62.4 m2 • R = 900 Btu.h-1.m-2 Thus, Q = 56160 Btu.h−1 =16.45kW 16
  • 17. Another room calculate by Estimate method Items Type of Room AREA Ratio Cooling Capacity m² Btu/h.m2 kW Btu/h 1 Conference Hall 265.45 1200 93.36 318540 2 Break Room 49.07 750 10.78 36802 3 Coffee Shop 73.6 1300 28.04 95680 4 Financial Office 98.14 850 24.48 83419 5 Hall 35.5 700 7.28 24850 6 Office 56.5 850 14.07 48025 7 Meeting Room 31.95 900 8.40 28755 8 Service Counter 36.8 1300 14.02 47840 9 Shop 87.7 800 20.56 70160 10 Toilet 38 500 5.56 19000 17
  • 18. IV. Load Calculation 2. Manual Method The Manual Method is the method used to calculate the cooling load of the building space with minimum errors. Total heating load: QT = QS + QL [W] oTotal sensitive loads QS = QStr+ QSRm+QSRv+QSoc+QSecl+QSequip oTotal latent loads QL= QLr+ QLoc+QLequip 18
  • 19. IV.Load Calculation Calculation heating load for TKR1 “ Reception Area’’ oTotal sensitive loads QS = 14445.26 W oTotal latent loads QL = 1197.58W Total heating load: QT= 14445.26 W + 1197.58W = 15642.84 W = 15.64 kW 19
  • 20. IV.Load Calculation Verify the cooling capacity coefficient R [Btu/h.m2]: • Manul method: R= 53367Btu.h−1 / 62.4 m2 = 855 Btu.h−1 • Estimate method: R = 900 Btu.h−1 From the calculation above by manual method, we see that error of cooling rate approximate 5 % compared to estimation method 20
  • 21. V. Selection 1. Selection indoor unit The total cooling load required is 109.8 kW 21(Hiong, 2016-2017)
  • 22. V. Selection The characteristic of outdoor unit model U-40ME2R8 are: • Cooling capacity 113 kW • Using with power supply 400/415 V/3-phase/50 Hz • Electrical rating for cooling option: 57.3 A • Refrigerant amount at shipment: 22.0 kg • Air flowrate: 48600 m3 h-1 22
  • 23. V. Selection 2. Selection indoor unit  For Conference Hall of TKR1: The requirement of cooling load is 93.36 kW. Catalogue of model mid static duct E1 type chosen that Its cooling capacity from 7.3 kW to 28 kW. E1 type is a kind of saving energy, the power input 45% less (compared to H1 type) 4 of S-224ME1E5 were chosen: Cooling capacity 4 × 22.4kW = 89.6kW 23
  • 25. VI.VRF System Installation 1. Air duct installation 25 2. Indoor unit installation
  • 26. VI.VRF System Installation 3. Copper pipe installation 26
  • 27. VI.VRF System Installation 4. Drainage water pipe installation 27
  • 28. VI.VRF System Installation 5. Outdoor unit installation 28
  • 29. VII. Testing and Commissioning Before we start operation VRF, we have to: 1. Test refrigerant pipe 2. Adding refrigerant 3. Check at main power on 4. Testing and commissioning 29
  • 30. 30 1. Test refrigerant pipe a. Check for any leakage in the refrigerant piping b. Perform vacuum drying to remove all moisture
  • 31. • Keeping the valve of the outdoor unit closed • If the specified amount of refrigerant cannot be charged, fully open the valves of the outdoor unit at liquid and gas sides, operate the air conditioner in COOL mode 31 2. Adding refrigerant
  • 32. Check on the outdoor unit Check on the setting indoor unit 32 3. Check at main power on a. Check ON the rotary switches of outdoor unit b. Check ON the setting indoor unit
  • 33. • Incoming supply for outdoor phrase sequence for 3 phases, Incoming Voltage (380~415V). • Incoming voltage for Indoor 220~240V and ensure power supply all Indoor unit is turn "ON". • Once all the setting is set and check, then start addressing the system by short-circuit pin CN-30 33 4. Testing and commissioning
  • 34. 34  Start addressing the system by short-circuit pin CN-30 Laptop - Window 7 professional – 32 or 64 bits operation system  Normal USB Printer Wire  Panasonic Flash Writer – 8F000900210 / Part Code – 6233214375  To be purchase from Panasonic (Oudom, 2017)
  • 35. 35 a. Indoor fan speed and temperature. OUTDOOR Screen INDOOR Screen b. Outdoor Compressor temperature, Gas temperature and etc.  After the result have to be printed out by manufacture and to be attached in Testing and Commissioning form for VRF recording. (Oudom, 2017)
  • 36. VIII. Conclusion • The calculation cooling load by estimation and manual seem a litter bit difference value. The selection of the systems that suitable for reception area and conference hall is outdoor unit model U-40ME2R8 which maximum cooling capacity is 113 kW. • To get the best result of VRF system, we have to understand about plan and condition for installation of indoor unit, outdoor unit, air duct, copper pipe, and drainage water pipe. • VRF testing and commissioning is a part which we use the method statement to carry on indoor unit, outdoor unit operation after installation. 36
  • 37. Thank You For Your Attention ! Q & A 37 Thank you for your attention!!! Question?