Department of Mechanical Engineering
Faculty of Engineering & Technology, Jamia Millia Islamia
Design of A/C system for a Multiplex
Under Supervision of Prof. J. A. Usmani
Project – I
BTM – 791
Submitted by :
Mahfooz Alam
Musawwir Alam
Md. Iftikhar
Nasir Aziz
Md. Abdul Khaliq
Introduction
The average summer temperatures experienced by most countries are increasing every year
and consequently the energy needs to provide air-conditioning is also increasing annually. The
HVAC industry has a challenging task of providing energy efficient technologies to satisfy
this growing demand with a minimum impact on global warming and ozone depletion.
The control of properties of air to suit the physiological requirements of the human body or to
assist in improvement of the quality of industrial process is known as air conditioning. This
requires the simultaneous control of temperature humidity ,air circulation(ventilation),outdoor,
dust content, bacteria content, ionic content, light, pressure etc. the art of air conditioning
developed only gradually from the predecessors arts of cooling , cleaning, heating and
ventilation. The human body produces certain amount of heat due to metabolism. The heat
produced depends on the degree of activity and the average temperature of healthy human
being is 37C.when the air temperature is lesser than the body surface temperature; the body
loses heat by convection and evaporation. If the DBT of the air is greater than the body
surface temperature, the convection effects will heat rather than cool the body.[1]
Fig.1 - Humidity Vs. temperature chart
The comfort air-conditioning systems are divided into three groups:
1. Summer-Air Conditioning System: The problems encountered in summer A/C are:
 To reduce the sensible heat
 To reduce water vapor content of the air by cooling and dehumidifying. The removal of water
vapor from the air is termed as dehumidification of air. The dehumidification of air is only
possible if the air cooled below the dew point temperature of the air.
2. Winter Air Conditioning System: The problem encountered in winter A/C is to increase the
sensible heat and water vapor content of air by heating and humidification. The addition of
water vapor to the air is termed as a humidification of air.
Fig.2 - Relative humidity Vs. temperature chart
3. Year Round Air Conditioning System: This system assures the control of temperature and
humidity of air in an enclosed surface throughout of the year. When the atmospheric
conditions are changing as per season. In many countries, both summer and winter are very
discomfort able. Under six conditions year round A/C system must be capable of maintaining
a specified temperature and humidity with the A/C spaces regardless of outside weather
conditions. In most of the A/C applications for industry the common problem is to control the
temperatures, humidity and air motion for maintaining the quantity of the product to perform a
specific industrial process, successfully.[1]
Fig. 3 – Building Orientation
Cooling Load calculation
Heating and cooling loads are the measure of energy needed to be added or removed from a
space by the HVAC system to provide the desired level of comfort within a space. Right-
sizing the HVAC system begins with an accurate understanding of the heating and cooling
loads on a space. Right-sizing is selecting HVAC equipment and designing the air distribution
system to meet the accurate predicted heating and cooling loads of the house. The values
determined by the heating and cooling load calculation process will dictate the equipment
selection and duct design to deliver conditioned air to the rooms of the house, right-sizing the
HVAC system. The heating and cooling load calculation results will have a direct impact on
first construction costs along with the operating energy efficiency, occupant comfort, indoor
air quality, and building durability.[2]
Fig.4 - Required cooling capacities for various building types
Fig.5 - Various load components
Sample Problem :
A school classroom is 6 m long, 6 m wide and 3 m high. There is a 2.5 m x 4 m window in the
east wall. Only the east wall/window is exterior. Assume the thermal conditions in adjacent
spaces (west, south, north, above and below) are the same as those of the classroom.
Determine the cooling load at 9:00 am, 12:00 noon on July 21.[3]
Other known conditions include:
Latitude = 40o
N
Ground reflectance = 0.2
Clear sky with a clearness number = 1.0
Overall window heat transmission coefficient = 7.0 W/m2
K
Room dry-bulb temperature = 25.5°C
Permissible temperature exceeded = 2.5%
Schedule of occupancy: 20 people enter at 8:00 am and stay for 8 hours
Lighting schedule: 300 W on at 8:00 AM for 8 hours
Exterior wall structure:
• Outside surface, A0
• Face brick (100 mm), A2
• Insulation (50 mm), B3
• Concrete block (100 mm), C3
• Inside surface, E0
Exterior window:
• Single glazing, 3 mm
• No exterior shading, SC = 1.0
Solution :
Cooling Load due to Exterior wall:
U =1/R = 0.643 W/m2
K
From Table A28-33A, find wall type 13.
From Table A28-32, CLTD9:00 = 9 and CLTD12:00 = 14 for east wall.
CLTD Corrected = CLTD + (25.5 - Ti) + (Tm - 29.4)
Ti = inside temperature
Tm = mean outdoor temperature
Tm = (maximum outdoor temperature) - (daily range)/2
At 9:00 am CLTD Corrected = 9 + (25.5 - 25.5) + (31 -9/2 - 29.4) = 6.1 K
At 12:00 am CLTD Corrected = 14 + (25.5 - 25.5) + (31 -9/2 - 29.4) = 11.1 K
Q = U A (CLTD)
Q = 0.643 (W/m2
K) x (6 x 3 - 4 x 2.5) m2
x 6.1 = 34 W (at 9 am)
Q = 0.643 (W/m2
K) x (6 x 3 - 4 x 2.5) m2
x 11.1 = 62 W (at 12 noon)
Layer Unit Resistance (R value)
m
2
K/W
A0 0.059
A2 0.076
B3 1.173
C3 0.125
E0 0.121
Total 1.554
Window conduction:
From Table A28-34, CLTD9:00 = 1 and CLTD12:00 = 5
CLTD Corrected = CLTD + (25.5 - Ti) + (Tm - 29.4)
CLTD corrected = 1 + 0 + (31 - 9/2 - 29.4) = -1.9 K (at 9 am)
CLTD Corrected = 5 + 0 + (31 - 9/2 - 29.4) = 2.1 K (at 12 noon)
Q = U A (CLTD)
Q = 7.0 W/m2
K x 4 x 2.5 m2
x (-1.9 K) = -133 W (at 9 am)
Q = 7.0 W/m2
K x 4 x 2.5 m2
x 2.1 K = 147 W (at 12 noon)
Solar load through glass:
From Table A28-35B, find zone type is A
From Table A28-36, find CLF = 576 at 9 am and CLF = 211 at 12 noon
Q = A (SC) (SCL)
Q = (2.5 x 4 m2
) x 1.0 x 576 = 5760 W (at 9 am)
Q = (2.5 x 4 m2
) x 1.0 x 211 =2110 W (at 12 noon)
People:
From Table A28-35B, find zone type is B
From Table A28-3, find sensible/latent heat gain = 70 W
From Table A28-37, find CLF9:00 (1) = 0.65 and CLF12:00 (3) =0.85
Q Sensible = N (sensible heat gain) CLF
Q Sensible = 20 x 70 W x 0.65 = 910 W (at 9 am)
Q Sensible = 20 x 70 x 0.85 = 1190 W (at 12 noon)
Q Latent = N (latent heat gain)
Q Latent = 20 x 45 = 900 W (at 9 am and 12 noon)
Lighting:
From Table A28-35B, find zone type is B
From Table A28-38, find CLF9:00 (1) = 0.75 and CLF12:00 (3) = 0.93
Q Lighting = W Full Fsa (CLF)
Q Lighting = 300 W x 1 x 1 x 0.75 = 225 W (at 9 am)
Q Lighting = 300 x 1 x 1 x 0.93 = 279 W (at 12 noon)
TOTAL COOLING LOAD:
Component 9.00 AM 12.00 Noon
Wall 34 62
Window conduction -133 147
Window solar transmission 5760 2110
People 910 1190
Lights 225 279
Total 6796 W 3788 W
Design of duct system:
1. Air should be conveyed as directly as possible to save space, power and material
2. Sudden changes in directions should be avoided. When not possible to avoid sudden changes,
turning vanes should be used to reduce pressure loss
3. Diverging sections should be gradual. Angle of divergence ≤ 20.
4. Aspect ratio should be as close to 1.0 as possible. Normally, it should not exceed 4.
5. Air velocities should be within permissible limits to reduce noise and vibration.
6. Duct material should be as smooth as possible to reduce frictional losses.[4]
Fig.7 - General layout of HVAC system
Fig. 8 – Ductwork
Fig. 9 – Types of Duct
Importance of HVAC:
As the outside weather changes, the environment in which your equipment is housed will
change as well. It is important to protect the equipment from over-heating, freezing, moisture,
etc. In addition to telecom shelters, HVAC units are also commonly used in data centers and
server rooms. Saving money is one of the main reasons a person should maintain their HVAC
unit. An HVAC unit that is running efficiently, as well as a home that is properly insulated,
means less money spent on electricity, heating and cooling costs. HVAC maintenance is also
important to prevent the need for major repairs or replacements.[4]
1. Healthy Air
A properly maintained HVAC unit will not only keep a home warm or cool, but it will prevent
problems with air quality. Clean filters and coils mean better breathing for an entire family.
An unmaintained HVAC unit is a breeding ground for dirt, mold and bacteria, all of which can
cause or worsen respiratory problems for those living home.
2. System Life
The better a person maintains their HVAC unit, the longer that unit will be able to function
well and provide cooling and heating to a home or building. With proper HVAC maintenance,
a unit can last well over 10 years. Considering the amount of money a person spends to install
an HVAC unit, it makes sense they would want to keep that unit running well for as long as
possible.
3. Efficiency
As with the life of the system, a well-maintained HVAC unit will run more efficiently.
Research shows that dirty or unmaintained units need to work 20 percent harder to produce
the same amount of cooling or heating as a well-maintained machine. Less energy will be
expended when it is running, which means less stress on the components of the machine. The
less wear and tear on the machine means simple maintenance during the spring and fall
months. Maintenance will be much quicker and smoother if a person takes the preventive
steps to keep a system running in tip-top shape.
4. Less Emergency Repairs
Most HVAC units may need emergency repairs from time to time. Well-maintained units are
less likely to fail during the months of hard use (June through September and December
through March). Keeping a unit up-to-date on all inspections and maintenance checks means
less worry that the unit will break down when it is needed the most.
5.Parts Under Warranty
In the event of a problem, the part or component in question might still be under a warranty.
This is another important reason to maintain an HVAC unit on a regular basis. Keep a list of
all warranty expiration dates and check the parts prior to that date to ensure there are no
problems before it is too late. Parts under warranty can often be fixed at no cost, aside from
the labor charges that may arise if homeowners are unable to fix or replace parts alone.
For many obvious reasons, HVAC maintenance is important. Scheduling regular checks and
following through on fixing minor problems will help homeowners enjoy the comfort of a
system with the worry of it failing. A well-maintained unit is likely to have less serious
problems, meaning less hassle and unnecessary costs.
References:
[1] C.P. Arora, 2000, ‘Refrigeration and air conditioning’, Air Conditioning.
[2] http://nptel.ac.in/courses/112105129/pdf/R%26AC%2520Lecture%252035.pdf .
[3] A. Bhatia, ‘Cooling Load Calculations and Principles’, Continuing Education and
Development, Course No: M06-004.
[4] R.K Rajput, 2009, ‘A textbook of refrigeration and air conditioning’, Design of
Ducts, S. K. Kataria & Sons.

More Related Content

PPT
maths
PDF
Analysis of warehouse in staad pro.
PPTX
Doubly reinforced beam design
PPT
Structure Design-I (Bending moment & Shear force Part II)
PPT
44558176 chapter-2-stress-and-strain-axial-loading
PDF
Unit 1. force system, solved problems on force system.pdf
PDF
Optimized modeling and design of steel structures using etabs
PPTX
Analysis Of Thin Shell
maths
Analysis of warehouse in staad pro.
Doubly reinforced beam design
Structure Design-I (Bending moment & Shear force Part II)
44558176 chapter-2-stress-and-strain-axial-loading
Unit 1. force system, solved problems on force system.pdf
Optimized modeling and design of steel structures using etabs
Analysis Of Thin Shell

What's hot (20)

PDF
Northern peripheral road all info by regrob
PPTX
ANALYSIS AND DESIGN OF G+3 STOREY BUILDING USING STAAD PRO vi8 Software
PDF
Integral table for electomagnetic
DOCX
Structural anaysis and design of g + 5 storey building using bentley stadd pr...
PDF
Solution manual 17 19
DOCX
Som formulas pdf
PPTX
Great Civil Engineers
PPTX
Law Of Polygon | Mechanical Engineering
PDF
Unit 6- Plate Bending Theory.pdf
DOC
Gamma beta functions-1
PPTX
Moment of Inertia by Prof. Malay Badodariya
PDF
Roof truss design
PDF
Aplicaciones de espacios y subespacios vectoriales en la carrera de tecnologi...
PDF
Comparative Study on the Design of Square,Rectangular and Circular Concrete W...
DOCX
Project
PDF
Lecture 04 som 26.02.2021
PPTX
Session 5 design of rcc structural elements PROF YADUNANDAN
PDF
Fatigue usefull 1
PPTX
Principle of Superposition
PPT
Analysis and Design of Earthquake Resistant RC multi storied (G+3) Residentia...
Northern peripheral road all info by regrob
ANALYSIS AND DESIGN OF G+3 STOREY BUILDING USING STAAD PRO vi8 Software
Integral table for electomagnetic
Structural anaysis and design of g + 5 storey building using bentley stadd pr...
Solution manual 17 19
Som formulas pdf
Great Civil Engineers
Law Of Polygon | Mechanical Engineering
Unit 6- Plate Bending Theory.pdf
Gamma beta functions-1
Moment of Inertia by Prof. Malay Badodariya
Roof truss design
Aplicaciones de espacios y subespacios vectoriales en la carrera de tecnologi...
Comparative Study on the Design of Square,Rectangular and Circular Concrete W...
Project
Lecture 04 som 26.02.2021
Session 5 design of rcc structural elements PROF YADUNANDAN
Fatigue usefull 1
Principle of Superposition
Analysis and Design of Earthquake Resistant RC multi storied (G+3) Residentia...
Ad

Similar to Design of AC system for a Multiplex (20)

PDF
Design of air conditioning and ventilation system for a
PDF
Design of air conditioning and ventilation system for a multi storey office b...
PPTX
air conditioning mechanical process
DOCX
PDF
HVAC System Analysis of two-storey hospital building
PDF
Raters & HVAC
PPT
Load estimation1 for heating load and room
PDF
Cooling load estimation by CLTD method and HAP 4.5 for an evaporative cooling...
PDF
HVAC Project
PPTX
Estimating the effects of energy conservation construction code
PDF
Design of an Air Distribution System for a Multi Storey Office Building
PPTX
Design of HVAC system for Multiplex
PDF
Analysis of Air Conditioning Arrangement for Two Floor Shopping Complex by us...
PDF
Cooling load calculations and principles
PDF
[ME-20249]Complex Engineering RAC file.pdf
PPTX
Air Conditioning case study
PDF
12 Cooling Load Calculations
PDF
2015 x472 class 02 - generation systems
PPTX
Linked In Radiant Panel Presentation
PPTX
UNIT4-SUSTANABLE HVAC.pptx you know ypou
Design of air conditioning and ventilation system for a
Design of air conditioning and ventilation system for a multi storey office b...
air conditioning mechanical process
HVAC System Analysis of two-storey hospital building
Raters & HVAC
Load estimation1 for heating load and room
Cooling load estimation by CLTD method and HAP 4.5 for an evaporative cooling...
HVAC Project
Estimating the effects of energy conservation construction code
Design of an Air Distribution System for a Multi Storey Office Building
Design of HVAC system for Multiplex
Analysis of Air Conditioning Arrangement for Two Floor Shopping Complex by us...
Cooling load calculations and principles
[ME-20249]Complex Engineering RAC file.pdf
Air Conditioning case study
12 Cooling Load Calculations
2015 x472 class 02 - generation systems
Linked In Radiant Panel Presentation
UNIT4-SUSTANABLE HVAC.pptx you know ypou
Ad

More from Mahfooz Alam (20)

PDF
Design of AC system for Multiplex
PPT
Xrd mahfooz
PPTX
Super mahfooz
PPTX
Sem mahfooz
PPTX
Sem mahfooz
PPTX
Pvd final 17 etmm10 mahfooz
PPTX
Mahfooz eta
PPTX
mahfooz_toughness of finegrained copper
PPTX
mahfooz_ supercapacitor
PPTX
mahfooz_pulsed electrodeposition technology
PPT
mahfooz_piezoelectricity
PPTX
mahfooz_materials for h2 storage
PPTX
mahfooz_laser
PPTX
mahfooz_inhibition of stress corrosion cracking in stainless steels
PPTX
mahfooz_hall-petch-effect-in-bulk-nanostructured-material
PPTX
mahfooz _graphene
PPTX
mahfooz galvonic corossion
PPTX
mahfooz_deformation in cryst_al
PPTX
mahfooz_21st century materials
PPTX
mahfooz_yield criteria lab
Design of AC system for Multiplex
Xrd mahfooz
Super mahfooz
Sem mahfooz
Sem mahfooz
Pvd final 17 etmm10 mahfooz
Mahfooz eta
mahfooz_toughness of finegrained copper
mahfooz_ supercapacitor
mahfooz_pulsed electrodeposition technology
mahfooz_piezoelectricity
mahfooz_materials for h2 storage
mahfooz_laser
mahfooz_inhibition of stress corrosion cracking in stainless steels
mahfooz_hall-petch-effect-in-bulk-nanostructured-material
mahfooz _graphene
mahfooz galvonic corossion
mahfooz_deformation in cryst_al
mahfooz_21st century materials
mahfooz_yield criteria lab

Recently uploaded (20)

PPTX
Foundation to blockchain - A guide to Blockchain Tech
PPTX
MCN 401 KTU-2019-PPE KITS-MODULE 2.pptx
PDF
composite construction of structures.pdf
PDF
Automation-in-Manufacturing-Chapter-Introduction.pdf
PDF
SM_6th-Sem__Cse_Internet-of-Things.pdf IOT
PPTX
bas. eng. economics group 4 presentation 1.pptx
PDF
The CXO Playbook 2025 – Future-Ready Strategies for C-Suite Leaders Cerebrai...
PPT
Project quality management in manufacturing
PPTX
Recipes for Real Time Voice AI WebRTC, SLMs and Open Source Software.pptx
PDF
Operating System & Kernel Study Guide-1 - converted.pdf
PPTX
Construction Project Organization Group 2.pptx
DOCX
ASol_English-Language-Literature-Set-1-27-02-2023-converted.docx
PDF
Well-logging-methods_new................
PPTX
M Tech Sem 1 Civil Engineering Environmental Sciences.pptx
PDF
Digital Logic Computer Design lecture notes
PDF
Embodied AI: Ushering in the Next Era of Intelligent Systems
PPTX
additive manufacturing of ss316l using mig welding
PDF
TFEC-4-2020-Design-Guide-for-Timber-Roof-Trusses.pdf
PPTX
FINAL REVIEW FOR COPD DIANOSIS FOR PULMONARY DISEASE.pptx
PDF
Enhancing Cyber Defense Against Zero-Day Attacks using Ensemble Neural Networks
Foundation to blockchain - A guide to Blockchain Tech
MCN 401 KTU-2019-PPE KITS-MODULE 2.pptx
composite construction of structures.pdf
Automation-in-Manufacturing-Chapter-Introduction.pdf
SM_6th-Sem__Cse_Internet-of-Things.pdf IOT
bas. eng. economics group 4 presentation 1.pptx
The CXO Playbook 2025 – Future-Ready Strategies for C-Suite Leaders Cerebrai...
Project quality management in manufacturing
Recipes for Real Time Voice AI WebRTC, SLMs and Open Source Software.pptx
Operating System & Kernel Study Guide-1 - converted.pdf
Construction Project Organization Group 2.pptx
ASol_English-Language-Literature-Set-1-27-02-2023-converted.docx
Well-logging-methods_new................
M Tech Sem 1 Civil Engineering Environmental Sciences.pptx
Digital Logic Computer Design lecture notes
Embodied AI: Ushering in the Next Era of Intelligent Systems
additive manufacturing of ss316l using mig welding
TFEC-4-2020-Design-Guide-for-Timber-Roof-Trusses.pdf
FINAL REVIEW FOR COPD DIANOSIS FOR PULMONARY DISEASE.pptx
Enhancing Cyber Defense Against Zero-Day Attacks using Ensemble Neural Networks

Design of AC system for a Multiplex

  • 1. Department of Mechanical Engineering Faculty of Engineering & Technology, Jamia Millia Islamia Design of A/C system for a Multiplex Under Supervision of Prof. J. A. Usmani Project – I BTM – 791 Submitted by : Mahfooz Alam Musawwir Alam Md. Iftikhar Nasir Aziz Md. Abdul Khaliq
  • 2. Introduction The average summer temperatures experienced by most countries are increasing every year and consequently the energy needs to provide air-conditioning is also increasing annually. The HVAC industry has a challenging task of providing energy efficient technologies to satisfy this growing demand with a minimum impact on global warming and ozone depletion. The control of properties of air to suit the physiological requirements of the human body or to assist in improvement of the quality of industrial process is known as air conditioning. This requires the simultaneous control of temperature humidity ,air circulation(ventilation),outdoor, dust content, bacteria content, ionic content, light, pressure etc. the art of air conditioning developed only gradually from the predecessors arts of cooling , cleaning, heating and ventilation. The human body produces certain amount of heat due to metabolism. The heat produced depends on the degree of activity and the average temperature of healthy human being is 37C.when the air temperature is lesser than the body surface temperature; the body loses heat by convection and evaporation. If the DBT of the air is greater than the body surface temperature, the convection effects will heat rather than cool the body.[1] Fig.1 - Humidity Vs. temperature chart
  • 3. The comfort air-conditioning systems are divided into three groups: 1. Summer-Air Conditioning System: The problems encountered in summer A/C are:  To reduce the sensible heat  To reduce water vapor content of the air by cooling and dehumidifying. The removal of water vapor from the air is termed as dehumidification of air. The dehumidification of air is only possible if the air cooled below the dew point temperature of the air. 2. Winter Air Conditioning System: The problem encountered in winter A/C is to increase the sensible heat and water vapor content of air by heating and humidification. The addition of water vapor to the air is termed as a humidification of air. Fig.2 - Relative humidity Vs. temperature chart 3. Year Round Air Conditioning System: This system assures the control of temperature and humidity of air in an enclosed surface throughout of the year. When the atmospheric conditions are changing as per season. In many countries, both summer and winter are very discomfort able. Under six conditions year round A/C system must be capable of maintaining a specified temperature and humidity with the A/C spaces regardless of outside weather conditions. In most of the A/C applications for industry the common problem is to control the temperatures, humidity and air motion for maintaining the quantity of the product to perform a specific industrial process, successfully.[1]
  • 4. Fig. 3 – Building Orientation
  • 5. Cooling Load calculation Heating and cooling loads are the measure of energy needed to be added or removed from a space by the HVAC system to provide the desired level of comfort within a space. Right- sizing the HVAC system begins with an accurate understanding of the heating and cooling loads on a space. Right-sizing is selecting HVAC equipment and designing the air distribution system to meet the accurate predicted heating and cooling loads of the house. The values determined by the heating and cooling load calculation process will dictate the equipment selection and duct design to deliver conditioned air to the rooms of the house, right-sizing the HVAC system. The heating and cooling load calculation results will have a direct impact on first construction costs along with the operating energy efficiency, occupant comfort, indoor air quality, and building durability.[2] Fig.4 - Required cooling capacities for various building types
  • 6. Fig.5 - Various load components
  • 7. Sample Problem : A school classroom is 6 m long, 6 m wide and 3 m high. There is a 2.5 m x 4 m window in the east wall. Only the east wall/window is exterior. Assume the thermal conditions in adjacent spaces (west, south, north, above and below) are the same as those of the classroom. Determine the cooling load at 9:00 am, 12:00 noon on July 21.[3] Other known conditions include: Latitude = 40o N Ground reflectance = 0.2 Clear sky with a clearness number = 1.0 Overall window heat transmission coefficient = 7.0 W/m2 K Room dry-bulb temperature = 25.5°C Permissible temperature exceeded = 2.5% Schedule of occupancy: 20 people enter at 8:00 am and stay for 8 hours Lighting schedule: 300 W on at 8:00 AM for 8 hours Exterior wall structure: • Outside surface, A0 • Face brick (100 mm), A2 • Insulation (50 mm), B3 • Concrete block (100 mm), C3 • Inside surface, E0 Exterior window: • Single glazing, 3 mm • No exterior shading, SC = 1.0 Solution : Cooling Load due to Exterior wall: U =1/R = 0.643 W/m2 K From Table A28-33A, find wall type 13. From Table A28-32, CLTD9:00 = 9 and CLTD12:00 = 14 for east wall. CLTD Corrected = CLTD + (25.5 - Ti) + (Tm - 29.4) Ti = inside temperature Tm = mean outdoor temperature Tm = (maximum outdoor temperature) - (daily range)/2
  • 8. At 9:00 am CLTD Corrected = 9 + (25.5 - 25.5) + (31 -9/2 - 29.4) = 6.1 K At 12:00 am CLTD Corrected = 14 + (25.5 - 25.5) + (31 -9/2 - 29.4) = 11.1 K Q = U A (CLTD) Q = 0.643 (W/m2 K) x (6 x 3 - 4 x 2.5) m2 x 6.1 = 34 W (at 9 am) Q = 0.643 (W/m2 K) x (6 x 3 - 4 x 2.5) m2 x 11.1 = 62 W (at 12 noon) Layer Unit Resistance (R value) m 2 K/W A0 0.059 A2 0.076 B3 1.173 C3 0.125 E0 0.121 Total 1.554 Window conduction: From Table A28-34, CLTD9:00 = 1 and CLTD12:00 = 5 CLTD Corrected = CLTD + (25.5 - Ti) + (Tm - 29.4) CLTD corrected = 1 + 0 + (31 - 9/2 - 29.4) = -1.9 K (at 9 am) CLTD Corrected = 5 + 0 + (31 - 9/2 - 29.4) = 2.1 K (at 12 noon) Q = U A (CLTD) Q = 7.0 W/m2 K x 4 x 2.5 m2 x (-1.9 K) = -133 W (at 9 am) Q = 7.0 W/m2 K x 4 x 2.5 m2 x 2.1 K = 147 W (at 12 noon) Solar load through glass: From Table A28-35B, find zone type is A From Table A28-36, find CLF = 576 at 9 am and CLF = 211 at 12 noon Q = A (SC) (SCL) Q = (2.5 x 4 m2 ) x 1.0 x 576 = 5760 W (at 9 am) Q = (2.5 x 4 m2 ) x 1.0 x 211 =2110 W (at 12 noon)
  • 9. People: From Table A28-35B, find zone type is B From Table A28-3, find sensible/latent heat gain = 70 W From Table A28-37, find CLF9:00 (1) = 0.65 and CLF12:00 (3) =0.85 Q Sensible = N (sensible heat gain) CLF Q Sensible = 20 x 70 W x 0.65 = 910 W (at 9 am) Q Sensible = 20 x 70 x 0.85 = 1190 W (at 12 noon) Q Latent = N (latent heat gain) Q Latent = 20 x 45 = 900 W (at 9 am and 12 noon) Lighting: From Table A28-35B, find zone type is B From Table A28-38, find CLF9:00 (1) = 0.75 and CLF12:00 (3) = 0.93 Q Lighting = W Full Fsa (CLF) Q Lighting = 300 W x 1 x 1 x 0.75 = 225 W (at 9 am) Q Lighting = 300 x 1 x 1 x 0.93 = 279 W (at 12 noon) TOTAL COOLING LOAD: Component 9.00 AM 12.00 Noon Wall 34 62 Window conduction -133 147 Window solar transmission 5760 2110 People 910 1190 Lights 225 279 Total 6796 W 3788 W
  • 10. Design of duct system: 1. Air should be conveyed as directly as possible to save space, power and material 2. Sudden changes in directions should be avoided. When not possible to avoid sudden changes, turning vanes should be used to reduce pressure loss 3. Diverging sections should be gradual. Angle of divergence ≤ 20. 4. Aspect ratio should be as close to 1.0 as possible. Normally, it should not exceed 4. 5. Air velocities should be within permissible limits to reduce noise and vibration. 6. Duct material should be as smooth as possible to reduce frictional losses.[4] Fig.7 - General layout of HVAC system
  • 11. Fig. 8 – Ductwork
  • 12. Fig. 9 – Types of Duct Importance of HVAC: As the outside weather changes, the environment in which your equipment is housed will change as well. It is important to protect the equipment from over-heating, freezing, moisture, etc. In addition to telecom shelters, HVAC units are also commonly used in data centers and server rooms. Saving money is one of the main reasons a person should maintain their HVAC unit. An HVAC unit that is running efficiently, as well as a home that is properly insulated, means less money spent on electricity, heating and cooling costs. HVAC maintenance is also important to prevent the need for major repairs or replacements.[4] 1. Healthy Air A properly maintained HVAC unit will not only keep a home warm or cool, but it will prevent problems with air quality. Clean filters and coils mean better breathing for an entire family. An unmaintained HVAC unit is a breeding ground for dirt, mold and bacteria, all of which can cause or worsen respiratory problems for those living home.
  • 13. 2. System Life The better a person maintains their HVAC unit, the longer that unit will be able to function well and provide cooling and heating to a home or building. With proper HVAC maintenance, a unit can last well over 10 years. Considering the amount of money a person spends to install an HVAC unit, it makes sense they would want to keep that unit running well for as long as possible. 3. Efficiency As with the life of the system, a well-maintained HVAC unit will run more efficiently. Research shows that dirty or unmaintained units need to work 20 percent harder to produce the same amount of cooling or heating as a well-maintained machine. Less energy will be expended when it is running, which means less stress on the components of the machine. The less wear and tear on the machine means simple maintenance during the spring and fall months. Maintenance will be much quicker and smoother if a person takes the preventive steps to keep a system running in tip-top shape. 4. Less Emergency Repairs Most HVAC units may need emergency repairs from time to time. Well-maintained units are less likely to fail during the months of hard use (June through September and December through March). Keeping a unit up-to-date on all inspections and maintenance checks means less worry that the unit will break down when it is needed the most. 5.Parts Under Warranty In the event of a problem, the part or component in question might still be under a warranty. This is another important reason to maintain an HVAC unit on a regular basis. Keep a list of all warranty expiration dates and check the parts prior to that date to ensure there are no problems before it is too late. Parts under warranty can often be fixed at no cost, aside from the labor charges that may arise if homeowners are unable to fix or replace parts alone.
  • 14. For many obvious reasons, HVAC maintenance is important. Scheduling regular checks and following through on fixing minor problems will help homeowners enjoy the comfort of a system with the worry of it failing. A well-maintained unit is likely to have less serious problems, meaning less hassle and unnecessary costs.
  • 15. References: [1] C.P. Arora, 2000, ‘Refrigeration and air conditioning’, Air Conditioning. [2] http://nptel.ac.in/courses/112105129/pdf/R%26AC%2520Lecture%252035.pdf . [3] A. Bhatia, ‘Cooling Load Calculations and Principles’, Continuing Education and Development, Course No: M06-004. [4] R.K Rajput, 2009, ‘A textbook of refrigeration and air conditioning’, Design of Ducts, S. K. Kataria & Sons.