DESIGN OF CONTROL STRATEGIES FOR THE LOAD
FREQUENCY CONTROL (LFC) IN MULTI AREA
POWER SYSTEM FOR PARALLEL OPERATION OF
POWER PLANTS
Chitta Padmaja Priyanka
M. Tech, Department of Electrical Engineering,
PVKKIT, Anantapur, India
S.N.Lavanya
Lecturer in Electrical Engineering,
Government Polytechnic College, Tadipatri, India
G.N.S.Vaibhav
HOD, Assistant Professor, Department of Electrical Engineering,
PVKKIT, Anantapur, India
J. Ramesh
Assistant Professor, Department of Electrical Engineering,
PVKKIT, Anantapur, India
ABSTRACT
This paper features the Differential Evolution (DE) by controller parameters tuning algorithm
and also an application of a multi source power system to a Load Frequency Control (LFC) by
having several sources of power generation techniques. At first, a single area multi-source power
system using integral controllers for every unit is taken and DE procedure is implemented to attain
the controller parameters. Several mutation procedures of DE are estimated and the control
parameters of DE for best obtained procedure are tuned by implementing numerous runs of
algorithm for every change in parameter. Multi-area multi-source power system is also discussed
and a HDVC link is also taken in accordance with the current AC tie line for the internal
connection between the areas. The two variables of Integrals which are to be enhanced using tuned
DE algorithm are proportional integral and proportional integral derivative.
The advantage of the proposed strategy has been exposed by estimating the results with the
freshly published enhanced output feedback controller for the similar power systems. Further, the
assessment is conducted by performing several procedures like overshoot, tie line power derivation
followed by a step load perturbation (SLP), settling time and standard error criteria of frequency.
It is also observed that, the maximum output of the feedback controller is less than the dynamic
Design of Control Strategies for the Load Frequency Control (LFC) in Multi Area Power System for Parallel
Operation of Power Plants
http://www.iaeme.com/IJEET/index.asp 9 editor@iaeme.com
performance of the proposed controller. Additionally, the proposed power system is not affected by
altering the loading conditions, size of SLP and system parameters.
Key words: Differential Evolution (DE), step load perturbation (SLP), HDVC link, Multi-area
multi-source power system, Load Frequency Control (LFC).
Cite this Article: Chitta Padmaja Priyanka, S.N. Lavanya, G.N.S. Vaibhav and J. Ramesh, Design
of Control Strategies for the Load Frequency Control (LFC) in Multi Area Power System for
Parallel Operation of Power Plants. International Journal of Electrical Engineering & Technology,
7(5), 2016, pp. 08–19.
http://www.iaeme.com/IJEET/issues.asp?JType=IJEET&VType=7&IType=5
1. INTRODUCTION
Load Frequency Control (LFC) is the problem of controlling the real power output of generating units in
response to changes in tie-line power interchange and system frequency within specified limits. LFC is
also a part of Automatic Generation Control (AGC) and plays a very important in the operation and control
of power systems. . Large Scale Power Systems are generally composed of control areas representing
coherent groups of generators, which have combination of hydro, thermal, nuclear, gas, and renewable
energy sources. Researchers across the world are trying to propose several new strategies for LFC of
power systems to maintain the system frequency and tie line flow at their scheduled i.e. pre-defined values
during normal operation and also during small perturbations. It can be seen through literature survey that,
most of the LFC power system works have been carried out on two area thermal–thermal or hydro-thermal
systems. It is noticed that, large amount of research work indicates to propose better AGC systems based
on Neural Network, Modern Control Theory, Reinforcement Learning [8], Fuzzy Systems and ANFIS
approach. But, with these advanced approaches there are complications and also need experienced users
which in turn reduces their applicability. Due to its structural simplicity and reliability the classical
Proportional Integral Derivative (PID) controller remains an engineer’s preferred choice, which even has
an advantage of favorable ratio between performances and cost. This model requires lower user-skills,
minimal development effort and simplified dynamic modeling. In current technology, modern artificial
intelligence-based approaches have been projected to optimize the PI/PID controller parameters for AGC
system. The increase in complexity and size of electric power systems along with raise in power demand
has made it compelling to use the intelligent systems that combine methodologies, techniques and
knowledge from varied sources for the real-time control of power systems. The design problem for the
proposed controller is developed as an optimization problem. A frequency controller is needed to maintain
the system frequency, as burden of a power system is constant and never given to ensure the quality of
supply of energy, at the desired nominal value. In the deregulated energy system, control area contains
various disturbances and varied types of uncertainties because of more complex modeling errors of the
system and the changes in the structure of power system. Therefore, we need a control strategy which not
only maintains the desired tie-line power and flow rate constancy but can also achieve zero steady-state
error and inadvertent exchange.
The most popular feedback controller used by the process industries is the proportional integral
derivative (PID) controller is the. It is a robust controller, easy to understand that it can provide excellent
control performance despite the various dynamic characteristics of the process plant. As the name
proposes, the PID algorithm has basically three modes, proportional mode, integral mode and derivative
mode. A proportional controller effects in reducing the rise time but can never eliminate the steady state
error. Where as an integral control can eliminate the steady-state error, but it will make the transient
response still worse. The derivative control improves the system stability by decreasing surplus, and
improved transient response. Proportional integral controllers (PI) are nowadays most often used in the
industry. We can use a controller without the derivative mode (D) when a fast system response is not
required; there is high delay in the transport system and during high noise and disturbance present during
Chitta Padmaja Priyanka, S.N.Lavanya, G.N.S.Vaibhav and J. Ramesh
http://www.iaeme.com/IJEET/index.asp 10 editor@iaeme.com
the process of operation. Derivative mode helps in improving the system stability and allows increase gain
and decrease in integral gain, which in turn boosts the speed of response proportional controller. PID
controller is mostly used when quick response and stability are main concern. In view of above, I, PI and
PID controllers are considered analytical herein. In the design of a modern technique based on the
optimization controller, we first define the objective function based on the specifications and limitations.
So the design of the objective function is for tuning the controller and generally based on a performance
index that considers the entire closed-loop system response. Time domain conventional output
specifications are rise time, steady-state error, overshooting peak, settling time.
2. DESIGN OF CONTROL SYSTEM
For the design of controller in the system the prominent specimen to be considered is the two area system
covering the warming of gas turbines, hydraulic and thermal units. Figure 1 shows the LFC power system
under study. This system is used for simulation by linearising the governors, hydraulic turbines, reheat
turbines, gas turbines. The participation and contribution of each unit to the rated load is decided by its
parameter adjustment factor. In each Control unit the sum of the participation factor need to be equal to
1.In Figure.1R1, UT and KT are parameter of regulation, output of control and participation factor
respectively for thermal unit; R2,UH and KH are parameter of regulation, output of control and
participation factor respectively for hydraulic unit; R3,HG and KG are parameter of regulation, output of
control and participation factor respectively for gas unit, is the constant speed governor thermal unit
(seconds), is steam turbine time constant (seconds), Kr is the constant reheat steam turbinate is the
reheat time constant of the steam turbine (seconds), is time nominal starting penstock water
(seconds), is the regulator of the hydraulic turbine speed reset the time (seconds), is Hydro turbine
speed governor transient droop time constant(seconds), is hydro turbine main regulator time constant
servo speed (seconds), is the time constant standby gas turbine;where c is the time constant delay of the
gas turbine and speed regulator in seconds, is the valve positioned of the gas turbine, is the constant of
the gas turbine valve positioner, is the gas turbine fuel time constant (seconds), is the gas turbine time
delay combustion reaction (seconds), is the gas turbine compressor discharge at constant volume time
in (seconds), is gain of power system (Hz/puMW) , is the system time constant power in (seconds),
∆F is the incremental change in the exchange rate and incremental load ∆PD.The nominal system
parameters are displayed in reference.
For our current study integral of time-weighted absolute error (ITAE) is preferred objective function as
the deviation of power in the control areas will be diminished quickly and also used in study of ACG.
Hence objective function is expressed as:
J=ITAE= |∆ |. .
Where the simulation is time interval and ∆ is the frequency deviation system. As the constraints
of the problem are the limits of the driver parameters. Therefore, our design problem can be forged as the
below optimization problem. Subject to diminish J:
! "
≤ ! ≤ ! %&
Where our objective functions is J and !'()
and !'*+
theminimum control parameters and maximum
control parameters. As proclaimed in the literature, the minimum and maximum values of the controller
parameters are chosen as -1 and 1 respectively.
Design of Control Strategies for the Load Frequency Control (LFC) in Multi Area Power System for Parallel
Operation of Power Plants
http://www.iaeme.com/IJEET/index.asp 11 editor@iaeme.com
Figure 1 Transfer function model of multiple sources-multiple areas with HVDC link
3. CONVENTIONAL CONTROLLER TUNING METHODS
As of now the PID (proportional integral derivative) controller is the most common control algorithm.
Most of the feedback loops are being controlled by this algorithm or with minor variations in it. This can
be implemented in different forms like a stand-alone controller or as a part of a Direct Digital Control
package or a hierarchical distributed process control system. PID algorithm consists of three basic modes:
• Proportional mode
• Integral mode
• Derivative mode
A proportional controller regulates the reaction to the current error and rise time, but can never
eliminate the steady-state error. Integral control regulates the reaction based on the sum of recent errors
and eliminates steady-state error, but it makes the transient response worse. Derivative control regulates
the reaction to the rate at which the error has been changing i.e. increases the stability of the system, which
in turn reduces the overshoot, and improves the transient response.
Proportional Integral controllers are the most regularly used controllers in industry now. We can use a
controller without D mode when: a fast response of the system is not mandatory, large noise and
disturbances are present during operation of the process and there is significant delay in the transport
system. Derivative mode increases the stability of the system and enables improvement in gain K and
decreases integral time constant Ti, which in turn increases the speed of the controller response.PID
Chitta Padmaja Priyanka, S.N.Lavanya, G.N.S.Vaibhav and J. Ramesh
http://www.iaeme.com/IJEET/index.asp 12 editor@iaeme.com
control is generally used when the stability and quick response is mandatory. In this paper for Load
Frequency Control we have considered I, PI, PID controllers. By setting the control parameters to their
optimum values for obtaining desired control response we tune these controllers. Foremost requirement is
stability of the multi-area system. Anyways as different systems will have different behavior and different
applications will have different requirements and these requirements may conflict with each another. Even
though the principle of PID is simple and has only three parameters, tuning of ID is challenging as it needs
to be answered in complex criteria. Manual setting method, PID tuning methods software and Ziegler-
Nichols tuning method are some of the prominent control loop tuning methods.
4. PSO CONTROLLER
James Kennedy and Russell Eberhart recommended Particle swarm optimization in 1995, which is
population movement and swarm intelligence, based speculative optimization technique. PSO is a
computational technique, developed and inspired by social behavior of bird flocking or fish schooling. A
group of random particles (solutions) are generated in this technique. Each particle is now treated as a
point in an n-dimensional space, which will adjust its "fly" according to the flight experience of other
particles and its own experience of flight. According to the value of fitness, the best solution is determined
for the current iteration and the best fitness value is also stored. The best possible solution is known as
pbest. Another finest fitness value is also tracked in the iterations so far obtained. This finest fitness value
is the global best and the corresponding particle solution is called gbest. In each of the iteration all of the
particles have been restored by following the pbest (best previous position) and gbest (best particle among
all the particles) in the swarm. There is no crossover operation involved PSO. In Evolutionary
Programming (EP) balance between global and local search we can set the strategy parameter, while
equilibrium in PSO is reached by the inertial weight factor (w).
PID controller with PSO optimization is designed for LFC and tie-power control. Main objectives are
to control the frequency and tie-between area with good power oscillation damping, also get good
performance in this study, the optimal values of the PK parameters Ki and Kd for PID controller easily and
accurately calculated using a PSO.In a typical run of the PSO, an initial population is generated randomly.
This is known as initial population generation 0th. Each individual of the initial population has an index
value associated performance. The use of performance index information, the PSO then produces a new
population. So as to obtain the performance index value for each one of the individual in the current
population, the system needs to be simulated. The PSO will now produce the next generation of people
who can use crossover operators and mutation breeding. These processes are kept repeating till the
population is converged and the optimal value of parameters found. The document aims to use the PSO
algorithm in order to obtain optimal values of the PID controller to a system of two frequency load area.
Each adjustment controller may represent a particle in the search space that changes its parameters
proportionality constant Kp, an integral constant Ki, and Kd derivative constant to minimize the error
function. The error function used here is the integral time absolute error (ITAE).
4.1. PSO Steps: Steps PSO as Implemented for the Optimization
• Step 1: Initialize an array of particles with random positions and velocities associated to satisfy the
inequality constraints.
• Step 2: Check satisfying the equality constraints and modify the solution if necessary.
• Step 3: Assess the fitness function of each particle.
• Step 4: Compare the current value of the fitness function better with particles above value (pbest). If the
current fitness value is lower, then assign the current value of fitness for pbest and assigned the coordinates
(positions) to pbest x.
• Step 5: Determine the current global minimum value of fitness between the current positions.
Design of Control Strategies for the Load Frequency Control (LFC) in Multi Area Power System for Parallel
Operation of Power Plants
http://www.iaeme.com/IJEET/index.asp 13 editor@iaeme.com
• Step 6: Compare the current global minimum above the minimum overall (gbest). If the current global
minimum is better than gbest, then assign the global minimum current for gbest and assigned the coordinates
(positions) to gbestx.
• Step 7: Change speeds.
• Step 8: Each particle moves to the new position and return to step 2.
• Step 9: Repeat from step 2-8 until the stopping criterion is satisfied or we have reached the maximum
number of iterations.
Figure 2 Flowchart For PSO
5. DIFFERENTIAL EVOLUTION
Differential Evolution (DE) is a population based indefinite optimization algorithm which is capable of
handling non-linear, non-differentiable and also multi-modal objective functions, which has some readily
selected control parameters. The design problem of the proposed controller is then formulated as an
optimization problem and here DE is used in searching optimal control parameters. DE works with two
different people; the old generation and the new generation of the very same population. The population
size can be adjusted by the parameter NP. This population is composed of actual dimension values D
Chitta Padmaja Priyanka, S.N.Lavanya, G.N.S.Vaibhav and J. Ramesh
http://www.iaeme.com/IJEET/index.asp 14 editor@iaeme.com
vectors which equals to the number of design parameters divided by variables control. This population is
run randomly within the initial parameter. The optimization process is mainly affected by these three main
operations: mutation, crossover and selection. In each of the generation, the individuals in the current
population become the targets vectors. In vector for each target, the mutation operation produces a mutant
vector, then by addition of the weighted difference between any two vectors selected randomly, a third
vector is made target. The cut operation now generates a new vector, which is called as test vector by
mixing the entries of the vector mutant with that of the target vector. If this test vector gets a better fitness
value than that of the target vector, then this test vector replaces the target vector in the preceding
generation. Evolutionary operators are as described below:
5.1. Initialization
For each parameter j with the lower and upper bound the values of the initial parameters are usually
uniformly at random in the interval [ ,
-
; ,
.
].
5.2. Mutation
For any given parameter vector X0,2, we take the three vectors (X34,2X35,2 ,X36,2) are randomly selected in
such a way that the indices i, r1, r2 and r3 are distinct. The donor vector V0,284 can be created by adding
the weighted difference between the two vectors to a third vector as:
V0,284=X34,2+ F. (X35,2- X36,2),
Where F is a constant from (0, 2)
5.3. Crossover
These three parents are now selected for the crossover and the child is a perturbation of any one of them.
Our trial vector Ui,G+1 is developed from the elements of this target vector (Xi, G) and the elements of the
donor vector (Xi, G). Elements of the donor vector then enter the trial vector with probability CR as:
Uj,i,G+1=9
V:,0,284 if rand:,0 ≤ CR CDE = GHIJK
X:,0,284 if rand:,0 > MN CDE = GHIJK
O
Withrand:,0~ U (0, 1), I3RSTis a random integer from (1, 2, . . ., D) where D is the solution’s dimension
i.e. number of control variables. I3RST ensures that V0,284 ≠ X0,284
5.4. Selection
The target vector X0,2is now compared with the trial vector V0,284and the one with the better fitness value is
admitted to the further generations. The selection operation in DE can be represented by the below
equation:
, 84=V
U0,284 if f( U0,284) < [(X0,2)
X0,2C ℎ]D^(_]
O
Where I∈ [ 1,a ]
Design of Control Strategies for the Load Frequency Control (LFC) in Multi Area Power System for Parallel
Operation of Power Plants
http://www.iaeme.com/IJEET/index.asp 15 editor@iaeme.com
Figure 3 Flow Diagram of DE Flow
6. RESULTS AND COMPARISION
During the simulation study, Error signals f1, f2 and tie line power required for the controller software is
transferred to the PSO. All positions of the particles in each dimension are held within the limits specified
by the user, and Velocities subject to the [Vmin, Vmax] range. A gradual increase in demand of 0.01 pu is
applied to zone 1 The frequency deviation of the first area frequency and f1 and second f2 deviation of the
area and the area between clamping signal power closed loop system shown in Figure. 4, 5, 6. Similarly a
step increase in demand of 0.01 applies to Area2. Frequency deviation of the first area and the f1 and f2
frequency of the second area and the area between clamping signal power circuitry of the closed loop
system are shown in Figure 7,8,9.
Chitta Padmaja Priyanka, S.N.Lavanya, G.N.S.Vaibhav and J. Ramesh
http://www.iaeme.com/IJEET/index.asp 16 editor@iaeme.com
Figure 4 Change in Frequency of Area-1 for 1% change in Area-1
Figure 5 Change in Frequency of Area-2 for 1% change in Area-1
Figure 6 Change in Tie Line Power for 1% change in Area-1
Design of Control Strategies for the Load Frequency Control (LFC) in Multi Area Power System for Parallel
Operation of Power Plants
http://www.iaeme.com/IJEET/index.asp 17 editor@iaeme.com
Figure 7 Change in Frequency of Area-1 for 1% change in Area-2
Figure 8 Change in Frequency of Area-2 for 1% change in Area-2
Figure 9 Change in Tie Line Power for 1% change in Area-2
Chitta Padmaja Priyanka, S.N.Lavanya, G.N.S.Vaibhav and J. Ramesh
http://www.iaeme.com/IJEET/index.asp 18 editor@iaeme.com
Simulation results show improved performance in the time domain specifications for a load of 0.01 pu
step Using the PSO approach, global and local solutions could be found simultaneously for a better
adjustment of the controller parameters . The PID value that was obtained by the PSO algorithm is
compared with the PID controller derived from differential evolution algorithm, PID controller, PI
controller and the I in different perspectives namely, robustness and stability. All simulations were carried
out using MATLAB A comparison of time domain specifications overshoot and settling time for a load of
0.01 pu step in area 1 are tabulated as given in the table (2) and it is very clearly that the PSO based
controller dramatically reduces overshoot by a large value. Settling time improved.
7. CONCLUSION
In this thesis, Load Frequency Control (LFC) of multi-unit source power system having different sources
of power generation like thermal, hydro and gas power plants is presented. The controller parameters are
tuned using particle swarm optimization (PSO) technique, Differential Evolution algorithm technique, PID
controller, PI controller and I controller. The superiority of our proposed approach has been interpreted
clearly by analysing the results with Integral (I) controller, proportional integral (PI) controller,
Proportional Integral Derivative (PID) Controller and DE employed PID controller for the same power
systems by using different performance measures like overshoot, settling time and standard error criteria of
frequency and tie-line power deviation using a step load perturbation (SLP). It is observed that, the
dynamic performance of proposed controller PSO is revised. Additionally, it is also seen that the proposed
system is flexible and is not affected by any change in its loading condition, system parameters and size of
SLP.
APPENDIX B: SYSTEM SETTINGS
b4= b5= 0.4312 p.u. MW/Hz; cH = 2000 MW; c-= 1840 MW; N4= N5= N6= 2.4 Hz/p.u.; = 0.08 s; =
0.3 s; = 0.3; = 10 s; 4= 5= 68.9566 Hz/p.u. MW; 4= 5= 11.49 s; 45= 0.0433; *45= -1;
= 1 s; = 5 s; = 28.75 s; = 0.2 s; = 0.6 s; d = 1 s; = 1; = 0.05 s; = 0.23 s; = 0.01
s; = 0.2 s; = 0.543478; = 0.326084; = 0.130438; = 1; = 0.2 s.
REFERENCES
[1] BanajaMohanty, Sidhartha panda, P.K Hota., controller parameters tuning of differential evolution
algorithm and its application to load frequency control of multi source power system, Electrical power
and energy systems 54(2014)77-85
[2] Ibraheem, Kumar P, Kothari DP. Recent philosophies of automatic generation control strategies in
power systems. IEEE Trans Power Syst 2005; 20:34657.
[3] Parmar KPS, Majhi S, Kothari DP. Load frequency control of a realistic power system with multi-source
power generation. Int J Elect Power Energy Syst2012; 42:426–33.
[4] Ghosal SP. Optimization of PID gains by particle swarm optimization in fuzzy based automatic
generation control. Electr Power Syst Res 2004; 72:203–12.
[5] Rout UK, Sahu RK, Panda S. Design and analysis of differential evolution algorithm based automatic
generation control for interconnected power system, Ain Shams Eng J
2012;http://dx.doi.org/10.1016/j.asej.2012.10.010.
[6] Das S, Suganthan PN. Differential evolution: a survey of the state-of-the-art. IEEE Trans Evol Comput
2011; 15:4–31.
[7] Sahu RK, Panda S, Rout UK. DE optimized parallel 2-DOF PID controller for load frequency control of
power system with governor dead-band nonlinearity. Int J Electr Power Energy Syst 2013; 49:19–33.
Design of Control Strategies for the Load Frequency Control (LFC) in Multi Area Power System for Parallel
Operation of Power Plants
http://www.iaeme.com/IJEET/index.asp 19 editor@iaeme.com
[8] Rout UK, Sahu RK, Panda S. Design and analysis of differential evolution algorithm based automatic
generation control for interconnected power system, Ain Shams Eng J 2012.
http://dx.doi.org/10.1016/j.asej.2012.10.010
[9] Kundur P. Power system stability and control. New York: Mc-Grall Hill; 1994.
[10] Elgerd OI. Electric energy systems theory an introduction. New Delhi: Tata McGraw-Hill; 1983.
[11] Yao Zhang, Lili Dong, and Zhiqiang Gao, "Load frequency control for multiple-area power systems,"
American Control Conference, ACC '09, pp.2773-2778, June 2009.
[12] Lili Dong, Yao Zhang, and Zhiqiang Gao, “robust decentralized load frequency controller for
interconnected power systems”, I Transactions, vol. 51, issue 3, pp. 410-419, May 2012.
[13] Ho Jae Lee, Jin Bae Park, and Young Hoon Joo, “Robust load frequency control for uncertain nonlinear
power systems: A fuzzy logic approach”, Information sciences, vol. 176, issue 23, pp. 3520-3537,
December 2006.
[14] H. Bevrani, and P.R. Daneshmand, "Fuzzy logic based load frequency control concerning high
penetration of wind turbines", IEEE Systems Journal, vol.6, no.1, pp.173-180, March 2012.
[15] J. Talaq, and F. Al-Basri, "Adaptive fuzzy gain scheduling for load frequency control", IEEE
Transactions on Power Systems , vol.14, no.1, pp.145-150, Feb 1999.
[16] Devendra Mittal, Om Prakash Mahela and Rohit Jain, “Detection and Analysis of Power Quality
Disturbances under Faulty Conditions in Electrical Power System”. International Journal of Electrical
Engineering & Technology (IJEET), 4(2), 2014, pp. 25–36.
[17] Li Pingkang, Zhu Hengjun, and Li Yuyun, "Genetic algorithm optimization for AGC of multi-area
power systems," 2002 IEEE Region 10 Technical Conference on Computers, Communications, Control
and Power Engineering, vol.3, pp.1818-1821, Oct. 2002.
[18] Fatemeh Daneshfar, Hassan Bevrani, “Multi objective design of load frequency control using genetic
algorithms”, International Journal of Electrical Power & Energy Systems, vol. 42, issue 1, pp. 257-263,
November 2012.
[19] K. Hari Krishna and Dr. K. Chandra Sekhar, “Modeling Analysis of AGC in Multi Source Deregulated
Power Systems”. International Journal of Electrical Engineering & Technology (IJEET), 5(7), 2014, pp.
56–66.

More Related Content

PDF
Iaetsd load frequency control for a distributed grid
PDF
Automatic load frequency control of two area power system with conventional a...
PDF
Automatic generation-control-of-interconnected-power-system-with-generation-r...
PDF
Automatic generation control of thermal generating unit by using conventional...
PPTX
Frequency Control of Power Systems
PDF
Automatic generation control of two area interconnected power system using pa...
PPTX
frequency regulation of deregulated power system having grc integrated with r...
PDF
Tubitak ucte training 1_1final_eng
Iaetsd load frequency control for a distributed grid
Automatic load frequency control of two area power system with conventional a...
Automatic generation-control-of-interconnected-power-system-with-generation-r...
Automatic generation control of thermal generating unit by using conventional...
Frequency Control of Power Systems
Automatic generation control of two area interconnected power system using pa...
frequency regulation of deregulated power system having grc integrated with r...
Tubitak ucte training 1_1final_eng

What's hot (20)

PDF
Load Frequency Control of Multi Area System using Integral-Fuzzy Controller
PPTX
Project ppt
PDF
PPTX
CONTROLLING FREQUENCY DEVIATIONS IN INTERCONNECTED POWER SYSTEM USING SMART ...
PPTX
An Under frequency Load Shedding Scheme for
PDF
EE6603 - Power System Operation & Control
DOCX
Exp 8 (1)8. Load-frequency dynamics of single area power system
PDF
3.10 eet in electrical systems
PDF
V044145150
PDF
Implementation of hysteresis current control for single phase grid connected ...
PDF
Ijeet 06 08_005
PDF
Optimal Tuning of PI Controllers for Doubly-Fed Induction Generator-Based Win...
PDF
Cuckoo Search Optimization Algorithm based Load Frequency Control of Intercon...
PDF
Ak4101210215
PDF
Under frequency load shedding for energy management using anfis case study
PDF
Power system planing and operation (pce5312) chapter five
PDF
Current control of grid-connected inverter using integral sliding mode contro...
PDF
Effects of the Droop Speed Governor and Automatic Generation Control AGC on G...
DOCX
Optimized coordinated economic dispatch and automatic generation control for ...
PDF
J010346786
Load Frequency Control of Multi Area System using Integral-Fuzzy Controller
Project ppt
CONTROLLING FREQUENCY DEVIATIONS IN INTERCONNECTED POWER SYSTEM USING SMART ...
An Under frequency Load Shedding Scheme for
EE6603 - Power System Operation & Control
Exp 8 (1)8. Load-frequency dynamics of single area power system
3.10 eet in electrical systems
V044145150
Implementation of hysteresis current control for single phase grid connected ...
Ijeet 06 08_005
Optimal Tuning of PI Controllers for Doubly-Fed Induction Generator-Based Win...
Cuckoo Search Optimization Algorithm based Load Frequency Control of Intercon...
Ak4101210215
Under frequency load shedding for energy management using anfis case study
Power system planing and operation (pce5312) chapter five
Current control of grid-connected inverter using integral sliding mode contro...
Effects of the Droop Speed Governor and Automatic Generation Control AGC on G...
Optimized coordinated economic dispatch and automatic generation control for ...
J010346786
Ad

Viewers also liked (20)

PDF
LOAD FREQUENCY CONTROL IN TWO AREA NETWORK INCLUDING DG
PDF
Load frequency control in co ordination with frequency controllable hvdc link...
PDF
Load / Frequency balancing Control systems study
 
PDF
Power Systems Engineering - Load Frequency Control Derivation & Calculatio...
PPTX
Determination of Voltage Regulation and Power system losses
PDF
Load frequency control
PDF
Calculating the efficiency and regulation of transformer using matlab
PPTX
Methods of Voltage Control
PPTX
Presentation1
PPT
Smart Grid
PPTX
Biomass To Fuel Cell Ppt 7 2012 Ls
PPTX
Method of voltage control
PPTX
Load Frequency Control of Two Area System
PPTX
Grid Voltage Regulation
PPTX
Reactive power management
PPTX
Power systems voltage and power control
PPTX
Power System Operation and Control
PPTX
Economic load dispatch
PDF
Protection of transmission lines (distance)
PPTX
Reactive power compensation
LOAD FREQUENCY CONTROL IN TWO AREA NETWORK INCLUDING DG
Load frequency control in co ordination with frequency controllable hvdc link...
Load / Frequency balancing Control systems study
 
Power Systems Engineering - Load Frequency Control Derivation & Calculatio...
Determination of Voltage Regulation and Power system losses
Load frequency control
Calculating the efficiency and regulation of transformer using matlab
Methods of Voltage Control
Presentation1
Smart Grid
Biomass To Fuel Cell Ppt 7 2012 Ls
Method of voltage control
Load Frequency Control of Two Area System
Grid Voltage Regulation
Reactive power management
Power systems voltage and power control
Power System Operation and Control
Economic load dispatch
Protection of transmission lines (distance)
Reactive power compensation
Ad

Similar to DESIGN OF CONTROL STRATEGIES FOR THE LOAD FREQUENCY CONTROL (LFC) IN MULTI AREA POWER SYSTEM FOR PARALLEL OPERATION OF POWER PLANTS (20)

PDF
IRJET- Optimum Design of PSO based Tuning using PID Controller for an Automat...
PDF
IRJET- Design and Analysis of Fuzzy and GA-PID Controllers for Optimized Perf...
PDF
IRJET- Analysis of 3-Phase Induction Motor with High Step-Up PWM DC-DC Conver...
PDF
Pa3426282645
PDF
IRJET- Load Frequency Control of a Wind Integrated Power System using Convent...
PDF
IRJET- Comparative Study of Load Frequency Control using PID and Fuzzy- PID C...
PDF
Implementation of closed loop control technique for improving the performance...
PPTX
SASHI_CS_ASSIGNMENT (1) on pid controller.pptx
PDF
G011115473
PDF
Hybrid controller design using gain scheduling approach for compressor systems
PDF
Convergence Parameter Analysis for Different Metaheuristic Methods Control Co...
PDF
A New Adaptive PID Controller
PDF
Development of a 2 degree of freedom-proportional integral derivative control...
PDF
Control and Monitoring of Hydro Power Plants A Review
PDF
Open-Switch Fault-Tolerant Control of a Grid-Side Converter in a Wind Power G...
PDF
Permanent Magnet Synchronous Generator Wind Turbine Pitch Angle Control by Fu...
PDF
IRJET- Load Frequency Control of a Renewable Source Integrated Four Area ...
PDF
Adıgüzel Hydroelectric Power Plant’s Modelling and LoadFrequency Control by F...
PDF
A New Control Method for the Multi-Area LFC System Based on Port-Hamiltonian ...
PDF
IRJET- PSO Tuned PID Controller for Single-Area Multi- Source LFC System
IRJET- Optimum Design of PSO based Tuning using PID Controller for an Automat...
IRJET- Design and Analysis of Fuzzy and GA-PID Controllers for Optimized Perf...
IRJET- Analysis of 3-Phase Induction Motor with High Step-Up PWM DC-DC Conver...
Pa3426282645
IRJET- Load Frequency Control of a Wind Integrated Power System using Convent...
IRJET- Comparative Study of Load Frequency Control using PID and Fuzzy- PID C...
Implementation of closed loop control technique for improving the performance...
SASHI_CS_ASSIGNMENT (1) on pid controller.pptx
G011115473
Hybrid controller design using gain scheduling approach for compressor systems
Convergence Parameter Analysis for Different Metaheuristic Methods Control Co...
A New Adaptive PID Controller
Development of a 2 degree of freedom-proportional integral derivative control...
Control and Monitoring of Hydro Power Plants A Review
Open-Switch Fault-Tolerant Control of a Grid-Side Converter in a Wind Power G...
Permanent Magnet Synchronous Generator Wind Turbine Pitch Angle Control by Fu...
IRJET- Load Frequency Control of a Renewable Source Integrated Four Area ...
Adıgüzel Hydroelectric Power Plant’s Modelling and LoadFrequency Control by F...
A New Control Method for the Multi-Area LFC System Based on Port-Hamiltonian ...
IRJET- PSO Tuned PID Controller for Single-Area Multi- Source LFC System

More from IAEME Publication (20)

PDF
IAEME_Publication_Call_for_Paper_September_2022.pdf
PDF
MODELING AND ANALYSIS OF SURFACE ROUGHNESS AND WHITE LATER THICKNESS IN WIRE-...
PDF
A STUDY ON THE REASONS FOR TRANSGENDER TO BECOME ENTREPRENEURS
PDF
BROAD UNEXPOSED SKILLS OF TRANSGENDER ENTREPRENEURS
PDF
DETERMINANTS AFFECTING THE USER'S INTENTION TO USE MOBILE BANKING APPLICATIONS
PDF
ANALYSE THE USER PREDILECTION ON GPAY AND PHONEPE FOR DIGITAL TRANSACTIONS
PDF
VOICE BASED ATM FOR VISUALLY IMPAIRED USING ARDUINO
PDF
IMPACT OF EMOTIONAL INTELLIGENCE ON HUMAN RESOURCE MANAGEMENT PRACTICES AMONG...
PDF
VISUALISING AGING PARENTS & THEIR CLOSE CARERS LIFE JOURNEY IN AGING ECONOMY
PDF
A STUDY ON THE IMPACT OF ORGANIZATIONAL CULTURE ON THE EFFECTIVENESS OF PERFO...
PDF
GANDHI ON NON-VIOLENT POLICE
PDF
A STUDY ON TALENT MANAGEMENT AND ITS IMPACT ON EMPLOYEE RETENTION IN SELECTED...
PDF
ATTRITION IN THE IT INDUSTRY DURING COVID-19 PANDEMIC: LINKING EMOTIONAL INTE...
PDF
INFLUENCE OF TALENT MANAGEMENT PRACTICES ON ORGANIZATIONAL PERFORMANCE A STUD...
PDF
A STUDY OF VARIOUS TYPES OF LOANS OF SELECTED PUBLIC AND PRIVATE SECTOR BANKS...
PDF
EXPERIMENTAL STUDY OF MECHANICAL AND TRIBOLOGICAL RELATION OF NYLON/BaSO4 POL...
PDF
ROLE OF SOCIAL ENTREPRENEURSHIP IN RURAL DEVELOPMENT OF INDIA - PROBLEMS AND ...
PDF
OPTIMAL RECONFIGURATION OF POWER DISTRIBUTION RADIAL NETWORK USING HYBRID MET...
PDF
APPLICATION OF FRUGAL APPROACH FOR PRODUCTIVITY IMPROVEMENT - A CASE STUDY OF...
PDF
A MULTIPLE – CHANNEL QUEUING MODELS ON FUZZY ENVIRONMENT
IAEME_Publication_Call_for_Paper_September_2022.pdf
MODELING AND ANALYSIS OF SURFACE ROUGHNESS AND WHITE LATER THICKNESS IN WIRE-...
A STUDY ON THE REASONS FOR TRANSGENDER TO BECOME ENTREPRENEURS
BROAD UNEXPOSED SKILLS OF TRANSGENDER ENTREPRENEURS
DETERMINANTS AFFECTING THE USER'S INTENTION TO USE MOBILE BANKING APPLICATIONS
ANALYSE THE USER PREDILECTION ON GPAY AND PHONEPE FOR DIGITAL TRANSACTIONS
VOICE BASED ATM FOR VISUALLY IMPAIRED USING ARDUINO
IMPACT OF EMOTIONAL INTELLIGENCE ON HUMAN RESOURCE MANAGEMENT PRACTICES AMONG...
VISUALISING AGING PARENTS & THEIR CLOSE CARERS LIFE JOURNEY IN AGING ECONOMY
A STUDY ON THE IMPACT OF ORGANIZATIONAL CULTURE ON THE EFFECTIVENESS OF PERFO...
GANDHI ON NON-VIOLENT POLICE
A STUDY ON TALENT MANAGEMENT AND ITS IMPACT ON EMPLOYEE RETENTION IN SELECTED...
ATTRITION IN THE IT INDUSTRY DURING COVID-19 PANDEMIC: LINKING EMOTIONAL INTE...
INFLUENCE OF TALENT MANAGEMENT PRACTICES ON ORGANIZATIONAL PERFORMANCE A STUD...
A STUDY OF VARIOUS TYPES OF LOANS OF SELECTED PUBLIC AND PRIVATE SECTOR BANKS...
EXPERIMENTAL STUDY OF MECHANICAL AND TRIBOLOGICAL RELATION OF NYLON/BaSO4 POL...
ROLE OF SOCIAL ENTREPRENEURSHIP IN RURAL DEVELOPMENT OF INDIA - PROBLEMS AND ...
OPTIMAL RECONFIGURATION OF POWER DISTRIBUTION RADIAL NETWORK USING HYBRID MET...
APPLICATION OF FRUGAL APPROACH FOR PRODUCTIVITY IMPROVEMENT - A CASE STUDY OF...
A MULTIPLE – CHANNEL QUEUING MODELS ON FUZZY ENVIRONMENT

Recently uploaded (20)

PPTX
Recipes for Real Time Voice AI WebRTC, SLMs and Open Source Software.pptx
PDF
Operating System & Kernel Study Guide-1 - converted.pdf
PPTX
MCN 401 KTU-2019-PPE KITS-MODULE 2.pptx
DOCX
573137875-Attendance-Management-System-original
PPTX
bas. eng. economics group 4 presentation 1.pptx
PDF
R24 SURVEYING LAB MANUAL for civil enggi
PDF
keyrequirementskkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkk
PDF
BMEC211 - INTRODUCTION TO MECHATRONICS-1.pdf
PPT
Mechanical Engineering MATERIALS Selection
PPTX
FINAL REVIEW FOR COPD DIANOSIS FOR PULMONARY DISEASE.pptx
PDF
Mitigating Risks through Effective Management for Enhancing Organizational Pe...
PPTX
CYBER-CRIMES AND SECURITY A guide to understanding
PDF
Mohammad Mahdi Farshadian CV - Prospective PhD Student 2026
PPTX
MET 305 2019 SCHEME MODULE 2 COMPLETE.pptx
PDF
Evaluating the Democratization of the Turkish Armed Forces from a Normative P...
PPTX
OOP with Java - Java Introduction (Basics)
DOCX
ASol_English-Language-Literature-Set-1-27-02-2023-converted.docx
PPTX
Engineering Ethics, Safety and Environment [Autosaved] (1).pptx
PPTX
web development for engineering and engineering
PPTX
M Tech Sem 1 Civil Engineering Environmental Sciences.pptx
Recipes for Real Time Voice AI WebRTC, SLMs and Open Source Software.pptx
Operating System & Kernel Study Guide-1 - converted.pdf
MCN 401 KTU-2019-PPE KITS-MODULE 2.pptx
573137875-Attendance-Management-System-original
bas. eng. economics group 4 presentation 1.pptx
R24 SURVEYING LAB MANUAL for civil enggi
keyrequirementskkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkk
BMEC211 - INTRODUCTION TO MECHATRONICS-1.pdf
Mechanical Engineering MATERIALS Selection
FINAL REVIEW FOR COPD DIANOSIS FOR PULMONARY DISEASE.pptx
Mitigating Risks through Effective Management for Enhancing Organizational Pe...
CYBER-CRIMES AND SECURITY A guide to understanding
Mohammad Mahdi Farshadian CV - Prospective PhD Student 2026
MET 305 2019 SCHEME MODULE 2 COMPLETE.pptx
Evaluating the Democratization of the Turkish Armed Forces from a Normative P...
OOP with Java - Java Introduction (Basics)
ASol_English-Language-Literature-Set-1-27-02-2023-converted.docx
Engineering Ethics, Safety and Environment [Autosaved] (1).pptx
web development for engineering and engineering
M Tech Sem 1 Civil Engineering Environmental Sciences.pptx

DESIGN OF CONTROL STRATEGIES FOR THE LOAD FREQUENCY CONTROL (LFC) IN MULTI AREA POWER SYSTEM FOR PARALLEL OPERATION OF POWER PLANTS

  • 1. http://www.iaeme.com/IJEET/index.asp 8 editor@iaeme.com International Journal of Electrical Engineering & Technology (IJEET) Volume 7, Issue 5, September–October, 2016, pp.08–19, Article ID: IJEET_07_05_002 Available online at http://www.iaeme.com/IJEET/issues.asp?JType=IJEET&VType=7&IType=5 ISSN Print: 0976-6545 and ISSN Online: 0976-6553 Journal Impact Factor (2016): 8.1891 (Calculated by GISI) www.jifactor.com © IAEME Publication DESIGN OF CONTROL STRATEGIES FOR THE LOAD FREQUENCY CONTROL (LFC) IN MULTI AREA POWER SYSTEM FOR PARALLEL OPERATION OF POWER PLANTS Chitta Padmaja Priyanka M. Tech, Department of Electrical Engineering, PVKKIT, Anantapur, India S.N.Lavanya Lecturer in Electrical Engineering, Government Polytechnic College, Tadipatri, India G.N.S.Vaibhav HOD, Assistant Professor, Department of Electrical Engineering, PVKKIT, Anantapur, India J. Ramesh Assistant Professor, Department of Electrical Engineering, PVKKIT, Anantapur, India ABSTRACT This paper features the Differential Evolution (DE) by controller parameters tuning algorithm and also an application of a multi source power system to a Load Frequency Control (LFC) by having several sources of power generation techniques. At first, a single area multi-source power system using integral controllers for every unit is taken and DE procedure is implemented to attain the controller parameters. Several mutation procedures of DE are estimated and the control parameters of DE for best obtained procedure are tuned by implementing numerous runs of algorithm for every change in parameter. Multi-area multi-source power system is also discussed and a HDVC link is also taken in accordance with the current AC tie line for the internal connection between the areas. The two variables of Integrals which are to be enhanced using tuned DE algorithm are proportional integral and proportional integral derivative. The advantage of the proposed strategy has been exposed by estimating the results with the freshly published enhanced output feedback controller for the similar power systems. Further, the assessment is conducted by performing several procedures like overshoot, tie line power derivation followed by a step load perturbation (SLP), settling time and standard error criteria of frequency. It is also observed that, the maximum output of the feedback controller is less than the dynamic
  • 2. Design of Control Strategies for the Load Frequency Control (LFC) in Multi Area Power System for Parallel Operation of Power Plants http://www.iaeme.com/IJEET/index.asp 9 editor@iaeme.com performance of the proposed controller. Additionally, the proposed power system is not affected by altering the loading conditions, size of SLP and system parameters. Key words: Differential Evolution (DE), step load perturbation (SLP), HDVC link, Multi-area multi-source power system, Load Frequency Control (LFC). Cite this Article: Chitta Padmaja Priyanka, S.N. Lavanya, G.N.S. Vaibhav and J. Ramesh, Design of Control Strategies for the Load Frequency Control (LFC) in Multi Area Power System for Parallel Operation of Power Plants. International Journal of Electrical Engineering & Technology, 7(5), 2016, pp. 08–19. http://www.iaeme.com/IJEET/issues.asp?JType=IJEET&VType=7&IType=5 1. INTRODUCTION Load Frequency Control (LFC) is the problem of controlling the real power output of generating units in response to changes in tie-line power interchange and system frequency within specified limits. LFC is also a part of Automatic Generation Control (AGC) and plays a very important in the operation and control of power systems. . Large Scale Power Systems are generally composed of control areas representing coherent groups of generators, which have combination of hydro, thermal, nuclear, gas, and renewable energy sources. Researchers across the world are trying to propose several new strategies for LFC of power systems to maintain the system frequency and tie line flow at their scheduled i.e. pre-defined values during normal operation and also during small perturbations. It can be seen through literature survey that, most of the LFC power system works have been carried out on two area thermal–thermal or hydro-thermal systems. It is noticed that, large amount of research work indicates to propose better AGC systems based on Neural Network, Modern Control Theory, Reinforcement Learning [8], Fuzzy Systems and ANFIS approach. But, with these advanced approaches there are complications and also need experienced users which in turn reduces their applicability. Due to its structural simplicity and reliability the classical Proportional Integral Derivative (PID) controller remains an engineer’s preferred choice, which even has an advantage of favorable ratio between performances and cost. This model requires lower user-skills, minimal development effort and simplified dynamic modeling. In current technology, modern artificial intelligence-based approaches have been projected to optimize the PI/PID controller parameters for AGC system. The increase in complexity and size of electric power systems along with raise in power demand has made it compelling to use the intelligent systems that combine methodologies, techniques and knowledge from varied sources for the real-time control of power systems. The design problem for the proposed controller is developed as an optimization problem. A frequency controller is needed to maintain the system frequency, as burden of a power system is constant and never given to ensure the quality of supply of energy, at the desired nominal value. In the deregulated energy system, control area contains various disturbances and varied types of uncertainties because of more complex modeling errors of the system and the changes in the structure of power system. Therefore, we need a control strategy which not only maintains the desired tie-line power and flow rate constancy but can also achieve zero steady-state error and inadvertent exchange. The most popular feedback controller used by the process industries is the proportional integral derivative (PID) controller is the. It is a robust controller, easy to understand that it can provide excellent control performance despite the various dynamic characteristics of the process plant. As the name proposes, the PID algorithm has basically three modes, proportional mode, integral mode and derivative mode. A proportional controller effects in reducing the rise time but can never eliminate the steady state error. Where as an integral control can eliminate the steady-state error, but it will make the transient response still worse. The derivative control improves the system stability by decreasing surplus, and improved transient response. Proportional integral controllers (PI) are nowadays most often used in the industry. We can use a controller without the derivative mode (D) when a fast system response is not required; there is high delay in the transport system and during high noise and disturbance present during
  • 3. Chitta Padmaja Priyanka, S.N.Lavanya, G.N.S.Vaibhav and J. Ramesh http://www.iaeme.com/IJEET/index.asp 10 editor@iaeme.com the process of operation. Derivative mode helps in improving the system stability and allows increase gain and decrease in integral gain, which in turn boosts the speed of response proportional controller. PID controller is mostly used when quick response and stability are main concern. In view of above, I, PI and PID controllers are considered analytical herein. In the design of a modern technique based on the optimization controller, we first define the objective function based on the specifications and limitations. So the design of the objective function is for tuning the controller and generally based on a performance index that considers the entire closed-loop system response. Time domain conventional output specifications are rise time, steady-state error, overshooting peak, settling time. 2. DESIGN OF CONTROL SYSTEM For the design of controller in the system the prominent specimen to be considered is the two area system covering the warming of gas turbines, hydraulic and thermal units. Figure 1 shows the LFC power system under study. This system is used for simulation by linearising the governors, hydraulic turbines, reheat turbines, gas turbines. The participation and contribution of each unit to the rated load is decided by its parameter adjustment factor. In each Control unit the sum of the participation factor need to be equal to 1.In Figure.1R1, UT and KT are parameter of regulation, output of control and participation factor respectively for thermal unit; R2,UH and KH are parameter of regulation, output of control and participation factor respectively for hydraulic unit; R3,HG and KG are parameter of regulation, output of control and participation factor respectively for gas unit, is the constant speed governor thermal unit (seconds), is steam turbine time constant (seconds), Kr is the constant reheat steam turbinate is the reheat time constant of the steam turbine (seconds), is time nominal starting penstock water (seconds), is the regulator of the hydraulic turbine speed reset the time (seconds), is Hydro turbine speed governor transient droop time constant(seconds), is hydro turbine main regulator time constant servo speed (seconds), is the time constant standby gas turbine;where c is the time constant delay of the gas turbine and speed regulator in seconds, is the valve positioned of the gas turbine, is the constant of the gas turbine valve positioner, is the gas turbine fuel time constant (seconds), is the gas turbine time delay combustion reaction (seconds), is the gas turbine compressor discharge at constant volume time in (seconds), is gain of power system (Hz/puMW) , is the system time constant power in (seconds), ∆F is the incremental change in the exchange rate and incremental load ∆PD.The nominal system parameters are displayed in reference. For our current study integral of time-weighted absolute error (ITAE) is preferred objective function as the deviation of power in the control areas will be diminished quickly and also used in study of ACG. Hence objective function is expressed as: J=ITAE= |∆ |. . Where the simulation is time interval and ∆ is the frequency deviation system. As the constraints of the problem are the limits of the driver parameters. Therefore, our design problem can be forged as the below optimization problem. Subject to diminish J: ! " ≤ ! ≤ ! %& Where our objective functions is J and !'() and !'*+ theminimum control parameters and maximum control parameters. As proclaimed in the literature, the minimum and maximum values of the controller parameters are chosen as -1 and 1 respectively.
  • 4. Design of Control Strategies for the Load Frequency Control (LFC) in Multi Area Power System for Parallel Operation of Power Plants http://www.iaeme.com/IJEET/index.asp 11 editor@iaeme.com Figure 1 Transfer function model of multiple sources-multiple areas with HVDC link 3. CONVENTIONAL CONTROLLER TUNING METHODS As of now the PID (proportional integral derivative) controller is the most common control algorithm. Most of the feedback loops are being controlled by this algorithm or with minor variations in it. This can be implemented in different forms like a stand-alone controller or as a part of a Direct Digital Control package or a hierarchical distributed process control system. PID algorithm consists of three basic modes: • Proportional mode • Integral mode • Derivative mode A proportional controller regulates the reaction to the current error and rise time, but can never eliminate the steady-state error. Integral control regulates the reaction based on the sum of recent errors and eliminates steady-state error, but it makes the transient response worse. Derivative control regulates the reaction to the rate at which the error has been changing i.e. increases the stability of the system, which in turn reduces the overshoot, and improves the transient response. Proportional Integral controllers are the most regularly used controllers in industry now. We can use a controller without D mode when: a fast response of the system is not mandatory, large noise and disturbances are present during operation of the process and there is significant delay in the transport system. Derivative mode increases the stability of the system and enables improvement in gain K and decreases integral time constant Ti, which in turn increases the speed of the controller response.PID
  • 5. Chitta Padmaja Priyanka, S.N.Lavanya, G.N.S.Vaibhav and J. Ramesh http://www.iaeme.com/IJEET/index.asp 12 editor@iaeme.com control is generally used when the stability and quick response is mandatory. In this paper for Load Frequency Control we have considered I, PI, PID controllers. By setting the control parameters to their optimum values for obtaining desired control response we tune these controllers. Foremost requirement is stability of the multi-area system. Anyways as different systems will have different behavior and different applications will have different requirements and these requirements may conflict with each another. Even though the principle of PID is simple and has only three parameters, tuning of ID is challenging as it needs to be answered in complex criteria. Manual setting method, PID tuning methods software and Ziegler- Nichols tuning method are some of the prominent control loop tuning methods. 4. PSO CONTROLLER James Kennedy and Russell Eberhart recommended Particle swarm optimization in 1995, which is population movement and swarm intelligence, based speculative optimization technique. PSO is a computational technique, developed and inspired by social behavior of bird flocking or fish schooling. A group of random particles (solutions) are generated in this technique. Each particle is now treated as a point in an n-dimensional space, which will adjust its "fly" according to the flight experience of other particles and its own experience of flight. According to the value of fitness, the best solution is determined for the current iteration and the best fitness value is also stored. The best possible solution is known as pbest. Another finest fitness value is also tracked in the iterations so far obtained. This finest fitness value is the global best and the corresponding particle solution is called gbest. In each of the iteration all of the particles have been restored by following the pbest (best previous position) and gbest (best particle among all the particles) in the swarm. There is no crossover operation involved PSO. In Evolutionary Programming (EP) balance between global and local search we can set the strategy parameter, while equilibrium in PSO is reached by the inertial weight factor (w). PID controller with PSO optimization is designed for LFC and tie-power control. Main objectives are to control the frequency and tie-between area with good power oscillation damping, also get good performance in this study, the optimal values of the PK parameters Ki and Kd for PID controller easily and accurately calculated using a PSO.In a typical run of the PSO, an initial population is generated randomly. This is known as initial population generation 0th. Each individual of the initial population has an index value associated performance. The use of performance index information, the PSO then produces a new population. So as to obtain the performance index value for each one of the individual in the current population, the system needs to be simulated. The PSO will now produce the next generation of people who can use crossover operators and mutation breeding. These processes are kept repeating till the population is converged and the optimal value of parameters found. The document aims to use the PSO algorithm in order to obtain optimal values of the PID controller to a system of two frequency load area. Each adjustment controller may represent a particle in the search space that changes its parameters proportionality constant Kp, an integral constant Ki, and Kd derivative constant to minimize the error function. The error function used here is the integral time absolute error (ITAE). 4.1. PSO Steps: Steps PSO as Implemented for the Optimization • Step 1: Initialize an array of particles with random positions and velocities associated to satisfy the inequality constraints. • Step 2: Check satisfying the equality constraints and modify the solution if necessary. • Step 3: Assess the fitness function of each particle. • Step 4: Compare the current value of the fitness function better with particles above value (pbest). If the current fitness value is lower, then assign the current value of fitness for pbest and assigned the coordinates (positions) to pbest x. • Step 5: Determine the current global minimum value of fitness between the current positions.
  • 6. Design of Control Strategies for the Load Frequency Control (LFC) in Multi Area Power System for Parallel Operation of Power Plants http://www.iaeme.com/IJEET/index.asp 13 editor@iaeme.com • Step 6: Compare the current global minimum above the minimum overall (gbest). If the current global minimum is better than gbest, then assign the global minimum current for gbest and assigned the coordinates (positions) to gbestx. • Step 7: Change speeds. • Step 8: Each particle moves to the new position and return to step 2. • Step 9: Repeat from step 2-8 until the stopping criterion is satisfied or we have reached the maximum number of iterations. Figure 2 Flowchart For PSO 5. DIFFERENTIAL EVOLUTION Differential Evolution (DE) is a population based indefinite optimization algorithm which is capable of handling non-linear, non-differentiable and also multi-modal objective functions, which has some readily selected control parameters. The design problem of the proposed controller is then formulated as an optimization problem and here DE is used in searching optimal control parameters. DE works with two different people; the old generation and the new generation of the very same population. The population size can be adjusted by the parameter NP. This population is composed of actual dimension values D
  • 7. Chitta Padmaja Priyanka, S.N.Lavanya, G.N.S.Vaibhav and J. Ramesh http://www.iaeme.com/IJEET/index.asp 14 editor@iaeme.com vectors which equals to the number of design parameters divided by variables control. This population is run randomly within the initial parameter. The optimization process is mainly affected by these three main operations: mutation, crossover and selection. In each of the generation, the individuals in the current population become the targets vectors. In vector for each target, the mutation operation produces a mutant vector, then by addition of the weighted difference between any two vectors selected randomly, a third vector is made target. The cut operation now generates a new vector, which is called as test vector by mixing the entries of the vector mutant with that of the target vector. If this test vector gets a better fitness value than that of the target vector, then this test vector replaces the target vector in the preceding generation. Evolutionary operators are as described below: 5.1. Initialization For each parameter j with the lower and upper bound the values of the initial parameters are usually uniformly at random in the interval [ , - ; , . ]. 5.2. Mutation For any given parameter vector X0,2, we take the three vectors (X34,2X35,2 ,X36,2) are randomly selected in such a way that the indices i, r1, r2 and r3 are distinct. The donor vector V0,284 can be created by adding the weighted difference between the two vectors to a third vector as: V0,284=X34,2+ F. (X35,2- X36,2), Where F is a constant from (0, 2) 5.3. Crossover These three parents are now selected for the crossover and the child is a perturbation of any one of them. Our trial vector Ui,G+1 is developed from the elements of this target vector (Xi, G) and the elements of the donor vector (Xi, G). Elements of the donor vector then enter the trial vector with probability CR as: Uj,i,G+1=9 V:,0,284 if rand:,0 ≤ CR CDE = GHIJK X:,0,284 if rand:,0 > MN CDE = GHIJK O Withrand:,0~ U (0, 1), I3RSTis a random integer from (1, 2, . . ., D) where D is the solution’s dimension i.e. number of control variables. I3RST ensures that V0,284 ≠ X0,284 5.4. Selection The target vector X0,2is now compared with the trial vector V0,284and the one with the better fitness value is admitted to the further generations. The selection operation in DE can be represented by the below equation: , 84=V U0,284 if f( U0,284) < [(X0,2) X0,2C ℎ]D^(_] O Where I∈ [ 1,a ]
  • 8. Design of Control Strategies for the Load Frequency Control (LFC) in Multi Area Power System for Parallel Operation of Power Plants http://www.iaeme.com/IJEET/index.asp 15 editor@iaeme.com Figure 3 Flow Diagram of DE Flow 6. RESULTS AND COMPARISION During the simulation study, Error signals f1, f2 and tie line power required for the controller software is transferred to the PSO. All positions of the particles in each dimension are held within the limits specified by the user, and Velocities subject to the [Vmin, Vmax] range. A gradual increase in demand of 0.01 pu is applied to zone 1 The frequency deviation of the first area frequency and f1 and second f2 deviation of the area and the area between clamping signal power closed loop system shown in Figure. 4, 5, 6. Similarly a step increase in demand of 0.01 applies to Area2. Frequency deviation of the first area and the f1 and f2 frequency of the second area and the area between clamping signal power circuitry of the closed loop system are shown in Figure 7,8,9.
  • 9. Chitta Padmaja Priyanka, S.N.Lavanya, G.N.S.Vaibhav and J. Ramesh http://www.iaeme.com/IJEET/index.asp 16 editor@iaeme.com Figure 4 Change in Frequency of Area-1 for 1% change in Area-1 Figure 5 Change in Frequency of Area-2 for 1% change in Area-1 Figure 6 Change in Tie Line Power for 1% change in Area-1
  • 10. Design of Control Strategies for the Load Frequency Control (LFC) in Multi Area Power System for Parallel Operation of Power Plants http://www.iaeme.com/IJEET/index.asp 17 editor@iaeme.com Figure 7 Change in Frequency of Area-1 for 1% change in Area-2 Figure 8 Change in Frequency of Area-2 for 1% change in Area-2 Figure 9 Change in Tie Line Power for 1% change in Area-2
  • 11. Chitta Padmaja Priyanka, S.N.Lavanya, G.N.S.Vaibhav and J. Ramesh http://www.iaeme.com/IJEET/index.asp 18 editor@iaeme.com Simulation results show improved performance in the time domain specifications for a load of 0.01 pu step Using the PSO approach, global and local solutions could be found simultaneously for a better adjustment of the controller parameters . The PID value that was obtained by the PSO algorithm is compared with the PID controller derived from differential evolution algorithm, PID controller, PI controller and the I in different perspectives namely, robustness and stability. All simulations were carried out using MATLAB A comparison of time domain specifications overshoot and settling time for a load of 0.01 pu step in area 1 are tabulated as given in the table (2) and it is very clearly that the PSO based controller dramatically reduces overshoot by a large value. Settling time improved. 7. CONCLUSION In this thesis, Load Frequency Control (LFC) of multi-unit source power system having different sources of power generation like thermal, hydro and gas power plants is presented. The controller parameters are tuned using particle swarm optimization (PSO) technique, Differential Evolution algorithm technique, PID controller, PI controller and I controller. The superiority of our proposed approach has been interpreted clearly by analysing the results with Integral (I) controller, proportional integral (PI) controller, Proportional Integral Derivative (PID) Controller and DE employed PID controller for the same power systems by using different performance measures like overshoot, settling time and standard error criteria of frequency and tie-line power deviation using a step load perturbation (SLP). It is observed that, the dynamic performance of proposed controller PSO is revised. Additionally, it is also seen that the proposed system is flexible and is not affected by any change in its loading condition, system parameters and size of SLP. APPENDIX B: SYSTEM SETTINGS b4= b5= 0.4312 p.u. MW/Hz; cH = 2000 MW; c-= 1840 MW; N4= N5= N6= 2.4 Hz/p.u.; = 0.08 s; = 0.3 s; = 0.3; = 10 s; 4= 5= 68.9566 Hz/p.u. MW; 4= 5= 11.49 s; 45= 0.0433; *45= -1; = 1 s; = 5 s; = 28.75 s; = 0.2 s; = 0.6 s; d = 1 s; = 1; = 0.05 s; = 0.23 s; = 0.01 s; = 0.2 s; = 0.543478; = 0.326084; = 0.130438; = 1; = 0.2 s. REFERENCES [1] BanajaMohanty, Sidhartha panda, P.K Hota., controller parameters tuning of differential evolution algorithm and its application to load frequency control of multi source power system, Electrical power and energy systems 54(2014)77-85 [2] Ibraheem, Kumar P, Kothari DP. Recent philosophies of automatic generation control strategies in power systems. IEEE Trans Power Syst 2005; 20:34657. [3] Parmar KPS, Majhi S, Kothari DP. Load frequency control of a realistic power system with multi-source power generation. Int J Elect Power Energy Syst2012; 42:426–33. [4] Ghosal SP. Optimization of PID gains by particle swarm optimization in fuzzy based automatic generation control. Electr Power Syst Res 2004; 72:203–12. [5] Rout UK, Sahu RK, Panda S. Design and analysis of differential evolution algorithm based automatic generation control for interconnected power system, Ain Shams Eng J 2012;http://dx.doi.org/10.1016/j.asej.2012.10.010. [6] Das S, Suganthan PN. Differential evolution: a survey of the state-of-the-art. IEEE Trans Evol Comput 2011; 15:4–31. [7] Sahu RK, Panda S, Rout UK. DE optimized parallel 2-DOF PID controller for load frequency control of power system with governor dead-band nonlinearity. Int J Electr Power Energy Syst 2013; 49:19–33.
  • 12. Design of Control Strategies for the Load Frequency Control (LFC) in Multi Area Power System for Parallel Operation of Power Plants http://www.iaeme.com/IJEET/index.asp 19 editor@iaeme.com [8] Rout UK, Sahu RK, Panda S. Design and analysis of differential evolution algorithm based automatic generation control for interconnected power system, Ain Shams Eng J 2012. http://dx.doi.org/10.1016/j.asej.2012.10.010 [9] Kundur P. Power system stability and control. New York: Mc-Grall Hill; 1994. [10] Elgerd OI. Electric energy systems theory an introduction. New Delhi: Tata McGraw-Hill; 1983. [11] Yao Zhang, Lili Dong, and Zhiqiang Gao, "Load frequency control for multiple-area power systems," American Control Conference, ACC '09, pp.2773-2778, June 2009. [12] Lili Dong, Yao Zhang, and Zhiqiang Gao, “robust decentralized load frequency controller for interconnected power systems”, I Transactions, vol. 51, issue 3, pp. 410-419, May 2012. [13] Ho Jae Lee, Jin Bae Park, and Young Hoon Joo, “Robust load frequency control for uncertain nonlinear power systems: A fuzzy logic approach”, Information sciences, vol. 176, issue 23, pp. 3520-3537, December 2006. [14] H. Bevrani, and P.R. Daneshmand, "Fuzzy logic based load frequency control concerning high penetration of wind turbines", IEEE Systems Journal, vol.6, no.1, pp.173-180, March 2012. [15] J. Talaq, and F. Al-Basri, "Adaptive fuzzy gain scheduling for load frequency control", IEEE Transactions on Power Systems , vol.14, no.1, pp.145-150, Feb 1999. [16] Devendra Mittal, Om Prakash Mahela and Rohit Jain, “Detection and Analysis of Power Quality Disturbances under Faulty Conditions in Electrical Power System”. International Journal of Electrical Engineering & Technology (IJEET), 4(2), 2014, pp. 25–36. [17] Li Pingkang, Zhu Hengjun, and Li Yuyun, "Genetic algorithm optimization for AGC of multi-area power systems," 2002 IEEE Region 10 Technical Conference on Computers, Communications, Control and Power Engineering, vol.3, pp.1818-1821, Oct. 2002. [18] Fatemeh Daneshfar, Hassan Bevrani, “Multi objective design of load frequency control using genetic algorithms”, International Journal of Electrical Power & Energy Systems, vol. 42, issue 1, pp. 257-263, November 2012. [19] K. Hari Krishna and Dr. K. Chandra Sekhar, “Modeling Analysis of AGC in Multi Source Deregulated Power Systems”. International Journal of Electrical Engineering & Technology (IJEET), 5(7), 2014, pp. 56–66.