Selection and requirements of fire alarm control system
According to the requirements of the code, the fire alarm control system can be divided into
regional alarm system, centralized alarm system and control center alarm system.
I. The regional alarm system is applicable to the protected objects that only need to link the
audible and visual alarm, and do not need to link other automatic fire fighting equipment.
The regional fire alarm system can set fire alarm controller.
The design of the regional fire alarm system shall comply with the following requirements:
1. The system shall consist of fire detector, manual fire alarm button, fire audible and visual alarm
and fire alarm controller.
2. The system may include a graphic display device in the fire control room and an fire alarm
displayer to indicate the fire floor.
3. The fire control room can not be set up for the regional fire alarm system, but the fire alarm
controller should be set up in the place with people on duty.
4. When the system is equipped with the graphic display device in the fire control room, the
graphic display device performs the functions of remote information transmission and remote
query.
5. If no graphic display device is set in the system, fire alarm transmission device should be set.
Similar functions are performed by fire alarm transmission equipment.
II. The centralized fire alarm system is applicable to the protected objects that need to be linked
with other fire fighting equipment in addition to the sound and light alarm.
The centralized fire alarm system needs to adopt the connected fire alarm controller.
A centralized fire alarm system can be connected to multiple regional fire alarm systems.
The centralized fire alarm system shall be equipped with fire control room and graphic display
device.
And shall comply with the following provisions:
1. The system shall consist of fire detector, manual fire alarm button, fire audible and visual alarm,
fire emergency broadcast, special telephone for fire fighting, graphic display device in fire control
room, fire alarm controller, fire linkage controller, etc.
2. The fire alarm controller, fire linkage controller, graphic display device of fire control room,
control device of fire emergency broadcast, telephone switchboard for fire control and other fire
equipment in the system should be installed in the fire control room.
3. The graphical display device of the fire control room shall perform the function of remote
information transmission and remote query.
There is no separate alarm linkage controller in practice. All of them are connected fire alarm
controllers with linkage function.
In the fire control room as shown in the figure, the fire alarm controller, the control device of fire
emergency broadcast, the switchboard for fire fighting, and the graphic display device of the fire
control room are all assembled in the fire control cabinet of the piano table type.
III. Control center alarm system is generally suitable for building groups or large volume of
protection objects.
Usually there are the following situations:
1. The building complex may be equipped with two or more fire control rooms.
2. Products of different enterprises or different series of products of the same enterprise are
used in the phased construction of the architectural complex, and multiple systems are
networked in the phased construction.
3. In the large-scale system, due to the system capacity limit, multiple centralized control of the
connected fire alarm controller is set. This is quite common.
The design of the control center alarm system should not only meet the functions of the
centralized control system.
The following requirements should also be met:
1. When there are two or more fire control rooms, a main fire control room shall be determined.
The main fire control room shall be able to display all fire alarm signals and linkage control status
signals, and it shall be able to control important fire equipment.
Fire fighting equipment in each fire control room can transmit and display status information to
each other, but they should not control each other.
2. When there is only one fire control room with multiple centrally controlled fire alarm
controllers, the master controller shall be set in the fire control room, which shall be able to
display all fire alarm signals and linkage control status signals, and shall be able to control all
linkage devices.
The direct manual control device of the fire pump, smoke control and smoke exhaust fan and
other important equipment should be set up in the fire control room together with the main
controller.

More Related Content

PDF
fire alarm system fire graphic display device
PDF
overview of automatic fire-alarm systems
PDF
overview of automatic fire-alarm systems
PDF
Lecture 5 Fire Alarm System.pdf
PPTX
FIRE ALARM SYSTEM
PDF
How to linkage fire alarm system parts addressable fire alarm system
PDF
linkage fire alarm system parts
PDF
addressable fire alarm system loop
fire alarm system fire graphic display device
overview of automatic fire-alarm systems
overview of automatic fire-alarm systems
Lecture 5 Fire Alarm System.pdf
FIRE ALARM SYSTEM
How to linkage fire alarm system parts addressable fire alarm system
linkage fire alarm system parts
addressable fire alarm system loop

Similar to fire alarm system types (20)

PDF
FIRE DETECTION & ALARM SYSTEMS.pdf
PPTX
UNIT-V FIRE SAFETY INSTALLATION
PPTX
UNIT-5.pptx
PDF
division of fire alarm areas
PDF
Fire Alarm ... Design, Components, Applications
PPT
Chapter 07
PPT
Chapter 08
PPTX
Fundamentals of Fire Alarm System
DOCX
Em latest
PDF
Codigos y perifericos rep 2001
PPTX
Fire Detection and Alarm Systems
PPT
Fire basics 1-3-functions_to_docs_08
PPTX
Fire Detection and Alarm System Orientation.pptx
PPTX
Basic Fire Detection and Alarm Systems.pptx
PDF
Building services final report
PPTX
[011725].pptx fire safety project alarm
PPTX
[000417].pptxbasic fire alarm system over
PDF
Fire alarm and gas extinguishing system instruction
PPTX
New Microsoft PowerPoint Presentation.pptx
PPTX
Functioning of a Fire alarm panel
FIRE DETECTION & ALARM SYSTEMS.pdf
UNIT-V FIRE SAFETY INSTALLATION
UNIT-5.pptx
division of fire alarm areas
Fire Alarm ... Design, Components, Applications
Chapter 07
Chapter 08
Fundamentals of Fire Alarm System
Em latest
Codigos y perifericos rep 2001
Fire Detection and Alarm Systems
Fire basics 1-3-functions_to_docs_08
Fire Detection and Alarm System Orientation.pptx
Basic Fire Detection and Alarm Systems.pptx
Building services final report
[011725].pptx fire safety project alarm
[000417].pptxbasic fire alarm system over
Fire alarm and gas extinguishing system instruction
New Microsoft PowerPoint Presentation.pptx
Functioning of a Fire alarm panel
Ad

More from Vedard Security Alarm System Store (20)

PDF
carbon monoxide detection system environment security fire alarm fire security
PDF
test of gas fire extinguishing system fire security systems maintenance
PDF
Residual current electrical fire detector
PDF
linkage of gas fire extinguishing system with fire alarm
PDF
wireless fire alarm system fire linkage fire fighting security control
PDF
YA-D300 explosion proof gas detector manual.pdf
PDF
Solar-powered Wireless Infrared Beam and Grating
PDF
Complete home and business security system alarm system category
PDF
wireless fire alarm installation and debugging procedures.pdf
PDF
linkage of gas fire extinguishing system with fire alarm
PDF
test of gas fire extinguishing system
PDF
electric fire temperature detectors
PDF
independent electric fire detection system
PDF
fire alarm linkage smoke exhaust
PDF
addressable fire alarm system bus loop
PDF
addressable fire alarm bus short circuit isolator
PDF
fire manual call and hydrant button
PDF
addressable fire alarm system input module
PDF
carbon monoxide detection system
PDF
gas fire extinguish system
carbon monoxide detection system environment security fire alarm fire security
test of gas fire extinguishing system fire security systems maintenance
Residual current electrical fire detector
linkage of gas fire extinguishing system with fire alarm
wireless fire alarm system fire linkage fire fighting security control
YA-D300 explosion proof gas detector manual.pdf
Solar-powered Wireless Infrared Beam and Grating
Complete home and business security system alarm system category
wireless fire alarm installation and debugging procedures.pdf
linkage of gas fire extinguishing system with fire alarm
test of gas fire extinguishing system
electric fire temperature detectors
independent electric fire detection system
fire alarm linkage smoke exhaust
addressable fire alarm system bus loop
addressable fire alarm bus short circuit isolator
fire manual call and hydrant button
addressable fire alarm system input module
carbon monoxide detection system
gas fire extinguish system
Ad

Recently uploaded (20)

PPTX
Chemical Technological Processes, Feasibility Study and Chemical Process Indu...
PDF
Categorization of Factors Affecting Classification Algorithms Selection
PDF
August 2025 - Top 10 Read Articles in Network Security & Its Applications
PDF
ChapteR012372321DFGDSFGDFGDFSGDFGDFGDFGSDFGDFGFD
PPTX
Feature types and data preprocessing steps
PDF
737-MAX_SRG.pdf student reference guides
PPTX
Software Engineering and software moduleing
PDF
III.4.1.2_The_Space_Environment.p pdffdf
PPTX
Fundamentals of safety and accident prevention -final (1).pptx
PDF
Human-AI Collaboration: Balancing Agentic AI and Autonomy in Hybrid Systems
PDF
BIO-INSPIRED HORMONAL MODULATION AND ADAPTIVE ORCHESTRATION IN S-AI-GPT
PDF
Influence of Green Infrastructure on Residents’ Endorsement of the New Ecolog...
PPTX
Management Information system : MIS-e-Business Systems.pptx
PPTX
Module 8- Technological and Communication Skills.pptx
PDF
Abrasive, erosive and cavitation wear.pdf
PPTX
CURRICULAM DESIGN engineering FOR CSE 2025.pptx
PPTX
"Array and Linked List in Data Structures with Types, Operations, Implementat...
PDF
Visual Aids for Exploratory Data Analysis.pdf
PPTX
communication and presentation skills 01
PPTX
Graph Data Structures with Types, Traversals, Connectivity, and Real-Life App...
Chemical Technological Processes, Feasibility Study and Chemical Process Indu...
Categorization of Factors Affecting Classification Algorithms Selection
August 2025 - Top 10 Read Articles in Network Security & Its Applications
ChapteR012372321DFGDSFGDFGDFSGDFGDFGDFGSDFGDFGFD
Feature types and data preprocessing steps
737-MAX_SRG.pdf student reference guides
Software Engineering and software moduleing
III.4.1.2_The_Space_Environment.p pdffdf
Fundamentals of safety and accident prevention -final (1).pptx
Human-AI Collaboration: Balancing Agentic AI and Autonomy in Hybrid Systems
BIO-INSPIRED HORMONAL MODULATION AND ADAPTIVE ORCHESTRATION IN S-AI-GPT
Influence of Green Infrastructure on Residents’ Endorsement of the New Ecolog...
Management Information system : MIS-e-Business Systems.pptx
Module 8- Technological and Communication Skills.pptx
Abrasive, erosive and cavitation wear.pdf
CURRICULAM DESIGN engineering FOR CSE 2025.pptx
"Array and Linked List in Data Structures with Types, Operations, Implementat...
Visual Aids for Exploratory Data Analysis.pdf
communication and presentation skills 01
Graph Data Structures with Types, Traversals, Connectivity, and Real-Life App...

fire alarm system types

  • 1. Selection and requirements of fire alarm control system According to the requirements of the code, the fire alarm control system can be divided into regional alarm system, centralized alarm system and control center alarm system. I. The regional alarm system is applicable to the protected objects that only need to link the audible and visual alarm, and do not need to link other automatic fire fighting equipment. The regional fire alarm system can set fire alarm controller. The design of the regional fire alarm system shall comply with the following requirements: 1. The system shall consist of fire detector, manual fire alarm button, fire audible and visual alarm and fire alarm controller. 2. The system may include a graphic display device in the fire control room and an fire alarm displayer to indicate the fire floor. 3. The fire control room can not be set up for the regional fire alarm system, but the fire alarm controller should be set up in the place with people on duty. 4. When the system is equipped with the graphic display device in the fire control room, the graphic display device performs the functions of remote information transmission and remote query. 5. If no graphic display device is set in the system, fire alarm transmission device should be set. Similar functions are performed by fire alarm transmission equipment. II. The centralized fire alarm system is applicable to the protected objects that need to be linked with other fire fighting equipment in addition to the sound and light alarm. The centralized fire alarm system needs to adopt the connected fire alarm controller. A centralized fire alarm system can be connected to multiple regional fire alarm systems.
  • 2. The centralized fire alarm system shall be equipped with fire control room and graphic display device. And shall comply with the following provisions: 1. The system shall consist of fire detector, manual fire alarm button, fire audible and visual alarm, fire emergency broadcast, special telephone for fire fighting, graphic display device in fire control room, fire alarm controller, fire linkage controller, etc. 2. The fire alarm controller, fire linkage controller, graphic display device of fire control room, control device of fire emergency broadcast, telephone switchboard for fire control and other fire equipment in the system should be installed in the fire control room. 3. The graphical display device of the fire control room shall perform the function of remote information transmission and remote query. There is no separate alarm linkage controller in practice. All of them are connected fire alarm controllers with linkage function. In the fire control room as shown in the figure, the fire alarm controller, the control device of fire emergency broadcast, the switchboard for fire fighting, and the graphic display device of the fire control room are all assembled in the fire control cabinet of the piano table type. III. Control center alarm system is generally suitable for building groups or large volume of protection objects. Usually there are the following situations: 1. The building complex may be equipped with two or more fire control rooms. 2. Products of different enterprises or different series of products of the same enterprise are used in the phased construction of the architectural complex, and multiple systems are networked in the phased construction. 3. In the large-scale system, due to the system capacity limit, multiple centralized control of the
  • 3. connected fire alarm controller is set. This is quite common. The design of the control center alarm system should not only meet the functions of the centralized control system. The following requirements should also be met: 1. When there are two or more fire control rooms, a main fire control room shall be determined. The main fire control room shall be able to display all fire alarm signals and linkage control status signals, and it shall be able to control important fire equipment. Fire fighting equipment in each fire control room can transmit and display status information to each other, but they should not control each other. 2. When there is only one fire control room with multiple centrally controlled fire alarm controllers, the master controller shall be set in the fire control room, which shall be able to display all fire alarm signals and linkage control status signals, and shall be able to control all linkage devices. The direct manual control device of the fire pump, smoke control and smoke exhaust fan and other important equipment should be set up in the fire control room together with the main controller.