Planning and Implementing Communications Systems in
Residential and Non-Residential Buildings
Dr. Abdelhay Ali
Lecture 5
Fire Alarm
System
2
References
Textbooks
1- Low Current Systems for Electrical Power Engineers by prof. Mahmoud Gilany
2- Light Current Systems Guide by Dr. Abd Almonem Shaban
3- Low-Current Systems Engineer'S Technical Handbook , A Guide to Design and
Supervision" by Habbieb Mansour.
Online classes at other schools
Light Current Course 2021 Level#3
3
Outline
1. More about sensors
2. Alarms
3. Modules
4. Fire Alarm Control Panel
5. Fire Alarm Repeater Panel
4
Outline
1. More about sensors
2. Alarms
3. Modules
4. Fire Alarm Control Panel
5. Fire Alarm Repeater Panel
5
More about sensors
6
More about sensors
7
More about sensors
8
More about sensors
9
More about sensors
10
More about sensors
11
Manual Break Glass
Also called the call points. Call PointIf a person sees the fire
before hearing the alarm, he presses the call unit so that the
siren goes off to warn of the presence of a fire.
More about sensors
12
Manual Break Glass
More about sensors
13
Manual Break Glass
Outline
1. More about sensors
2. Alarms
3. Modules
4. Fire Alarm Control Panel
5. Fire Alarm Repeater Panel
14
Alarms
15
An audible or light alarm was issued when a fire occurred in order to evacuate the area where the
fire appeared in preparation for extinguishing the fire. There are different types and methods of
alarms such as bells, sirens, flash lights and loudspeakers
A- Bells
B- siren
C- Flash or Strobe Light
D- Speaker
Optical warning devices are used, which give
intermittent light in high-noise places and places
where there are deaf people, as well as in hospitals as
an additional warning method.
Outline
1. More about sensors
2. Alarms
3. Modules
4. Fire Alarm Control Panel
5. Fire Alarm Repeater Panel
16
Modules
17
They are units that manage and control some operations such as the Control Module, Auto Dialer,
Door Holder, Monitor Module, and
A- Control Module
It is used to control stopping or starting some operations during a fire, as it transmits a signal from
the FACP main control panel to the device to be stopped or started during a fire, such as: -
- Turn off the elevators.
- Close some electrical panels
- Operating the Smoke Exhaust Fan
- Turn off the Fresh Air Fan because it helps to increase the fire
Modules
18
B- Monitor Module (M.M)
The Monitor Module is an addressable unit used to monitor unaddressed units and can be used
In addressing traditional systems to give it a title and thus can be combined in addressing systems
as shown in the following figure
Modules
19
C- Door Holder
It is placed behind the escape doors so that it works to hold the door after the first person opens it
when he escapes so as to ensure that the door is not answered or closed again in the faces of those
fleeing from the fire
Modules
20
D- Auto Dialer
It is a communication device that contains a set of numbers to call the fire, ambulance and
security services in the building.
Outline
1. More about sensors
2. Alarms
3. Modules
4. Fire Alarm Control Panel
5. Fire Alarm Repeater Panel
21
Fire Alarm Control Panel
22
The FACP controls the system, supplies it with the necessary voltage, and monitors its work, as
the signal from the detectors reaches it, and it operates the bells, sirens and indicator lights.
- It operates on a voltage of 220V-50Hz and is equipped with backup batteries that operate
automatically in the event of a power outage for a period of not less than 24 hours, and it has a
device that charges the batteries when the power returns.
- It is equipped with the possibility of self-testing and gives an audio warning signal in the event
of a failure in the panel or in any part of the system components, or in the event of a power
outage or disconnection of the batteries.
- Equipped with a key to give a general warning to evacuate the place.
- Manual control to check and stop devices, fire signals, turn off alarms, and restart the system
again.
- It can disable the closed door control system.
Fire Alarm Control Panel
23
- The FACP fire panel is placed in the security room, if any, or
the light current room, or in any visible place for easy detection
of the locationof the fire.
- It can disable the Fresh Air Fans, as well as the electric
elevatorsby giving a signal to the. Control Module
- The fire panel operates the Smoke Exhaust Fan as well as the
fire pumps
Fire Alarm Control Panel
24
Fire Alarm Control Panel
25
Types of FACP
A-Conventional type
B- Addressable type
C- Wireless Fire Alarm System
Fire Alarm Control Panel
26
A- conventional FACP
It is an early warning system against fire that depends on a group of reagents connected to each
other on a specific area (Radial System) and gives a warning on this area through which the security
men move in this area and detect the location of the fire.
- Detectors are connected to circuits, as well as alarm devices to other circuits, as shown in the
following figure, noting that the number of detectors in a single circuit, the zone, should not exceed
the number stipulated according to the manufacturer of fire panels. For example, the maximum
number of reagents in the 32 zones is a detector according to Cooper, and also up to 30 detectors,
according to Menvier.
- In the traditional control system, each group of conventional fire detectors is connected to a
separate electrical circuit called the Zone to monitor a specific area so that any detector from the
group sends a signal to the control panel to warn of a fire without specifying the number or address
of the detector that sensed the fire
Fire Alarm Control Panel
27
A- conventional FACP
Fire Alarm Control Panel
28
A- conventional FACP
This system is used in buildings and small establishments and is characterized by a
relatively lower cost. It is also used in less important areas because when a
malfunction occurs in one of the detectors, all the detectors after it are out of
service because it is an open loop (Open Loop).
-
Fire Alarm Control Panel
29
A- conventional FACP
-
Fire Alarm Control Panel
30
B- Addressable type
- This system depends in its work on connecting a group of detectors with each
other on a closed circuit (Closed Loop), so that each sensor or detector takes
the numbers and names of the places in which it is located. Addressed control
panel Knowing the location of the fire In contrast to the traditional control
panel, all alarms operate.
- Detectors and alarms, as well as monitoring and control units, can be
connected to the same Loop circuit so that it does not exceed the maximum
number of points in the circuit, which varies from one company to another and
may reach 200 devices in some companies -
Fire Alarm Control Panel
31
B- Addressable type
Fire Alarm Control Panel
32
B- Addressable type
Fire Alarm Control Panel
33
C- Wireless Fire Alarm System
It is an early warning system against a fire of the wireless type. It is used in the event that there are
no pipes and cables, as in the case of old buildings or ancient buildings, in which any cracking is
prohibited to lay cables or pipes, and it depends on a certain number of sensors.
Outline
1. More about sensors
2. Alarms
3. Modules
4. Fire Alarm Control Panel
5. Fire Alarm Repeater Panel
34
Fire Alarm Repeater Panel
35
This panel is used in the addressing system when there is a place far from the main panel and we
want to control the alarm system in this place or monitor it from close and this distance may reach
2000 m.
The Repeater Panel is placed in this place and linked to the main panel, thus dealing with the fire
alarm system in this area through the Repeater Panel, knowing that the main panel is aware of what
is happening, but not in detail.
Thanks
36

More Related Content

PDF
Pipeline leak detection system
PPT
Fire protection systems
PDF
Hazardous Area Classification in Oil & Gas Industry.pdf
PDF
Fire Alarm System.pdf
PDF
Basic Guide to NFPA 13 Occupancy and Commodity Classifications
PPTX
Fire and Gas Detection System_ - Simplified_Revised
PDF
Fire pumps in brief
PPT
Chapter 04
Pipeline leak detection system
Fire protection systems
Hazardous Area Classification in Oil & Gas Industry.pdf
Fire Alarm System.pdf
Basic Guide to NFPA 13 Occupancy and Commodity Classifications
Fire and Gas Detection System_ - Simplified_Revised
Fire pumps in brief
Chapter 04

What's hot (20)

PPTX
Fire, flame & smoke detectors
PPT
Sprinkler Spacing
PDF
Basics of Fire fighting
PPT
fire detection and alarm system
PPT
Fire Protection System Design
PPTX
Fire protection system...
PPS
PDF
Pneumatic system MCQ
PPTX
Time response analysis
PDF
Engineering Economy
PPT
Air Compressor
PPTX
Fire Protection Systems Unit-I
PPT
ACO-7 Emergency Aircraft Evacuation and Assistance
PDF
Control system Lab record
PPTX
Chapter 1 basic components of control system
PDF
Fire protection
PPTX
warehouse storage - commuduties classifications.pptx
PDF
Basics of hydraulics- أساسيات الهيدروليك
PDF
Construction equipment management chapter 3
PDF
Heat and smoke detectors
Fire, flame & smoke detectors
Sprinkler Spacing
Basics of Fire fighting
fire detection and alarm system
Fire Protection System Design
Fire protection system...
Pneumatic system MCQ
Time response analysis
Engineering Economy
Air Compressor
Fire Protection Systems Unit-I
ACO-7 Emergency Aircraft Evacuation and Assistance
Control system Lab record
Chapter 1 basic components of control system
Fire protection
warehouse storage - commuduties classifications.pptx
Basics of hydraulics- أساسيات الهيدروليك
Construction equipment management chapter 3
Heat and smoke detectors
Ad

Similar to Lecture 5 Fire Alarm System.pdf (20)

PDF
FIRE ALARM SYSTEM.pdf
PDF
Fire Alarm System for safety of electrical systems
PDF
cdocumentsandsettingsdeedesktopfda-1-090226130600-phpapp01 (2).pdf
PDF
FIRE DETECTION & ALARM SYSTEMS.pdf
PPTX
Basic Fire Detection and Alarm Systems.pptx
PPT
FIRE DETECTION & ALARM SYSTEM........ppt
PPT
Building Electronics (Fire Detection and Alarm System and CCTV)
PPT
Why are fire detection & alarm system is required in buildings?
PPTX
Fundamentals of Fire Alarm System
PDF
Addressable fire alarm system
PPTX
FIRE ALARM SYSTEM
DOCX
Em latest
PDF
FIRE DETECTION & ALARM SYSTEMS-1.Why are fire detection & alarm systems requi...
PPT
Burglar alarm basics-6
PPTX
Fire detectionand alarm systems 090512042400-phpapp01(1)
PPT
Fire and Gas Detection System : Part 1_The Field Devices and Its Panels
PDF
Fundamental training on Fire Detection & Alarm System
PPT
1-Operate Fire and Gas Detection System.ppt
PDF
Fire Alarm ... Design, Components, Applications
FIRE ALARM SYSTEM.pdf
Fire Alarm System for safety of electrical systems
cdocumentsandsettingsdeedesktopfda-1-090226130600-phpapp01 (2).pdf
FIRE DETECTION & ALARM SYSTEMS.pdf
Basic Fire Detection and Alarm Systems.pptx
FIRE DETECTION & ALARM SYSTEM........ppt
Building Electronics (Fire Detection and Alarm System and CCTV)
Why are fire detection & alarm system is required in buildings?
Fundamentals of Fire Alarm System
Addressable fire alarm system
FIRE ALARM SYSTEM
Em latest
FIRE DETECTION & ALARM SYSTEMS-1.Why are fire detection & alarm systems requi...
Burglar alarm basics-6
Fire detectionand alarm systems 090512042400-phpapp01(1)
Fire and Gas Detection System : Part 1_The Field Devices and Its Panels
Fundamental training on Fire Detection & Alarm System
1-Operate Fire and Gas Detection System.ppt
Fire Alarm ... Design, Components, Applications
Ad

Recently uploaded (20)

PDF
null (2) bgfbg bfgb bfgb fbfg bfbgf b.pdf
PPTX
Internet of Things (IOT) - A guide to understanding
PDF
PPT on Performance Review to get promotions
PPT
Introduction, IoT Design Methodology, Case Study on IoT System for Weather Mo...
PDF
Automation-in-Manufacturing-Chapter-Introduction.pdf
PDF
BMEC211 - INTRODUCTION TO MECHATRONICS-1.pdf
PDF
Embodied AI: Ushering in the Next Era of Intelligent Systems
PDF
The CXO Playbook 2025 – Future-Ready Strategies for C-Suite Leaders Cerebrai...
PDF
Well-logging-methods_new................
PPT
Project quality management in manufacturing
PPTX
Current and future trends in Computer Vision.pptx
PDF
BIO-INSPIRED HORMONAL MODULATION AND ADAPTIVE ORCHESTRATION IN S-AI-GPT
PPTX
Infosys Presentation by1.Riyan Bagwan 2.Samadhan Naiknavare 3.Gaurav Shinde 4...
PDF
Categorization of Factors Affecting Classification Algorithms Selection
PDF
PREDICTION OF DIABETES FROM ELECTRONIC HEALTH RECORDS
PPTX
UNIT-1 - COAL BASED THERMAL POWER PLANTS
PPTX
CYBER-CRIMES AND SECURITY A guide to understanding
PPTX
Fundamentals of Mechanical Engineering.pptx
PDF
Mitigating Risks through Effective Management for Enhancing Organizational Pe...
DOCX
573137875-Attendance-Management-System-original
null (2) bgfbg bfgb bfgb fbfg bfbgf b.pdf
Internet of Things (IOT) - A guide to understanding
PPT on Performance Review to get promotions
Introduction, IoT Design Methodology, Case Study on IoT System for Weather Mo...
Automation-in-Manufacturing-Chapter-Introduction.pdf
BMEC211 - INTRODUCTION TO MECHATRONICS-1.pdf
Embodied AI: Ushering in the Next Era of Intelligent Systems
The CXO Playbook 2025 – Future-Ready Strategies for C-Suite Leaders Cerebrai...
Well-logging-methods_new................
Project quality management in manufacturing
Current and future trends in Computer Vision.pptx
BIO-INSPIRED HORMONAL MODULATION AND ADAPTIVE ORCHESTRATION IN S-AI-GPT
Infosys Presentation by1.Riyan Bagwan 2.Samadhan Naiknavare 3.Gaurav Shinde 4...
Categorization of Factors Affecting Classification Algorithms Selection
PREDICTION OF DIABETES FROM ELECTRONIC HEALTH RECORDS
UNIT-1 - COAL BASED THERMAL POWER PLANTS
CYBER-CRIMES AND SECURITY A guide to understanding
Fundamentals of Mechanical Engineering.pptx
Mitigating Risks through Effective Management for Enhancing Organizational Pe...
573137875-Attendance-Management-System-original

Lecture 5 Fire Alarm System.pdf

  • 1. Planning and Implementing Communications Systems in Residential and Non-Residential Buildings Dr. Abdelhay Ali
  • 3. References Textbooks 1- Low Current Systems for Electrical Power Engineers by prof. Mahmoud Gilany 2- Light Current Systems Guide by Dr. Abd Almonem Shaban 3- Low-Current Systems Engineer'S Technical Handbook , A Guide to Design and Supervision" by Habbieb Mansour. Online classes at other schools Light Current Course 2021 Level#3 3
  • 4. Outline 1. More about sensors 2. Alarms 3. Modules 4. Fire Alarm Control Panel 5. Fire Alarm Repeater Panel 4
  • 5. Outline 1. More about sensors 2. Alarms 3. Modules 4. Fire Alarm Control Panel 5. Fire Alarm Repeater Panel 5
  • 11. More about sensors 11 Manual Break Glass Also called the call points. Call PointIf a person sees the fire before hearing the alarm, he presses the call unit so that the siren goes off to warn of the presence of a fire.
  • 14. Outline 1. More about sensors 2. Alarms 3. Modules 4. Fire Alarm Control Panel 5. Fire Alarm Repeater Panel 14
  • 15. Alarms 15 An audible or light alarm was issued when a fire occurred in order to evacuate the area where the fire appeared in preparation for extinguishing the fire. There are different types and methods of alarms such as bells, sirens, flash lights and loudspeakers A- Bells B- siren C- Flash or Strobe Light D- Speaker Optical warning devices are used, which give intermittent light in high-noise places and places where there are deaf people, as well as in hospitals as an additional warning method.
  • 16. Outline 1. More about sensors 2. Alarms 3. Modules 4. Fire Alarm Control Panel 5. Fire Alarm Repeater Panel 16
  • 17. Modules 17 They are units that manage and control some operations such as the Control Module, Auto Dialer, Door Holder, Monitor Module, and A- Control Module It is used to control stopping or starting some operations during a fire, as it transmits a signal from the FACP main control panel to the device to be stopped or started during a fire, such as: - - Turn off the elevators. - Close some electrical panels - Operating the Smoke Exhaust Fan - Turn off the Fresh Air Fan because it helps to increase the fire
  • 18. Modules 18 B- Monitor Module (M.M) The Monitor Module is an addressable unit used to monitor unaddressed units and can be used In addressing traditional systems to give it a title and thus can be combined in addressing systems as shown in the following figure
  • 19. Modules 19 C- Door Holder It is placed behind the escape doors so that it works to hold the door after the first person opens it when he escapes so as to ensure that the door is not answered or closed again in the faces of those fleeing from the fire
  • 20. Modules 20 D- Auto Dialer It is a communication device that contains a set of numbers to call the fire, ambulance and security services in the building.
  • 21. Outline 1. More about sensors 2. Alarms 3. Modules 4. Fire Alarm Control Panel 5. Fire Alarm Repeater Panel 21
  • 22. Fire Alarm Control Panel 22 The FACP controls the system, supplies it with the necessary voltage, and monitors its work, as the signal from the detectors reaches it, and it operates the bells, sirens and indicator lights. - It operates on a voltage of 220V-50Hz and is equipped with backup batteries that operate automatically in the event of a power outage for a period of not less than 24 hours, and it has a device that charges the batteries when the power returns. - It is equipped with the possibility of self-testing and gives an audio warning signal in the event of a failure in the panel or in any part of the system components, or in the event of a power outage or disconnection of the batteries. - Equipped with a key to give a general warning to evacuate the place. - Manual control to check and stop devices, fire signals, turn off alarms, and restart the system again. - It can disable the closed door control system.
  • 23. Fire Alarm Control Panel 23 - The FACP fire panel is placed in the security room, if any, or the light current room, or in any visible place for easy detection of the locationof the fire. - It can disable the Fresh Air Fans, as well as the electric elevatorsby giving a signal to the. Control Module - The fire panel operates the Smoke Exhaust Fan as well as the fire pumps
  • 24. Fire Alarm Control Panel 24
  • 25. Fire Alarm Control Panel 25 Types of FACP A-Conventional type B- Addressable type C- Wireless Fire Alarm System
  • 26. Fire Alarm Control Panel 26 A- conventional FACP It is an early warning system against fire that depends on a group of reagents connected to each other on a specific area (Radial System) and gives a warning on this area through which the security men move in this area and detect the location of the fire. - Detectors are connected to circuits, as well as alarm devices to other circuits, as shown in the following figure, noting that the number of detectors in a single circuit, the zone, should not exceed the number stipulated according to the manufacturer of fire panels. For example, the maximum number of reagents in the 32 zones is a detector according to Cooper, and also up to 30 detectors, according to Menvier. - In the traditional control system, each group of conventional fire detectors is connected to a separate electrical circuit called the Zone to monitor a specific area so that any detector from the group sends a signal to the control panel to warn of a fire without specifying the number or address of the detector that sensed the fire
  • 27. Fire Alarm Control Panel 27 A- conventional FACP
  • 28. Fire Alarm Control Panel 28 A- conventional FACP This system is used in buildings and small establishments and is characterized by a relatively lower cost. It is also used in less important areas because when a malfunction occurs in one of the detectors, all the detectors after it are out of service because it is an open loop (Open Loop). -
  • 29. Fire Alarm Control Panel 29 A- conventional FACP -
  • 30. Fire Alarm Control Panel 30 B- Addressable type - This system depends in its work on connecting a group of detectors with each other on a closed circuit (Closed Loop), so that each sensor or detector takes the numbers and names of the places in which it is located. Addressed control panel Knowing the location of the fire In contrast to the traditional control panel, all alarms operate. - Detectors and alarms, as well as monitoring and control units, can be connected to the same Loop circuit so that it does not exceed the maximum number of points in the circuit, which varies from one company to another and may reach 200 devices in some companies -
  • 31. Fire Alarm Control Panel 31 B- Addressable type
  • 32. Fire Alarm Control Panel 32 B- Addressable type
  • 33. Fire Alarm Control Panel 33 C- Wireless Fire Alarm System It is an early warning system against a fire of the wireless type. It is used in the event that there are no pipes and cables, as in the case of old buildings or ancient buildings, in which any cracking is prohibited to lay cables or pipes, and it depends on a certain number of sensors.
  • 34. Outline 1. More about sensors 2. Alarms 3. Modules 4. Fire Alarm Control Panel 5. Fire Alarm Repeater Panel 34
  • 35. Fire Alarm Repeater Panel 35 This panel is used in the addressing system when there is a place far from the main panel and we want to control the alarm system in this place or monitor it from close and this distance may reach 2000 m. The Repeater Panel is placed in this place and linked to the main panel, thus dealing with the fire alarm system in this area through the Repeater Panel, knowing that the main panel is aware of what is happening, but not in detail.