SlideShare a Scribd company logo
1-Operate Fire and Gas Detection System.ppt
Fire And Gas
Detection System
(FGDS)
Presentation Objective
And Contents
• This presentation is implemented to provide the necessary
general information for ELNG fire and gas detection system.
• It highlight &clarify the following points:
 purpose of the FGDS system.
 layout and description of all system devices.
 operational perimeters.
Purpose Of the FGD System
• The overall goal of “Fire and Gas Detection System” is to
warn against the presence of flammable liquid spills, flammable
or toxic gas releases, and/or fires in Buildings or in the plant.
This detection will accomplish the following:
 Provide warning to personnel at the Control Building, Fire Station and locally
as deemed necessary.
 Provide a specific hazard location for operations and emergency response
personnel.
 Provide a possible indication as to the extent of the problems.
Monitoring
• FGDS System is monitored by:
 Fire and Gas Control Panel “Notifier
Panel" which located in: Main control room,
Fire Station, Compressor Substations,
Storage/Loading Substation Propane
Substations, Main Switchgear Building, and
Marine Terminal Building.
 Building Fire and Gas Panel local inputs located in
administration building, CCC building, warehouse
,maintenance building, marine terminal building
“MTB”, plant buildings, fire station and main control
room ”MCR”.
 Human Monitoring Interface ”HMI” located in Main Control Room
“MCR” and in Fire Station .
Building
FAP
Area Fire
Alarm Panel
(Addressable)
System Highlights:
• Gas detection and machine controls are Allen Bradley PLC 5 and SLC500 PLC (Redundant Processors)
• Fire Alarm is Notifier NFS-640 Addressable Fire Alarm Panels with Noti-Fire-Net
• Local HMI Equipment is Allen Bradley Panelview Plus 700 Color Touch-screen Industrial Terminal
• Detection devices include Point IR, Open Path IR, RTD, UV/IR and IR/IR
CENTRAL CONTROL ROOM FIRE STATION
F/O Link
HMI
• Central HMI is Allen Bradley RSView32. System status sent via Modbus to DCS System
Dual
Processor
PLC
Local
HMI
Building
FAP
Area Fire
Alarm Panel
(Addressable)
Dual
Processor
PLC
Local
HMI
Building
FAP
Area Fire
Alarm Panel
(Addressable)
Dual
Processor
PLC
Local
HMI
Building
FAP
Area Fire
Alarm Panel
(Addressable)
Dual
Processor
PLC
Modbus
DCS
Dual
Processor
PLC
Central Station
Fire Alarm
Panel
HMI
LAN
Redundant F/O DH+
Redundant F/O Noti-Fire-Net
LNG Storage Area Marine Terminal Propane Area Substa Compression Substa
Local
HMI
Central Station
Fire Alarm
Panel
FGDS Component
• The F&G Detection System incorporate four main
systems:
 Fire Detection And Alarm Systems.
 Gas Detection And Alarm Systems.
 Low Temperature Spill System.
 Emergency Warning System.
Fire&Gas Detection And Alarm System
• F&G detection devices distributed in all buildings
and allover the plant.
 The Buildings : Smoke Detectors, Heat Detectors ,Gas Detectors and
Manual call points.
 The Plant : UV&IR Flame Detectors, Open Path Gas Detectors, Point Gas
Detectors, Combustible Gas Detectors , Leak Detectors and Manual call points.
Building Fire Detection And Alarm
System
• Buildings designed with due considerations for
the requirements of NFPA 101, “Life Safety
Code”.
• All buildings provided with low flame spread
interior finish , non-combustible furnishings and
safety features in accordance with NFPA 101.
taking into account API RP 752 “Management
of Hazards Associated with Location of Process
Plant Buildings” provisions.
• Each building has its own fire detection & alarm system,
and fire and gas alarm panel for annunciation of alarms by
the building smoke, gas and/or heat detectors.
Smoke Detectors
• Two types of smoke detectors used:
A- Ionized Gases Detectors (Invisible Products Of
Combustion).
• B- Visible-Products – Of – Composition
Heat Detectors
• These devices sense over heating inside certain rooms in
the building.
Gas Detectors
• These detectors located in the entrance dumber of
HVAC and Lab. Room.
The Plant Fire&Gas Detection And
Alarm System
• The Fire Alarm and Gas Detection Systems are independent
and fully segregated from other systems. The F&G system
contain interfaces with the Process DCS system for alarm
display. The F&G system also perform in conjunction with the
Fire Suppression System and the various Building Fire
Detection Systems.
• Automatic fire and gas detection devices installed at strategic
locations in the plant to monitor hazardous conditions and
events. In addition, manual call points strategically located
throughout the plant .
UV/IR Flame Detectors
• FL 3100 flame detector monitors in both UV&IR spectral
range reducing possibility of false alarms caused by
lightening ,arc welding and hot objects.
• Typical response time < 3sec. @50ft
• 120O
maximum horizontal field of view.
• -40
o
c to +85
o
c operating temperature.
• COPM ( Continuous Optical Path Monitoring), the optical path is self checked
once every minute on both the UV&IR sides to make sure the windows are not
dirty, and that the test sources and detectors are working properly.
FL3100 Field of View (Horizontal)
15°
HORIZONTAL
SENSITIVITY
HORIZONTAL
(±5°)
0°
50%
75%
100%
±60°
±30°
±45°
±15°
60°
45°
10'
15'
40'
35'
30'
25'
20'
30°
15° 50'
45'
0°
25'
50'
50'
50'
50'
30'
<20'
25'
50'
50'
50'
<5'
15'
<5'
<5'
75%
TABLE CHART
100% 50%
60°
45°
30°
+45°
+60°
SENSITIVITY
75%
100%
50%
FL3100 Field of View (Vertical)
HORIZONTAL
SENSITIVITY
HORIZONTAL
0°
50%
75%
100%
±60°
±30°
±45°
±15°
25'
50'
50'
50'
50'
30'
<20'
25'
50'
50'
50'
<5'
15'
<5'
<5'
75%
100% 50%
-45°
-30°
-15°
-60°
0°
50'
+15°
40'
45'
35'
+30°
+45°
25'
30'
20'
10'
15'
+60°
VERTICAL
TABLE CHART
100%
75%
50%
(±5°)
SENSITIVITY
±60° 20'
VERTICAL
±45°
±30°
±15°
0°
50'
50'
50'
50'
100%
<20' <20'
30'
50'
50'
50'
<20'
25'
25'
25'
75% 50%
75%
100%
50%
Open Path Gas Detectors
• IR 5000 is an open path gas detectors using a single IR
beam technology and has an auto zero and auto track
alignment .
• Measurement depends on the length and the size of the gas cloud.
concentration x Length = measurement
This detector is a dual range one: 0-5 LEL*meter and 0-5000ppm*meter
• Detect very small leaks with 0-5000ppm range before they become major
problems.
• The 0-5LEL*meter range alerts that there is a major leak somewhere between
the source and detector
IR Open Path Gas Detector Alarm
Indications on HMI
IR Point Gas Detectors
• IR2100 is an IR point gas detector which several dozen
gases and vapors can be detected.
• 0-100LEL
• Whenever anything fails the IR2100 will go into the fault
mode.
Combustible gas detector
• IR000S is a Combustible gas
detector , hydrocarbon gas
highly reliable, self-contained,
microprocessor-controlled
monitor with integral 3 digit
readout. It is designed to
measure and display
concentrations of combustible
gases in the range 0-100%
LEL, but will continue to
display concentrations up to
120% LEL.
IR Point Gas Detectors and
Combustible gas detector Alarm
Indications on HMI
Leak Gas Detector
(low temp. spill detector)
• These detectors detect spillage
of cryogenic liquid by
detecting decreasing in
surrounded temperature.
Heat Detectors
• When tank pressure getting
high and over PSV’S set point
the PSV’s open to
atmosphere, LNG Vapor
Released and may fire
happened due to Electrical
Static charge on the PSV’s
Stacks. Heat detector which
placed on the PSV’s Stacks
Send Signal to the Solenoid
on the Nitrogen Cylinder to
initiate the Dry Chemical
Powder System to
Extinguishing the Fire.
Detectors location
1-Operate Fire and Gas Detection System.ppt
1-Operate Fire and Gas Detection System.ppt
1-Operate Fire and Gas Detection System.ppt
1-Operate Fire and Gas Detection System.ppt
1-Operate Fire and Gas Detection System.ppt
1-Operate Fire and Gas Detection System.ppt
1-Operate Fire and Gas Detection System.ppt
1-Operate Fire and Gas Detection System.ppt
1-Operate Fire and Gas Detection System.ppt
Emergency warning and evacuation
system
• A plant-wide alarm annunciation system for separate and distinctive
alarming of fire, and accidental release/spill incidents. The plant-
wide alarm system consists of interchangeable alarm tone generating
devices and field-mounted horns suitable for the classified areas.
• Process area strobe lights suitable for classified areas provided in
high noise areas for alarming purposes.
• The standard alarm devices for building interiors of non-hazardous
occupancies is a combination of horn/strobe light.
• Manual call points MAC's located along the periphery roads
around process train and utility area, and LNG storage area with
a travel distance of maximum 60 m. At LNG loading jetty,
MAC’s shall also be located on the trestle at a maximum
distance of 60 m from the jetty head and at a strategic points on
the jetty head (if applicable).
• MAC’s are pull handle type
and suitable for installation in
hazardous area when installed
outside of building.
Emergency Response
• In case of any emergency situation, the emergency alarm
will be activated.
• Head to the nearest muster point In the Upwind direction.
•Report your self to the muster point checker
• Wait for further instructions.
1-Operate Fire and Gas Detection System.ppt
Emergency muster points
Wind socks
• Wind socks distributed all over the site in high and
visible locations
• Wind socks are very useful especially in emergency
situation. During evacuation all persons should
observe wind socks to head to the safest muster
point. (upwind)
• Emergency response team using wind socks for
expecting gas leak and fire spread direction.
1-Operate Fire and Gas Detection System.ppt
Emergency contact No.
IDKU Duty Manager:
0127477123
0104999854
(Emergency phone at fire station)
2222
Control room
2223, 2225
Thank you for your attention

More Related Content

PPT
Fire and Gas Detection System : Part 1_The Field Devices and Its Panels
PPT
Fire and Gas Detection System : Part 3_Technical Features, Locating Detectors...
PPT
F&G 04.07.2007.ppt
PPTX
Gas sensor Presentation to PVE eeeeeeeeeeee
PPTX
FDA-Fire detection and alarm system
PPT
Building Electronics (Fire Detection and Alarm System and CCTV)
PDF
cdocumentsandsettingsdeedesktopfda-1-090226130600-phpapp01 (2).pdf
PPT
fire detection and alarm system
Fire and Gas Detection System : Part 1_The Field Devices and Its Panels
Fire and Gas Detection System : Part 3_Technical Features, Locating Detectors...
F&G 04.07.2007.ppt
Gas sensor Presentation to PVE eeeeeeeeeeee
FDA-Fire detection and alarm system
Building Electronics (Fire Detection and Alarm System and CCTV)
cdocumentsandsettingsdeedesktopfda-1-090226130600-phpapp01 (2).pdf
fire detection and alarm system

Similar to 1-Operate Fire and Gas Detection System.ppt (20)

PPT
FIRE DETECTION & ALARM SYSTEM........ppt
PPTX
Introduction-to-ISA-TR84.00.07.pptx fantastic book for reference about isa
PPT
Fire and Gas Detection System : Part 2_Block Diagram_Philosophy, Signal Types...
PPTX
Fire Detection and Alarm System (FDAS).pptx
PPTX
Fire Detection and Alarm Systems
PDF
FIRE DETECTION & ALARM SYSTEMS-1.Why are fire detection & alarm systems requi...
PPTX
Fire and Gas Detection System_ - Simplified_Revised
PPTX
Fundamentals of Fire Alarm System
PPT
Net Safety Monitoring Flame & Gas Detection
PPTX
CHAPTER 17- EXPOSICIÓN INGLES.pptx
PPTX
Introduction to FIRElink.pptx
PPT
Fire alarm systems
PPT
Why are fire detection & alarm system is required in buildings?
DOCX
Honeywell XionUltra-040-FLWT Multi-Spectrum Flame Detector
PPTX
Overview of Fire Alarm Systems.pptx
PDF
Fire Alarm System.pdf
PDF
FIRE ALARM SYSTEM.pdf
PDF
Fire Alarm System for safety of electrical systems
PPTX
Fire detection and alarm system
PPTX
Fire detection and alarm system
FIRE DETECTION & ALARM SYSTEM........ppt
Introduction-to-ISA-TR84.00.07.pptx fantastic book for reference about isa
Fire and Gas Detection System : Part 2_Block Diagram_Philosophy, Signal Types...
Fire Detection and Alarm System (FDAS).pptx
Fire Detection and Alarm Systems
FIRE DETECTION & ALARM SYSTEMS-1.Why are fire detection & alarm systems requi...
Fire and Gas Detection System_ - Simplified_Revised
Fundamentals of Fire Alarm System
Net Safety Monitoring Flame & Gas Detection
CHAPTER 17- EXPOSICIÓN INGLES.pptx
Introduction to FIRElink.pptx
Fire alarm systems
Why are fire detection & alarm system is required in buildings?
Honeywell XionUltra-040-FLWT Multi-Spectrum Flame Detector
Overview of Fire Alarm Systems.pptx
Fire Alarm System.pdf
FIRE ALARM SYSTEM.pdf
Fire Alarm System for safety of electrical systems
Fire detection and alarm system
Fire detection and alarm system
Ad

Recently uploaded (20)

PPTX
Geodesy 1.pptx...............................................
PPTX
Current and future trends in Computer Vision.pptx
PPTX
Lecture Notes Electrical Wiring System Components
PPTX
Artificial Intelligence
PPTX
bas. eng. economics group 4 presentation 1.pptx
PPTX
CH1 Production IntroductoryConcepts.pptx
PPTX
Construction Project Organization Group 2.pptx
DOCX
ASol_English-Language-Literature-Set-1-27-02-2023-converted.docx
PDF
Automation-in-Manufacturing-Chapter-Introduction.pdf
PDF
SM_6th-Sem__Cse_Internet-of-Things.pdf IOT
PPTX
OOP with Java - Java Introduction (Basics)
PPT
Mechanical Engineering MATERIALS Selection
PDF
Evaluating the Democratization of the Turkish Armed Forces from a Normative P...
PPTX
MET 305 2019 SCHEME MODULE 2 COMPLETE.pptx
PPTX
CARTOGRAPHY AND GEOINFORMATION VISUALIZATION chapter1 NPTE (2).pptx
PDF
PPT on Performance Review to get promotions
PPTX
UNIT-1 - COAL BASED THERMAL POWER PLANTS
PDF
Mitigating Risks through Effective Management for Enhancing Organizational Pe...
PDF
PRIZ Academy - 9 Windows Thinking Where to Invest Today to Win Tomorrow.pdf
PPTX
Sustainable Sites - Green Building Construction
Geodesy 1.pptx...............................................
Current and future trends in Computer Vision.pptx
Lecture Notes Electrical Wiring System Components
Artificial Intelligence
bas. eng. economics group 4 presentation 1.pptx
CH1 Production IntroductoryConcepts.pptx
Construction Project Organization Group 2.pptx
ASol_English-Language-Literature-Set-1-27-02-2023-converted.docx
Automation-in-Manufacturing-Chapter-Introduction.pdf
SM_6th-Sem__Cse_Internet-of-Things.pdf IOT
OOP with Java - Java Introduction (Basics)
Mechanical Engineering MATERIALS Selection
Evaluating the Democratization of the Turkish Armed Forces from a Normative P...
MET 305 2019 SCHEME MODULE 2 COMPLETE.pptx
CARTOGRAPHY AND GEOINFORMATION VISUALIZATION chapter1 NPTE (2).pptx
PPT on Performance Review to get promotions
UNIT-1 - COAL BASED THERMAL POWER PLANTS
Mitigating Risks through Effective Management for Enhancing Organizational Pe...
PRIZ Academy - 9 Windows Thinking Where to Invest Today to Win Tomorrow.pdf
Sustainable Sites - Green Building Construction
Ad

1-Operate Fire and Gas Detection System.ppt

  • 2. Fire And Gas Detection System (FGDS)
  • 3. Presentation Objective And Contents • This presentation is implemented to provide the necessary general information for ELNG fire and gas detection system. • It highlight &clarify the following points:  purpose of the FGDS system.  layout and description of all system devices.  operational perimeters.
  • 4. Purpose Of the FGD System • The overall goal of “Fire and Gas Detection System” is to warn against the presence of flammable liquid spills, flammable or toxic gas releases, and/or fires in Buildings or in the plant. This detection will accomplish the following:  Provide warning to personnel at the Control Building, Fire Station and locally as deemed necessary.  Provide a specific hazard location for operations and emergency response personnel.  Provide a possible indication as to the extent of the problems.
  • 5. Monitoring • FGDS System is monitored by:  Fire and Gas Control Panel “Notifier Panel" which located in: Main control room, Fire Station, Compressor Substations, Storage/Loading Substation Propane Substations, Main Switchgear Building, and Marine Terminal Building.
  • 6.  Building Fire and Gas Panel local inputs located in administration building, CCC building, warehouse ,maintenance building, marine terminal building “MTB”, plant buildings, fire station and main control room ”MCR”.
  • 7.  Human Monitoring Interface ”HMI” located in Main Control Room “MCR” and in Fire Station .
  • 8. Building FAP Area Fire Alarm Panel (Addressable) System Highlights: • Gas detection and machine controls are Allen Bradley PLC 5 and SLC500 PLC (Redundant Processors) • Fire Alarm is Notifier NFS-640 Addressable Fire Alarm Panels with Noti-Fire-Net • Local HMI Equipment is Allen Bradley Panelview Plus 700 Color Touch-screen Industrial Terminal • Detection devices include Point IR, Open Path IR, RTD, UV/IR and IR/IR CENTRAL CONTROL ROOM FIRE STATION F/O Link HMI • Central HMI is Allen Bradley RSView32. System status sent via Modbus to DCS System Dual Processor PLC Local HMI Building FAP Area Fire Alarm Panel (Addressable) Dual Processor PLC Local HMI Building FAP Area Fire Alarm Panel (Addressable) Dual Processor PLC Local HMI Building FAP Area Fire Alarm Panel (Addressable) Dual Processor PLC Modbus DCS Dual Processor PLC Central Station Fire Alarm Panel HMI LAN Redundant F/O DH+ Redundant F/O Noti-Fire-Net LNG Storage Area Marine Terminal Propane Area Substa Compression Substa Local HMI Central Station Fire Alarm Panel
  • 9. FGDS Component • The F&G Detection System incorporate four main systems:  Fire Detection And Alarm Systems.  Gas Detection And Alarm Systems.  Low Temperature Spill System.  Emergency Warning System.
  • 10. Fire&Gas Detection And Alarm System • F&G detection devices distributed in all buildings and allover the plant.  The Buildings : Smoke Detectors, Heat Detectors ,Gas Detectors and Manual call points.  The Plant : UV&IR Flame Detectors, Open Path Gas Detectors, Point Gas Detectors, Combustible Gas Detectors , Leak Detectors and Manual call points.
  • 11. Building Fire Detection And Alarm System • Buildings designed with due considerations for the requirements of NFPA 101, “Life Safety Code”. • All buildings provided with low flame spread interior finish , non-combustible furnishings and safety features in accordance with NFPA 101. taking into account API RP 752 “Management of Hazards Associated with Location of Process Plant Buildings” provisions.
  • 12. • Each building has its own fire detection & alarm system, and fire and gas alarm panel for annunciation of alarms by the building smoke, gas and/or heat detectors.
  • 13. Smoke Detectors • Two types of smoke detectors used: A- Ionized Gases Detectors (Invisible Products Of Combustion).
  • 14. • B- Visible-Products – Of – Composition
  • 15. Heat Detectors • These devices sense over heating inside certain rooms in the building.
  • 16. Gas Detectors • These detectors located in the entrance dumber of HVAC and Lab. Room.
  • 17. The Plant Fire&Gas Detection And Alarm System • The Fire Alarm and Gas Detection Systems are independent and fully segregated from other systems. The F&G system contain interfaces with the Process DCS system for alarm display. The F&G system also perform in conjunction with the Fire Suppression System and the various Building Fire Detection Systems. • Automatic fire and gas detection devices installed at strategic locations in the plant to monitor hazardous conditions and events. In addition, manual call points strategically located throughout the plant .
  • 18. UV/IR Flame Detectors • FL 3100 flame detector monitors in both UV&IR spectral range reducing possibility of false alarms caused by lightening ,arc welding and hot objects. • Typical response time < 3sec. @50ft • 120O maximum horizontal field of view. • -40 o c to +85 o c operating temperature. • COPM ( Continuous Optical Path Monitoring), the optical path is self checked once every minute on both the UV&IR sides to make sure the windows are not dirty, and that the test sources and detectors are working properly.
  • 19. FL3100 Field of View (Horizontal) 15° HORIZONTAL SENSITIVITY HORIZONTAL (±5°) 0° 50% 75% 100% ±60° ±30° ±45° ±15° 60° 45° 10' 15' 40' 35' 30' 25' 20' 30° 15° 50' 45' 0° 25' 50' 50' 50' 50' 30' <20' 25' 50' 50' 50' <5' 15' <5' <5' 75% TABLE CHART 100% 50% 60° 45° 30° +45° +60° SENSITIVITY 75% 100% 50%
  • 20. FL3100 Field of View (Vertical) HORIZONTAL SENSITIVITY HORIZONTAL 0° 50% 75% 100% ±60° ±30° ±45° ±15° 25' 50' 50' 50' 50' 30' <20' 25' 50' 50' 50' <5' 15' <5' <5' 75% 100% 50% -45° -30° -15° -60° 0° 50' +15° 40' 45' 35' +30° +45° 25' 30' 20' 10' 15' +60° VERTICAL TABLE CHART 100% 75% 50% (±5°) SENSITIVITY ±60° 20' VERTICAL ±45° ±30° ±15° 0° 50' 50' 50' 50' 100% <20' <20' 30' 50' 50' 50' <20' 25' 25' 25' 75% 50% 75% 100% 50%
  • 21. Open Path Gas Detectors • IR 5000 is an open path gas detectors using a single IR beam technology and has an auto zero and auto track alignment . • Measurement depends on the length and the size of the gas cloud. concentration x Length = measurement This detector is a dual range one: 0-5 LEL*meter and 0-5000ppm*meter • Detect very small leaks with 0-5000ppm range before they become major problems.
  • 22. • The 0-5LEL*meter range alerts that there is a major leak somewhere between the source and detector
  • 23. IR Open Path Gas Detector Alarm Indications on HMI
  • 24. IR Point Gas Detectors • IR2100 is an IR point gas detector which several dozen gases and vapors can be detected. • 0-100LEL • Whenever anything fails the IR2100 will go into the fault mode.
  • 25. Combustible gas detector • IR000S is a Combustible gas detector , hydrocarbon gas highly reliable, self-contained, microprocessor-controlled monitor with integral 3 digit readout. It is designed to measure and display concentrations of combustible gases in the range 0-100% LEL, but will continue to display concentrations up to 120% LEL.
  • 26. IR Point Gas Detectors and Combustible gas detector Alarm Indications on HMI
  • 27. Leak Gas Detector (low temp. spill detector) • These detectors detect spillage of cryogenic liquid by detecting decreasing in surrounded temperature.
  • 28. Heat Detectors • When tank pressure getting high and over PSV’S set point the PSV’s open to atmosphere, LNG Vapor Released and may fire happened due to Electrical Static charge on the PSV’s Stacks. Heat detector which placed on the PSV’s Stacks Send Signal to the Solenoid on the Nitrogen Cylinder to initiate the Dry Chemical Powder System to Extinguishing the Fire.
  • 39. Emergency warning and evacuation system • A plant-wide alarm annunciation system for separate and distinctive alarming of fire, and accidental release/spill incidents. The plant- wide alarm system consists of interchangeable alarm tone generating devices and field-mounted horns suitable for the classified areas. • Process area strobe lights suitable for classified areas provided in high noise areas for alarming purposes. • The standard alarm devices for building interiors of non-hazardous occupancies is a combination of horn/strobe light.
  • 40. • Manual call points MAC's located along the periphery roads around process train and utility area, and LNG storage area with a travel distance of maximum 60 m. At LNG loading jetty, MAC’s shall also be located on the trestle at a maximum distance of 60 m from the jetty head and at a strategic points on the jetty head (if applicable).
  • 41. • MAC’s are pull handle type and suitable for installation in hazardous area when installed outside of building.
  • 42. Emergency Response • In case of any emergency situation, the emergency alarm will be activated. • Head to the nearest muster point In the Upwind direction. •Report your self to the muster point checker • Wait for further instructions.
  • 45. Wind socks • Wind socks distributed all over the site in high and visible locations • Wind socks are very useful especially in emergency situation. During evacuation all persons should observe wind socks to head to the safest muster point. (upwind) • Emergency response team using wind socks for expecting gas leak and fire spread direction.
  • 47. Emergency contact No. IDKU Duty Manager: 0127477123 0104999854 (Emergency phone at fire station) 2222 Control room 2223, 2225
  • 48. Thank you for your attention