Fire and Gas Detection System
(Offshore Facilities)
(Part 1 : The Field Devices and Its Panels)
Chun Chet Gan (Ir.)
MSc Operations Management
[Manchester School Management]
University of Manchester Institute of Science and Technology (UMIST),
United Kingdom.
BEng (Hons) Mechanical Engineering
[Simon Building]
University of Manchester, United Kingdom
The Purpose of Fire and Gas Detection
• The purpose of Fire and Gas Detection System, with the detectors located at
outdoor and indoor areas of the platform, is to protect the platform from a gas leak
or a fire. These areas are segregated into two (2) areas:-
1) outdoor, and
2) indoor areas.
• Outdoor areas are zoned into hazard open process or non hazard utility areas.
• Enclosed rooms are indoor areas (inside a closed structure or a building).
The Detection Area – Outdoor and Indoor
• In general, process areas (outdoor) are highly hazardous. It contains hydrocarbon
inventories and these areas are regarded as hazard areas on the platform. The
classification of these hazardous areas are defined by Safety.
- Hazard equipment are vessels, pumps, hydrocarbon pipelines, turbine generators,
etc.
• Utilities areas (are considered as outdoor areas) are non-hazardous zones of a
platform.
- Example of equipment in these areas are firewater pumps, diesel tanks, instrument
air compressors.
- Others equipment like water storage tank, sewage macerator, etc. are also
regarded as non-hazardous area.
• Indoor areas are safe areas on the platform.
• Example of these areas are:
- Control Room,
- Switchgear Room,
- Motor Control Centre MCC
• However, battery rooms are hazardous areas.
Fire and Gas Detection System in Two Parts
- Field Devices and Control Panels
• The detection system is segregated into two parts. These are:-
1) Field Devices - located outside in the process areas, utility areas or inside rooms,
and
2) Control Panels – these are logic solvers (or programmable logic controllers PLC,
addressable controllers), with graphic screens, to perform the required functions
(alarm and shutdown) in case of a detection.
• The following are pictures of fire and gas detectors and detection panels.
• Flame detectors
– Ultraviolet (UV)
– Ultraviolet and Infrared (UV/IR)
– Infrared (Triple IR)
Model X3301
(Triple IR)
Courtesy of DETRONICS
Model S251f+
(Triple IR)
Courtesy of THORN
Type of Field Devices
(this slide is from previous internal lecture)
• Smoke detectors
– Optical
– Ionization
(being phased out due to
!stringent! disposal requirements
of radioactive substances)
• Heat detectors
– rate of rise
– fixed
Model 601P
Smoke Detector
Model 601H-R Model 601H-F
Heat Detector
Courtesy of THORN
Type of Field Devices
(this slide is from previous internal lecture)
Type of Field Devices
(this slide is from previous internal lecture)
• Pneumatic fusible plugs
(pressure sensors will send a signal to
fire and gas system FGS upon
detection of low air pressure)
– Melt at 71 degree celsius
• Manual alarm callpoint
– Breakglass or pushbutton
Model SS-6-FTA-160
Fusible Plug
MODEL SM87 BG
MODEL SM87 PB
Courtesy of MEDC
Courtesy of SWAGELOK
Type of Field Devices
(this slide is from previous internal lecture)
• Gas detectors
– Infrared, electrochemical,
catalytic (point detectors)
– Infrared (line-of-sight)
Courtesy of DRAEGER
Model Polytron 2IR
Model Pulsar
Model Polytron FX
Model APEX
Model ECLIPSE
Courtesy of DETRONICS
Model OPECL
Courtesy of DETRONICS
Courtesy of SIEGER
Types of Fire and Gas Panel
(this slide is from previous internal lecture)
• Programmable Logic Controller (PLC based)
- Main Panel
- Addressable Panel
Model MINERVA
Courtesy of THORN
Courtesy of Honeywell
Model Honeywell Icon
Series Console MMI
Model Honeywell Fail
Safe
Controller (FSC)
ANIMATION OF A GAS LEAK
V-1
WIND
GD-1
GD-2
Tx
Rx
ANIMATION OF PLACING
FLAME DETECTORS
FD-1
FD-2
V-1
FD-3
ANIMATION OF A SHUTDOWN
GD
2oo3
GD
GD
&
Maintenance
Enabled
Reset w latched
Alarm
Shutdown
Principle of Gas Detection (1)
(this slide is from previous internal lecture)
100
Principle of Gas Detection (2)
• The principle of detection is based on absorption of infrared light by hydrocarbon
gas in the measurement chamber.
• For open path (or line-of-sight) gas detectors, the measurement area in between the
receiver and the transmitter unit is the hazardous area that required to be monitored
by these units. It is this area that this set of detectors are aligned diagonally across
or straight over the equipment. The unit of measurement is LEL.m or LFL.m
• LEL is the abbreviation for lower explosive limit whereas LFL is lower
flammability limit.
• LEL.m or LFL.m is the concentration of the gas cloud multiply by the distance
between the receiver and the transmitter unit.
- For example, if the gas cloud is 20 %LEL or %LFL, and the distance between the
receiver and the transmitter unit is 5 metres, then the measurement reading is about
20 %LEL x 5.0m = 1.0 LEL.m (0.20x5 = 1.0LEL.m). If the gas cloud is 60%LEL
and the distance is 5 metres, the reading is 60 %LEL x 5m = 3.0 LEL.m
Principle of Flame Detection (1)
(Ultraviolet & Infrared Wavelengths) (this slide is from previous internal
lecture)
Extracted from NFPA 72
recommended guide on Code of
Practice
Principle of Flame Detection (2)
• UV Flame Detector – This detector detects UV light source in a fire. UV light
source are found in hydrogen flame.
• UV/IR Flame Detector – This detector must detects both UV and IR light source
before this detector considers the target/detection area as a confirmed detection.
• Triple IR Flame Detector – This detector has three (3) infrared sensors. Infrared
light source are found in hydrocarbon flame.
Principle of Activation (1)
GD
FD
2ooN
Maintenance
Override
&
Alarm
or
Shutdown
Latched
Reset
Principle of Activation (2)
• The controller is either an electronic and pneumatic panel.
• The electronic panels are as below:
1) main panel (redundant/triplicated TMR),
2) addressable panel, and
3) instrument package panels (like turbine generators, firewater pumps, instrument
air compressor, etc.).
• 4) Others panels, shutdown panel or Public Address General Alarm PAGA panel
• Fire and gas signals to/from various panels (item 2 - 4) will be connected to the
main panel.
• Pneumatic panels (only pressure transmitter/switch signal connected to the PLC) is
a sub-system to the main panel.
• Also known as an electro/pneumatic panel (partial electronic), e.g. fusible plug
panel, deluge panel, etc., the instrument air is used to pressurized fusible tubes.
The Method of Detection of Field Detectors (1)
The principle of measurement/detection for field devices are:-
• Gas detectors (point HC or open path) – By infrared sensor(s). The concentrated
gas will block the light from reaching the sensor. The detection of an early warning
below the Lower Explosive Limits LEL will enable the controller to perform a
shutdown and sound the alarms.
• Flame detectors – A fire will be detected by the sensor (infrared wavelength). The
detector will detect a fire only after it develops.
• Manual call points – It is a detection by manual activation. The call points are
located at the edge of the platform or exit in the room visible to inhabitant of the
platform.
• Heat detectors – It detects the change in temperature rise (Rate-of-rise) or
temperature in exceed of a fixed setpoint in a room.
• Smoke detectors (optical) – Smoke particles in measurement chamber block light
from an internal source to the sensor. It detects smoke particles before a fire
develops.
• Fusible plugs – Melting of plugs at fixed elevated temperature due to heat. It is an
outdoor protection device.
The Method of Activation (1)
• Non-Fail Safe (i.e. an energized output on alarm/activation) - This non-fail safe
activation will activate output signals only if it is required to be activated.
(In normal practice, when the deluge valve is required to be activated, an output
signal will be sent to the solenoid that is part of the deluge valve).
• Fail Safe – otherwise, the fail safe outputs are de-energized on alarm/activation.
(If it is a fail safe application, the output signal will be deactivated when it is
required to perform a function. Example of this application is the fire and gas
outputs to a shutdown panel/system).
• Other applications like a fault signal, has to be supervised to ensure that this signal
is noticed when there is a failure in the panel.
• The detection system has to safe guard the platform from a gas leak or a fire. When
it occurs, the system must work.
• It is very unlikely that the redundant device fails when a shutdown is required.
Other means has to be sorted to ASSURE a safe operation.
The Methods of Detection of Electronic &
Pneumatic Panel (2)
• Electronic panels – are complete platform solution, with calculated failures (low
failure and with redundant I/Os and processors). It takes into account of redundant
failure(s), if it occurs.
• Pneumatic panels – has become a partial, but proven reliable solution due to its
depressurization mode. Air line leakages will bring the platform to a safe condition.
The Location of the Detectors
(and Its Application)
• The types of detectors and its recommended location are in the next slide.
• This table shows the type of detectors in the areas mentioned in the previous slides.
- Gas and flame detectors are mainly outdoor devices.
- Smoke and heat detectors are indoor devices.
- Manual call point can be located either in indoor and/or outdoor areas.
- Fusible Plugs are outdoor fire detection devices, location as per API RP 14C
guidelines.
(You can locate flame detectors inside a room if it is appropriate. However, smoke
and heat detectors are always located inside an enclosure(s).
• These are the devices to detect gas (early warning) or fire (either early warning or
after the fire is fully developed).
The Location of the Detectors
(and Its Application)
(this slide is from previous internal lecture)
The Location of the Panels
(and Its Application)
• The control panels are located either in the control room or outside in the open
areas.
• Electronic Panels with its redundant processors and safe failures have proven its use
on offshore platform, with proper design considerations.
• Pneumatic Panel, the oldest method, has is rigid and reliable (mechanically) method
of shutting down a platform.
• The detection system is connected to the deluge system (sometimes, not always) to
cool the equipment when the platform is undergoing depressurization through the
vent pipes.
• At the same time fire and gas signals from other system/panels will send signals to
the fire and gas detection panel for fault alarm or shutdown purposes.
(e.g. gas turbine panel upon detection of gas or fire will send signal to fire and gas
panel to close the fuel lines)
Part 1 : The Field Devices and Its
Panels
• End of Lesson 1
• Questions
Own Notes (1)
• Part 1 : The Field Devices and Its Panels
• The Purpose of Fire and Gas Detection
• The Detection Area – Outdoor and Indoor
• Fire and Gas Detection System in Two Parts - Field Devices and Control Panels
• Type of Field Devices
(this slide is from previous internal lecture)
• Types of Fire and Gas Panel
(this slide is from previous internal lecture)
• ANIMATION OF A GAS LEAK
• ANIMATION OF PLACING FLAME DETECTORS
• ANIMATION OF A SHUTDOWN
Own Notes (2)
• PRINCIPLES OF GAS DETECTION
(this slide is from previous internal lecture)
• PRINCIPLES OF FLAME DETECTION
(Ultraviolet & Infrared Wavelengths) (this slide is from previous internal
lecture)
• PRINCIPLE OF AN ACTIVATION
• The Method of Detection of Field Detectors
• The Methods of Activation (Detection of Electronic & Pneumatic Panel)
• The Location of the Detectors
(and Its Application)
(this slide is from previous internal lecture)
• The Location of the Panels
(and Its Application)

More Related Content

PPT
valve maintenance-packing-replacement
PPT
Functional-Safety-Overview-UL.ppt
PPTX
fire & gas detection system
PPT
General Safety Presentation
PPTX
Basic concepts of QA and QC
PDF
Environmental, Social, and Governance (ESG) Activities
PDF
ESG-Driven Safety Excellence - The Practical Guide for Safety Experts_Consul...
PPTX
Bms system
valve maintenance-packing-replacement
Functional-Safety-Overview-UL.ppt
fire & gas detection system
General Safety Presentation
Basic concepts of QA and QC
Environmental, Social, and Governance (ESG) Activities
ESG-Driven Safety Excellence - The Practical Guide for Safety Experts_Consul...
Bms system

What's hot (20)

PPT
Fire and Gas Detection System : Part 2_Block Diagram_Philosophy, Signal Types...
PPT
F&G 04.07.2007.ppt
PPT
FIRE FIGHTING NOTES PART 02 BY ER. EZAZUL HAQUE SIDDIQUE .PPT
PPTX
Concept of hazardous area classification.
PPTX
Fire and Gas Detection System_ - Simplified_Revised
PDF
Study 5: Pre-commissioning Safety Review
PDF
Fundamental training on Fire Detection & Alarm System
PPTX
Hazardous area classification and Elecrtical, Instrument and Process Engineer...
PPTX
Fire detection and alarm systems
PPTX
Fundamentals of Fire Alarm System
PDF
Fire fighting -2 By Er. Ezaz
PPTX
Fire safety
PDF
Hazardous Area Classification
PDF
Hazardous Area Classification in Oil & Gas Industry.pdf
PDF
Steam & water analysis system (swas)
PPTX
Boiler safety protection
PDF
Nfpa20 standard for the installation of stationary pumps for fire protection ...
Fire and Gas Detection System : Part 2_Block Diagram_Philosophy, Signal Types...
F&G 04.07.2007.ppt
FIRE FIGHTING NOTES PART 02 BY ER. EZAZUL HAQUE SIDDIQUE .PPT
Concept of hazardous area classification.
Fire and Gas Detection System_ - Simplified_Revised
Study 5: Pre-commissioning Safety Review
Fundamental training on Fire Detection & Alarm System
Hazardous area classification and Elecrtical, Instrument and Process Engineer...
Fire detection and alarm systems
Fundamentals of Fire Alarm System
Fire fighting -2 By Er. Ezaz
Fire safety
Hazardous Area Classification
Hazardous Area Classification in Oil & Gas Industry.pdf
Steam & water analysis system (swas)
Boiler safety protection
Nfpa20 standard for the installation of stationary pumps for fire protection ...
Ad

Similar to Fire and Gas Detection System : Part 1_The Field Devices and Its Panels (20)

PPT
Fire and Gas Detection System : Part 3_Technical Features, Locating Detectors...
PPT
Building Electronics (Fire Detection and Alarm System and CCTV)
PPT
FIRE DETECTION & ALARM SYSTEM........ppt
PDF
FIRE DETECTION & ALARM SYSTEMS-1.Why are fire detection & alarm systems requi...
PDF
cdocumentsandsettingsdeedesktopfda-1-090226130600-phpapp01 (2).pdf
PPT
1-Operate Fire and Gas Detection System.ppt
PPT
Fire alarm systems
PPT
Intro to basic fire alarm technology
PPT
fire detection and alarm system
PPTX
FDA-Fire detection and alarm system
PPS
Omni Guard 660 Flame Detector Presentation
PPTX
Fire detectionand alarm systems 090512042400-phpapp01(1)
PPT
Why are fire detection & alarm system is required in buildings?
PDF
fire-alarm-system-discussion.ppt (1).pdf
PPT
gersgtsedgdfgsrqw3terydrh
PPTX
Fire Alarm System_Instrumentation_Safety
PDF
The Fire Detection and the alarm system
PDF
FIRE ALARM SYSTEM.pdf
PDF
Fire Alarm System for safety of electrical systems
PDF
Fire Alarm System.pdf
Fire and Gas Detection System : Part 3_Technical Features, Locating Detectors...
Building Electronics (Fire Detection and Alarm System and CCTV)
FIRE DETECTION & ALARM SYSTEM........ppt
FIRE DETECTION & ALARM SYSTEMS-1.Why are fire detection & alarm systems requi...
cdocumentsandsettingsdeedesktopfda-1-090226130600-phpapp01 (2).pdf
1-Operate Fire and Gas Detection System.ppt
Fire alarm systems
Intro to basic fire alarm technology
fire detection and alarm system
FDA-Fire detection and alarm system
Omni Guard 660 Flame Detector Presentation
Fire detectionand alarm systems 090512042400-phpapp01(1)
Why are fire detection & alarm system is required in buildings?
fire-alarm-system-discussion.ppt (1).pdf
gersgtsedgdfgsrqw3terydrh
Fire Alarm System_Instrumentation_Safety
The Fire Detection and the alarm system
FIRE ALARM SYSTEM.pdf
Fire Alarm System for safety of electrical systems
Fire Alarm System.pdf
Ad

More from Gan Chun Chet (20)

PPTX
The Mutant Mint Leaf - A DNA Replication (Aquaponics System)
PDF
Machine Setup Time - A Limit Determiner (Tool)
PPTX
Trust Measurement Presentation_Part 3
PDF
Predicting Machine Setup Time_Suggeting A Limit Determiner, Institute of Engi...
PDF
Predictive Method in Analyzing Past Data_(May_09), Institute of Engineers Mal...
PDF
Modelling Trust of Customer and Supplier Interaction_2023 Vol 10 Issue 1.pdf
PDF
Oil and Gas Industry : Datasheet for Fire and Gas Detectors.pdf
PPTX
Trust Measurement Presentation_2.pptx
PPTX
Boundary Layer Oscillation for Aircraft Cavity/Surfaces
PPTX
Noise dB to dBA Calculation_Gan Chun Chet.pptx
PPTX
Noise Error Calculation_Gan Chun Chet.pptx
PDF
Noise_Proofing Linking Equations.pdf
PDF
The Prediction of Time Trending Techniques in Manufacuturing
DOCX
The Philosophy and Characteristics of Trust Measurement in Practice.docx
PDF
Trust Measurement Gan Chun Chet 07.01.2022
PDF
mV to dBm Airflow Across Cavity_Gan Chun Chet_07.01.2021
PDF
Control System_3rd Order System_Root Locus Method
PDF
PID Controllers Control Engineering
PPTX
Noise Reduction Modelling Study for Aircraft Cavity - Chun C Gan
PDF
Calculation worksheet air flow across rectangular cavity low mach
The Mutant Mint Leaf - A DNA Replication (Aquaponics System)
Machine Setup Time - A Limit Determiner (Tool)
Trust Measurement Presentation_Part 3
Predicting Machine Setup Time_Suggeting A Limit Determiner, Institute of Engi...
Predictive Method in Analyzing Past Data_(May_09), Institute of Engineers Mal...
Modelling Trust of Customer and Supplier Interaction_2023 Vol 10 Issue 1.pdf
Oil and Gas Industry : Datasheet for Fire and Gas Detectors.pdf
Trust Measurement Presentation_2.pptx
Boundary Layer Oscillation for Aircraft Cavity/Surfaces
Noise dB to dBA Calculation_Gan Chun Chet.pptx
Noise Error Calculation_Gan Chun Chet.pptx
Noise_Proofing Linking Equations.pdf
The Prediction of Time Trending Techniques in Manufacuturing
The Philosophy and Characteristics of Trust Measurement in Practice.docx
Trust Measurement Gan Chun Chet 07.01.2022
mV to dBm Airflow Across Cavity_Gan Chun Chet_07.01.2021
Control System_3rd Order System_Root Locus Method
PID Controllers Control Engineering
Noise Reduction Modelling Study for Aircraft Cavity - Chun C Gan
Calculation worksheet air flow across rectangular cavity low mach

Recently uploaded (20)

PDF
Types of control:Qualitative vs Quantitative
PPTX
New Microsoft PowerPoint Presentation - Copy.pptx
PDF
Training And Development of Employee .pdf
PDF
DOC-20250806-WA0002._20250806_112011_0000.pdf
PPTX
The Marketing Journey - Tracey Phillips - Marketing Matters 7-2025.pptx
PPT
Data mining for business intelligence ch04 sharda
DOCX
Business Management - unit 1 and 2
PDF
Dr. Enrique Segura Ense Group - A Self-Made Entrepreneur And Executive
PDF
kom-180-proposal-for-a-directive-amending-directive-2014-45-eu-and-directive-...
PDF
Roadmap Map-digital Banking feature MB,IB,AB
PDF
COST SHEET- Tender and Quotation unit 2.pdf
PDF
Reconciliation AND MEMORANDUM RECONCILATION
PPTX
CkgxkgxydkydyldylydlydyldlyddolydyoyyU2.pptx
PDF
Ôn tập tiếng anh trong kinh doanh nâng cao
PDF
WRN_Investor_Presentation_August 2025.pdf
PPTX
AI-assistance in Knowledge Collection and Curation supporting Safe and Sustai...
PDF
Nidhal Samdaie CV - International Business Consultant
DOCX
unit 1 COST ACCOUNTING AND COST SHEET
PPT
340036916-American-Literature-Literary-Period-Overview.ppt
PDF
Katrina Stoneking: Shaking Up the Alcohol Beverage Industry
Types of control:Qualitative vs Quantitative
New Microsoft PowerPoint Presentation - Copy.pptx
Training And Development of Employee .pdf
DOC-20250806-WA0002._20250806_112011_0000.pdf
The Marketing Journey - Tracey Phillips - Marketing Matters 7-2025.pptx
Data mining for business intelligence ch04 sharda
Business Management - unit 1 and 2
Dr. Enrique Segura Ense Group - A Self-Made Entrepreneur And Executive
kom-180-proposal-for-a-directive-amending-directive-2014-45-eu-and-directive-...
Roadmap Map-digital Banking feature MB,IB,AB
COST SHEET- Tender and Quotation unit 2.pdf
Reconciliation AND MEMORANDUM RECONCILATION
CkgxkgxydkydyldylydlydyldlyddolydyoyyU2.pptx
Ôn tập tiếng anh trong kinh doanh nâng cao
WRN_Investor_Presentation_August 2025.pdf
AI-assistance in Knowledge Collection and Curation supporting Safe and Sustai...
Nidhal Samdaie CV - International Business Consultant
unit 1 COST ACCOUNTING AND COST SHEET
340036916-American-Literature-Literary-Period-Overview.ppt
Katrina Stoneking: Shaking Up the Alcohol Beverage Industry

Fire and Gas Detection System : Part 1_The Field Devices and Its Panels

  • 1. Fire and Gas Detection System (Offshore Facilities) (Part 1 : The Field Devices and Its Panels) Chun Chet Gan (Ir.) MSc Operations Management [Manchester School Management] University of Manchester Institute of Science and Technology (UMIST), United Kingdom. BEng (Hons) Mechanical Engineering [Simon Building] University of Manchester, United Kingdom
  • 2. The Purpose of Fire and Gas Detection • The purpose of Fire and Gas Detection System, with the detectors located at outdoor and indoor areas of the platform, is to protect the platform from a gas leak or a fire. These areas are segregated into two (2) areas:- 1) outdoor, and 2) indoor areas. • Outdoor areas are zoned into hazard open process or non hazard utility areas. • Enclosed rooms are indoor areas (inside a closed structure or a building).
  • 3. The Detection Area – Outdoor and Indoor • In general, process areas (outdoor) are highly hazardous. It contains hydrocarbon inventories and these areas are regarded as hazard areas on the platform. The classification of these hazardous areas are defined by Safety. - Hazard equipment are vessels, pumps, hydrocarbon pipelines, turbine generators, etc. • Utilities areas (are considered as outdoor areas) are non-hazardous zones of a platform. - Example of equipment in these areas are firewater pumps, diesel tanks, instrument air compressors. - Others equipment like water storage tank, sewage macerator, etc. are also regarded as non-hazardous area. • Indoor areas are safe areas on the platform. • Example of these areas are: - Control Room, - Switchgear Room, - Motor Control Centre MCC • However, battery rooms are hazardous areas.
  • 4. Fire and Gas Detection System in Two Parts - Field Devices and Control Panels • The detection system is segregated into two parts. These are:- 1) Field Devices - located outside in the process areas, utility areas or inside rooms, and 2) Control Panels – these are logic solvers (or programmable logic controllers PLC, addressable controllers), with graphic screens, to perform the required functions (alarm and shutdown) in case of a detection. • The following are pictures of fire and gas detectors and detection panels.
  • 5. • Flame detectors – Ultraviolet (UV) – Ultraviolet and Infrared (UV/IR) – Infrared (Triple IR) Model X3301 (Triple IR) Courtesy of DETRONICS Model S251f+ (Triple IR) Courtesy of THORN Type of Field Devices (this slide is from previous internal lecture)
  • 6. • Smoke detectors – Optical – Ionization (being phased out due to !stringent! disposal requirements of radioactive substances) • Heat detectors – rate of rise – fixed Model 601P Smoke Detector Model 601H-R Model 601H-F Heat Detector Courtesy of THORN Type of Field Devices (this slide is from previous internal lecture)
  • 7. Type of Field Devices (this slide is from previous internal lecture) • Pneumatic fusible plugs (pressure sensors will send a signal to fire and gas system FGS upon detection of low air pressure) – Melt at 71 degree celsius • Manual alarm callpoint – Breakglass or pushbutton Model SS-6-FTA-160 Fusible Plug MODEL SM87 BG MODEL SM87 PB Courtesy of MEDC Courtesy of SWAGELOK
  • 8. Type of Field Devices (this slide is from previous internal lecture) • Gas detectors – Infrared, electrochemical, catalytic (point detectors) – Infrared (line-of-sight) Courtesy of DRAEGER Model Polytron 2IR Model Pulsar Model Polytron FX Model APEX Model ECLIPSE Courtesy of DETRONICS Model OPECL Courtesy of DETRONICS Courtesy of SIEGER
  • 9. Types of Fire and Gas Panel (this slide is from previous internal lecture) • Programmable Logic Controller (PLC based) - Main Panel - Addressable Panel Model MINERVA Courtesy of THORN Courtesy of Honeywell Model Honeywell Icon Series Console MMI Model Honeywell Fail Safe Controller (FSC)
  • 10. ANIMATION OF A GAS LEAK V-1 WIND GD-1 GD-2 Tx Rx
  • 11. ANIMATION OF PLACING FLAME DETECTORS FD-1 FD-2 V-1 FD-3
  • 12. ANIMATION OF A SHUTDOWN GD 2oo3 GD GD & Maintenance Enabled Reset w latched Alarm Shutdown
  • 13. Principle of Gas Detection (1) (this slide is from previous internal lecture) 100
  • 14. Principle of Gas Detection (2) • The principle of detection is based on absorption of infrared light by hydrocarbon gas in the measurement chamber. • For open path (or line-of-sight) gas detectors, the measurement area in between the receiver and the transmitter unit is the hazardous area that required to be monitored by these units. It is this area that this set of detectors are aligned diagonally across or straight over the equipment. The unit of measurement is LEL.m or LFL.m • LEL is the abbreviation for lower explosive limit whereas LFL is lower flammability limit. • LEL.m or LFL.m is the concentration of the gas cloud multiply by the distance between the receiver and the transmitter unit. - For example, if the gas cloud is 20 %LEL or %LFL, and the distance between the receiver and the transmitter unit is 5 metres, then the measurement reading is about 20 %LEL x 5.0m = 1.0 LEL.m (0.20x5 = 1.0LEL.m). If the gas cloud is 60%LEL and the distance is 5 metres, the reading is 60 %LEL x 5m = 3.0 LEL.m
  • 15. Principle of Flame Detection (1) (Ultraviolet & Infrared Wavelengths) (this slide is from previous internal lecture) Extracted from NFPA 72 recommended guide on Code of Practice
  • 16. Principle of Flame Detection (2) • UV Flame Detector – This detector detects UV light source in a fire. UV light source are found in hydrogen flame. • UV/IR Flame Detector – This detector must detects both UV and IR light source before this detector considers the target/detection area as a confirmed detection. • Triple IR Flame Detector – This detector has three (3) infrared sensors. Infrared light source are found in hydrocarbon flame.
  • 17. Principle of Activation (1) GD FD 2ooN Maintenance Override & Alarm or Shutdown Latched Reset
  • 18. Principle of Activation (2) • The controller is either an electronic and pneumatic panel. • The electronic panels are as below: 1) main panel (redundant/triplicated TMR), 2) addressable panel, and 3) instrument package panels (like turbine generators, firewater pumps, instrument air compressor, etc.). • 4) Others panels, shutdown panel or Public Address General Alarm PAGA panel • Fire and gas signals to/from various panels (item 2 - 4) will be connected to the main panel. • Pneumatic panels (only pressure transmitter/switch signal connected to the PLC) is a sub-system to the main panel. • Also known as an electro/pneumatic panel (partial electronic), e.g. fusible plug panel, deluge panel, etc., the instrument air is used to pressurized fusible tubes.
  • 19. The Method of Detection of Field Detectors (1) The principle of measurement/detection for field devices are:- • Gas detectors (point HC or open path) – By infrared sensor(s). The concentrated gas will block the light from reaching the sensor. The detection of an early warning below the Lower Explosive Limits LEL will enable the controller to perform a shutdown and sound the alarms. • Flame detectors – A fire will be detected by the sensor (infrared wavelength). The detector will detect a fire only after it develops. • Manual call points – It is a detection by manual activation. The call points are located at the edge of the platform or exit in the room visible to inhabitant of the platform. • Heat detectors – It detects the change in temperature rise (Rate-of-rise) or temperature in exceed of a fixed setpoint in a room. • Smoke detectors (optical) – Smoke particles in measurement chamber block light from an internal source to the sensor. It detects smoke particles before a fire develops. • Fusible plugs – Melting of plugs at fixed elevated temperature due to heat. It is an outdoor protection device.
  • 20. The Method of Activation (1) • Non-Fail Safe (i.e. an energized output on alarm/activation) - This non-fail safe activation will activate output signals only if it is required to be activated. (In normal practice, when the deluge valve is required to be activated, an output signal will be sent to the solenoid that is part of the deluge valve). • Fail Safe – otherwise, the fail safe outputs are de-energized on alarm/activation. (If it is a fail safe application, the output signal will be deactivated when it is required to perform a function. Example of this application is the fire and gas outputs to a shutdown panel/system). • Other applications like a fault signal, has to be supervised to ensure that this signal is noticed when there is a failure in the panel. • The detection system has to safe guard the platform from a gas leak or a fire. When it occurs, the system must work. • It is very unlikely that the redundant device fails when a shutdown is required. Other means has to be sorted to ASSURE a safe operation.
  • 21. The Methods of Detection of Electronic & Pneumatic Panel (2) • Electronic panels – are complete platform solution, with calculated failures (low failure and with redundant I/Os and processors). It takes into account of redundant failure(s), if it occurs. • Pneumatic panels – has become a partial, but proven reliable solution due to its depressurization mode. Air line leakages will bring the platform to a safe condition.
  • 22. The Location of the Detectors (and Its Application) • The types of detectors and its recommended location are in the next slide. • This table shows the type of detectors in the areas mentioned in the previous slides. - Gas and flame detectors are mainly outdoor devices. - Smoke and heat detectors are indoor devices. - Manual call point can be located either in indoor and/or outdoor areas. - Fusible Plugs are outdoor fire detection devices, location as per API RP 14C guidelines. (You can locate flame detectors inside a room if it is appropriate. However, smoke and heat detectors are always located inside an enclosure(s). • These are the devices to detect gas (early warning) or fire (either early warning or after the fire is fully developed).
  • 23. The Location of the Detectors (and Its Application) (this slide is from previous internal lecture)
  • 24. The Location of the Panels (and Its Application) • The control panels are located either in the control room or outside in the open areas. • Electronic Panels with its redundant processors and safe failures have proven its use on offshore platform, with proper design considerations. • Pneumatic Panel, the oldest method, has is rigid and reliable (mechanically) method of shutting down a platform. • The detection system is connected to the deluge system (sometimes, not always) to cool the equipment when the platform is undergoing depressurization through the vent pipes. • At the same time fire and gas signals from other system/panels will send signals to the fire and gas detection panel for fault alarm or shutdown purposes. (e.g. gas turbine panel upon detection of gas or fire will send signal to fire and gas panel to close the fuel lines)
  • 25. Part 1 : The Field Devices and Its Panels • End of Lesson 1 • Questions
  • 26. Own Notes (1) • Part 1 : The Field Devices and Its Panels • The Purpose of Fire and Gas Detection • The Detection Area – Outdoor and Indoor • Fire and Gas Detection System in Two Parts - Field Devices and Control Panels • Type of Field Devices (this slide is from previous internal lecture) • Types of Fire and Gas Panel (this slide is from previous internal lecture) • ANIMATION OF A GAS LEAK • ANIMATION OF PLACING FLAME DETECTORS • ANIMATION OF A SHUTDOWN
  • 27. Own Notes (2) • PRINCIPLES OF GAS DETECTION (this slide is from previous internal lecture) • PRINCIPLES OF FLAME DETECTION (Ultraviolet & Infrared Wavelengths) (this slide is from previous internal lecture) • PRINCIPLE OF AN ACTIVATION • The Method of Detection of Field Detectors • The Methods of Activation (Detection of Electronic & Pneumatic Panel) • The Location of the Detectors (and Its Application) (this slide is from previous internal lecture) • The Location of the Panels (and Its Application)