2. Class B Initiating Device Circuit
4.7K
EOLR
4.7K
EOLR
Class B Notification Appliance Circuit
Class B Circuits
End of line supervision resistors
are required to supervise the
integrity of the loop.
3. Single open circuit condition causes a
trouble on the panel and renders all
devices beyond the fault inoperative.
Class B Initiating Device Circuit
4.7K
EOLR
4.7K
EOLR
Class B Notification Appliance Circuit
Class B Circuits
4. Class A Initiating Device Circuit
Class A Notification Appliance Circuit
Class A Circuits
End of line supervision resistors are not
necessary as the loop returns to the
panel and is driven from both ends.
5. Class A Initiating Device Circuit
Class A Notification Appliance Circuit
Class A Circuits
Single open circuit condition causes a
trouble on the panel. All devices on the
loop remain operative.
6. Addressable Device - A fire alarm system
component with discreet identification that can
have its status individually identified or that is
used to individually control other functions.
Analog Addressable Sensor - An initiating
device that transmits a signal indicating varying
degrees of condition as contrasted with a
conventional or addressable initiating device,
which can only indicate an off/on condition.
Fire Alarm Terminology
7. Protocol - A language for communicating between
control panels and their proprietary devices.
SLC Interface - A system component that connects a
signaling line circuit to any combination of initiating devices,
initiating device circuits, notification appliances, notification
appliance circuits, system control outputs and other
signaling line circuits.
Signaling Line Circuit (SLC) - A circuit or path between any
combination of circuit interfaces, control units, or
transmitters over which multiple system input signals or out
put signals or both are carried.
8. Conventional control panels range in size from 1 zone
to over 100 zones.
Zones typically consist of some or all of the initiating
devices in an area or floor of a building.
Some control panels zone capacity is expandable
while others are not, limiting its usefulness if a facility
adds additional buildings or rooms.
Comparing System Types
To better understand today’s newer technology, a firm understanding of the types of systems
available is necessary. The three most popular types of systems installed today are:
• Conventional
• Addressable
• Analog Addressable
Conventional Systems
9. Conventional Systems
Zone 1
4.7K
EOLR
Zone 2
FIRE
FIRE
SILENT KNIGHT
FIRE
FIRE
SILENT KNIGHT
FIRE
FIRE
SILENT KNIGHT
FIRE
FIRE
SILENT KNIGHT
FIRE
FIRE
SILENT KNIGHT
FACP
NAC 1
Multiple devices are combined
into a single zone. Zones can
contain 30 or more devices.
4.7K
EOLR
10. Conventional Systems
Care must be taken when laying
out zones to comply with code
requirements.
Zone 1
4.7K
EOLR
Zone 2
FIRE
FIRE
SILENT KNIGHT
NAC 1
4.7K
EOLR
11. Zone Considerations
2007 NFPA 72 6.8.5.5.2 Limits the number of waterflow
switches in a single zone to 5.
2007 NFPA 72 6.8.5.6.2 Limits the number of
supervisory devices in a single zone to 20.
2007 NFPA 72 Annex A.4.4.6.6 Suggests that the
maximum number of square feet in a single zone be
limited to no more than 22,500.
12. Conventional Systems
Wiring must be installed in a
supervised manner either Class A,
or Class B with an EOLR.
Zone #1
4.7K
EOLR
4.7K
EOLR
Zone #2
NAC #1
13. Conventional Systems
Alarm conditions are annunciated
by zone only. Inspection is
required to determine the device.
Zone #1
4.7K
EOLR
4.7K
EOLR
Zone #2
NAC #1
FIRE!
14. Conventional Systems
Trouble conditions are annunciated
by zone only. Inspection is required
to determine the cause.
4.7K
EOLR
Zone #1
4.7K
EOLR
4.7K
EOLR
Zone #2
NAC #1
15. Conventional Systems
Information transmitted to the central
station is by zone at best. Many
panels send Alarm, Supv, Trbl only.
RJ RJ
Zone #1
4.7K
EOLR
4.7K
EOLR
Zone #2
NAC #1
16. Addressable Systems
An addressable systems point capacity is
determined by the amount of SLC “Signaling
Line Circuits” it contains.
Each SLC circuit provides power,
communication, & supervision for all of the
devices connected to it.
Each SLC can accommodate over 100
addressable devices, depending upon the
manufacturer.
FACP
17. Addressable Systems
FACP
Each SLC loop can contain a variety of
addressable devices. Non-addressable devices
are connected via addressable module.
FIRE
FIRE
SILENT KNIGHT
Addressable
Pull Station
Addressable
Heat Detector
4.7K
EOLR
NAC #1
Addressable
Smoke Detector
Addressable
Input Module
(Waterflow)
Addressable
Smoke Detector
Addressable
Relay Module
(Fan Shutdown)
18. Addressable Systems
Each point on the SLC loop is given
a unique address when installed.
001 002
003
004
005
006
FACP
FIRE
FIRE
SILENT KNIGHT
Addressable
Pull Station
Addressable
Relay Module
(Fan Shutdown)
Addressable
Heat Detector
4.7K
EOLR
NAC #1
Addressable
Smoke Detector
Addressable
Input Module
(Waterflow)
Addressable
Smoke Detector
19. Addressable Systems
Supervision is accomplished from
the panel by polling the devices on
the SLC loop.
001 002
003
004
005
006
FACP
FIRE
FIRE
SILENT KNIGHT
Addressable
Pull Station
Addressable
Relay Module
(Fan Shutdown)
Addressable
Heat Detector
4.7K
EOLR
Addressable
Smoke Detector
Addressable
Input Module
(Waterflow)
Addressable
Smoke Detector
NAC #1
20. Addressable Systems
Supervision is accomplished from
the panel by polling the devices on
the SLC loop.
001 002
003
004
005
006
FACP
FIRE
FIRE
SILENT KNIGHT
Addressable
Pull Station
Addressable
Relay Module
(Fan Shutdown)
Addressable
Heat Detector
4.7K
EOLR
Addressable
Smoke Detector
Addressable
Input Module
(Waterflow)
Addressable
Smoke Detector
NAC #1
21. Addressable Systems
Supervision is accomplished from
the panel by polling the devices on
the SLC loop.
001 002
003
004
005
006
FACP
FIRE
FIRE
SILENT KNIGHT
Addressable
Pull Station
Addressable
Relay Module
(Fan Shutdown)
Addressable
Heat Detector
4.7K
EOLR
Addressable
Smoke Detector
Addressable
Input Module
(Waterflow)
Addressable
Smoke Detector
NAC #1
22. Addressable Systems
Supervision is accomplished from
the panel by polling the devices on
the SLC loop.
001 002
003
004
005
006
FACP
FIRE
FIRE
SILENT KNIGHT
Addressable
Pull Station
Addressable
Relay Module
(Fan Shutdown)
Addressable
Heat Detector
4.7K
EOLR
Addressable
Smoke Detector
Addressable
Input Module
(Waterflow)
Addressable
Smoke Detector
NAC #1
23. Addressable Systems
Supervision is accomplished from
the panel by polling the devices on
the SLC loop.
001 002
003
004
005
006
FACP
FIRE
FIRE
SILENT KNIGHT
Addressable
Pull Station
Addressable
Relay Module
(Fan Shutdown)
Addressable
Heat Detector
4.7K
EOLR
Addressable
Smoke Detector
Addressable
Input Module
(Waterflow)
Addressable
Smoke Detector
NAC #1
24. Addressable Systems
Supervision is accomplished from
the panel by polling the devices on
the SLC loop.
001 002
003
004
005
006
FACP
FIRE
FIRE
SILENT KNIGHT
Addressable
Pull Station
Addressable
Relay Module
(Fan Shutdown)
Addressable
Heat Detector
4.7K
EOLR
Addressable
Smoke Detector
Addressable
Input Module
(Waterflow)
Addressable
Smoke Detector
NAC #1
25. Addressable Systems
Supervision is accomplished from
the panel by polling the devices on
the SLC loop.
001 002
003
004
005
006
FACP
FIRE
FIRE
SILENT KNIGHT
Addressable
Pull Station
Addressable
Relay Module
(Fan Shutdown)
Addressable
Heat Detector
4.7K
EOLR
Addressable
Smoke Detector
Addressable
Input Module
(Waterflow)
Addressable
Smoke Detector
NAC #1
26. Addressable Systems
Supervision is accomplished from
the panel by polling the devices on
the SLC loop.
001 002
003
004
005
006
FACP
FIRE
FIRE
SILENT KNIGHT
Addressable
Pull Station
Addressable
Relay Module
(Fan Shutdown)
Addressable
Heat Detector
4.7K
EOLR
Addressable
Smoke Detector
Addressable
Input Module
(Waterflow)
Addressable
Smoke Detector
NAC #1
27. Addressable Systems
Supervision is accomplished from
the panel by polling the devices on
the SLC loop.
001 002
003
004
005
006
FACP
FIRE
FIRE
SILENT KNIGHT
Addressable
Pull Station
Addressable
Relay Module
(Fan Shutdown)
Addressable
Heat Detector
4.7K
EOLR
Addressable
Smoke Detector
Addressable
Input Module
(Waterflow)
Addressable
Smoke Detector
NAC #1
28. Addressable Systems
Supervision is accomplished from
the panel by polling the devices on
the SLC loop.
001 002
003
004
005
006
FACP
FIRE
FIRE
SILENT KNIGHT
Addressable
Pull Station
Addressable
Relay Module
(Fan Shutdown)
Addressable
Heat Detector
4.7K
EOLR
Addressable
Smoke Detector
Addressable
Input Module
(Waterflow)
Addressable
Smoke Detector
NAC #1
29. Addressable Systems
Supervision is accomplished from
the panel by polling the devices on
the SLC loop.
001 002
003
004
005
006
FACP
FIRE
FIRE
SILENT KNIGHT
Addressable
Pull Station
Addressable
Relay Module
(Fan Shutdown)
Addressable
Heat Detector
4.7K
EOLR
Addressable
Smoke Detector
Addressable
Input Module
(Waterflow)
Addressable
Smoke Detector
NAC #1
30. Addressable Systems
Supervision is accomplished from
the panel by polling the devices on
the SLC loop.
001 002
003
004
005
006
FIRE
FIRE
SILENT KNIGHT
Addressable
Pull Station
Addressable
Relay Module
(Fan Shutdown)
Addressable
Heat Detector
4.7K
EOLR
Addressable
Smoke Detector
Addressable
Input Module
(Waterflow)
Addressable
Smoke Detector
FACP
NAC #1
31. Addressable Systems
Supervision is accomplished from
the panel by polling the devices on
the SLC loop.
< Replay
001 002
003
004
005
006
FACP
FIRE
FIRE
SILENT KNIGHT
Addressable
Pull Station
Addressable
Relay Module
(Fan Shutdown)
Addressable
Heat Detector
4.7K
EOLR
Addressable
Smoke Detector
Addressable
Input Module
(Waterflow)
Addressable
Smoke Detector
NAC #1
32. Addressable Systems
Alarm conditions are annunciated
by point allowing responding
personnel to quickly find the fire.
ALARM POINT 006
LOBBY SMOKE DETECTOR
001 002
003
004
005
006
FACP
FIRE
FIRE
SILENT KNIGHT
Addressable
Pull Station
Addressable
Relay Module
(Fan Shutdown)
Addressable
Heat Detector
4.7K
EOLR
Addressable
Smoke Detector
Addressable
Input Module
(Waterflow)
Addressable
Smoke Detector
NAC #1
FIRE!
33. Addressable Systems
Trouble conditions can be located
more quickly by analyzing the
affected points.
TRBL POINT 006
DISCONNECTED
LOBBY SMOKE DETECTOR
001 002
003
004
005
006
FACP
FIRE
FIRE
SILENT KNIGHT
Addressable
Pull Station
Addressable
Relay Module
(Fan Shutdown)
Addressable
Heat Detector
4.7K
EOLR
Addressable
Smoke Detector
Addressable
Input Module
(Waterflow)
Addressable
Smoke Detector
NAC #1
34. Addressable Systems
More detailed information can be
sent to the central station aiding in
a quick resolution to the problem.
RJ
RJ
001 002
003
004
005
006
FACP
FIRE
FIRE
SILENT KNIGHT
Addressable
Pull Station
Addressable
Relay Module
(Fan Shutdown)
Addressable
Heat Detector
4.7K
EOLR
Addressable
Smoke Detector
Addressable
Input Module
(Waterflow)
Addressable
Smoke Detector
NAC #1
35. Addressable Systems
Since supervision is accomplished
through polling, t-tapped wiring is
permitted. (Class B wiring)
001 002
003
004
005
006
FACP
FIRE
FIRE
SILENT KNIGHT
Addressable
Pull Station
Addressable
Relay Module
(Fan Shutdown)
Addressable
Heat Detector
4.7K
EOLR
Addressable
Smoke Detector
Addressable
Input Module
(Waterflow)
Addressable
Smoke Detector
NAC #1
36. Addressable Systems
Many systems support flexible
input/output programming to link
initiating devices to outputs.
001 002
003
004
005
006
FACP
FIRE
FIRE
SILENT KNIGHT
Addressable
Pull Station
Addressable
Relay Module
(Fan Shutdown)
Addressable
Heat Detector
4.7K
EOLR
Addressable
Smoke Detector
Addressable
Input Module
(Waterflow)
Addressable
Smoke Detector
NAC #1
FIRE!
37. Comparison
Conventional
Lower initial equipment costs.
Wide range of compatible devices.
Can be easier to program.
Limited expansion capability.
Addressable
Easier to install.
More system status information at
the panel and central station.
Input/Output programming much
more flexible.
Usually much more room
available to expand.
38. Analog Addressable Systems
Detectors in an analog addressable systems
become “sensors” relaying information to the
control panel corresponding to how much
smoke or heat that detector is sensing.
The control panel makes the decisions based
on this information when to alarm etc.
39. Analog Addressable Systems
Addressable
Relay Module
(Fan Shutdown)
Addressable
Heat Sensor
10K
EOLR
Addressable
Smoke Sensor
Addressable
Input Module
(Waterflow)
001 002
003
004
005
Addressable
Pull Station
Addressable
Smoke Sensor
006
HEAT DETECTOR
MECHANICAL ROOM
POINT 001 A=062
NORMAL F=190
Supervision is still checked by
polling. In addition an analog
value is transmitted to the
panel for processing.
NAC #1
40. Analog Addressable Systems
SMOKE DETECTOR
LOBBY NORTH
POINT 002 A=060
NORMAL F=188
Supervision is still checked by
polling. In addition an analog
value is transmitted to the
panel for processing.
Addressable
Relay Module
(Fan Shutdown)
Addressable
Heat Sensor
Addressable
Smoke Sensor
Addressable
Input Module
(Waterflow)
001 002
003
004
005
Addressable
Pull Station
Addressable
Smoke Detector
006
10K
EOLR
NAC #1
41. Analog Addressable Systems
RELAY MODULE
FAN SHUTDOWN
POINT 003 A=N/A
NORMAL F=N/A
Supervision is still checked by
polling. In addition an analog
value is transmitted to the
panel for processing.
Addressable
Relay Module
(Fan Shutdown)
Addressable
Heat Sensor
Addressable
Smoke Sensor
Addressable
Input Module
(Waterflow)
001 002
003
004
005
Addressable
Pull Station
Addressable
Smoke Sensor
006
10K
EOLR
NAC #1
42. Analog Addressable Systems
INPUT MODULE
WATERFLOW
POINT 004 A=N/A
NORMAL F=N/A
Supervision is still checked by
polling. In addition an analog
value is transmitted to the
panel for processing.
Addressable
Relay Module
(Fan Shutdown)
Addressable
Heat Sensor
Addressable
Smoke Sensor
Addressable
Input Module
(Waterflow)
001 002
003
004
005
Addressable
Pull Station
Addressable
Smoke Sensor
006
10K
EOLR
NAC #1
43. Analog Addressable Systems
Supervision is still checked by
polling. In addition an analog
value is transmitted to the
panel for processing.
INPUT MODULE
MANUAL PULL
POINT 005 A=N/A
NORMAL F=N/A
Addressable
Relay Module
(Fan Shutdown)
Addressable
Heat Sensor
Addressable
Smoke Sensor
Addressable
Input Module
(Waterflow)
001 002
003
004
005
Addressable
Pull Station
Addressable
Smoke Sensor
006
10K
EOLR
NAC #1
44. Analog Addressable Systems
SMOKE DETECTOR
FRONT DESK
POINT 006 A=061
NORMAL F=189
Supervision is still checked by
polling. In addition an analog
value is transmitted to the
panel for processing.
Addressable
Relay Module
(Fan Shutdown)
Addressable
Heat Sensor
Addressable
Smoke Sensor
Addressable
Input Module
(Waterflow)
001 002
003
004
005
Addressable
Pull Station
Addressable
Smoke Sensor
006
10K
EOLR
NAC #1
45. Analog Addressable Systems
HEAT DETECTOR
MECHANICAL ROOM
POINT 001 A=062
NORMAL F=190
Supervision is still checked by
polling. In addition an analog
value is transmitted to the
panel for processing.
Addressable
Relay Module
(Fan Shutdown)
Addressable
Heat Sensor
Addressable
Smoke Sensor
Addressable
Input Module
(Waterflow)
001 002
003
004
005
Addressable
Pull Station
Addressable
Smoke Sensor
006
10K
EOLR
NAC #1
46. Analog Addressable Systems
SMOKE DETECTOR
LOBBY NORTH
POINT 002 A=060
NORMAL F=188
Supervision is still checked by
polling. In addition an analog
value is transmitted to the
panel for processing.
Addressable
Relay Module
(Fan Shutdown)
Addressable
Heat Sensor
Addressable
Smoke Sensor
Addressable
Input Module
(Waterflow)
001 002
003
004
005
Addressable
Pull Station
Addressable
Smoke Sensor
006
10K
EOLR
NAC #1
47. Analog Addressable Systems
RELAY MODULE
FAN SHUTDOWN
POINT 003 A=N/A
NORMAL F=N/A
Supervision is still checked by
polling. In addition an analog
value is transmitted to the
panel for processing.
Addressable
Relay Module
(Fan Shutdown)
Addressable
Heat Sensor
Addressable
Smoke Sensor
Addressable
Input Module
(Waterflow)
001 002
003
004
005
Addressable
Pull Station
Addressable
Smoke Sensor
006
10K
EOLR
NAC #1
48. Analog Addressable Systems
INPUT MODULE
WATERFLOW
POINT 004 A=N/A
NORMAL F=N/A
Supervision is still checked by
polling. In addition an analog
value is transmitted to the
panel for processing.
Addressable
Relay Module
(Fan Shutdown)
Addressable
Heat Sensor
Addressable
Smoke Sensor
Addressable
Input Module
(Waterflow)
001 002
003
004
005
Addressable
Pull Station
Addressable
Smoke Sensor
006
10K
EOLR
NAC #1
49. Analog Addressable Systems
Supervision is still checked by
polling. In addition an analog
value is transmitted to the
panel for processing.
INPUT MODULE
MANUAL PULL
POINT 005 A=N/A
NORMAL F=N/A
Addressable
Relay Module
(Fan Shutdown)
Addressable
Heat Sensor
Addressable
Smoke Sensor
Addressable
Input Module
(Waterflow)
001 002
003
004
005
Addressable
Pull Station
Addressable
Smoke Sensor
006
10K
EOLR
NAC #1
50. Analog Addressable Systems
SMOKE DETECTOR
FRONT DESK
POINT 006 A=061
NORMAL F=189
< Replay
Addressable
Relay Module
(Fan Shutdown)
Addressable
Heat Sensor
Addressable
Smoke Sensor
Addressable
Input Module
(Waterflow)
001 002
003
004
005
Addressable
Pull Station
Addressable
Smoke Sensor
006
10K
EOLR
NAC #1
51. Analog Addressable Systems
This analog value corresponds
to the amount of heat or
smoke in that detectors area
of coverage. Higher = more.
HEAT DETECTOR
MECHANICAL ROOM
POINT 001 A=062
NORMAL F=190
Addressable
Relay Module
(Fan Shutdown)
Addressable
Heat Sensor
Addressable
Smoke Sensor
Addressable
Input Module
(Waterflow)
001 002
003
004
005
Addressable
Pull Station
Addressable
Smoke Sensor
006
10K
EOLR
NAC #1
52. Analog Addressable Systems
If the analog value exceeds
the alarm threshold, an alarm
occurs. This alarm threshold is
calculated by the panel.
HEAT DETECTOR
MECHANICAL ROOM
POINT 001 A=062
NORMAL F=190
Addressable
Relay Module
(Fan Shutdown)
Addressable
Heat Sensor
Addressable
Smoke Sensor
Addressable
Input Module
(Waterflow)
001 002
003
004
005
Addressable
Pull Station
Addressable
Smoke Sensor
006
10K
EOLR
NAC #1
53. Analog Addressable Systems
INPUT MODULE
WATERFLOW
POINT 004 A=N/A
NORMAL F=N/A
Input/output modules do not
relay analog values to the
panel as they are monitoring
or controlling on/off devices.
Addressable
Relay Module
(Fan Shutdown)
Addressable
Heat Sensor
Addressable
Smoke Sensor
Addressable
Input Module
(Waterflow)
001 002
003
004
005
Addressable
Pull Station
Addressable
Smoke Sensor
006
10K
EOLR
NAC #1