Fire Detection and Alarm
System Basics
Class B Initiating Device Circuit
4.7K
EOLR
4.7K
EOLR
Class B Notification Appliance Circuit
Class B Circuits
End of line supervision resistors
are required to supervise the
integrity of the loop.
Single open circuit condition causes a
trouble on the panel and renders all
devices beyond the fault inoperative.
Class B Initiating Device Circuit
4.7K
EOLR
4.7K
EOLR
Class B Notification Appliance Circuit
Class B Circuits
Class A Initiating Device Circuit
Class A Notification Appliance Circuit
Class A Circuits
End of line supervision resistors are not
necessary as the loop returns to the
panel and is driven from both ends.
Class A Initiating Device Circuit
Class A Notification Appliance Circuit
Class A Circuits
Single open circuit condition causes a
trouble on the panel. All devices on the
loop remain operative.
Addressable Device - A fire alarm system
component with discreet identification that can
have its status individually identified or that is
used to individually control other functions.
Analog Addressable Sensor - An initiating
device that transmits a signal indicating varying
degrees of condition as contrasted with a
conventional or addressable initiating device,
which can only indicate an off/on condition.
Fire Alarm Terminology
Protocol - A language for communicating between
control panels and their proprietary devices.
SLC Interface - A system component that connects a
signaling line circuit to any combination of initiating devices,
initiating device circuits, notification appliances, notification
appliance circuits, system control outputs and other
signaling line circuits.
Signaling Line Circuit (SLC) - A circuit or path between any
combination of circuit interfaces, control units, or
transmitters over which multiple system input signals or out
put signals or both are carried.
 Conventional control panels range in size from 1 zone
to over 100 zones.
 Zones typically consist of some or all of the initiating
devices in an area or floor of a building.
 Some control panels zone capacity is expandable
while others are not, limiting its usefulness if a facility
adds additional buildings or rooms.
Comparing System Types
To better understand today’s newer technology, a firm understanding of the types of systems
available is necessary. The three most popular types of systems installed today are:
• Conventional
• Addressable
• Analog Addressable
Conventional Systems
Conventional Systems
Zone 1
4.7K
EOLR
Zone 2
FIRE
FIRE
SILENT KNIGHT
FIRE
FIRE
SILENT KNIGHT
FIRE
FIRE
SILENT KNIGHT
FIRE
FIRE
SILENT KNIGHT
FIRE
FIRE
SILENT KNIGHT
FACP
NAC 1
Multiple devices are combined
into a single zone. Zones can
contain 30 or more devices.
4.7K
EOLR
Conventional Systems
Care must be taken when laying
out zones to comply with code
requirements.
Zone 1
4.7K
EOLR
Zone 2
FIRE
FIRE
SILENT KNIGHT
NAC 1
4.7K
EOLR
Zone Considerations
 2007 NFPA 72 6.8.5.5.2 Limits the number of waterflow
switches in a single zone to 5.
 2007 NFPA 72 6.8.5.6.2 Limits the number of
supervisory devices in a single zone to 20.
 2007 NFPA 72 Annex A.4.4.6.6 Suggests that the
maximum number of square feet in a single zone be
limited to no more than 22,500.
Conventional Systems
Wiring must be installed in a
supervised manner either Class A,
or Class B with an EOLR.
Zone #1
4.7K
EOLR
4.7K
EOLR
Zone #2
NAC #1
Conventional Systems
Alarm conditions are annunciated
by zone only. Inspection is
required to determine the device.
Zone #1
4.7K
EOLR
4.7K
EOLR
Zone #2
NAC #1
FIRE!
Conventional Systems
Trouble conditions are annunciated
by zone only. Inspection is required
to determine the cause.
4.7K
EOLR
Zone #1
4.7K
EOLR
4.7K
EOLR
Zone #2
NAC #1
Conventional Systems
Information transmitted to the central
station is by zone at best. Many
panels send Alarm, Supv, Trbl only.
RJ RJ
Zone #1
4.7K
EOLR
4.7K
EOLR
Zone #2
NAC #1
Addressable Systems
 An addressable systems point capacity is
determined by the amount of SLC “Signaling
Line Circuits” it contains.
 Each SLC circuit provides power,
communication, & supervision for all of the
devices connected to it.
 Each SLC can accommodate over 100
addressable devices, depending upon the
manufacturer.
FACP
Addressable Systems
FACP
Each SLC loop can contain a variety of
addressable devices. Non-addressable devices
are connected via addressable module.
FIRE
FIRE
SILENT KNIGHT
Addressable
Pull Station
Addressable
Heat Detector
4.7K
EOLR
NAC #1
Addressable
Smoke Detector
Addressable
Input Module
(Waterflow)
Addressable
Smoke Detector
Addressable
Relay Module
(Fan Shutdown)
Addressable Systems
Each point on the SLC loop is given
a unique address when installed.
001 002
003
004
005
006
FACP
FIRE
FIRE
SILENT KNIGHT
Addressable
Pull Station
Addressable
Relay Module
(Fan Shutdown)
Addressable
Heat Detector
4.7K
EOLR
NAC #1
Addressable
Smoke Detector
Addressable
Input Module
(Waterflow)
Addressable
Smoke Detector
Addressable Systems
Supervision is accomplished from
the panel by polling the devices on
the SLC loop.
001 002
003
004
005
006
FACP
FIRE
FIRE
SILENT KNIGHT
Addressable
Pull Station
Addressable
Relay Module
(Fan Shutdown)
Addressable
Heat Detector
4.7K
EOLR
Addressable
Smoke Detector
Addressable
Input Module
(Waterflow)
Addressable
Smoke Detector
NAC #1
Addressable Systems
Supervision is accomplished from
the panel by polling the devices on
the SLC loop.
001 002
003
004
005
006
FACP
FIRE
FIRE
SILENT KNIGHT
Addressable
Pull Station
Addressable
Relay Module
(Fan Shutdown)
Addressable
Heat Detector
4.7K
EOLR
Addressable
Smoke Detector
Addressable
Input Module
(Waterflow)
Addressable
Smoke Detector
NAC #1
Addressable Systems
Supervision is accomplished from
the panel by polling the devices on
the SLC loop.
001 002
003
004
005
006
FACP
FIRE
FIRE
SILENT KNIGHT
Addressable
Pull Station
Addressable
Relay Module
(Fan Shutdown)
Addressable
Heat Detector
4.7K
EOLR
Addressable
Smoke Detector
Addressable
Input Module
(Waterflow)
Addressable
Smoke Detector
NAC #1
Addressable Systems
Supervision is accomplished from
the panel by polling the devices on
the SLC loop.
001 002
003
004
005
006
FACP
FIRE
FIRE
SILENT KNIGHT
Addressable
Pull Station
Addressable
Relay Module
(Fan Shutdown)
Addressable
Heat Detector
4.7K
EOLR
Addressable
Smoke Detector
Addressable
Input Module
(Waterflow)
Addressable
Smoke Detector
NAC #1
Addressable Systems
Supervision is accomplished from
the panel by polling the devices on
the SLC loop.
001 002
003
004
005
006
FACP
FIRE
FIRE
SILENT KNIGHT
Addressable
Pull Station
Addressable
Relay Module
(Fan Shutdown)
Addressable
Heat Detector
4.7K
EOLR
Addressable
Smoke Detector
Addressable
Input Module
(Waterflow)
Addressable
Smoke Detector
NAC #1
Addressable Systems
Supervision is accomplished from
the panel by polling the devices on
the SLC loop.
001 002
003
004
005
006
FACP
FIRE
FIRE
SILENT KNIGHT
Addressable
Pull Station
Addressable
Relay Module
(Fan Shutdown)
Addressable
Heat Detector
4.7K
EOLR
Addressable
Smoke Detector
Addressable
Input Module
(Waterflow)
Addressable
Smoke Detector
NAC #1
Addressable Systems
Supervision is accomplished from
the panel by polling the devices on
the SLC loop.
001 002
003
004
005
006
FACP
FIRE
FIRE
SILENT KNIGHT
Addressable
Pull Station
Addressable
Relay Module
(Fan Shutdown)
Addressable
Heat Detector
4.7K
EOLR
Addressable
Smoke Detector
Addressable
Input Module
(Waterflow)
Addressable
Smoke Detector
NAC #1
Addressable Systems
Supervision is accomplished from
the panel by polling the devices on
the SLC loop.
001 002
003
004
005
006
FACP
FIRE
FIRE
SILENT KNIGHT
Addressable
Pull Station
Addressable
Relay Module
(Fan Shutdown)
Addressable
Heat Detector
4.7K
EOLR
Addressable
Smoke Detector
Addressable
Input Module
(Waterflow)
Addressable
Smoke Detector
NAC #1
Addressable Systems
Supervision is accomplished from
the panel by polling the devices on
the SLC loop.
001 002
003
004
005
006
FACP
FIRE
FIRE
SILENT KNIGHT
Addressable
Pull Station
Addressable
Relay Module
(Fan Shutdown)
Addressable
Heat Detector
4.7K
EOLR
Addressable
Smoke Detector
Addressable
Input Module
(Waterflow)
Addressable
Smoke Detector
NAC #1
Addressable Systems
Supervision is accomplished from
the panel by polling the devices on
the SLC loop.
001 002
003
004
005
006
FACP
FIRE
FIRE
SILENT KNIGHT
Addressable
Pull Station
Addressable
Relay Module
(Fan Shutdown)
Addressable
Heat Detector
4.7K
EOLR
Addressable
Smoke Detector
Addressable
Input Module
(Waterflow)
Addressable
Smoke Detector
NAC #1
Addressable Systems
Supervision is accomplished from
the panel by polling the devices on
the SLC loop.
001 002
003
004
005
006
FACP
FIRE
FIRE
SILENT KNIGHT
Addressable
Pull Station
Addressable
Relay Module
(Fan Shutdown)
Addressable
Heat Detector
4.7K
EOLR
Addressable
Smoke Detector
Addressable
Input Module
(Waterflow)
Addressable
Smoke Detector
NAC #1
Addressable Systems
Supervision is accomplished from
the panel by polling the devices on
the SLC loop.
001 002
003
004
005
006
FIRE
FIRE
SILENT KNIGHT
Addressable
Pull Station
Addressable
Relay Module
(Fan Shutdown)
Addressable
Heat Detector
4.7K
EOLR
Addressable
Smoke Detector
Addressable
Input Module
(Waterflow)
Addressable
Smoke Detector
FACP
NAC #1
Addressable Systems
Supervision is accomplished from
the panel by polling the devices on
the SLC loop.
< Replay
001 002
003
004
005
006
FACP
FIRE
FIRE
SILENT KNIGHT
Addressable
Pull Station
Addressable
Relay Module
(Fan Shutdown)
Addressable
Heat Detector
4.7K
EOLR
Addressable
Smoke Detector
Addressable
Input Module
(Waterflow)
Addressable
Smoke Detector
NAC #1
Addressable Systems
Alarm conditions are annunciated
by point allowing responding
personnel to quickly find the fire.
ALARM POINT 006
LOBBY SMOKE DETECTOR
001 002
003
004
005
006
FACP
FIRE
FIRE
SILENT KNIGHT
Addressable
Pull Station
Addressable
Relay Module
(Fan Shutdown)
Addressable
Heat Detector
4.7K
EOLR
Addressable
Smoke Detector
Addressable
Input Module
(Waterflow)
Addressable
Smoke Detector
NAC #1
FIRE!
Addressable Systems
Trouble conditions can be located
more quickly by analyzing the
affected points.
TRBL POINT 006
DISCONNECTED
LOBBY SMOKE DETECTOR
001 002
003
004
005
006
FACP
FIRE
FIRE
SILENT KNIGHT
Addressable
Pull Station
Addressable
Relay Module
(Fan Shutdown)
Addressable
Heat Detector
4.7K
EOLR
Addressable
Smoke Detector
Addressable
Input Module
(Waterflow)
Addressable
Smoke Detector
NAC #1
Addressable Systems
More detailed information can be
sent to the central station aiding in
a quick resolution to the problem.
RJ
RJ
001 002
003
004
005
006
FACP
FIRE
FIRE
SILENT KNIGHT
Addressable
Pull Station
Addressable
Relay Module
(Fan Shutdown)
Addressable
Heat Detector
4.7K
EOLR
Addressable
Smoke Detector
Addressable
Input Module
(Waterflow)
Addressable
Smoke Detector
NAC #1
Addressable Systems
Since supervision is accomplished
through polling, t-tapped wiring is
permitted. (Class B wiring)
001 002
003
004
005
006
FACP
FIRE
FIRE
SILENT KNIGHT
Addressable
Pull Station
Addressable
Relay Module
(Fan Shutdown)
Addressable
Heat Detector
4.7K
EOLR
Addressable
Smoke Detector
Addressable
Input Module
(Waterflow)
Addressable
Smoke Detector
NAC #1
Addressable Systems
Many systems support flexible
input/output programming to link
initiating devices to outputs.
001 002
003
004
005
006
FACP
FIRE
FIRE
SILENT KNIGHT
Addressable
Pull Station
Addressable
Relay Module
(Fan Shutdown)
Addressable
Heat Detector
4.7K
EOLR
Addressable
Smoke Detector
Addressable
Input Module
(Waterflow)
Addressable
Smoke Detector
NAC #1
FIRE!
Comparison
 Conventional
 Lower initial equipment costs.
 Wide range of compatible devices.
 Can be easier to program.
 Limited expansion capability.
 Addressable
 Easier to install.
 More system status information at
the panel and central station.
 Input/Output programming much
more flexible.
 Usually much more room
available to expand.
Analog Addressable Systems
 Detectors in an analog addressable systems
become “sensors” relaying information to the
control panel corresponding to how much
smoke or heat that detector is sensing.
 The control panel makes the decisions based
on this information when to alarm etc.
Analog Addressable Systems
Addressable
Relay Module
(Fan Shutdown)
Addressable
Heat Sensor
10K
EOLR
Addressable
Smoke Sensor
Addressable
Input Module
(Waterflow)
001 002
003
004
005
Addressable
Pull Station
Addressable
Smoke Sensor
006
HEAT DETECTOR
MECHANICAL ROOM
POINT 001 A=062
NORMAL F=190
Supervision is still checked by
polling. In addition an analog
value is transmitted to the
panel for processing.
NAC #1
Analog Addressable Systems
SMOKE DETECTOR
LOBBY NORTH
POINT 002 A=060
NORMAL F=188
Supervision is still checked by
polling. In addition an analog
value is transmitted to the
panel for processing.
Addressable
Relay Module
(Fan Shutdown)
Addressable
Heat Sensor
Addressable
Smoke Sensor
Addressable
Input Module
(Waterflow)
001 002
003
004
005
Addressable
Pull Station
Addressable
Smoke Detector
006
10K
EOLR
NAC #1
Analog Addressable Systems
RELAY MODULE
FAN SHUTDOWN
POINT 003 A=N/A
NORMAL F=N/A
Supervision is still checked by
polling. In addition an analog
value is transmitted to the
panel for processing.
Addressable
Relay Module
(Fan Shutdown)
Addressable
Heat Sensor
Addressable
Smoke Sensor
Addressable
Input Module
(Waterflow)
001 002
003
004
005
Addressable
Pull Station
Addressable
Smoke Sensor
006
10K
EOLR
NAC #1
Analog Addressable Systems
INPUT MODULE
WATERFLOW
POINT 004 A=N/A
NORMAL F=N/A
Supervision is still checked by
polling. In addition an analog
value is transmitted to the
panel for processing.
Addressable
Relay Module
(Fan Shutdown)
Addressable
Heat Sensor
Addressable
Smoke Sensor
Addressable
Input Module
(Waterflow)
001 002
003
004
005
Addressable
Pull Station
Addressable
Smoke Sensor
006
10K
EOLR
NAC #1
Analog Addressable Systems
Supervision is still checked by
polling. In addition an analog
value is transmitted to the
panel for processing.
INPUT MODULE
MANUAL PULL
POINT 005 A=N/A
NORMAL F=N/A
Addressable
Relay Module
(Fan Shutdown)
Addressable
Heat Sensor
Addressable
Smoke Sensor
Addressable
Input Module
(Waterflow)
001 002
003
004
005
Addressable
Pull Station
Addressable
Smoke Sensor
006
10K
EOLR
NAC #1
Analog Addressable Systems
SMOKE DETECTOR
FRONT DESK
POINT 006 A=061
NORMAL F=189
Supervision is still checked by
polling. In addition an analog
value is transmitted to the
panel for processing.
Addressable
Relay Module
(Fan Shutdown)
Addressable
Heat Sensor
Addressable
Smoke Sensor
Addressable
Input Module
(Waterflow)
001 002
003
004
005
Addressable
Pull Station
Addressable
Smoke Sensor
006
10K
EOLR
NAC #1
Analog Addressable Systems
HEAT DETECTOR
MECHANICAL ROOM
POINT 001 A=062
NORMAL F=190
Supervision is still checked by
polling. In addition an analog
value is transmitted to the
panel for processing.
Addressable
Relay Module
(Fan Shutdown)
Addressable
Heat Sensor
Addressable
Smoke Sensor
Addressable
Input Module
(Waterflow)
001 002
003
004
005
Addressable
Pull Station
Addressable
Smoke Sensor
006
10K
EOLR
NAC #1
Analog Addressable Systems
SMOKE DETECTOR
LOBBY NORTH
POINT 002 A=060
NORMAL F=188
Supervision is still checked by
polling. In addition an analog
value is transmitted to the
panel for processing.
Addressable
Relay Module
(Fan Shutdown)
Addressable
Heat Sensor
Addressable
Smoke Sensor
Addressable
Input Module
(Waterflow)
001 002
003
004
005
Addressable
Pull Station
Addressable
Smoke Sensor
006
10K
EOLR
NAC #1
Analog Addressable Systems
RELAY MODULE
FAN SHUTDOWN
POINT 003 A=N/A
NORMAL F=N/A
Supervision is still checked by
polling. In addition an analog
value is transmitted to the
panel for processing.
Addressable
Relay Module
(Fan Shutdown)
Addressable
Heat Sensor
Addressable
Smoke Sensor
Addressable
Input Module
(Waterflow)
001 002
003
004
005
Addressable
Pull Station
Addressable
Smoke Sensor
006
10K
EOLR
NAC #1
Analog Addressable Systems
INPUT MODULE
WATERFLOW
POINT 004 A=N/A
NORMAL F=N/A
Supervision is still checked by
polling. In addition an analog
value is transmitted to the
panel for processing.
Addressable
Relay Module
(Fan Shutdown)
Addressable
Heat Sensor
Addressable
Smoke Sensor
Addressable
Input Module
(Waterflow)
001 002
003
004
005
Addressable
Pull Station
Addressable
Smoke Sensor
006
10K
EOLR
NAC #1
Analog Addressable Systems
Supervision is still checked by
polling. In addition an analog
value is transmitted to the
panel for processing.
INPUT MODULE
MANUAL PULL
POINT 005 A=N/A
NORMAL F=N/A
Addressable
Relay Module
(Fan Shutdown)
Addressable
Heat Sensor
Addressable
Smoke Sensor
Addressable
Input Module
(Waterflow)
001 002
003
004
005
Addressable
Pull Station
Addressable
Smoke Sensor
006
10K
EOLR
NAC #1
Analog Addressable Systems
SMOKE DETECTOR
FRONT DESK
POINT 006 A=061
NORMAL F=189
< Replay
Addressable
Relay Module
(Fan Shutdown)
Addressable
Heat Sensor
Addressable
Smoke Sensor
Addressable
Input Module
(Waterflow)
001 002
003
004
005
Addressable
Pull Station
Addressable
Smoke Sensor
006
10K
EOLR
NAC #1
Analog Addressable Systems
This analog value corresponds
to the amount of heat or
smoke in that detectors area
of coverage. Higher = more.
HEAT DETECTOR
MECHANICAL ROOM
POINT 001 A=062
NORMAL F=190
Addressable
Relay Module
(Fan Shutdown)
Addressable
Heat Sensor
Addressable
Smoke Sensor
Addressable
Input Module
(Waterflow)
001 002
003
004
005
Addressable
Pull Station
Addressable
Smoke Sensor
006
10K
EOLR
NAC #1
Analog Addressable Systems
If the analog value exceeds
the alarm threshold, an alarm
occurs. This alarm threshold is
calculated by the panel.
HEAT DETECTOR
MECHANICAL ROOM
POINT 001 A=062
NORMAL F=190
Addressable
Relay Module
(Fan Shutdown)
Addressable
Heat Sensor
Addressable
Smoke Sensor
Addressable
Input Module
(Waterflow)
001 002
003
004
005
Addressable
Pull Station
Addressable
Smoke Sensor
006
10K
EOLR
NAC #1
Analog Addressable Systems
INPUT MODULE
WATERFLOW
POINT 004 A=N/A
NORMAL F=N/A
Input/output modules do not
relay analog values to the
panel as they are monitoring
or controlling on/off devices.
Addressable
Relay Module
(Fan Shutdown)
Addressable
Heat Sensor
Addressable
Smoke Sensor
Addressable
Input Module
(Waterflow)
001 002
003
004
005
Addressable
Pull Station
Addressable
Smoke Sensor
006
10K
EOLR
NAC #1
THE END

More Related Content

PDF
Fire Alarm System.pdf
PDF
FIRE ALARM SYSTEM.pdf
PDF
FireAlarmSystemOperationalBasics (1).pdf
PPT
Fire Alarm protection and detection note 22.ppt
PDF
Addressable fire alarm system
PDF
The Fire Detection and the alarm system
PDF
Fire Alarm ... Design, Components, Applications
PPT
gersgtsedgdfgsrqw3terydrh
Fire Alarm System.pdf
FIRE ALARM SYSTEM.pdf
FireAlarmSystemOperationalBasics (1).pdf
Fire Alarm protection and detection note 22.ppt
Addressable fire alarm system
The Fire Detection and the alarm system
Fire Alarm ... Design, Components, Applications
gersgtsedgdfgsrqw3terydrh

Similar to FIRE DETECTION AND ALARM SYSTEM_FUNCTIONALITY.pptx (20)

PDF
Fire Alarm System for safety of electrical systems
PPTX
Fire Detection and Alarm Systems
PPT
Intro to basic fire alarm technology
PDF
HST New Fire Alarm System
PPTX
Demystifying Fault Isolators
PPT
Fire basics 1-1-fundamentals
PDF
2015 Hochiki Product Catalog_Reduced
PDF
Fundamental training on Fire Detection & Alarm System
PPTX
1540 Ch 3 PowerPoint.pptx
PDF
ES-200X Ficha técnica.pdf
PDF
FIRE DETECTION & ALARM SYSTEMS.pdf
PDF
Lecture 5 Fire Alarm System.pdf
PPT
Fire detection & alarm system
PPTX
UNIT-V FIRE SAFETY INSTALLATION
PPTX
UNIT-5.pptx
PPT
Chapter 07
PDF
Smartline020 4-f user-manual
PPTX
Overview of Fire Alarm Systems.pptx
PPTX
Fire detectionand alarm systems 090512042400-phpapp01(1)
PDF
Re 700
Fire Alarm System for safety of electrical systems
Fire Detection and Alarm Systems
Intro to basic fire alarm technology
HST New Fire Alarm System
Demystifying Fault Isolators
Fire basics 1-1-fundamentals
2015 Hochiki Product Catalog_Reduced
Fundamental training on Fire Detection & Alarm System
1540 Ch 3 PowerPoint.pptx
ES-200X Ficha técnica.pdf
FIRE DETECTION & ALARM SYSTEMS.pdf
Lecture 5 Fire Alarm System.pdf
Fire detection & alarm system
UNIT-V FIRE SAFETY INSTALLATION
UNIT-5.pptx
Chapter 07
Smartline020 4-f user-manual
Overview of Fire Alarm Systems.pptx
Fire detectionand alarm systems 090512042400-phpapp01(1)
Re 700
Ad

Recently uploaded (20)

PPTX
KOM of Painting work and Equipment Insulation REV00 update 25-dec.pptx
PPTX
Tartificialntelligence_presentation.pptx
PDF
7 ChatGPT Prompts to Help You Define Your Ideal Customer Profile.pdf
PDF
Unlocking AI with Model Context Protocol (MCP)
PDF
project resource management chapter-09.pdf
PDF
Hindi spoken digit analysis for native and non-native speakers
PDF
Transform Your ITIL® 4 & ITSM Strategy with AI in 2025.pdf
PDF
Enhancing emotion recognition model for a student engagement use case through...
PPTX
A Presentation on Touch Screen Technology
PPTX
1. Introduction to Computer Programming.pptx
PDF
Encapsulation theory and applications.pdf
PDF
DP Operators-handbook-extract for the Mautical Institute
PDF
Assigned Numbers - 2025 - Bluetooth® Document
PPTX
Programs and apps: productivity, graphics, security and other tools
PDF
Video forgery: An extensive analysis of inter-and intra-frame manipulation al...
PDF
Encapsulation_ Review paper, used for researhc scholars
PDF
A comparative analysis of optical character recognition models for extracting...
PDF
Mushroom cultivation and it's methods.pdf
PDF
WOOl fibre morphology and structure.pdf for textiles
PDF
DASA ADMISSION 2024_FirstRound_FirstRank_LastRank.pdf
KOM of Painting work and Equipment Insulation REV00 update 25-dec.pptx
Tartificialntelligence_presentation.pptx
7 ChatGPT Prompts to Help You Define Your Ideal Customer Profile.pdf
Unlocking AI with Model Context Protocol (MCP)
project resource management chapter-09.pdf
Hindi spoken digit analysis for native and non-native speakers
Transform Your ITIL® 4 & ITSM Strategy with AI in 2025.pdf
Enhancing emotion recognition model for a student engagement use case through...
A Presentation on Touch Screen Technology
1. Introduction to Computer Programming.pptx
Encapsulation theory and applications.pdf
DP Operators-handbook-extract for the Mautical Institute
Assigned Numbers - 2025 - Bluetooth® Document
Programs and apps: productivity, graphics, security and other tools
Video forgery: An extensive analysis of inter-and intra-frame manipulation al...
Encapsulation_ Review paper, used for researhc scholars
A comparative analysis of optical character recognition models for extracting...
Mushroom cultivation and it's methods.pdf
WOOl fibre morphology and structure.pdf for textiles
DASA ADMISSION 2024_FirstRound_FirstRank_LastRank.pdf
Ad

FIRE DETECTION AND ALARM SYSTEM_FUNCTIONALITY.pptx

  • 1. Fire Detection and Alarm System Basics
  • 2. Class B Initiating Device Circuit 4.7K EOLR 4.7K EOLR Class B Notification Appliance Circuit Class B Circuits End of line supervision resistors are required to supervise the integrity of the loop.
  • 3. Single open circuit condition causes a trouble on the panel and renders all devices beyond the fault inoperative. Class B Initiating Device Circuit 4.7K EOLR 4.7K EOLR Class B Notification Appliance Circuit Class B Circuits
  • 4. Class A Initiating Device Circuit Class A Notification Appliance Circuit Class A Circuits End of line supervision resistors are not necessary as the loop returns to the panel and is driven from both ends.
  • 5. Class A Initiating Device Circuit Class A Notification Appliance Circuit Class A Circuits Single open circuit condition causes a trouble on the panel. All devices on the loop remain operative.
  • 6. Addressable Device - A fire alarm system component with discreet identification that can have its status individually identified or that is used to individually control other functions. Analog Addressable Sensor - An initiating device that transmits a signal indicating varying degrees of condition as contrasted with a conventional or addressable initiating device, which can only indicate an off/on condition. Fire Alarm Terminology
  • 7. Protocol - A language for communicating between control panels and their proprietary devices. SLC Interface - A system component that connects a signaling line circuit to any combination of initiating devices, initiating device circuits, notification appliances, notification appliance circuits, system control outputs and other signaling line circuits. Signaling Line Circuit (SLC) - A circuit or path between any combination of circuit interfaces, control units, or transmitters over which multiple system input signals or out put signals or both are carried.
  • 8.  Conventional control panels range in size from 1 zone to over 100 zones.  Zones typically consist of some or all of the initiating devices in an area or floor of a building.  Some control panels zone capacity is expandable while others are not, limiting its usefulness if a facility adds additional buildings or rooms. Comparing System Types To better understand today’s newer technology, a firm understanding of the types of systems available is necessary. The three most popular types of systems installed today are: • Conventional • Addressable • Analog Addressable Conventional Systems
  • 9. Conventional Systems Zone 1 4.7K EOLR Zone 2 FIRE FIRE SILENT KNIGHT FIRE FIRE SILENT KNIGHT FIRE FIRE SILENT KNIGHT FIRE FIRE SILENT KNIGHT FIRE FIRE SILENT KNIGHT FACP NAC 1 Multiple devices are combined into a single zone. Zones can contain 30 or more devices. 4.7K EOLR
  • 10. Conventional Systems Care must be taken when laying out zones to comply with code requirements. Zone 1 4.7K EOLR Zone 2 FIRE FIRE SILENT KNIGHT NAC 1 4.7K EOLR
  • 11. Zone Considerations  2007 NFPA 72 6.8.5.5.2 Limits the number of waterflow switches in a single zone to 5.  2007 NFPA 72 6.8.5.6.2 Limits the number of supervisory devices in a single zone to 20.  2007 NFPA 72 Annex A.4.4.6.6 Suggests that the maximum number of square feet in a single zone be limited to no more than 22,500.
  • 12. Conventional Systems Wiring must be installed in a supervised manner either Class A, or Class B with an EOLR. Zone #1 4.7K EOLR 4.7K EOLR Zone #2 NAC #1
  • 13. Conventional Systems Alarm conditions are annunciated by zone only. Inspection is required to determine the device. Zone #1 4.7K EOLR 4.7K EOLR Zone #2 NAC #1 FIRE!
  • 14. Conventional Systems Trouble conditions are annunciated by zone only. Inspection is required to determine the cause. 4.7K EOLR Zone #1 4.7K EOLR 4.7K EOLR Zone #2 NAC #1
  • 15. Conventional Systems Information transmitted to the central station is by zone at best. Many panels send Alarm, Supv, Trbl only. RJ RJ Zone #1 4.7K EOLR 4.7K EOLR Zone #2 NAC #1
  • 16. Addressable Systems  An addressable systems point capacity is determined by the amount of SLC “Signaling Line Circuits” it contains.  Each SLC circuit provides power, communication, & supervision for all of the devices connected to it.  Each SLC can accommodate over 100 addressable devices, depending upon the manufacturer. FACP
  • 17. Addressable Systems FACP Each SLC loop can contain a variety of addressable devices. Non-addressable devices are connected via addressable module. FIRE FIRE SILENT KNIGHT Addressable Pull Station Addressable Heat Detector 4.7K EOLR NAC #1 Addressable Smoke Detector Addressable Input Module (Waterflow) Addressable Smoke Detector Addressable Relay Module (Fan Shutdown)
  • 18. Addressable Systems Each point on the SLC loop is given a unique address when installed. 001 002 003 004 005 006 FACP FIRE FIRE SILENT KNIGHT Addressable Pull Station Addressable Relay Module (Fan Shutdown) Addressable Heat Detector 4.7K EOLR NAC #1 Addressable Smoke Detector Addressable Input Module (Waterflow) Addressable Smoke Detector
  • 19. Addressable Systems Supervision is accomplished from the panel by polling the devices on the SLC loop. 001 002 003 004 005 006 FACP FIRE FIRE SILENT KNIGHT Addressable Pull Station Addressable Relay Module (Fan Shutdown) Addressable Heat Detector 4.7K EOLR Addressable Smoke Detector Addressable Input Module (Waterflow) Addressable Smoke Detector NAC #1
  • 20. Addressable Systems Supervision is accomplished from the panel by polling the devices on the SLC loop. 001 002 003 004 005 006 FACP FIRE FIRE SILENT KNIGHT Addressable Pull Station Addressable Relay Module (Fan Shutdown) Addressable Heat Detector 4.7K EOLR Addressable Smoke Detector Addressable Input Module (Waterflow) Addressable Smoke Detector NAC #1
  • 21. Addressable Systems Supervision is accomplished from the panel by polling the devices on the SLC loop. 001 002 003 004 005 006 FACP FIRE FIRE SILENT KNIGHT Addressable Pull Station Addressable Relay Module (Fan Shutdown) Addressable Heat Detector 4.7K EOLR Addressable Smoke Detector Addressable Input Module (Waterflow) Addressable Smoke Detector NAC #1
  • 22. Addressable Systems Supervision is accomplished from the panel by polling the devices on the SLC loop. 001 002 003 004 005 006 FACP FIRE FIRE SILENT KNIGHT Addressable Pull Station Addressable Relay Module (Fan Shutdown) Addressable Heat Detector 4.7K EOLR Addressable Smoke Detector Addressable Input Module (Waterflow) Addressable Smoke Detector NAC #1
  • 23. Addressable Systems Supervision is accomplished from the panel by polling the devices on the SLC loop. 001 002 003 004 005 006 FACP FIRE FIRE SILENT KNIGHT Addressable Pull Station Addressable Relay Module (Fan Shutdown) Addressable Heat Detector 4.7K EOLR Addressable Smoke Detector Addressable Input Module (Waterflow) Addressable Smoke Detector NAC #1
  • 24. Addressable Systems Supervision is accomplished from the panel by polling the devices on the SLC loop. 001 002 003 004 005 006 FACP FIRE FIRE SILENT KNIGHT Addressable Pull Station Addressable Relay Module (Fan Shutdown) Addressable Heat Detector 4.7K EOLR Addressable Smoke Detector Addressable Input Module (Waterflow) Addressable Smoke Detector NAC #1
  • 25. Addressable Systems Supervision is accomplished from the panel by polling the devices on the SLC loop. 001 002 003 004 005 006 FACP FIRE FIRE SILENT KNIGHT Addressable Pull Station Addressable Relay Module (Fan Shutdown) Addressable Heat Detector 4.7K EOLR Addressable Smoke Detector Addressable Input Module (Waterflow) Addressable Smoke Detector NAC #1
  • 26. Addressable Systems Supervision is accomplished from the panel by polling the devices on the SLC loop. 001 002 003 004 005 006 FACP FIRE FIRE SILENT KNIGHT Addressable Pull Station Addressable Relay Module (Fan Shutdown) Addressable Heat Detector 4.7K EOLR Addressable Smoke Detector Addressable Input Module (Waterflow) Addressable Smoke Detector NAC #1
  • 27. Addressable Systems Supervision is accomplished from the panel by polling the devices on the SLC loop. 001 002 003 004 005 006 FACP FIRE FIRE SILENT KNIGHT Addressable Pull Station Addressable Relay Module (Fan Shutdown) Addressable Heat Detector 4.7K EOLR Addressable Smoke Detector Addressable Input Module (Waterflow) Addressable Smoke Detector NAC #1
  • 28. Addressable Systems Supervision is accomplished from the panel by polling the devices on the SLC loop. 001 002 003 004 005 006 FACP FIRE FIRE SILENT KNIGHT Addressable Pull Station Addressable Relay Module (Fan Shutdown) Addressable Heat Detector 4.7K EOLR Addressable Smoke Detector Addressable Input Module (Waterflow) Addressable Smoke Detector NAC #1
  • 29. Addressable Systems Supervision is accomplished from the panel by polling the devices on the SLC loop. 001 002 003 004 005 006 FACP FIRE FIRE SILENT KNIGHT Addressable Pull Station Addressable Relay Module (Fan Shutdown) Addressable Heat Detector 4.7K EOLR Addressable Smoke Detector Addressable Input Module (Waterflow) Addressable Smoke Detector NAC #1
  • 30. Addressable Systems Supervision is accomplished from the panel by polling the devices on the SLC loop. 001 002 003 004 005 006 FIRE FIRE SILENT KNIGHT Addressable Pull Station Addressable Relay Module (Fan Shutdown) Addressable Heat Detector 4.7K EOLR Addressable Smoke Detector Addressable Input Module (Waterflow) Addressable Smoke Detector FACP NAC #1
  • 31. Addressable Systems Supervision is accomplished from the panel by polling the devices on the SLC loop. < Replay 001 002 003 004 005 006 FACP FIRE FIRE SILENT KNIGHT Addressable Pull Station Addressable Relay Module (Fan Shutdown) Addressable Heat Detector 4.7K EOLR Addressable Smoke Detector Addressable Input Module (Waterflow) Addressable Smoke Detector NAC #1
  • 32. Addressable Systems Alarm conditions are annunciated by point allowing responding personnel to quickly find the fire. ALARM POINT 006 LOBBY SMOKE DETECTOR 001 002 003 004 005 006 FACP FIRE FIRE SILENT KNIGHT Addressable Pull Station Addressable Relay Module (Fan Shutdown) Addressable Heat Detector 4.7K EOLR Addressable Smoke Detector Addressable Input Module (Waterflow) Addressable Smoke Detector NAC #1 FIRE!
  • 33. Addressable Systems Trouble conditions can be located more quickly by analyzing the affected points. TRBL POINT 006 DISCONNECTED LOBBY SMOKE DETECTOR 001 002 003 004 005 006 FACP FIRE FIRE SILENT KNIGHT Addressable Pull Station Addressable Relay Module (Fan Shutdown) Addressable Heat Detector 4.7K EOLR Addressable Smoke Detector Addressable Input Module (Waterflow) Addressable Smoke Detector NAC #1
  • 34. Addressable Systems More detailed information can be sent to the central station aiding in a quick resolution to the problem. RJ RJ 001 002 003 004 005 006 FACP FIRE FIRE SILENT KNIGHT Addressable Pull Station Addressable Relay Module (Fan Shutdown) Addressable Heat Detector 4.7K EOLR Addressable Smoke Detector Addressable Input Module (Waterflow) Addressable Smoke Detector NAC #1
  • 35. Addressable Systems Since supervision is accomplished through polling, t-tapped wiring is permitted. (Class B wiring) 001 002 003 004 005 006 FACP FIRE FIRE SILENT KNIGHT Addressable Pull Station Addressable Relay Module (Fan Shutdown) Addressable Heat Detector 4.7K EOLR Addressable Smoke Detector Addressable Input Module (Waterflow) Addressable Smoke Detector NAC #1
  • 36. Addressable Systems Many systems support flexible input/output programming to link initiating devices to outputs. 001 002 003 004 005 006 FACP FIRE FIRE SILENT KNIGHT Addressable Pull Station Addressable Relay Module (Fan Shutdown) Addressable Heat Detector 4.7K EOLR Addressable Smoke Detector Addressable Input Module (Waterflow) Addressable Smoke Detector NAC #1 FIRE!
  • 37. Comparison  Conventional  Lower initial equipment costs.  Wide range of compatible devices.  Can be easier to program.  Limited expansion capability.  Addressable  Easier to install.  More system status information at the panel and central station.  Input/Output programming much more flexible.  Usually much more room available to expand.
  • 38. Analog Addressable Systems  Detectors in an analog addressable systems become “sensors” relaying information to the control panel corresponding to how much smoke or heat that detector is sensing.  The control panel makes the decisions based on this information when to alarm etc.
  • 39. Analog Addressable Systems Addressable Relay Module (Fan Shutdown) Addressable Heat Sensor 10K EOLR Addressable Smoke Sensor Addressable Input Module (Waterflow) 001 002 003 004 005 Addressable Pull Station Addressable Smoke Sensor 006 HEAT DETECTOR MECHANICAL ROOM POINT 001 A=062 NORMAL F=190 Supervision is still checked by polling. In addition an analog value is transmitted to the panel for processing. NAC #1
  • 40. Analog Addressable Systems SMOKE DETECTOR LOBBY NORTH POINT 002 A=060 NORMAL F=188 Supervision is still checked by polling. In addition an analog value is transmitted to the panel for processing. Addressable Relay Module (Fan Shutdown) Addressable Heat Sensor Addressable Smoke Sensor Addressable Input Module (Waterflow) 001 002 003 004 005 Addressable Pull Station Addressable Smoke Detector 006 10K EOLR NAC #1
  • 41. Analog Addressable Systems RELAY MODULE FAN SHUTDOWN POINT 003 A=N/A NORMAL F=N/A Supervision is still checked by polling. In addition an analog value is transmitted to the panel for processing. Addressable Relay Module (Fan Shutdown) Addressable Heat Sensor Addressable Smoke Sensor Addressable Input Module (Waterflow) 001 002 003 004 005 Addressable Pull Station Addressable Smoke Sensor 006 10K EOLR NAC #1
  • 42. Analog Addressable Systems INPUT MODULE WATERFLOW POINT 004 A=N/A NORMAL F=N/A Supervision is still checked by polling. In addition an analog value is transmitted to the panel for processing. Addressable Relay Module (Fan Shutdown) Addressable Heat Sensor Addressable Smoke Sensor Addressable Input Module (Waterflow) 001 002 003 004 005 Addressable Pull Station Addressable Smoke Sensor 006 10K EOLR NAC #1
  • 43. Analog Addressable Systems Supervision is still checked by polling. In addition an analog value is transmitted to the panel for processing. INPUT MODULE MANUAL PULL POINT 005 A=N/A NORMAL F=N/A Addressable Relay Module (Fan Shutdown) Addressable Heat Sensor Addressable Smoke Sensor Addressable Input Module (Waterflow) 001 002 003 004 005 Addressable Pull Station Addressable Smoke Sensor 006 10K EOLR NAC #1
  • 44. Analog Addressable Systems SMOKE DETECTOR FRONT DESK POINT 006 A=061 NORMAL F=189 Supervision is still checked by polling. In addition an analog value is transmitted to the panel for processing. Addressable Relay Module (Fan Shutdown) Addressable Heat Sensor Addressable Smoke Sensor Addressable Input Module (Waterflow) 001 002 003 004 005 Addressable Pull Station Addressable Smoke Sensor 006 10K EOLR NAC #1
  • 45. Analog Addressable Systems HEAT DETECTOR MECHANICAL ROOM POINT 001 A=062 NORMAL F=190 Supervision is still checked by polling. In addition an analog value is transmitted to the panel for processing. Addressable Relay Module (Fan Shutdown) Addressable Heat Sensor Addressable Smoke Sensor Addressable Input Module (Waterflow) 001 002 003 004 005 Addressable Pull Station Addressable Smoke Sensor 006 10K EOLR NAC #1
  • 46. Analog Addressable Systems SMOKE DETECTOR LOBBY NORTH POINT 002 A=060 NORMAL F=188 Supervision is still checked by polling. In addition an analog value is transmitted to the panel for processing. Addressable Relay Module (Fan Shutdown) Addressable Heat Sensor Addressable Smoke Sensor Addressable Input Module (Waterflow) 001 002 003 004 005 Addressable Pull Station Addressable Smoke Sensor 006 10K EOLR NAC #1
  • 47. Analog Addressable Systems RELAY MODULE FAN SHUTDOWN POINT 003 A=N/A NORMAL F=N/A Supervision is still checked by polling. In addition an analog value is transmitted to the panel for processing. Addressable Relay Module (Fan Shutdown) Addressable Heat Sensor Addressable Smoke Sensor Addressable Input Module (Waterflow) 001 002 003 004 005 Addressable Pull Station Addressable Smoke Sensor 006 10K EOLR NAC #1
  • 48. Analog Addressable Systems INPUT MODULE WATERFLOW POINT 004 A=N/A NORMAL F=N/A Supervision is still checked by polling. In addition an analog value is transmitted to the panel for processing. Addressable Relay Module (Fan Shutdown) Addressable Heat Sensor Addressable Smoke Sensor Addressable Input Module (Waterflow) 001 002 003 004 005 Addressable Pull Station Addressable Smoke Sensor 006 10K EOLR NAC #1
  • 49. Analog Addressable Systems Supervision is still checked by polling. In addition an analog value is transmitted to the panel for processing. INPUT MODULE MANUAL PULL POINT 005 A=N/A NORMAL F=N/A Addressable Relay Module (Fan Shutdown) Addressable Heat Sensor Addressable Smoke Sensor Addressable Input Module (Waterflow) 001 002 003 004 005 Addressable Pull Station Addressable Smoke Sensor 006 10K EOLR NAC #1
  • 50. Analog Addressable Systems SMOKE DETECTOR FRONT DESK POINT 006 A=061 NORMAL F=189 < Replay Addressable Relay Module (Fan Shutdown) Addressable Heat Sensor Addressable Smoke Sensor Addressable Input Module (Waterflow) 001 002 003 004 005 Addressable Pull Station Addressable Smoke Sensor 006 10K EOLR NAC #1
  • 51. Analog Addressable Systems This analog value corresponds to the amount of heat or smoke in that detectors area of coverage. Higher = more. HEAT DETECTOR MECHANICAL ROOM POINT 001 A=062 NORMAL F=190 Addressable Relay Module (Fan Shutdown) Addressable Heat Sensor Addressable Smoke Sensor Addressable Input Module (Waterflow) 001 002 003 004 005 Addressable Pull Station Addressable Smoke Sensor 006 10K EOLR NAC #1
  • 52. Analog Addressable Systems If the analog value exceeds the alarm threshold, an alarm occurs. This alarm threshold is calculated by the panel. HEAT DETECTOR MECHANICAL ROOM POINT 001 A=062 NORMAL F=190 Addressable Relay Module (Fan Shutdown) Addressable Heat Sensor Addressable Smoke Sensor Addressable Input Module (Waterflow) 001 002 003 004 005 Addressable Pull Station Addressable Smoke Sensor 006 10K EOLR NAC #1
  • 53. Analog Addressable Systems INPUT MODULE WATERFLOW POINT 004 A=N/A NORMAL F=N/A Input/output modules do not relay analog values to the panel as they are monitoring or controlling on/off devices. Addressable Relay Module (Fan Shutdown) Addressable Heat Sensor Addressable Smoke Sensor Addressable Input Module (Waterflow) 001 002 003 004 005 Addressable Pull Station Addressable Smoke Sensor 006 10K EOLR NAC #1