Design and Specification of Harmonic Filters for Variable Frequency Drives
Jesús A. Baez Moreno
ITESM (Departamento de Ingeniería Eléctrica)
Monterrey, NL. CP. 64849
ABSTRACT
This paper presents a method that can be applied to
design and specify low voltage harmonic filters for
variable frequency drives. The proposed methodology is
used to analyze an electrical distribution system feeding
a group of variable frequency drives.
1. INTRODUCTION
Generalized use of Variable Frequency Drives has
increased harmonic distortion at electrical distribution
systems. Some pieces of equipment, such as personal
computers, programmable controllers and
microprocessor-based instrumentation are very sensitive
to harmonic distortion. Proper application of harmonic
filters can help to keep harmonic distortion within
acceptable limits.
This paper describes a simple methodology that can be
applied to design harmonic filters for an electrical
system that will feed variable frequency drives. The
proposed methodology calculates the harmonic voltage
attenuation factor produced by filters [1]. Attenuation
factor is then used to estimate voltage harmonic
distortion at the point of connection and also the
harmonic currents injected into the system.
A computer program (EXCEL Macro) was developed
using Visual Basic for Application language to simulate
system performance. The application of this program to
the analysis of a electrical distribution system feeding a
group of VFDs is also presented.
2. SOLUTION METHODOLOGY
Figure 1 shows a one-line diagram of a electrical
distribution system feeding a Variable Frequency Drive
(VFD). The harmonic filter consists of a capacitor and
an inductor connected in series.
~
Utility
Nonlinear
Load (VFD)
Filter
Low Voltage Bus
Figure 1. One-line diagram of the electrical distribution
system feeding the VFD
A harmonic filter modifies all harmonic voltages at the
point of connection(Low Voltage Bus). Maximum
attenuation occurs for the voltage whose frequency is
equal or close to the resonant frequency of the filter. In
order to quantify how harmonic voltages are affected, we
will define the attenuation factor[1] as
( )
a h
V h
Vf h
n =
( )
( )
Where:
V(h): Harmonic voltage without the filter at the low
voltage bus.
Vf(h): The h-th Harmonic voltage with the filter at the
low voltage bus
an(h) : Attenuation factor of the harmonic voltage(h)
due to the (n-th) tuned filter.
Figure 2 illustrates the basic circuit used to calculate the
h-th harmonic attenuation factor produced by the n-th
harmonic filter. In this diagram, I(h) represents the h-th
harmonic injected by the variable frequency drive, Zs(h)
accounts for the system impedance and Zn(h) represents
the n-th harmonic filter impedance at the h-th harmonic.
I(h)
Zn(h)
Zs(h)
jh
SCKVA
−
j
h KVAn
j h
h KVAn
n
2
Figure 2. Circuit used for harmonic voltage calculation.
The n-th harmonic filter impedance at the harmonic
frequency (h) can be expressed in terms of the filter
kVAR(kVAn) and its tuning frequency (hn) as:
Z h
j
kVAn
h
h h
j
kVAn
h h
h h
n
n
( )
( )
= −





 =
−






2
2 2
2
1 n
n
The distribution system impedance seen by the low
voltage bus at the harmonic frequency (h) is related to
the low voltage bus short circuit kVA as follows:
Zs h
j h
SCkVA
( ) =
In order to simplify the calculation, the filter and the
system are represented by their admittance values.
Yn h
kVAn
j
h h
h h
Ys h
SCKVA
jh
( )
( )
=
−






=
n
2
n
2
2
The equivalent admittance seen by the VFD is calculated
by adding Yn(h) and Ys(h)
Yeq h
kVAn
j h
h h
h h
SCKVA
jh
( ) =
−





 +
2
2
n
2
n
2
[ ]
Yeq h
jh
kVAn SCKVA
( ) = +
1
δ
where:
δ =
−






h h
h h
2
2
n
2
n
2
The attenuation factor an(h) is then obtained as [1]:
[ ]
an h
V h
Vf h
Yeq h
Ys h
jh
kVAn SCKVA
SCKVA
jh
an h
kVAn
SCKVA
( )
( )
( )
( )
( )
( )
= = =
+
= +
1
1
δ
δ
When more than one filter is used, the attenuation
factor of the h-th harmonic voltage is given by
( )
( )
an h
kVA
SCKVA
kVA
SCKVA
h h
h h
n n N
n
k
n
k
N
k
( )
( ) ( )
( )
( )
= + + +










=
−
1 1
2
2
2
2
1
δ δ
δ
L
where:
Harmonic currents flowing into the tuned filters and into
the system(utility) with the connected filter(s) can be
calculated as follows:
In h
V h
Zn h
( )
( )
( )
= ; Is h
I h
an h
( )
( )
( )
=
I(h)
Zn(h)
Zs(h)
Is(h) If(h)
+
V(h)
-
Figure 3. Harmonic filter and system current calculation
Once these currents have been calculated, it is possible
to get filter’s specifications with the aid of the worksheet
filter.xls [3]
The above procedure is summarized in the flowchart
shown in Figure 4.
Read system data
UtilitySCMVA,XFMR(ZandkVA)
Drive KVA, Harmonic Spectra (%I(h)),
Displacement power factor
Filter(s) kVAr, Detuning Factors(α)
MaximumallowedTHDV(THDVmax)
Evaluate harmonic Voltages
and THDV without filters
V h I h h
DrivekVA
SCKVA
( ) [% ( )][ ]
=






Calculate attenuation factors an(h),
resulting harmonic voltages and THDV
( )
Vf h
V h
a h
n
( )
( )
= [ ]
THDV Vf h
h
=
=
∑ ( )
2
5
43
[ ]
THDV V h
h
=
=
∑ ( )
2
5
43
THDV<THDVmax?
Modify
filter(s) kVAr
Calculate harmonic
filter loading and harmonics
flowing into the system
Calculate filter specs
using spredasheet filters.xls
NO YES
In h
V h
Zn h
( )
( )
( )
=
SCMVA
13.8 kV 50
5.75% 1000 kVA
12903.2 SCKVA 480 V
THDV 3.58%
472.50 233.62
0.031911 Ω
Ω A RMS 0.03256 Ω
Ω A RMS
500kVAr 250kVAr
@ 600V @ 600V
5-th 7-th
900 kVA
6-pulse 250 HP 480-V CSI VFD(measured)
~
Generate Report
*Voltage/current distortion
* Filter sepecifications)
I s h
I h
an h
( )
( )
( )
=
;
an h
kVA
SCKVA
kVA
SCKVA
n n N
N
( )
( ) ( )
= + + +
1 1 1
δ δ
L
Figure 4. Flowchart for the proposed solution methodology
3. COMPUTER PROGRAM
The computer program was developed in an Excel
Workbook (VFD.XLS), using Visual Basic for
Applications Language[2].
Harmonic Spectra of Variable Frequency Drives is
stored in one worksheet within the same workbook. To
add harmonic spectra of a non listed VFD(or group of
VFDs), the user types in this worksheet a name for this
load and its harmonic spectra.
Simulation results are stored into the following
Worksheets:
1) SUMMARY : Summary of the results obtained in
the simulation (THDV, Filter specs)
2) VOLTAGES: Harmonic voltages in the low voltage
bus without filters, with filters and with plain
capacitors(no tuning reactor)
3) CURRENTS: Harmonic currents flowing into the
system with and without filters, and filter currents
4) FILTER-5: 5th harmonic filter design
specifications
5) FILTER-7: 7th harmonic filter design
specifications
The program was written under the following
assumptions:
1)This application was developed for VFDs operating at
240V and 480 V systems. For applications at 240V, 480
V capacitor banks are used, and the total KVAR rating
is adjusted to the next multiple of 25 kVAR
For applications at 480V , 600 V capacitor banks are
used and the total KVAR rating is adjusted to the next
multiple of 50 kVAR For example, if the user chooses a
300 kVAR bank at 480 V, the required kVAR rating at
600 V is 300(600/480) ^2 = 468.75 kVAR. The bank
kVAr rating is adjusted to 500 kVAR.
2) Load at the low voltage bus consists only of VFDs and
the resistive effect is neglected
3) 5th
and 7th
harmonic voltage distortion at the high
voltage side is given a as 2%. (This value can be
modified in Worksheets FILTER-5 and FILTER-7
4) Voltage at the low voltage bus is assumed constant
(1.0 pu).
4. SIMULATION RESULTS
The proposed methodology and the computer program
(VFD.XLS) were used to simulate the sample electrical
distribution system depicted in figure 5.
UTILITY
5th
7th
SCMVA=50
~
Z (%) = 5.75
1000 KVA
150-HP PWM VFDs
TOTAL LOAD =900 KVA
300 kVAR 150 kVAR
α=0.95 α=0.95
. . .
13.8 kV
480 V
Figure 5. One-line diagram of the electrical system
This system feeds a group of PWM variable frequency
drives with a total load of 900 kVA operating at 0.9(-)
displacement power factor. This loading condition
results in a very high harmonic current and voltage
distortion.
The proposed methodology was used to analyze the
effect of connecting two harmonic filters on low voltage
bus harmonic distortion levels.
Filter 1: 300 kVAR, 5-th harmonic filter tuned at
hn=4.75
Filter 2: 150 kVAR, 7-th harmonic filter tuned at
hn=6.65
The computer program calculates harmonic voltage and
current distortion with and without filters and also
calculates harmonic filter loading. A summary of the
simulation results is presented in figure 6 (actual
program output).
The effect of these harmonic filters on harmonic
voltages and currents distortion is presented in Tables 1
and 2.
Total harmonic current distortion (THDI) is reduced
from 35% to 7.5% and total harmonic voltage distortion
is reduced from 15.76 to 4.56 %.
Figure 7 shows the 5-th harmonic filter spec sheet.
Figure 6. Simulation Results (summary)
Table 1. Voltage at the low voltage bus with and without filters connected
NO FILTERS FILTERS
h %I(h) % V(h) a(h) % Vf(h)
5 33.7 11.753 6.03 1.9504
7 1.09 0.5322 7.66 0.0695
11 7.37 5.6546 2.55 2.2158
13 3.5 3.1736 2.39 1.3287
17 3.5 4.1501 2.25 1.8409
19 2.1 2.783 2.22 1.2526
23 1.6 2.5668 2.18 1.1759
25 1.4 2.4413 2.17 1.1247
29 0.8 1.6182 2.15 0.7513
31 0.9 1.946 2.15 0.906
35 0.6 1.4648 2.14 0.6848
37 0.5 1.2904 2.14 0.6042
41 0.4 1.1439 2.13 0.537
43 0.3 0.8998 2.13 0.4228
THDV(%) 15.176 4.5581
Table 2 . Harmonic currents flowing into the system and harmonic filters loading
XFMR(NO FILTERS) XFMR(FILTERS) 5TH FILTER 7TH FILTER
I(AMPS) I(AMPS) I(AMPS) I(AMPS)
FUNDAMENTAL 1082.5 982.62 402.75 196.90
5 364.8 60.54 347.45 43.18
7 11.8 1.54 1.60 8.66
11 79.8 31.26 21.50 27.02
13 37.9 15.86 10.24 11.78
17 37.9 16.81 10.20 10.88
19 22.7 10.23 6.11 6.39
23 17.3 7.93 4.64 4.75
25 15.2 6.98 4.05 4.12
29 8.7 4.02 2.31 2.33
31 9.7 4.54 2.60 2.61
35 6.5 3.04 1.73 1.73
37 5.4 2.53 1.44 1.44
41 4.3 2.03 1.15 1.14
43 3.2 1.53 0.86 0.86
HARM. CURRENT 379.2 73.85 348.55 55.01
RMS CURRENT 1147.0 985.39 532.63 204.44
THDI (%) 35.0% 7.52%
Low Voltage Filter Calculations: Example Filter Design Spreadsheet
SYSTEM INFORMATION:
Filter Specification: 5 th Power System Frequency: 60 Hz
Capacitor Bank Rating(Available) 500 kVAr Capacitor Rating: 600 Volts
Rated Bank Current: 481 Amps 60 Hz
Nominal Bus Voltage: 480 Derated Capacitor: 320 kVAr
Capacitor Current (actual): 384.9 Amps Total Harmonic Load: 900 kVA
Filter Tuning Harmonic: 4.75 Filter Tuning Frequency: 285 Hz
Cap Impedance (wye equivalent): 0.7200 Ω
Ω Cap Value (wye equivalent): 3684.1 uF
Reactor Impedance: 0.0319 Ω
Ω Reactor Rating: 0.0846 mH
Filter Full Load Current (actual): 402.8 Amps Supplied Compensation: 335 kVAr
Filter Full Load Current (rated): 503.4 Amps
Transformer Nameplate: 1000 Utility Side Vh: 2.00 % T H D
(Rating and Impedance) 5.75 (Utility Harmonic Voltage Source)
Load Harmonic Current: 86.54 % Fund Load Harmonic Current: 348.6 Amps
Utility Harmonic Current: 67.8 Amps Max Total Harm. Current: 416.4 Amps
CAPACITOR DUTY CALCULATIONS:
Filter RMS Current: 579.3 Amps Fundamental Cap Voltage: 502.3 Volts
Harmonic Cap Voltage: 103.9 Volts Maximum Peak Voltage: 606.1 Volts
RMS Capacitor Voltage: 512.9 Volts Maximum Peak Current: 819.1 Amps
CAPACITOR LIMITS: (IEEE Std 18-1980) FILTER CONFIGURATION:
Peak Voltage: 120% <−−−−−−> 101%
Current: 180% <−−−−−−> 120% XL => 0.0319 Ω
Ω
KVAr: 135% <−−−−−−> 103%
RMS Voltage: 110% <−−−−−−> 85% 500 kVAR
600 V
F I L T E R R E A C T O R D E S I G N S P E C I F I C A T I O N S :
Reactor Impedance: 0.0319 Ω
Ω Reactor Rating: 0.0846 mH
Fundamental Current: 402.8 Amps Harmonic Current: 416.4 Amps
Figure7. 5th
Harmonic filter specifications
5. CONCLUSIONS
The filter design iterative procedure can be greatly
simplified using the equations presented in this paper
along with the program developed.
Using the proposed methodology, it is possible to
determine the required rating of the filters to keep
harmonic distortion (voltage and current) within
acceptable limits and also define filters specifications.
ACKNOWLEDGEMENT
The author wishes to acknowledge the support received
from Electrotek Concepts Inc., which allowed me to
develop this project.
REFERENCES
[1] Peeran S.M. and Cascadden C. “Application, Design
and Specification of harmonic filters for Variable
Frequency Drives”, IEEE Trans. Ind. Applicat., vol. 31,
pp. 841-847, July/August 1995
[2] Boonin Elisabeth, Using Excel Visual Basic for
Applications, QUE, 1995
[3] ELECTROTEK, Harmflo+ Tech Notes, Issue # 93-
2, September, 1993
Jesus Baez. Received his BSEE in 1987, his Master of
Engineering degree in Electric Power Engineering in
1990 and his Master of Sciences Degree in Control
Engineering in 1995 from ITESM, Campus Monterrey.
He is professor of the Electrical Engineering Department
at ITESM since 1992. His research interest is simulation
and analysis of distribution and industrial power
systems.

More Related Content

PPTX
Madan mohan malaviya
PPTX
Areva "Manufacturing of transformer, uses & it’s accessories"
PDF
50620977 nbr-iec-60439-1-2003
ODP
Transformers protection, an introduction
PPT
Testing,maintenance&protection
PDF
Nbr iec 61439 1 - 2016 - versão corrigida-2017 - conjuntos de manobra e coman...
PPTX
Power transformer manufacturing process and testing
PDF
Theory for How to calculation capacitor bank
Madan mohan malaviya
Areva "Manufacturing of transformer, uses & it’s accessories"
50620977 nbr-iec-60439-1-2003
Transformers protection, an introduction
Testing,maintenance&protection
Nbr iec 61439 1 - 2016 - versão corrigida-2017 - conjuntos de manobra e coman...
Power transformer manufacturing process and testing
Theory for How to calculation capacitor bank

What's hot (20)

PDF
Relay testing procedure
PPT
substation protection basics.ppt
PPTX
GIS (Gas-Insulated Substation) by Bharat & Shanni
PDF
Cdvr service manual renr7941-00 _ sis - caterpillar
PPTX
ESI Electro Service India - Float Cum Battery Charger
PPT
Practical Power System Protection for Engineers and Technicians
PDF
A Importância do Aterramento e suas particularidades
PDF
Guide for Transformer Maintenance (Cigre-445)
PDF
Relay Setting Calculation For REF615/ REJ601
PDF
IEEE-std80.pdf
PDF
CLASE 03 - DISEÑO DE SISTEMAS DE PUESTA A TIERRA Y PARARRAYOS.pdf
PDF
Manual spark usina 150 a 200a-250a slim
PPTX
Power Supply System - Single Line Diagram
PDF
Barramento de subestações
PDF
Guia do eletricista
PPTX
BOQ _UN.pptx
PDF
Substation Maintenance
PPTX
Electrical maintenance and its relationship to safety
DOCX
PDF
Apostila para a Correção do fator de potência
Relay testing procedure
substation protection basics.ppt
GIS (Gas-Insulated Substation) by Bharat & Shanni
Cdvr service manual renr7941-00 _ sis - caterpillar
ESI Electro Service India - Float Cum Battery Charger
Practical Power System Protection for Engineers and Technicians
A Importância do Aterramento e suas particularidades
Guide for Transformer Maintenance (Cigre-445)
Relay Setting Calculation For REF615/ REJ601
IEEE-std80.pdf
CLASE 03 - DISEÑO DE SISTEMAS DE PUESTA A TIERRA Y PARARRAYOS.pdf
Manual spark usina 150 a 200a-250a slim
Power Supply System - Single Line Diagram
Barramento de subestações
Guia do eletricista
BOQ _UN.pptx
Substation Maintenance
Electrical maintenance and its relationship to safety
Apostila para a Correção do fator de potência
Ad

Similar to How to Design and spec harmonic filter.pdf (20)

PPT
VFD Fundamentals
PPTX
Analysis of harmonic at different level on distribution system ,its effect a...
PDF
International Journal of Computational Engineering Research(IJCER)
PPTX
MITIGATION OF POWER SYSTEM HARMONICS.pptx
PDF
Harmonic Voltage Distortions in Power Systems Due to Non Linear Loads
PDF
ANALYSIS OF TUNED FILTERS FOR MITIGATION OF HARMONIC CURRENT DISTORTION OF R...
PDF
Power quality improvement in a weak bus system using
PDF
Harmonic Analysis of VFD’s
PDF
Harmonic Analysis of Non-Linear Loads in Distribution System and Mitigation U...
PDF
Power quality improvement in a weak bus system using facts controller
PPT
PQ-1.ppt
PPTX
Active filter iora 2 consul
PPTX
Simulation of Harmonics Filters To Reduce Harmonics Distortion By Using MATLAB
PPTX
Product: Power Factor & Harmonics: StacoSine: MGE filter presentation
PDF
Power System Harmonics
PDF
Application of passive harmonic filters to mitigate source side current harmo...
PPTX
05 ETAP Harmonic Analysis.pptx
PDF
Cf25485491
PDF
Simulation Studies of Shunt Passive Harmonic Filters: Six Pulse Rectifier Loa...
VFD Fundamentals
Analysis of harmonic at different level on distribution system ,its effect a...
International Journal of Computational Engineering Research(IJCER)
MITIGATION OF POWER SYSTEM HARMONICS.pptx
Harmonic Voltage Distortions in Power Systems Due to Non Linear Loads
ANALYSIS OF TUNED FILTERS FOR MITIGATION OF HARMONIC CURRENT DISTORTION OF R...
Power quality improvement in a weak bus system using
Harmonic Analysis of VFD’s
Harmonic Analysis of Non-Linear Loads in Distribution System and Mitigation U...
Power quality improvement in a weak bus system using facts controller
PQ-1.ppt
Active filter iora 2 consul
Simulation of Harmonics Filters To Reduce Harmonics Distortion By Using MATLAB
Product: Power Factor & Harmonics: StacoSine: MGE filter presentation
Power System Harmonics
Application of passive harmonic filters to mitigate source side current harmo...
05 ETAP Harmonic Analysis.pptx
Cf25485491
Simulation Studies of Shunt Passive Harmonic Filters: Six Pulse Rectifier Loa...
Ad

Recently uploaded (20)

PDF
Abrasive, erosive and cavitation wear.pdf
PDF
Automation-in-Manufacturing-Chapter-Introduction.pdf
PDF
737-MAX_SRG.pdf student reference guides
PDF
Analyzing Impact of Pakistan Economic Corridor on Import and Export in Pakist...
PDF
Soil Improvement Techniques Note - Rabbi
PDF
The CXO Playbook 2025 – Future-Ready Strategies for C-Suite Leaders Cerebrai...
PDF
Exploratory_Data_Analysis_Fundamentals.pdf
PPTX
Safety Seminar civil to be ensured for safe working.
PPT
introduction to datamining and warehousing
PDF
keyrequirementskkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkk
PPTX
Artificial Intelligence
PPTX
6ME3A-Unit-II-Sensors and Actuators_Handouts.pptx
PDF
UNIT no 1 INTRODUCTION TO DBMS NOTES.pdf
PDF
null (2) bgfbg bfgb bfgb fbfg bfbgf b.pdf
PPTX
MET 305 2019 SCHEME MODULE 2 COMPLETE.pptx
PPT
Total quality management ppt for engineering students
PDF
EXPLORING LEARNING ENGAGEMENT FACTORS INFLUENCING BEHAVIORAL, COGNITIVE, AND ...
PDF
Categorization of Factors Affecting Classification Algorithms Selection
PDF
SMART SIGNAL TIMING FOR URBAN INTERSECTIONS USING REAL-TIME VEHICLE DETECTI...
PDF
Mitigating Risks through Effective Management for Enhancing Organizational Pe...
Abrasive, erosive and cavitation wear.pdf
Automation-in-Manufacturing-Chapter-Introduction.pdf
737-MAX_SRG.pdf student reference guides
Analyzing Impact of Pakistan Economic Corridor on Import and Export in Pakist...
Soil Improvement Techniques Note - Rabbi
The CXO Playbook 2025 – Future-Ready Strategies for C-Suite Leaders Cerebrai...
Exploratory_Data_Analysis_Fundamentals.pdf
Safety Seminar civil to be ensured for safe working.
introduction to datamining and warehousing
keyrequirementskkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkk
Artificial Intelligence
6ME3A-Unit-II-Sensors and Actuators_Handouts.pptx
UNIT no 1 INTRODUCTION TO DBMS NOTES.pdf
null (2) bgfbg bfgb bfgb fbfg bfbgf b.pdf
MET 305 2019 SCHEME MODULE 2 COMPLETE.pptx
Total quality management ppt for engineering students
EXPLORING LEARNING ENGAGEMENT FACTORS INFLUENCING BEHAVIORAL, COGNITIVE, AND ...
Categorization of Factors Affecting Classification Algorithms Selection
SMART SIGNAL TIMING FOR URBAN INTERSECTIONS USING REAL-TIME VEHICLE DETECTI...
Mitigating Risks through Effective Management for Enhancing Organizational Pe...

How to Design and spec harmonic filter.pdf

  • 1. Design and Specification of Harmonic Filters for Variable Frequency Drives Jesús A. Baez Moreno ITESM (Departamento de Ingeniería Eléctrica) Monterrey, NL. CP. 64849 ABSTRACT This paper presents a method that can be applied to design and specify low voltage harmonic filters for variable frequency drives. The proposed methodology is used to analyze an electrical distribution system feeding a group of variable frequency drives. 1. INTRODUCTION Generalized use of Variable Frequency Drives has increased harmonic distortion at electrical distribution systems. Some pieces of equipment, such as personal computers, programmable controllers and microprocessor-based instrumentation are very sensitive to harmonic distortion. Proper application of harmonic filters can help to keep harmonic distortion within acceptable limits. This paper describes a simple methodology that can be applied to design harmonic filters for an electrical system that will feed variable frequency drives. The proposed methodology calculates the harmonic voltage attenuation factor produced by filters [1]. Attenuation factor is then used to estimate voltage harmonic distortion at the point of connection and also the harmonic currents injected into the system. A computer program (EXCEL Macro) was developed using Visual Basic for Application language to simulate system performance. The application of this program to the analysis of a electrical distribution system feeding a group of VFDs is also presented. 2. SOLUTION METHODOLOGY Figure 1 shows a one-line diagram of a electrical distribution system feeding a Variable Frequency Drive (VFD). The harmonic filter consists of a capacitor and an inductor connected in series. ~ Utility Nonlinear Load (VFD) Filter Low Voltage Bus Figure 1. One-line diagram of the electrical distribution system feeding the VFD A harmonic filter modifies all harmonic voltages at the point of connection(Low Voltage Bus). Maximum attenuation occurs for the voltage whose frequency is equal or close to the resonant frequency of the filter. In order to quantify how harmonic voltages are affected, we will define the attenuation factor[1] as ( ) a h V h Vf h n = ( ) ( ) Where: V(h): Harmonic voltage without the filter at the low voltage bus. Vf(h): The h-th Harmonic voltage with the filter at the low voltage bus an(h) : Attenuation factor of the harmonic voltage(h) due to the (n-th) tuned filter.
  • 2. Figure 2 illustrates the basic circuit used to calculate the h-th harmonic attenuation factor produced by the n-th harmonic filter. In this diagram, I(h) represents the h-th harmonic injected by the variable frequency drive, Zs(h) accounts for the system impedance and Zn(h) represents the n-th harmonic filter impedance at the h-th harmonic. I(h) Zn(h) Zs(h) jh SCKVA − j h KVAn j h h KVAn n 2 Figure 2. Circuit used for harmonic voltage calculation. The n-th harmonic filter impedance at the harmonic frequency (h) can be expressed in terms of the filter kVAR(kVAn) and its tuning frequency (hn) as: Z h j kVAn h h h j kVAn h h h h n n ( ) ( ) = −       = −       2 2 2 2 1 n n The distribution system impedance seen by the low voltage bus at the harmonic frequency (h) is related to the low voltage bus short circuit kVA as follows: Zs h j h SCkVA ( ) = In order to simplify the calculation, the filter and the system are represented by their admittance values. Yn h kVAn j h h h h Ys h SCKVA jh ( ) ( ) = −       = n 2 n 2 2 The equivalent admittance seen by the VFD is calculated by adding Yn(h) and Ys(h) Yeq h kVAn j h h h h h SCKVA jh ( ) = −       + 2 2 n 2 n 2 [ ] Yeq h jh kVAn SCKVA ( ) = + 1 δ where: δ = −       h h h h 2 2 n 2 n 2 The attenuation factor an(h) is then obtained as [1]: [ ] an h V h Vf h Yeq h Ys h jh kVAn SCKVA SCKVA jh an h kVAn SCKVA ( ) ( ) ( ) ( ) ( ) ( ) = = = + = + 1 1 δ δ When more than one filter is used, the attenuation factor of the h-th harmonic voltage is given by ( ) ( ) an h kVA SCKVA kVA SCKVA h h h h n n N n k n k N k ( ) ( ) ( ) ( ) ( ) = + + +           = − 1 1 2 2 2 2 1 δ δ δ L where: Harmonic currents flowing into the tuned filters and into the system(utility) with the connected filter(s) can be calculated as follows: In h V h Zn h ( ) ( ) ( ) = ; Is h I h an h ( ) ( ) ( ) =
  • 3. I(h) Zn(h) Zs(h) Is(h) If(h) + V(h) - Figure 3. Harmonic filter and system current calculation Once these currents have been calculated, it is possible to get filter’s specifications with the aid of the worksheet filter.xls [3] The above procedure is summarized in the flowchart shown in Figure 4. Read system data UtilitySCMVA,XFMR(ZandkVA) Drive KVA, Harmonic Spectra (%I(h)), Displacement power factor Filter(s) kVAr, Detuning Factors(α) MaximumallowedTHDV(THDVmax) Evaluate harmonic Voltages and THDV without filters V h I h h DrivekVA SCKVA ( ) [% ( )][ ] =       Calculate attenuation factors an(h), resulting harmonic voltages and THDV ( ) Vf h V h a h n ( ) ( ) = [ ] THDV Vf h h = = ∑ ( ) 2 5 43 [ ] THDV V h h = = ∑ ( ) 2 5 43 THDV<THDVmax? Modify filter(s) kVAr Calculate harmonic filter loading and harmonics flowing into the system Calculate filter specs using spredasheet filters.xls NO YES In h V h Zn h ( ) ( ) ( ) = SCMVA 13.8 kV 50 5.75% 1000 kVA 12903.2 SCKVA 480 V THDV 3.58% 472.50 233.62 0.031911 Ω Ω A RMS 0.03256 Ω Ω A RMS 500kVAr 250kVAr @ 600V @ 600V 5-th 7-th 900 kVA 6-pulse 250 HP 480-V CSI VFD(measured) ~ Generate Report *Voltage/current distortion * Filter sepecifications) I s h I h an h ( ) ( ) ( ) = ; an h kVA SCKVA kVA SCKVA n n N N ( ) ( ) ( ) = + + + 1 1 1 δ δ L Figure 4. Flowchart for the proposed solution methodology
  • 4. 3. COMPUTER PROGRAM The computer program was developed in an Excel Workbook (VFD.XLS), using Visual Basic for Applications Language[2]. Harmonic Spectra of Variable Frequency Drives is stored in one worksheet within the same workbook. To add harmonic spectra of a non listed VFD(or group of VFDs), the user types in this worksheet a name for this load and its harmonic spectra. Simulation results are stored into the following Worksheets: 1) SUMMARY : Summary of the results obtained in the simulation (THDV, Filter specs) 2) VOLTAGES: Harmonic voltages in the low voltage bus without filters, with filters and with plain capacitors(no tuning reactor) 3) CURRENTS: Harmonic currents flowing into the system with and without filters, and filter currents 4) FILTER-5: 5th harmonic filter design specifications 5) FILTER-7: 7th harmonic filter design specifications The program was written under the following assumptions: 1)This application was developed for VFDs operating at 240V and 480 V systems. For applications at 240V, 480 V capacitor banks are used, and the total KVAR rating is adjusted to the next multiple of 25 kVAR For applications at 480V , 600 V capacitor banks are used and the total KVAR rating is adjusted to the next multiple of 50 kVAR For example, if the user chooses a 300 kVAR bank at 480 V, the required kVAR rating at 600 V is 300(600/480) ^2 = 468.75 kVAR. The bank kVAr rating is adjusted to 500 kVAR. 2) Load at the low voltage bus consists only of VFDs and the resistive effect is neglected 3) 5th and 7th harmonic voltage distortion at the high voltage side is given a as 2%. (This value can be modified in Worksheets FILTER-5 and FILTER-7 4) Voltage at the low voltage bus is assumed constant (1.0 pu). 4. SIMULATION RESULTS The proposed methodology and the computer program (VFD.XLS) were used to simulate the sample electrical distribution system depicted in figure 5. UTILITY 5th 7th SCMVA=50 ~ Z (%) = 5.75 1000 KVA 150-HP PWM VFDs TOTAL LOAD =900 KVA 300 kVAR 150 kVAR α=0.95 α=0.95 . . . 13.8 kV 480 V Figure 5. One-line diagram of the electrical system This system feeds a group of PWM variable frequency drives with a total load of 900 kVA operating at 0.9(-) displacement power factor. This loading condition results in a very high harmonic current and voltage distortion. The proposed methodology was used to analyze the effect of connecting two harmonic filters on low voltage bus harmonic distortion levels. Filter 1: 300 kVAR, 5-th harmonic filter tuned at hn=4.75 Filter 2: 150 kVAR, 7-th harmonic filter tuned at hn=6.65 The computer program calculates harmonic voltage and current distortion with and without filters and also calculates harmonic filter loading. A summary of the simulation results is presented in figure 6 (actual program output). The effect of these harmonic filters on harmonic voltages and currents distortion is presented in Tables 1 and 2. Total harmonic current distortion (THDI) is reduced from 35% to 7.5% and total harmonic voltage distortion is reduced from 15.76 to 4.56 %. Figure 7 shows the 5-th harmonic filter spec sheet.
  • 5. Figure 6. Simulation Results (summary) Table 1. Voltage at the low voltage bus with and without filters connected NO FILTERS FILTERS h %I(h) % V(h) a(h) % Vf(h) 5 33.7 11.753 6.03 1.9504 7 1.09 0.5322 7.66 0.0695 11 7.37 5.6546 2.55 2.2158 13 3.5 3.1736 2.39 1.3287 17 3.5 4.1501 2.25 1.8409 19 2.1 2.783 2.22 1.2526 23 1.6 2.5668 2.18 1.1759 25 1.4 2.4413 2.17 1.1247 29 0.8 1.6182 2.15 0.7513 31 0.9 1.946 2.15 0.906 35 0.6 1.4648 2.14 0.6848 37 0.5 1.2904 2.14 0.6042 41 0.4 1.1439 2.13 0.537 43 0.3 0.8998 2.13 0.4228 THDV(%) 15.176 4.5581
  • 6. Table 2 . Harmonic currents flowing into the system and harmonic filters loading XFMR(NO FILTERS) XFMR(FILTERS) 5TH FILTER 7TH FILTER I(AMPS) I(AMPS) I(AMPS) I(AMPS) FUNDAMENTAL 1082.5 982.62 402.75 196.90 5 364.8 60.54 347.45 43.18 7 11.8 1.54 1.60 8.66 11 79.8 31.26 21.50 27.02 13 37.9 15.86 10.24 11.78 17 37.9 16.81 10.20 10.88 19 22.7 10.23 6.11 6.39 23 17.3 7.93 4.64 4.75 25 15.2 6.98 4.05 4.12 29 8.7 4.02 2.31 2.33 31 9.7 4.54 2.60 2.61 35 6.5 3.04 1.73 1.73 37 5.4 2.53 1.44 1.44 41 4.3 2.03 1.15 1.14 43 3.2 1.53 0.86 0.86 HARM. CURRENT 379.2 73.85 348.55 55.01 RMS CURRENT 1147.0 985.39 532.63 204.44 THDI (%) 35.0% 7.52%
  • 7. Low Voltage Filter Calculations: Example Filter Design Spreadsheet SYSTEM INFORMATION: Filter Specification: 5 th Power System Frequency: 60 Hz Capacitor Bank Rating(Available) 500 kVAr Capacitor Rating: 600 Volts Rated Bank Current: 481 Amps 60 Hz Nominal Bus Voltage: 480 Derated Capacitor: 320 kVAr Capacitor Current (actual): 384.9 Amps Total Harmonic Load: 900 kVA Filter Tuning Harmonic: 4.75 Filter Tuning Frequency: 285 Hz Cap Impedance (wye equivalent): 0.7200 Ω Ω Cap Value (wye equivalent): 3684.1 uF Reactor Impedance: 0.0319 Ω Ω Reactor Rating: 0.0846 mH Filter Full Load Current (actual): 402.8 Amps Supplied Compensation: 335 kVAr Filter Full Load Current (rated): 503.4 Amps Transformer Nameplate: 1000 Utility Side Vh: 2.00 % T H D (Rating and Impedance) 5.75 (Utility Harmonic Voltage Source) Load Harmonic Current: 86.54 % Fund Load Harmonic Current: 348.6 Amps Utility Harmonic Current: 67.8 Amps Max Total Harm. Current: 416.4 Amps CAPACITOR DUTY CALCULATIONS: Filter RMS Current: 579.3 Amps Fundamental Cap Voltage: 502.3 Volts Harmonic Cap Voltage: 103.9 Volts Maximum Peak Voltage: 606.1 Volts RMS Capacitor Voltage: 512.9 Volts Maximum Peak Current: 819.1 Amps CAPACITOR LIMITS: (IEEE Std 18-1980) FILTER CONFIGURATION: Peak Voltage: 120% <−−−−−−> 101% Current: 180% <−−−−−−> 120% XL => 0.0319 Ω Ω KVAr: 135% <−−−−−−> 103% RMS Voltage: 110% <−−−−−−> 85% 500 kVAR 600 V F I L T E R R E A C T O R D E S I G N S P E C I F I C A T I O N S : Reactor Impedance: 0.0319 Ω Ω Reactor Rating: 0.0846 mH Fundamental Current: 402.8 Amps Harmonic Current: 416.4 Amps Figure7. 5th Harmonic filter specifications
  • 8. 5. CONCLUSIONS The filter design iterative procedure can be greatly simplified using the equations presented in this paper along with the program developed. Using the proposed methodology, it is possible to determine the required rating of the filters to keep harmonic distortion (voltage and current) within acceptable limits and also define filters specifications. ACKNOWLEDGEMENT The author wishes to acknowledge the support received from Electrotek Concepts Inc., which allowed me to develop this project. REFERENCES [1] Peeran S.M. and Cascadden C. “Application, Design and Specification of harmonic filters for Variable Frequency Drives”, IEEE Trans. Ind. Applicat., vol. 31, pp. 841-847, July/August 1995 [2] Boonin Elisabeth, Using Excel Visual Basic for Applications, QUE, 1995 [3] ELECTROTEK, Harmflo+ Tech Notes, Issue # 93- 2, September, 1993 Jesus Baez. Received his BSEE in 1987, his Master of Engineering degree in Electric Power Engineering in 1990 and his Master of Sciences Degree in Control Engineering in 1995 from ITESM, Campus Monterrey. He is professor of the Electrical Engineering Department at ITESM since 1992. His research interest is simulation and analysis of distribution and industrial power systems.