SlideShare a Scribd company logo
INSTRUMENTATION DEPARTMENT
VALVE POSITIONER
PRINCIPLES
AND
MAINTENANCE GUIDE
By,
Sangram Patnaik
Sr.Instrumentation Engineer
INSTRUMENTATION DEPARTMENT
CONTENTS
 INTRODUCTION TO CONTROL VALVE
 INTRODUCTION TO POSITIONER.
 INTRODUCTION TO CONTROL LOOP.
 POSITIONER DESIGN AND APPLICATIONS.
 CALIBRATION TECHNIQUES.
 CONDITION MONITORING/PREVENTATIVE MAINTENANCE.
 TROUBLE SHOOTING OF POSITIONERS.
 LASTEST DEVELOPMENT IN POSITIONERS.
 CONCLUSION.
2
INSTRUMENTATION DEPARTMENT
3
INTRODUCTION TO CONTROL VALVE.
 A CONTROL VALVE IS A FINAL CONTROL ELEMENT AND A
POWER OPERATED DEVICE WHICH MODIFIES THE FLOW
RATE IN A PROCESS CONTROL SYSTEM.
It is used for
• Flowing fluid or gases
• Reduction of Pressure
• As a variable orifice
• As a throttling or
modulating equipment
INSTRUMENTATION DEPARTMENT
4
TYPES OF CONTROL VALVES
GLOBE
GATE
DIAPHRAGM
PINCH OR CLAMP
GLOBE
ANGLE
THREE-WAY
BALL
BUTTER FLY
PLUG
SEGMENTED
BALL
FULL
BALL
CYLIDRICAL
TAPERED
ECCENTRIC
SPHERE
LINEAR
MOTION
ROTARY
MOTION
VALVE
INSTRUMENTATION DEPARTMENT
5
ACCESSORIES OF A CONTROL VALVE
 AIR FILTER REGULATOR
 VALVE POSITIONER
 VOLUME BOOSTER
 QUICK EXHAUST
 AIR LOCK RELAY
 LIMIT SWITCHES
 SOLENOID VALVE
 POSITION TRANSMITTERS
INSTRUMENTATION DEPARTMENT
INTRODUCTION TO POSITIONER.
 Positioner is one of important accessory of the final
control element i.e. Valves to maintain process
parameters within its set point which is provided.
 A valve positioner is a device used to increase or
decrease the air load pressure driving the actuator of a
control valve until the valve's stem reaches a position
balanced to the output signal from the process variable
instrument controller.
 Valve Positioners are used on controlling valves where
accurate and rapid control is required without error or
hysteresis.
6
INSTRUMENTATION DEPARTMENT
EVOLUTION OF POSITIONERS
`
1980-1990 : PNEUMATIC POSITIONER
1990-2000 : ELECTRO-PNEUMATIC POSITIONER
2000-2010 : ELECTRONIC POSITIONER
2010-2020 : SMART POSITIONER
7
INSTRUMENTATION DEPARTMENT
8
1. Pneumatic Positioner : A Pneumatic signal(3-15 psig) is supplied to
positioner. The positioner translates this to a required valve position and
supplies the valve actuator with the required air pressure to move the
valve to the correct position.
2. Electro-Pneumatic Positioner : This Positioner performs the same
function as the pneumatic type, but uses electrical current usually 4-20
mA instead of air as the input signal which uses I/P convertors.
3. Electronic positioner : This Positioner replaces the I/P convertor with an
microprocessor inside the positioner itself to perform the same function
as the Electro-Pneumatic Positioner.
4. Digital/Smart positioner : This type of positioner uses a microprocessor
to position the valve actuator and monitor and record data. They are very
accurate, use less air than analogue positioners, and allow for online
digital diagnostics.
TYPES OF POSITIONERS
INSTRUMENTATION DEPARTMENT
9
INTRODUCTION TO CONTROL LOOP.
 Positioners are part of a control loop. If not specified properly or if not
maintained properly, positioners can have an unacceptable effect on
process control, costing both maintenance time and materials.
 The control loop is fundamentally nothing more than a group of
individual components in a series, each of which responds to input from
the previous component by supplying output to the next component The
goal of the loop is to work together to control a process as desired when
challenged by some disturbance.
 Each process control loop may be described in terms of process
variables and control elements. The control elements include a sensor,
transmitter (usually lumped with the sensor), controller, and final control
element.
INSTRUMENTATION DEPARTMENT
10
 The tank level is measured by the level sensor, and the level transmitter
sends a corresponding signal to the controlling device.
 In most cases, this signal is electrical and has been scaled to correspond to
a maximum and minimum level of interest. In the controlling device, the
level signal is compared to a signal that corresponds to the desired tank level
(the set point).
EXAMPLE :
INSTRUMENTATION DEPARTMENT
11
POSITIONER DESIGN AND APPLICATIONS.
INSTRUMENTATION DEPARTMENT
12
1. POSITIONER FUNCTIONS :
 Provide an output pressure that tracks the input signal closely. This
does not necessarily mean that the input and output pressures are the
same.
 Provide an output pressure that increases (or decreases) rapidly
whenever there is a difference between the desired position and the
corresponding input pressure.
 Provide for tracking in which the output pressure increases with the
input pressure increase (direct acting), or in which the output pressure
decreases with the input pressure increase (reverse acting).
INSTRUMENTATION DEPARTMENT
13
2. POSITIONER BUILDING BLOCKS :
2.1 Input signal conversion: The pneumatic input is converted to a
mechanical motion. Positioner gain may be developed here using a
pneumatic amplifier.
INSTRUMENTATION DEPARTMENT
14
2.2 Output signal generation: A mechanical motion causes a
directional control valve to change position and supply air to (or
exhaust air from) the actuator.
2.3 Output signal correction: The gain developed earlier is reduced
to zero.
Input Signal Conversion
The input signal can be sent to the positioner is one of two ways:
• A pneumatic signal 3–15 psig directly from the controller.
• An electrical signal (4–20ma, 10–50ma, 0–10v) from the controller
that is converted to a pneumatic signal by a current to pneumatic
(I/P) converter or a voltage to pneumatic (E/P) converter that is
either external or internal to the positioner.
INSTRUMENTATION DEPARTMENT
15
•The pneumatic signal must be converted to a mechanical motion.
•This conversion process always begins with a diaphragm or bellows
chamber.
• The changing pressure is transformed to a linear motion.
•The linear motion is now used directly to position a directional
control valve within the positioner, or it is used to modulate the
flapper of a nozzle-flapper.
INSTRUMENTATION DEPARTMENT
16
FLAPPER-NOZZLE
INSTRUMENTATION DEPARTMENT
17
 During a steady state operation, supply air passes through two
restrictions. The first restriction is a fixed orifice and sized to permit
adequate flow for nozzle-flapper operation without affecting the
supply pressure.
The second restriction is caused by the flapper moving
toward/away from the nozzle. Moving the flapper toward the nozzle
increases the pressure in the nozzle chamber and vice versa.
 In other words, the orifice restriction size is smaller than the
nozzle restriction size, which allows the supply pressure to bleed to
atmosphere faster than it enters the unit through the fixed
restriction when the flapper is away from the nozzle.
 Thus, a small pressure change in the input will produce a large
change in the nozzle chamber pressure.
INSTRUMENTATION DEPARTMENT
18
OUTPUT SIGNAL GENERATOR
1. Connecting the Input Converter to Output Generator
INSTRUMENTATION DEPARTMENT
19
The input signal converter sends a linear motion that is used by the
output signal generator in one of two ways:
The linear motion is used directly to cause the output signal
generator to move and to transmit an output signal. For example,
an input diaphragm linear motion is connected directly to the stem
of a sliding spool directional control valve.
•The linear motion is used to move a balance beam that causes the
output signal generator to move and to generate an output signal.
2. Types of Output Signal Generators:
The term output signal generator describes the function of several
different types of mechanisms that are used to provide the output
signal. The manufacturers’ terms used to describe the output signal
generator function vary widely and include pilot valve, pneumatic
relay, pneumatic amplifier, and relay.
INSTRUMENTATION DEPARTMENT
20
3. Output Signal Correction:
The output signal correction is to use the feedback to nullify or
balance the output when the desired position is achieved.
Interface Between Valve and Positioner
•To begin the balancing process, a rod, bracket, or other suitable
device is attached to the stem.
•The device is mechanically routed to the positioner (for example,
using linkages) to provide the appropriate motion used by the
positioner: rotation or linear push-pull. If the motion is rotation,
•the input to the positioner is a lever.
INSTRUMENTATION DEPARTMENT
21
Positioner Input
 A linear feedback motion always results in a proportional feedback
to provide a balance force to nullify the output. In other words, no
matter where the stem is, any amount of movement of the stem
always results in the same but proportional amount of movement at
the positioner.
 There may be an interface that allows the input range to be
adjusted, but the motion remains linear. Sometimes it is necessary to
modify this input. This is where the rotary motion comes in.
 Rotary motion is used in the positioner to modify the feedback in
a non-linear way if desired. The reason for making it non-linear is to
compensate for some non-linearity in the control loop. The universal
method for doing this is by using a cam. Input from the stem causes
the input lever to rotate the cam.
INSTRUMENTATION DEPARTMENT
22
 The cam follower rides on the edge of the cam and follows the
cam contour. This allows the original input lever motion to be
changed, or characterized, before it is used to correct the output
through the balance beam.
INSTRUMENTATION DEPARTMENT
23
3. POSITIONERS APPLICATIONS :
 Limiting Control Valve Dead Band.
 Mitigating Stiction or Stick-Slip.
 Change Valve Response.
 Control Double Acting Actuator.
 Increase Shutoff Forces.
 Split-Ranging.
 Delays Due to Distance Between Controller or I/P Converter and
Valve.
INSTRUMENTATION DEPARTMENT
24
CALIBRATION.
The goal of calibration, or alignment, is to ensure that the
positioner is functioning correctly within design tolerances.
The basic calibration process consists of three steps:
I. Bench set confirmation
II. Feedback linkage alignment, including cam alignment
III. Zero and span adjustment
IV. Inline or Online Calibration.
BENCH SET CONFIRMATION
This Type of Calibration is generally followed before installing a
new valve into the process line. This calibration ensures proper
actuator operation with air pressure as specified by the
manufacturer. This calibration also mostly important for air-to-
open and air-to-fail valves before installation.
INSTRUMENTATION DEPARTMENT
25
Feedback linkage alignment, including cam alignment
The purpose of this calibration is to ensure that the zero and span of
the feedback mechanism position correspond to the fully open
(closed) and fully closed (open) valve travel positions.
Feedback alignment consists of the following:
1. Verifying that the installation is in accordance with appropriate
vendor information and plant documents to determine specific
requirements.
2. Verifying that the positioner is mounted rigidly to the valve.
3. Inspecting to determine that linkage is tight and that appropriate
washers are installed.
4. Checking and adjusting feedback linkage so that it is within
allowable limits.
5. Making sure there is freedom of movement throughout the range
of travel so that the positioner is not “in the stops” at the ends of
travel.
INSTRUMENTATION DEPARTMENT
26
6. Verifying that the appropriate cam is installed or, if the cam is a
multiple type, that the feedback mechanism is on the correct
range, for example, linear, square, or square root.
7. Setting the feedback mechanism to the zero position on the cam.
8. If applicable, setting the stroke lever parallel to the spring lever
at midstroke.
9. Stroking the valve and adjusting the appropriate linkages to
ensure that the cam rotates in the correct direction, stops at the
100% position, and returns to zero as appropriate
Zero and span adjustment
 The purpose of the zero and the span adjustments is to
synchronize the valve position to positioner demand. At first, this
seems to be just varying the input pressure from the bottom to the
top of the control range (for example, 3–15 psig [20.7–103.4 kPa])
and making sure that the valve strokes appropriately.
INSTRUMENTATION DEPARTMENT
27
 Before beginning the zero and span adjustment, determine if
the positioner is a motion balance type, for example, Metso,YTC. If
the motion beam has been repaired or otherwise affected by
maintenance, then beam or flapper levelling is required before
the zero and span adjustments.
 Before Zero and Span one should go through the technical
manual of the positioner.
 Zero adjustments are always done in conjunction with span
adjustments. In other words, after the span has been adjusted,
the zero adjustment must be re-verified to ensure that the zero
adjustment has not changed.
INSTRUMENTATION DEPARTMENT
28
INLINE OR ONLINE CALIBRATION
 Online Calibration can only be performed in smart or digital
positioner. The calibration is performed online in the field itself
ensuring both inlet and outlet manual valves adjacent are in close
condition.
 This Calibration the positioner itself has an option in its display
to calibrate the valve in the process line. Based on the calibration
results the decision of removing the valve outside the line or not
can be judged.
INSTRUMENTATION DEPARTMENT
29
CONDITION MONITORING/PREVENTATIVE
MAINTENANCE.
 Condition monitoring for positioners is primarily the
continuation of the calibration process. Calibration must be done
carefully and consistently for condition monitoring/preventive
maintenance to be effective. Persistent, significant calibration drifts
can be used to identify the need for positioner repair or
replacement.
 All condition-monitoring processes rely on the ability to trend
the right data accurately. In the hands of trained and experience
personnel, a digital acquisition system not only gathers data
accurately but does it quickly, efficiently and consistently monitor
the condition of the positioner before it gets fail.
INSTRUMENTATION DEPARTMENT
30
The Preventative Maintenance of the Positioner can be achieved
through three important preventative maintenance actions in the
field .They are :
1. Air supply check
2. Walk down inspection
3. Internal inspections (as applicable)
Air Supply Check
1. Verify air quality.
a. Air quality affects air positioner performance. Some positioner
manufacturers specify to maintain air quality within 3 to 7 microns.
b. The dew point may also be a factor and should be reviewed to
ensure that the air supply is per the manufacturer’s specification.
c. The oil or hydrocarbon content can be detrimental to elastomers,
thus increasing the likelihood of air leaks.
INSTRUMENTATION DEPARTMENT
31
2. Blow down the regulator, and inspect the effluent for
contaminants.
3. Verify the air supply pressure to detect regulator set point drift.
4. Inspect the regulator, tubing and fittings, and positioner for air
leaks using a soap solution or equivalent.
5. Inspect tubing for cracks and kinking.
Walk Down Inspection
A recommended checklist may contain the elements inspected in
the following tasks:
1. Observe the exterior to detect signs of physical damage to the
housing, connections, pipe/tubing, hoses, feedback and linkage.
2. Feel the housing, and carefully determine if it is firmly attached to
the valve.
3. Inspect for air leaks. If possible, check all pneumatic connections
with a soapsuds solution to detect any leakage.
INSTRUMENTATION DEPARTMENT
32
4. Observe the pressure gages, and note if pressures are consistent
with required supply pressures, expected signal pressure for valve
position, and expected output pressure for the valve position.
5. If the feedback cam position is visible, determine if its position is
consistent with the valve position.
6. Observe the valve motion to see if the response is consistent
with the changes in signal/output pressure variation.
Internal Inspection(Applicable)
It is recommended that the air supply be isolated when performing
the following internal inspections:
1. Inspect the pilot valves for sign of scarring and wear; clean or
replace them as necessary.
2. Ensure that the pilot valve is properly aligned.
3. Inspect the flapper for signs of pitting or damage.
4. Inspect the nozzle for signs of erosion or damage.
INSTRUMENTATION DEPARTMENT
33
5. Inspect the cam and cam roller for signs of wear.
6. Ensure that the cam roller rotates freely and is properly oriented.
7. Ensure that the cam roller snap rings are installed properly.
8. Ensure that the proper cam is installed and correctly oriented.
9. Inspect the springs, and verify that all are connected and of the
proper type.
10. Inspect the gaskets, O-rings, and filters. Clean or replace them as
necessary.
11. Replace the over-ranged gauges.
12. Ensure that the bypass block, relay and gauge block manifold are
tightened properly.
13. Clean the restrictions; for example, clean out the plunger.
Note : Internal Inspection should only performed during any shutdowns or after
process clearance.
INSTRUMENTATION DEPARTMENT
34
Trouble-Shooting.
 Troubleshooting is the systematic approach to data collection,
failure analysis, and the use of a test/measurement plan that
collectively result in high confidence that the complete cause of
system/equipment degradation has been corrected and that the
system/equipment has been restored to normal operation.
 Ideally, troubleshooting is a continuation of condition
monitoring/preventive maintenance. In Walk-down Preventative
Maintenance method the positioner operation can be obtained by
following symptoms based approach to determine the symptoms
of the positioner mounted in the field.
INSTRUMENTATION DEPARTMENT
35
INSTRUMENTATION DEPARTMENT
36
INSTRUMENTATION DEPARTMENT
37
Based on the Symptom the Following causes can be derived to solve
the problem.
INSTRUMENTATION DEPARTMENT
38
INSTRUMENTATION DEPARTMENT
39
INSTRUMENTATION DEPARTMENT
40
LATEST DEVELOPMENT IN POSITIONERS
FLOWSERVE ANNOUNCES TECHNOLOGY
BREAKTHROUGH WITH POSITIONER FOR WIRELESS
CONTROL OF VALVES
SMAR INTRODUCES HALL SENSOR THE
TECHNOLOGY OF LATEST-GENERATION
INTELLIGENT POSITIONER.
INSTRUMENTATION DEPARTMENT
41
CONCLUSION
From this , we can conclude the positioner is the integral part of
the valve opening and closing . It also plays an crucial role in
process loop control for controlling flow, pressure and
temperature in application in the industry.
From decades to decades with change in industrial
revolution, the positioner shape and size may change but not
its main function to control the valve operation.
INSTRUMENTATION DEPARTMENT
42
Suggestions Please ……………………
INSTRUMENTATION DEPARTMENT
43

More Related Content

PPTX
Control valve ppt
PPT
Industrial fan(ID FD Fans)
PPT
Control valve
PDF
Control Valves .pdf
PPT
Suction Rolls
PPTX
Tuning of pid controller
PDF
Understanding sil
PPT
Instrumentation system
Control valve ppt
Industrial fan(ID FD Fans)
Control valve
Control Valves .pdf
Suction Rolls
Tuning of pid controller
Understanding sil
Instrumentation system

What's hot (20)

PPTX
Control valve positioners
PPT
Control valves
PPT
Basic Control Valve Sizing and Selection
PPTX
Control valves
PPT
Pneumatic control valve
PPTX
Industrial process control
PPTX
Control Valves
PPT
Introduction to Pneumatic Systems
PPT
Process control 3 chapter
PPT
Control Valve Types
PPT
valve maintenance
PDF
Control Valves And Actuators
PPTX
pressure transmitter
PPTX
Process Control Fundamentals and How to read P&IDs
PPT
Basic instrumentation
PPTX
Mechanical Valve
PDF
Distributed Control System Basics
PPTX
Design and analysis of control valve with a multi stage anti cavitation trim
PDF
CONTROL VALVE questions.pdf
Control valve positioners
Control valves
Basic Control Valve Sizing and Selection
Control valves
Pneumatic control valve
Industrial process control
Control Valves
Introduction to Pneumatic Systems
Process control 3 chapter
Control Valve Types
valve maintenance
Control Valves And Actuators
pressure transmitter
Process Control Fundamentals and How to read P&IDs
Basic instrumentation
Mechanical Valve
Distributed Control System Basics
Design and analysis of control valve with a multi stage anti cavitation trim
CONTROL VALVE questions.pdf
Ad

Viewers also liked (19)

PDF
104980410 control-valve-calibration-procedure-fisher-hc6010
PPSX
01 General Control Valves Training.
PPT
Equipment calibration PPT by Shravan Kumar
PPT
Instrument Calibration
PPTX
control valve functional testing - Swetha
PPTX
Pneumatic controllers
PPTX
PDF
0155 EMP Phase 1 Flier v2
PDF
In-Situ Calibration: Methods & Pitfalls of Thermal Mass Flow Meter Sensor Fie...
PPT
Control valves
PPS
Formation and Discovery
PPT
3.2 e olss pump
PPTX
Final Control Element
PDF
Thermometers calibration
PPT
Calibration dasibi-ozone
PPT
3.4 e olss electronic control
PPTX
Electronic Multi-Tester
PDF
How to calibrate an ir thermometer, frank liebmann, 2013 05-07
PDF
Instrument Calibration
104980410 control-valve-calibration-procedure-fisher-hc6010
01 General Control Valves Training.
Equipment calibration PPT by Shravan Kumar
Instrument Calibration
control valve functional testing - Swetha
Pneumatic controllers
0155 EMP Phase 1 Flier v2
In-Situ Calibration: Methods & Pitfalls of Thermal Mass Flow Meter Sensor Fie...
Control valves
Formation and Discovery
3.2 e olss pump
Final Control Element
Thermometers calibration
Calibration dasibi-ozone
3.4 e olss electronic control
Electronic Multi-Tester
How to calibrate an ir thermometer, frank liebmann, 2013 05-07
Instrument Calibration
Ad

Similar to Instrumentation positioner presentation (20)

PPT
Process control 3 chapter
PPTX
On off controller
PDF
Fluke 1627722 w
PDF
Project Report - Spring 2014
PDF
PPTX
introduction to advanced control systems
PPT
Pneumatic Control Valve as a Final Control Element
PPT
Introduction to Pneumatic Control Valves.ppt
PPTX
Basics of Instrumentation & Control.pptx
PPTX
i to p conveter
PPT
Interfacing delta v to motorized actuators addressing control applications
PPTX
Final Control Element.pptx
PPTX
Session 06 - Instruments - Part 2
PPTX
PPTX
Basics of Instrumentation & Control.pptx
PPTX
Instruments - Part 2
PPTX
Control Systems
PPTX
Session 24 - Control Systems
PDF
C045051318
PDF
Effect of Different Defuzzification methods in a Fuzzy Based Liquid Flow cont...
Process control 3 chapter
On off controller
Fluke 1627722 w
Project Report - Spring 2014
introduction to advanced control systems
Pneumatic Control Valve as a Final Control Element
Introduction to Pneumatic Control Valves.ppt
Basics of Instrumentation & Control.pptx
i to p conveter
Interfacing delta v to motorized actuators addressing control applications
Final Control Element.pptx
Session 06 - Instruments - Part 2
Basics of Instrumentation & Control.pptx
Instruments - Part 2
Control Systems
Session 24 - Control Systems
C045051318
Effect of Different Defuzzification methods in a Fuzzy Based Liquid Flow cont...

Recently uploaded (20)

PPT
Project quality management in manufacturing
PDF
Mohammad Mahdi Farshadian CV - Prospective PhD Student 2026
PDF
Arduino robotics embedded978-1-4302-3184-4.pdf
PDF
Mitigating Risks through Effective Management for Enhancing Organizational Pe...
PDF
composite construction of structures.pdf
PDF
PPT on Performance Review to get promotions
PDF
Digital Logic Computer Design lecture notes
PPTX
MET 305 2019 SCHEME MODULE 2 COMPLETE.pptx
PPTX
Infosys Presentation by1.Riyan Bagwan 2.Samadhan Naiknavare 3.Gaurav Shinde 4...
PPTX
bas. eng. economics group 4 presentation 1.pptx
PPTX
web development for engineering and engineering
PPTX
Geodesy 1.pptx...............................................
PPTX
UNIT-1 - COAL BASED THERMAL POWER PLANTS
PDF
Embodied AI: Ushering in the Next Era of Intelligent Systems
PPTX
M Tech Sem 1 Civil Engineering Environmental Sciences.pptx
PPTX
CARTOGRAPHY AND GEOINFORMATION VISUALIZATION chapter1 NPTE (2).pptx
PPTX
Lecture Notes Electrical Wiring System Components
PPTX
UNIT 4 Total Quality Management .pptx
PDF
Evaluating the Democratization of the Turkish Armed Forces from a Normative P...
PPTX
Engineering Ethics, Safety and Environment [Autosaved] (1).pptx
Project quality management in manufacturing
Mohammad Mahdi Farshadian CV - Prospective PhD Student 2026
Arduino robotics embedded978-1-4302-3184-4.pdf
Mitigating Risks through Effective Management for Enhancing Organizational Pe...
composite construction of structures.pdf
PPT on Performance Review to get promotions
Digital Logic Computer Design lecture notes
MET 305 2019 SCHEME MODULE 2 COMPLETE.pptx
Infosys Presentation by1.Riyan Bagwan 2.Samadhan Naiknavare 3.Gaurav Shinde 4...
bas. eng. economics group 4 presentation 1.pptx
web development for engineering and engineering
Geodesy 1.pptx...............................................
UNIT-1 - COAL BASED THERMAL POWER PLANTS
Embodied AI: Ushering in the Next Era of Intelligent Systems
M Tech Sem 1 Civil Engineering Environmental Sciences.pptx
CARTOGRAPHY AND GEOINFORMATION VISUALIZATION chapter1 NPTE (2).pptx
Lecture Notes Electrical Wiring System Components
UNIT 4 Total Quality Management .pptx
Evaluating the Democratization of the Turkish Armed Forces from a Normative P...
Engineering Ethics, Safety and Environment [Autosaved] (1).pptx

Instrumentation positioner presentation

  • 1. INSTRUMENTATION DEPARTMENT VALVE POSITIONER PRINCIPLES AND MAINTENANCE GUIDE By, Sangram Patnaik Sr.Instrumentation Engineer
  • 2. INSTRUMENTATION DEPARTMENT CONTENTS  INTRODUCTION TO CONTROL VALVE  INTRODUCTION TO POSITIONER.  INTRODUCTION TO CONTROL LOOP.  POSITIONER DESIGN AND APPLICATIONS.  CALIBRATION TECHNIQUES.  CONDITION MONITORING/PREVENTATIVE MAINTENANCE.  TROUBLE SHOOTING OF POSITIONERS.  LASTEST DEVELOPMENT IN POSITIONERS.  CONCLUSION. 2
  • 3. INSTRUMENTATION DEPARTMENT 3 INTRODUCTION TO CONTROL VALVE.  A CONTROL VALVE IS A FINAL CONTROL ELEMENT AND A POWER OPERATED DEVICE WHICH MODIFIES THE FLOW RATE IN A PROCESS CONTROL SYSTEM. It is used for • Flowing fluid or gases • Reduction of Pressure • As a variable orifice • As a throttling or modulating equipment
  • 4. INSTRUMENTATION DEPARTMENT 4 TYPES OF CONTROL VALVES GLOBE GATE DIAPHRAGM PINCH OR CLAMP GLOBE ANGLE THREE-WAY BALL BUTTER FLY PLUG SEGMENTED BALL FULL BALL CYLIDRICAL TAPERED ECCENTRIC SPHERE LINEAR MOTION ROTARY MOTION VALVE
  • 5. INSTRUMENTATION DEPARTMENT 5 ACCESSORIES OF A CONTROL VALVE  AIR FILTER REGULATOR  VALVE POSITIONER  VOLUME BOOSTER  QUICK EXHAUST  AIR LOCK RELAY  LIMIT SWITCHES  SOLENOID VALVE  POSITION TRANSMITTERS
  • 6. INSTRUMENTATION DEPARTMENT INTRODUCTION TO POSITIONER.  Positioner is one of important accessory of the final control element i.e. Valves to maintain process parameters within its set point which is provided.  A valve positioner is a device used to increase or decrease the air load pressure driving the actuator of a control valve until the valve's stem reaches a position balanced to the output signal from the process variable instrument controller.  Valve Positioners are used on controlling valves where accurate and rapid control is required without error or hysteresis. 6
  • 7. INSTRUMENTATION DEPARTMENT EVOLUTION OF POSITIONERS ` 1980-1990 : PNEUMATIC POSITIONER 1990-2000 : ELECTRO-PNEUMATIC POSITIONER 2000-2010 : ELECTRONIC POSITIONER 2010-2020 : SMART POSITIONER 7
  • 8. INSTRUMENTATION DEPARTMENT 8 1. Pneumatic Positioner : A Pneumatic signal(3-15 psig) is supplied to positioner. The positioner translates this to a required valve position and supplies the valve actuator with the required air pressure to move the valve to the correct position. 2. Electro-Pneumatic Positioner : This Positioner performs the same function as the pneumatic type, but uses electrical current usually 4-20 mA instead of air as the input signal which uses I/P convertors. 3. Electronic positioner : This Positioner replaces the I/P convertor with an microprocessor inside the positioner itself to perform the same function as the Electro-Pneumatic Positioner. 4. Digital/Smart positioner : This type of positioner uses a microprocessor to position the valve actuator and monitor and record data. They are very accurate, use less air than analogue positioners, and allow for online digital diagnostics. TYPES OF POSITIONERS
  • 9. INSTRUMENTATION DEPARTMENT 9 INTRODUCTION TO CONTROL LOOP.  Positioners are part of a control loop. If not specified properly or if not maintained properly, positioners can have an unacceptable effect on process control, costing both maintenance time and materials.  The control loop is fundamentally nothing more than a group of individual components in a series, each of which responds to input from the previous component by supplying output to the next component The goal of the loop is to work together to control a process as desired when challenged by some disturbance.  Each process control loop may be described in terms of process variables and control elements. The control elements include a sensor, transmitter (usually lumped with the sensor), controller, and final control element.
  • 10. INSTRUMENTATION DEPARTMENT 10  The tank level is measured by the level sensor, and the level transmitter sends a corresponding signal to the controlling device.  In most cases, this signal is electrical and has been scaled to correspond to a maximum and minimum level of interest. In the controlling device, the level signal is compared to a signal that corresponds to the desired tank level (the set point). EXAMPLE :
  • 12. INSTRUMENTATION DEPARTMENT 12 1. POSITIONER FUNCTIONS :  Provide an output pressure that tracks the input signal closely. This does not necessarily mean that the input and output pressures are the same.  Provide an output pressure that increases (or decreases) rapidly whenever there is a difference between the desired position and the corresponding input pressure.  Provide for tracking in which the output pressure increases with the input pressure increase (direct acting), or in which the output pressure decreases with the input pressure increase (reverse acting).
  • 13. INSTRUMENTATION DEPARTMENT 13 2. POSITIONER BUILDING BLOCKS : 2.1 Input signal conversion: The pneumatic input is converted to a mechanical motion. Positioner gain may be developed here using a pneumatic amplifier.
  • 14. INSTRUMENTATION DEPARTMENT 14 2.2 Output signal generation: A mechanical motion causes a directional control valve to change position and supply air to (or exhaust air from) the actuator. 2.3 Output signal correction: The gain developed earlier is reduced to zero. Input Signal Conversion The input signal can be sent to the positioner is one of two ways: • A pneumatic signal 3–15 psig directly from the controller. • An electrical signal (4–20ma, 10–50ma, 0–10v) from the controller that is converted to a pneumatic signal by a current to pneumatic (I/P) converter or a voltage to pneumatic (E/P) converter that is either external or internal to the positioner.
  • 15. INSTRUMENTATION DEPARTMENT 15 •The pneumatic signal must be converted to a mechanical motion. •This conversion process always begins with a diaphragm or bellows chamber. • The changing pressure is transformed to a linear motion. •The linear motion is now used directly to position a directional control valve within the positioner, or it is used to modulate the flapper of a nozzle-flapper.
  • 17. INSTRUMENTATION DEPARTMENT 17  During a steady state operation, supply air passes through two restrictions. The first restriction is a fixed orifice and sized to permit adequate flow for nozzle-flapper operation without affecting the supply pressure. The second restriction is caused by the flapper moving toward/away from the nozzle. Moving the flapper toward the nozzle increases the pressure in the nozzle chamber and vice versa.  In other words, the orifice restriction size is smaller than the nozzle restriction size, which allows the supply pressure to bleed to atmosphere faster than it enters the unit through the fixed restriction when the flapper is away from the nozzle.  Thus, a small pressure change in the input will produce a large change in the nozzle chamber pressure.
  • 18. INSTRUMENTATION DEPARTMENT 18 OUTPUT SIGNAL GENERATOR 1. Connecting the Input Converter to Output Generator
  • 19. INSTRUMENTATION DEPARTMENT 19 The input signal converter sends a linear motion that is used by the output signal generator in one of two ways: The linear motion is used directly to cause the output signal generator to move and to transmit an output signal. For example, an input diaphragm linear motion is connected directly to the stem of a sliding spool directional control valve. •The linear motion is used to move a balance beam that causes the output signal generator to move and to generate an output signal. 2. Types of Output Signal Generators: The term output signal generator describes the function of several different types of mechanisms that are used to provide the output signal. The manufacturers’ terms used to describe the output signal generator function vary widely and include pilot valve, pneumatic relay, pneumatic amplifier, and relay.
  • 20. INSTRUMENTATION DEPARTMENT 20 3. Output Signal Correction: The output signal correction is to use the feedback to nullify or balance the output when the desired position is achieved. Interface Between Valve and Positioner •To begin the balancing process, a rod, bracket, or other suitable device is attached to the stem. •The device is mechanically routed to the positioner (for example, using linkages) to provide the appropriate motion used by the positioner: rotation or linear push-pull. If the motion is rotation, •the input to the positioner is a lever.
  • 21. INSTRUMENTATION DEPARTMENT 21 Positioner Input  A linear feedback motion always results in a proportional feedback to provide a balance force to nullify the output. In other words, no matter where the stem is, any amount of movement of the stem always results in the same but proportional amount of movement at the positioner.  There may be an interface that allows the input range to be adjusted, but the motion remains linear. Sometimes it is necessary to modify this input. This is where the rotary motion comes in.  Rotary motion is used in the positioner to modify the feedback in a non-linear way if desired. The reason for making it non-linear is to compensate for some non-linearity in the control loop. The universal method for doing this is by using a cam. Input from the stem causes the input lever to rotate the cam.
  • 22. INSTRUMENTATION DEPARTMENT 22  The cam follower rides on the edge of the cam and follows the cam contour. This allows the original input lever motion to be changed, or characterized, before it is used to correct the output through the balance beam.
  • 23. INSTRUMENTATION DEPARTMENT 23 3. POSITIONERS APPLICATIONS :  Limiting Control Valve Dead Band.  Mitigating Stiction or Stick-Slip.  Change Valve Response.  Control Double Acting Actuator.  Increase Shutoff Forces.  Split-Ranging.  Delays Due to Distance Between Controller or I/P Converter and Valve.
  • 24. INSTRUMENTATION DEPARTMENT 24 CALIBRATION. The goal of calibration, or alignment, is to ensure that the positioner is functioning correctly within design tolerances. The basic calibration process consists of three steps: I. Bench set confirmation II. Feedback linkage alignment, including cam alignment III. Zero and span adjustment IV. Inline or Online Calibration. BENCH SET CONFIRMATION This Type of Calibration is generally followed before installing a new valve into the process line. This calibration ensures proper actuator operation with air pressure as specified by the manufacturer. This calibration also mostly important for air-to- open and air-to-fail valves before installation.
  • 25. INSTRUMENTATION DEPARTMENT 25 Feedback linkage alignment, including cam alignment The purpose of this calibration is to ensure that the zero and span of the feedback mechanism position correspond to the fully open (closed) and fully closed (open) valve travel positions. Feedback alignment consists of the following: 1. Verifying that the installation is in accordance with appropriate vendor information and plant documents to determine specific requirements. 2. Verifying that the positioner is mounted rigidly to the valve. 3. Inspecting to determine that linkage is tight and that appropriate washers are installed. 4. Checking and adjusting feedback linkage so that it is within allowable limits. 5. Making sure there is freedom of movement throughout the range of travel so that the positioner is not “in the stops” at the ends of travel.
  • 26. INSTRUMENTATION DEPARTMENT 26 6. Verifying that the appropriate cam is installed or, if the cam is a multiple type, that the feedback mechanism is on the correct range, for example, linear, square, or square root. 7. Setting the feedback mechanism to the zero position on the cam. 8. If applicable, setting the stroke lever parallel to the spring lever at midstroke. 9. Stroking the valve and adjusting the appropriate linkages to ensure that the cam rotates in the correct direction, stops at the 100% position, and returns to zero as appropriate Zero and span adjustment  The purpose of the zero and the span adjustments is to synchronize the valve position to positioner demand. At first, this seems to be just varying the input pressure from the bottom to the top of the control range (for example, 3–15 psig [20.7–103.4 kPa]) and making sure that the valve strokes appropriately.
  • 27. INSTRUMENTATION DEPARTMENT 27  Before beginning the zero and span adjustment, determine if the positioner is a motion balance type, for example, Metso,YTC. If the motion beam has been repaired or otherwise affected by maintenance, then beam or flapper levelling is required before the zero and span adjustments.  Before Zero and Span one should go through the technical manual of the positioner.  Zero adjustments are always done in conjunction with span adjustments. In other words, after the span has been adjusted, the zero adjustment must be re-verified to ensure that the zero adjustment has not changed.
  • 28. INSTRUMENTATION DEPARTMENT 28 INLINE OR ONLINE CALIBRATION  Online Calibration can only be performed in smart or digital positioner. The calibration is performed online in the field itself ensuring both inlet and outlet manual valves adjacent are in close condition.  This Calibration the positioner itself has an option in its display to calibrate the valve in the process line. Based on the calibration results the decision of removing the valve outside the line or not can be judged.
  • 29. INSTRUMENTATION DEPARTMENT 29 CONDITION MONITORING/PREVENTATIVE MAINTENANCE.  Condition monitoring for positioners is primarily the continuation of the calibration process. Calibration must be done carefully and consistently for condition monitoring/preventive maintenance to be effective. Persistent, significant calibration drifts can be used to identify the need for positioner repair or replacement.  All condition-monitoring processes rely on the ability to trend the right data accurately. In the hands of trained and experience personnel, a digital acquisition system not only gathers data accurately but does it quickly, efficiently and consistently monitor the condition of the positioner before it gets fail.
  • 30. INSTRUMENTATION DEPARTMENT 30 The Preventative Maintenance of the Positioner can be achieved through three important preventative maintenance actions in the field .They are : 1. Air supply check 2. Walk down inspection 3. Internal inspections (as applicable) Air Supply Check 1. Verify air quality. a. Air quality affects air positioner performance. Some positioner manufacturers specify to maintain air quality within 3 to 7 microns. b. The dew point may also be a factor and should be reviewed to ensure that the air supply is per the manufacturer’s specification. c. The oil or hydrocarbon content can be detrimental to elastomers, thus increasing the likelihood of air leaks.
  • 31. INSTRUMENTATION DEPARTMENT 31 2. Blow down the regulator, and inspect the effluent for contaminants. 3. Verify the air supply pressure to detect regulator set point drift. 4. Inspect the regulator, tubing and fittings, and positioner for air leaks using a soap solution or equivalent. 5. Inspect tubing for cracks and kinking. Walk Down Inspection A recommended checklist may contain the elements inspected in the following tasks: 1. Observe the exterior to detect signs of physical damage to the housing, connections, pipe/tubing, hoses, feedback and linkage. 2. Feel the housing, and carefully determine if it is firmly attached to the valve. 3. Inspect for air leaks. If possible, check all pneumatic connections with a soapsuds solution to detect any leakage.
  • 32. INSTRUMENTATION DEPARTMENT 32 4. Observe the pressure gages, and note if pressures are consistent with required supply pressures, expected signal pressure for valve position, and expected output pressure for the valve position. 5. If the feedback cam position is visible, determine if its position is consistent with the valve position. 6. Observe the valve motion to see if the response is consistent with the changes in signal/output pressure variation. Internal Inspection(Applicable) It is recommended that the air supply be isolated when performing the following internal inspections: 1. Inspect the pilot valves for sign of scarring and wear; clean or replace them as necessary. 2. Ensure that the pilot valve is properly aligned. 3. Inspect the flapper for signs of pitting or damage. 4. Inspect the nozzle for signs of erosion or damage.
  • 33. INSTRUMENTATION DEPARTMENT 33 5. Inspect the cam and cam roller for signs of wear. 6. Ensure that the cam roller rotates freely and is properly oriented. 7. Ensure that the cam roller snap rings are installed properly. 8. Ensure that the proper cam is installed and correctly oriented. 9. Inspect the springs, and verify that all are connected and of the proper type. 10. Inspect the gaskets, O-rings, and filters. Clean or replace them as necessary. 11. Replace the over-ranged gauges. 12. Ensure that the bypass block, relay and gauge block manifold are tightened properly. 13. Clean the restrictions; for example, clean out the plunger. Note : Internal Inspection should only performed during any shutdowns or after process clearance.
  • 34. INSTRUMENTATION DEPARTMENT 34 Trouble-Shooting.  Troubleshooting is the systematic approach to data collection, failure analysis, and the use of a test/measurement plan that collectively result in high confidence that the complete cause of system/equipment degradation has been corrected and that the system/equipment has been restored to normal operation.  Ideally, troubleshooting is a continuation of condition monitoring/preventive maintenance. In Walk-down Preventative Maintenance method the positioner operation can be obtained by following symptoms based approach to determine the symptoms of the positioner mounted in the field.
  • 37. INSTRUMENTATION DEPARTMENT 37 Based on the Symptom the Following causes can be derived to solve the problem.
  • 40. INSTRUMENTATION DEPARTMENT 40 LATEST DEVELOPMENT IN POSITIONERS FLOWSERVE ANNOUNCES TECHNOLOGY BREAKTHROUGH WITH POSITIONER FOR WIRELESS CONTROL OF VALVES SMAR INTRODUCES HALL SENSOR THE TECHNOLOGY OF LATEST-GENERATION INTELLIGENT POSITIONER.
  • 41. INSTRUMENTATION DEPARTMENT 41 CONCLUSION From this , we can conclude the positioner is the integral part of the valve opening and closing . It also plays an crucial role in process loop control for controlling flow, pressure and temperature in application in the industry. From decades to decades with change in industrial revolution, the positioner shape and size may change but not its main function to control the valve operation.