Seismic Behavior of RC Flat Slab with and without Shear Wall
Technique by using Response Spectrum Analysis
Shivaraju G D1, Usha S2, Kumbar Bhanu Prakash3
1Assistant Professor, Department of Civil Engineering, SSIT
2Assistant Professor, Department of Civil Engineering, BRCE
3Former Assistant Professor, Department of Civil Engineering, MVJCE
----------------------------------------------------------------------***---------------------------------------------------------------------
Abstract - Earthquake resistant structures are structures
designed to withstand earthquakes. According to building
codes, earthquake resistant structures are intended to
withstand the largest earthquake of a certain probabilitythat
is likely to occur at their location. This means the loss of life
should be minimized by preventing collapse of the buildings
for rare earthquakes while the loss of functionality should be
limited for more frequent ones. In this paper, the dynamic
response of RC flat slab with bare frame and flat slab with
shear wall at different location is compared with static
response of the structure. Five models are considered for the
analysis which includes Equivalent Static Force Method and
Response Spectrum Analysis. From Equivalent static force
method base shear, maximum storey drift, displacement
results are obtained and from response spectrum analysis
acceleration results are obtained. For all the cases zone-5, soil
type-2 as per IS 1893-2002(part-1) isconsideredandanalysed
using ETABS, a commercially available finite elementanalysis
software package.
Key words : earthquake, equivalent static force method,
modal analysis, displacement, acceleration.
1. INTRODUCTION
Earthquake resistant design of RC buildings is a continuing
area of research since the earthquake engineering has started
not only in India but in other developed countries also. The
buildings still damage due to one or the other reason during
earthquakes. In spite of all the weaknesses in the structure,
either code imperfections or error in analysis and design, the
structural configuration system has played a vital role in
disaster. Reinforced Concrete Flat Slabs are one of the most
popular floor systems used in residentialbuildings,carparking
and manyotherstructures.Theyrepresentelegantandeasy-to-
construct floor systems. Flat slabs are favoured by both
architects and clients because of their aesthetic appeal and
economic advantage. A flatslab floor system is oftenthechoice
when it comes to heavier loads such as multi-storey car
parking, libraries and multi-storey buildings where larger
spans are also required. Flat slab building structures are
significantlymoreflexiblethantraditionalconcreteframe/wall
or frame structures, thus becoming more vulnerable to second
order p-effects under seismic excitations. Therefore, the
characteristics of the seismic behaviour of flat slab buildings
suggest that additional measures for guiding the conception
and design of these structures in seismic regions are needed.
Reinforced Concrete(RC)buildingsoftenhaveverticalSlab-like
RC walls called Shear Walls or structural walls in addition to
slabs, beams and columns. These RC wallsarereferredasshear
walls because they resist a high proportion of the shear due to
the lateral loads. However, failures of RC walls are not
necessarily dominated by shear deformations. Shear walls
define as vertically oriented wide beamsthatcarryearthquake
loads to the foundation. It can also be defined as a slender
vertical cantilever resisting the lateral load with or without
frames.
In this paper, the dynamic responseofRCflatslabwithbare
frame and flat slab with shear wall at different location is
compared with static response of the structure is studied. Five
models are considered for the analysis which includes
Equivalent Static Force Method and Response Spectrum
Analysis. From Equivalent static force method base shear,
maximum storey drift, displacement results are obtained and
from response spectrum analysis acceleration results are
obtained. For all the cases zone-5, soil type-2 as per IS 1893-
2002(part-1) is considered and analysed using ETABS, a
commercially available finite element analysis software
package.
2. EQUIVALENT STATIC FORCE METHOD
The seismic force effect on the structure can be translated
to equivalent lateral forceat the base of the structure andthen
this force will be distributed to the different stories and then to
the vertical structural elements (frames and/ or shear walls)
The static lateral force procedure may be used for the
following structures:
a. All structures, regular or irregular, in Seismic Zone 1
and in Seismic Zone 2.
b. Regular structures under 240 feet (73,152 mm) in
height.
c. Irregular structures not more than five stories or 65
feet (19,812 mm) in height.
d. Structures having a flexible upper portion supported
on a rigid lower portion where both portions of the
structure considered separately can be classified as
being regular, the average story stiffness of the lower
International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056
Volume: 06 Issue: 06 | June 2019 www.irjet.net p-ISSN: 2395-0072
© 2019, IRJET | Impact Factor value: 7.211 | ISO 9001:2008 Certified Journal | Page 3605
portion is at least 10 times the average story stiffness
of the upper portion and the period of the entire
structure is not greater than 1.1 times the period of
the upper portion considered as a separate structure
fixed at the base.
However, for simple regular structures, analysis by
equivalent linear static methods is often sufficient. This is
permitted in most codes of practice for regular, low- to
medium-rise buildings. It begins with an estimation of base
shear load and its distribution on each story calculated by
using formulas given in the code. Equivalentstaticanalysiscan
therefore work well for low to medium-rise buildings without
significant coupled lateral-torsional modes, in which only the
first mode in each direction is considered. Tall buildings (over,
say, 75 m), where second and higher modes can be important,
or buildings with torsional effects, are much less suitable for
the method, and require more complex methods to be used in
these circumstances (Earthquake Design Practice For
Buildings, E. Booth).
Regular buildings up to around 15 storeys in height can
usually be designed using equivalent static analysis; tall
buildings or those with significant irregularities in elevation
(sudden changes in mass or stiffness with height) or plan
(separation between the centres of stiffness and mass at any
level) require modal response spectrum analysis. Non-linear
static or dynamic analysis (time history analysis) is becoming
more common in design practice, and has for many years been
mandatory in Japan for buildings taller than 60m.
3. RESPONSE SPECTRUM ANALYSIS
In order to perform the seismic analysis and design of a
structure to be built at a particular location, the actual time
history record is required. However, it is not possible to have
such records at each and every location. Further, the seismic
analysis of structures cannotbecarriedoutsimplybasedonthe
peak value of the ground acceleration as the response of the
structure depend upon the frequencycontentofgroundmotion
and its own dynamic properties. To overcome the above
difficulties, earthquake response spectrum is the most popular
tool in the seismic analysis of structures. There are
computational advantages in using the response spectrum
methodof seismic analysis for prediction of displacementsand
member forces in structural systems. The method involves the
calculation of only the maximum values of the displacements
and member forces in each mode of vibration using smooth
design spectra that are the average of several earthquake
motions.
4. DESCRIPTION AND MODELLING OF BUILDING
A 3D RC frames with 5 bay by 4 bay and 7(G+6) storey of
dimension 25mx16mx23.5m, has been taken for seismic
analysis. Five building models are considered for comparison:
Model-1: Bare Frame with Flat Slab (BFFS)
Model-2: Exterior Shear Wall with Flat Slab (E-SWFS)
Model-3: L-Shaped Shear Wall with Flat Slab (L-SWFS)
Model-4: Rectangular Shear Wall with Flat Slab (R-SWFS)
Model-5: Lift core Shear Wall with Flat Slab (LC-SWFS)
5. LOAD CONSIDERATION
The following loading standards are considered on the
models during analysis
A. Gravity and Lateral loads
The RC frames comprises of columns, beams and flat slabs.
Analysis of the frames is done using ETABS 9.7.1 software. The
structural systems are subjected to 3 types of Primary Load
Cases as per provisions of Indian Standard Code of Practice for
Structural safety of Buildings, loading standards IS 875-1987
(Part I and II) and IS 1893 2002(Part I) they are:
i. Dead Load case (Vertical or Gravity load), denoted as
“DL”
ii. Live Load case (Vertical or Gravity load), denoted as
“LL”
iii. Floor Finish case(VerticalorGravityload),denotedas
“FF”
iv. Seismic Load in X-direction (Lateral or Earthquake
load), denoted as “Ex”
v. Seismic Load in Y-direction (Lateral or Earthquake
load), denoted as “Ey”
B. Gravity Loads
Gravity loads on the structure include the self-weight of
beams, columns, flat slabs. The self-weight of beams and
columns (frame members) and flat slabs (area sections) is
automatically considered by the program itself.
i. Dead Load (DL)
The dead load isconsideredasperIS875-1987(PartI-Dead
loads), “Code of Practice for Design Loads (Other than
Earthquake) for Buildings and Structures”.
 Unit weight of Reinforced Concrete = 25 kN/m3
 Floor finishes = 2 kN/m2
ii. Imposed/Live Load (LL)
The imposed load is considered as perIS 875-1987 (Part II-
Imposed loads), “Code of Practice for DesignLoads(Otherthan
Earthquake) for Buildings and Structures”.
International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056
Volume: 06 Issue: 06 | June 2019 www.irjet.net p-ISSN: 2395-0072
© 2019, IRJET | Impact Factor value: 7.211 | ISO 9001:2008 Certified Journal | Page 3606
 Imposed load on slab = 4 kN/m2
 Imposed load on roof = 4 kN/m2
C. Lateral Loads
i. Equivalent static lateral force method
The earthquake load is considered as per the IS 1893-
2002(Part 1). The factors considered are
Zone factor (z) = 0.36
Soil type = medium (Type-2)
Importance factor (I) = 1.0
Response reduction factor (R) =3.0
Time period,
For bare frame Ta = 0.075* h 0.75
Ta = 0.075* (22) 0.75 = 0.76 sec
For shear wall Ta = (0.09* h)/(sqrt of D)
Where D = base dimension in ‘m’
h = height of the building above the ground level in ‘m’
For D=25m in X-direction
Ta = (0.09* 22)/ (sqrt of 25) = 0.396 sec
For D=16m in Y-direction
Ta = (0.09* 22)/ (sqrt of 16) = 0.495 sec
ii. Response Spectrum Method
The earthquake load is considered as per the IS 1893-
2002(Part 1). The factors considered are
Soil Condition: Medium soil
Damping: 5%
TABLE-1: SEISMIC ZONES AS PER IS 1893(PART 1):2002
Seismic
Zone
II III IV V
Seismic
Intensity
Low Moderate Severe
Very
Severe
Zone
Factor (Z)
0.10 0.16 0.24 0.36
6. DETAILS OF RC FRAME
FIG -1: BUILDING PLAN-BARE FRAME
FIG -2: ELEVATION- FLAT SLAB WITH BARE FRAME
FIG-3: 3D VIEW- FLAT SLAB WITH BARE FRAME
International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056
Volume: 06 Issue: 06 | June 2019 www.irjet.net p-ISSN: 2395-0072
© 2019, IRJET | Impact Factor value: 7.211 | ISO 9001:2008 Certified Journal | Page 3607
A. Building Data
i. Grid System-Grid Dimensions (Plan)
Number of bays = 5 bay by 4 bay
Number of bays in X-direction = 5 bay
Number of bays in Y-direction = 4 bay
ii. Story Height
Number of Storeys =7 Storey (G +6)
Depth of foundation =1.5 m
Bottom storey =4.0 m
Other storeys =3.0 m
iii. Structural Elements Dimension
Beam size =0.2 m x 0.6 m
Column size =0.6 m x 0.6 m
Flat Slab thickness =0.20 m
Drop thickness =0.350 m
B. Material properties
i. Concrete (IS456:2000)
Grade of Concrete: M25 and M30
M25 for beams and Flat slabs
M30 for columns
Compressive strength of concrete, fck=25000 kN/m2 and
30000 kN/m2
Density of Concrete (weight per unit volume) =25 kN/m3
Modulus of Elasticity of concrete, Ef= (5000√fck) = 22.36X106
kN/m2 and 27.38 X106 kN/m2
Poisson’s ratio of concrete=0.2
ii.Steel (IS456:2000)
Grade of Steel: Fe 415
Yield Strength of Steel, Fy= 415000 kN/m2
C. ETABS Models of Structural Systems
Different types of frames considered for this analysis are as
follows:
Model-1: Bare Frame with Flat Slab (BFFS)
Model-2: Exterior Shear Wall with Flat Slab (E-SWFS)
Model-3: L-Shaped Shear Wall with Flat Slab (L-SWFS)
Model-4: Rectangular Shear Wall with Flat Slab (R-SWFS)
Model-5: Lift core Shear Wall with Flat Slab (LC-SWFS)
FIG-4: PLAN- FLAT SLAB WITH L- SHAPED SHEAR WALL
FIG-5: ELEVATION- FLAT SLAB WITH L-SHAPED SHEAR
WALL
FIG-6: 3D VIEW- FLAT SLAB WITH L-SHAPED SHEAR WALL
International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056
Volume: 06 Issue: 06 | June 2019 www.irjet.net p-ISSN: 2395-0072
© 2019, IRJET | Impact Factor value: 7.211 | ISO 9001:2008 Certified Journal | Page 3608
FIG-7: PLAN - FLAT SLAB WITH EXTERIOR - SHEAR WALL
FIG-8: PLAN - FLAT SLAB WITH RECTANGULAR- SHEAR
WALL
FIG-9: PLAN- FLAT SLAB WITH LIFT CORE- SHEAR WALL
7. RESULTS AND DISCUSSIONS
The analysis is carried out to compare the response of RC
flat slab with bare frame and flat slab with shear wall with
different location. Total five models are considered for the
linear static and dynamic analysis which includes Equivalent
Static Force Method and Response Spectrum Analysis. From
Equivalent Static Force Method base shear, maximum storey
drift and displacement results are obtained for zone-5, soil
type-2 as per IS 1893-2002(part-1). From Response Spectrum
Analysis acceleration results are obtained.
A. Storey and Base Shear
Storey and Base Shear (kN) in X Direction
No. of
Storeys
Model 1 Model 2 Model 3 Model
4
Model 5
Storey 6 826.49 1516.11 1515.46 1511.57 1792.21
Storey 5 1513.58 3203.75 2948.86 2994.38 3248.64
Storey 4 2014.29 4448.27 3999.87 4083.17 4309.66
Storey 3 2358.04 5317.30 4727.82 4838.84 5038.63
Storey 2 2574.27 5878.46 5192.07 5322.30 5496.96
Storey 1 2692.39 6199.37 5451.97 5594.44 5747.35
Ground
Floor
2743.25 6348.70 5583.76 5737.12 5859.55
TABLE -2: COMPARISON OF STOREY AND BASE SHEAR
ALONG X DIRECTION FOR DIFFERENT MODELS
FIG-10: COMPARISON OF STOREY AND BASE SHEAR ALONG
X DIRECTION FOR DIFFERENT MODELS
From Fig. 10, it is observed that, the decrease in storey
shear in bare frame (model- 1) is nearly 57%, 51%, 53% and
54% at ground floor (base level) comparedtomodel-2, model-
3, model-4 and model-5 in equivalent static lateral force
method for zone-5, medium soil in X-X direction. It is observed
that, there is a decrease in storey shear which is nearly69% to
78% in storey-6 compared to ground floor for all models (i.e.
model-1 to model-5) and the storey shear goes on increases
from storey-6 to ground floor in X-X direction in Equivalent
static force method for all models (i.e. model-1 to model-5).
TABLE-3: COMPARISON OF STOREY AND BASE SHEAR
ALONG Y DIRECTION FOR DIFFERENT MODELS
Storey and Base Shear (kN) in Y Direction
No. of
Storeys
Model 1 Model 2 Model 3 Model 4 Model 5
Storey 6 782.47 1516.11 1432.93 1511.57 1792.21
Storey 5 1432.96 3203.75 2788.27 2994.38 3248.64
Storey 4 1907.00 4448.27 3782.03 4083.17 4309.66
Storey 3 2232.44 5317.30 4470.34 4838.84 5038.63
Storey 2 2437.15 5878.46 4909.31 5322.30 5496.96
Storey 1 2548.99 6199.37 5155.06 5594.44 5747.35
Ground
Floor
2597.13 6348.70 5265.20 5717.57 5859.55
International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056
Volume: 06 Issue: 06 | June 2019 www.irjet.net p-ISSN: 2395-0072
© 2019, IRJET | Impact Factor value: 7.211 | ISO 9001:2008 Certified Journal | Page 3609
FIG-11: COMPARISON OF STOREY AND BASE SHEAR
ALONG Y DIRECTION FOR DIFFERENT MODELS
From Fig. 11, it is observed that, the decrease in storey
shear in bare frame (model-1) is nearly 59%, 51%, 55% and
56% at ground floor (base level) comparedtomodel-2, model-
3, model-4 and model-5 in equivalent static lateral force
method for zone-5, medium soil in Y-Y direction. It is observed
that, there was a decrease in storey shear which is nearly70%
to 80% in storey-6 compared to ground floor for all models
(i.e. model-1 to model-5) and the storey shear goes on
increases from storey-6 to ground floor in Y-Y direction in
Equivalent static force method for all models (i.e. model-1 to
model-5).
B. Storey and Base Displacements
Storey and Base Displacement (mm) in X Direction
No. of
Storeys
Model 1 Model 2 Model 3 Model 4 Model 5
Storey 6 35.89 1.19 17.76 4.95 2.78
Storey 5 33.52 1.09 15.05 4.26 2.45
Storey 4 29.96 0.95 12.21 3.51 2.07
Storey 3 25.31 0.79 9.37 2.74 1.67
Storey 2 19.87 0.62 6.62 1.99 1.26
Storey 1 13.94 0.44 4.13 1.30 0.86
Ground
Floor
7.83 0.27 2.06 0.70 0.50
TABLE-4: COMPARISON OF STOREY AND BASE
DISPLACEMENT ALONG X DIRECTION FOR DIFFERENT
MODELS
FIG-12: COMPARISON OF STOREY AND BASE
DISPLACEMENT ALONG X DIRECTION FOR DIFFERENT
MODELS
From Fig. 12, it is observed that, there is an increase in
displacement which is nearly 78% in storey-6 compared to
ground floor and the displacement goes on decreases from
storey-6 to ground floor in X-X direction in Equivalent static
force method. This shows the displacementvalueis morein top
floor compared to bottom floor because stiffnessparticipation
factor is more in ground floor compared to top floor in X-X
direction.
It is observed that, there is a increase in displacement
which is nearly 75% to 85% in storey-6 compared to ground
floor for all models (i.e. model-1 to model-5) and the
displacement goes on decreases from storey-6 to ground floor
in X-X direction in Equivalent static force method for all
models (i.e. model-1 to model-5).
Storey and Base Displacement (mm) in Y Direction
No. of
Storeys
Model 1 Model 2 Model 3 Model 4 Model 5
Storey 6 38.49 2.18 24.26 18.93 6.41
Storey 5 35.76 1.97 20.63 16.09 2.45
Storey 4 31.79 1.71 16.82 13.11 2.07
Storey 3 26.68 1.41 12.95 10.09 1.67
Storey 2 20.73 1.09 9.18 7.17 1.26
Storey 1 14.30 0.77 5.73 4.49 0.86
Ground
Floor
7.79 0.46 2.84 2.26 0.50
TABLE-5:COMPARISON OF STOREY AND BASE
DISPLACEMENT ALONG Y DIRECTION FOR DIFFERENT
MODELS
FIG-13: COMPARISON OF STOREY AND BASE
DISPLACEMENT ALONG Y DIRECTION FOR DIFFERENT
MODELS
From Fig. 13, it is observed that, there is an increase in
displacement which is nearly 80% in storey-6 compared to
ground floor and the displacement goes on decreases from
storey-6 to ground floor in Y-Y direction in Equivalent static
force method. This shows the displacementvalueis morein top
floor compared to bottom floor because stiffness participation
factor is more in ground floor compared to top floor in Y-Y
direction.
International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056
Volume: 06 Issue: 06 | June 2019 www.irjet.net p-ISSN: 2395-0072
© 2019, IRJET | Impact Factor value: 7.211 | ISO 9001:2008 Certified Journal | Page 3610
It is observed that, there is an increase in displacement
which is nearly 79% to 92% in storey-6 compared to ground
floor for all models (i.e. model-1 to model-5) and the
displacement goes on decreases from storey-6 to ground floor
in Y-Y direction in Equivalent static force method for all
models (i.e. model-1 to model-5).
C. Acceleration
Acceleration (m/s2) in X Direction
No. of
Storeys
Model 1 Model 2 Model 3 Model 4 Model
5
Storey 6 1.4117 2.4036 3.0290 2.8409 2.6354
Storey 5 1.1784 2.1916 2.4063 2.3684 2.2862
Storey 4 1.0627 1.9319 1.9772 1.9523 1.9434
Storey 3 0.9979 1.6638 1.7289 1.6437 1.6466
Storey 2 0.9637 1.3954 1.5426 1.3993 1.3789
Storey 1 0.8843 1.0988 1.2897 1.1403 1.1150
Ground
Floor
0.7006 0.7435 0.9084 0.7956 0.7888
TABLE-6:COMPARISON OF ACCELERATION ALONG X
DIRECTION FOR DIFFERENT MODELS
FIG-14: COMPARISON OF ACCELERATION ALONG X
DIRECTION FOR DIFFERENT MODELS
From Fig 14, it is observed that, there is an increase in
acceleration which is nearly 51% in storey-6 compared to
ground floor and the acceleration goes on decreases from
storey-6 to ground floor in X-X direction both in Equivalent
static force and response spectrum .This shows the
acceleration value is more in top floor compared to bottom
floor because mass participation factorismore ingroundfloor
compared to top floor both in X-X direction.
It is observed that, there is an increase in acceleration
which is nearly 55% to 85% in storey-6 compared to ground
floor for all models (i.e. model-1 to model-5) and the d
acceleration goes on decreases from storey-6 to ground floor
in X-X direction both in Equivalent static force and response
spectrum method for all models(i.e. model-1 to model-5).
Acceleration (m/s2) in Y Direction
No. of
Storeys
Model 1 Model 2 Model 3 Model 4 Model
5
Storey 6 1.3917 2.4920 2.8635 3.0816 2.7172
Storey 5 1.1326 2.2332 2.2712 2.408 2.3106
Storey 4 1.0209 1.9426 1.8817 1.9822 1.9508
Storey 3 0.9697 1.6669 1.6545 1.7318 1.6771
Storey 2 0.9504 1.4056 1.4769 1.5396 1.4548
Storey 1 0.8796 1.1185 1.2368 1.2942 1.2135
Ground
Floor
0.6967 0.7666 0.8759 0.9179 0.8748
TABLE-7:COMPARISON OF ACCELERATION ALONG Y
DIRECTION FOR DIFFERENT MODELS
FIG-15: COMPARISON OF ACCELERATION ALONG Y
DIRECTION FOR DIFFERENT MODELS
From Fig 15, it is observed that, there is an increase in
acceleration which is nearly 50% in storey-6 compared to
ground floor and the acceleration goes on decreases from
storey-6 to ground floor in Y-Y direction both in Equivalent
static force and response spectrum .This shows the
acceleration value is more in top floor compared to bottom
floor because mass participation factorismore ingroundfloor
compared to top floor both in Y-Y direction.
It is observed that, there is an increase in acceleration
which is nearly 50% to 70% in storey-6 compared to ground
floor for all models (i.e. model-1 to model-5) and the d
acceleration goes on decreases from storey-6 to ground floor
in Y-Y direction both in Equivalent static force and response
spectrum method for all models(i.e. model-1 to model-5).
8. CONCLUSIONS
This paper presents the summary of the study, for RC Flat
slab building for bare and shear wall with different location.
The effect of seismic load has been studied for the five types of
building with bare and shear wall with different location. On
the basis of the results following conclusionshavebeendrawn.
International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056
Volume: 06 Issue: 06 | June 2019 www.irjet.net p-ISSN: 2395-0072
© 2019, IRJET | Impact Factor value: 7.211 | ISO 9001:2008 Certified Journal | Page 3611
1. For all the structure, base shear is maximum at the
base level (ground floor). Base shear of flat slab R.C.C building
with bare frame is less than the flat slab building with shear
wall for different models or location because of mass
participation factor are more in shearwall buildingcompared
with that of flat slab with bare frame.
2. For all the structure, displacement increases as the
height increases. Displacement of flat slab R.C.C building with
bare frame is more than the flat slab building with shear wall
for different models or location because of stiffness
participation factor is more in shear wall building compared
with that of flat slab with bare frame. Displacement value for
model-2 (Exterior shear wall) is less compared with those
other models (i.e. model-1, model-3, model-4 and model-5).
Exterior shear wall structure gives better performance and
resists lateral displacement for seismic loads.
3. For flat slab building with bare frame, response
acceleration decreases with increase in the height of building,
however, for flat slab with shear wall; this change is not
significant because in both structures fewer members are
stiffened. Flat slab with bare frame is having less acceleration
value compared with that of flat slab with shear wall for
different models (i.e. model-2 to model-5).
REFERENCES
[1]. Pan A and MoehleJ. P, “LateralDisplacement Ductility
of RC Flat Plates”. ACI Structural Journal, 86:3, 1989, pp. 250-
258.
[2]. ACI-ASCE Committee 352, “Recommendations for
Design of Slab-Column Connections in Monolithic Reinforced
Concrete Structures”. ACI Structural Journal, 85:6, 1988, pp.
675-696.
[3]. Erberik M.A and Elnashai A.S, “Seismic Vulnerability
of Flat-Slab Structures”. Technical Report Mid-America
Earthquake Center DS-9 Project (Risk Assessment Modeling),
Civil and Environmental Engineering Department, University
of Illinois at Urbana-Champaign, USA, 2003, 178 pages.
[4]. Megally S and Ghali A, “Design Considerations for
Slab-Column Connections in Seismic Zones”. ACI Structural
Journal, 91:3, 1994, pp. 303-314.
[5]. Penelis G.G and Kappos A. J, “Earthquake Resistant
Concrete Structures”, E & FN Spon, London, UK, 1997.
[6]. Sobhy B.M, “A Comparative Study for Three-
DimensionalModelingandDesign-OrientedSeismicAnalysisof
Mid-rise Flat Slab Buildings”. M.Sc. Thesis, Structural
Engineering Department, Cairo University, Egypt, 1997.
[7]. Joshi D. S, Nene R. L, Muley M. D, Suresh Salgaonkar,
“Design of Reinforced Concrete Structure for Earthquake
Resistance”, Indian Society of Structural Engineers, pp.32-37.
[8]. Park R., “Capacity Design of Ductile RC Building
Structures for Earthquake Resistance”, Journal of the
Structural Engineer, Volume 70, No. 16, August 1 1992, pp.
279-289.
[9]. Sezen H., Whittaker A.S, Elwood and
Mosalam K.M, “Performance of Reinforced Concrete Buildings
during the August 17, 1999 Kocaeli, Turkey Earthquake, and
Seismic Design and Construction Practice in Turkey”, Journal
of Engineering Structures, Volume 25, 2003, pp. 103-114.

More Related Content

PDF
Influence of Concrete and Steel Outrigger and Belt Truss in High Rise Moment ...
PDF
STATIC LINEAR AND NON LINEAR (PUSHOVER) ANALYSIS OF RC BUILDING ON SLOPING GR...
PDF
A comparative study on force based design and direct displacement based desig...
PDF
Seismic Vulnerability of RC Building With and Without Soft Storey Effect Usi...
PDF
DESIGN AND ANALYSIS OF MULTI STORIED STRUCTURES USING STATIC NON LINEAR ANALYSIS
PPT
Elastic response spectra
PDF
Ijciet 06 08_007
PDF
Pushover analysis of multy story building
Influence of Concrete and Steel Outrigger and Belt Truss in High Rise Moment ...
STATIC LINEAR AND NON LINEAR (PUSHOVER) ANALYSIS OF RC BUILDING ON SLOPING GR...
A comparative study on force based design and direct displacement based desig...
Seismic Vulnerability of RC Building With and Without Soft Storey Effect Usi...
DESIGN AND ANALYSIS OF MULTI STORIED STRUCTURES USING STATIC NON LINEAR ANALYSIS
Elastic response spectra
Ijciet 06 08_007
Pushover analysis of multy story building

What's hot (20)

PDF
Descriptive study of pushover analysis in rcc structures of rigid joint
PDF
Non Linear Analysis of RCC Building with and Without Shear Wall
PDF
IRJET- Effect of Vertical Irregularities in R.C Frame Structures on Accuracy ...
PPTX
From force-based to displacement-based seismic design. What comes next?
PDF
Performance Based Evaluation of Shear Walled RCC Building by Pushover Analysis
PPT
The Pushover Analysis from basics - Rahul Leslie
PDF
PERFORMANCE BASED ANALYSIS OF VERTICALLY IRREGULAR STRUCTURE UNDER VARIOUS SE...
PDF
Variation of deflection of steel high rise structure due to p- delta effect c...
PDF
IRJET- Progressive Collapse of RCC Structure Due to Earthquake and Wind Load
PDF
Study of seismic analysis and design of multi storey symmetrical and asymmetr...
PDF
Non-Linear Static (Pushover) Analysis of Irregular Building Systems
PDF
Seismic response of existing rc building under revised seismic zone classific...
PDF
IRJET- Seismic Evolution of Soft Storeyed Structures When Exposed to Earth Qu...
PDF
Earthquake Analysis of Multi-Storied Buildings with Floating Columns
PPT
1223989 static pushover analysis
PDF
Modelling and Analysis of Pile Foundation
PDF
IRJET- Pushover Analysis on Reinforced Concrete Building using ETABS
PDF
Incremental Dynamic Analysis of RC Frames
PDF
IRJET- Comparative Study of Effect of Different Positions of Shear Wall o...
PPTX
A comparative study of static and response spectrum analysis of a rc building
Descriptive study of pushover analysis in rcc structures of rigid joint
Non Linear Analysis of RCC Building with and Without Shear Wall
IRJET- Effect of Vertical Irregularities in R.C Frame Structures on Accuracy ...
From force-based to displacement-based seismic design. What comes next?
Performance Based Evaluation of Shear Walled RCC Building by Pushover Analysis
The Pushover Analysis from basics - Rahul Leslie
PERFORMANCE BASED ANALYSIS OF VERTICALLY IRREGULAR STRUCTURE UNDER VARIOUS SE...
Variation of deflection of steel high rise structure due to p- delta effect c...
IRJET- Progressive Collapse of RCC Structure Due to Earthquake and Wind Load
Study of seismic analysis and design of multi storey symmetrical and asymmetr...
Non-Linear Static (Pushover) Analysis of Irregular Building Systems
Seismic response of existing rc building under revised seismic zone classific...
IRJET- Seismic Evolution of Soft Storeyed Structures When Exposed to Earth Qu...
Earthquake Analysis of Multi-Storied Buildings with Floating Columns
1223989 static pushover analysis
Modelling and Analysis of Pile Foundation
IRJET- Pushover Analysis on Reinforced Concrete Building using ETABS
Incremental Dynamic Analysis of RC Frames
IRJET- Comparative Study of Effect of Different Positions of Shear Wall o...
A comparative study of static and response spectrum analysis of a rc building
Ad

Similar to IRJET- Seismic Behavior of RC Flat Slab with and without Shear Wall Technique by using Response Spectrum Analysis (20)

PDF
Seismic Evolution of Soft Storeyed Buildings when Subjected to Real Time Eart...
PDF
IRJET- Seismic Analysis of Plan Regular and Irregular Buildings
PDF
Performance Based Evaluation of Conventional RC Framed Structure Compared wit...
PDF
IRJET- Comparative Analysis of Seismic Behavior of Flat Slab and Conventional...
PDF
Seismic performance of r c buildings on sloping grounds with different types ...
PDF
Seismic Response of Multi storey Flat Slab Building with and without Shear Wall
PDF
IRJET- A Review on Seismic Analysis and Sustainability of Multi Storey Struct...
PDF
Effects of Providing Shear wall and Bracing to Seismic Performance of Concret...
PDF
IRJET- Design of Earthquake Resistant Structure of Multi-Story RCC Building
PDF
IRJET- Seismic Analysis and Design of Regular and Irregular Framed Commer...
PDF
IRJET- Seismic Analysis of a RC Multi Storey Building with and without Floati...
PDF
Performing Pushover Analysis on High Rise Building With and Without Shear Wall
PDF
IRJET- A Study of Various Structural Framing Systems Subjected to Seismic Loads
PDF
Influence of Openings and Local Soil Conditions on the Seismic Behavior of Tu...
PDF
Dynamic Response of High Rise Structures Under The Influence of Shear Walls
PDF
Investigation on performance based non linear pushover analysis of flat plate...
PDF
IRJET- Effect of Bracing and Unbracing in Steel Stuctures by using ETabs
PDF
Seismic Performance and Shear Wall Location Assessment of a RC Building- Eva...
PDF
“Analysis of a Multistorey Building with Grid slab in Different Seismic Zones...
PDF
Seismic Response of RC Framed Structures Having Plan and Vertical Irregularit...
Seismic Evolution of Soft Storeyed Buildings when Subjected to Real Time Eart...
IRJET- Seismic Analysis of Plan Regular and Irregular Buildings
Performance Based Evaluation of Conventional RC Framed Structure Compared wit...
IRJET- Comparative Analysis of Seismic Behavior of Flat Slab and Conventional...
Seismic performance of r c buildings on sloping grounds with different types ...
Seismic Response of Multi storey Flat Slab Building with and without Shear Wall
IRJET- A Review on Seismic Analysis and Sustainability of Multi Storey Struct...
Effects of Providing Shear wall and Bracing to Seismic Performance of Concret...
IRJET- Design of Earthquake Resistant Structure of Multi-Story RCC Building
IRJET- Seismic Analysis and Design of Regular and Irregular Framed Commer...
IRJET- Seismic Analysis of a RC Multi Storey Building with and without Floati...
Performing Pushover Analysis on High Rise Building With and Without Shear Wall
IRJET- A Study of Various Structural Framing Systems Subjected to Seismic Loads
Influence of Openings and Local Soil Conditions on the Seismic Behavior of Tu...
Dynamic Response of High Rise Structures Under The Influence of Shear Walls
Investigation on performance based non linear pushover analysis of flat plate...
IRJET- Effect of Bracing and Unbracing in Steel Stuctures by using ETabs
Seismic Performance and Shear Wall Location Assessment of a RC Building- Eva...
“Analysis of a Multistorey Building with Grid slab in Different Seismic Zones...
Seismic Response of RC Framed Structures Having Plan and Vertical Irregularit...
Ad

More from IRJET Journal (20)

PDF
Enhanced heart disease prediction using SKNDGR ensemble Machine Learning Model
PDF
Utilizing Biomedical Waste for Sustainable Brick Manufacturing: A Novel Appro...
PDF
Kiona – A Smart Society Automation Project
PDF
DESIGN AND DEVELOPMENT OF BATTERY THERMAL MANAGEMENT SYSTEM USING PHASE CHANG...
PDF
Invest in Innovation: Empowering Ideas through Blockchain Based Crowdfunding
PDF
SPACE WATCH YOUR REAL-TIME SPACE INFORMATION HUB
PDF
A Review on Influence of Fluid Viscous Damper on The Behaviour of Multi-store...
PDF
Wireless Arduino Control via Mobile: Eliminating the Need for a Dedicated Wir...
PDF
Explainable AI(XAI) using LIME and Disease Detection in Mango Leaf by Transfe...
PDF
BRAIN TUMOUR DETECTION AND CLASSIFICATION
PDF
The Project Manager as an ambassador of the contract. The case of NEC4 ECC co...
PDF
"Enhanced Heat Transfer Performance in Shell and Tube Heat Exchangers: A CFD ...
PDF
Advancements in CFD Analysis of Shell and Tube Heat Exchangers with Nanofluid...
PDF
Breast Cancer Detection using Computer Vision
PDF
Auto-Charging E-Vehicle with its battery Management.
PDF
Analysis of high energy charge particle in the Heliosphere
PDF
A Novel System for Recommending Agricultural Crops Using Machine Learning App...
PDF
Auto-Charging E-Vehicle with its battery Management.
PDF
Analysis of high energy charge particle in the Heliosphere
PDF
Wireless Arduino Control via Mobile: Eliminating the Need for a Dedicated Wir...
Enhanced heart disease prediction using SKNDGR ensemble Machine Learning Model
Utilizing Biomedical Waste for Sustainable Brick Manufacturing: A Novel Appro...
Kiona – A Smart Society Automation Project
DESIGN AND DEVELOPMENT OF BATTERY THERMAL MANAGEMENT SYSTEM USING PHASE CHANG...
Invest in Innovation: Empowering Ideas through Blockchain Based Crowdfunding
SPACE WATCH YOUR REAL-TIME SPACE INFORMATION HUB
A Review on Influence of Fluid Viscous Damper on The Behaviour of Multi-store...
Wireless Arduino Control via Mobile: Eliminating the Need for a Dedicated Wir...
Explainable AI(XAI) using LIME and Disease Detection in Mango Leaf by Transfe...
BRAIN TUMOUR DETECTION AND CLASSIFICATION
The Project Manager as an ambassador of the contract. The case of NEC4 ECC co...
"Enhanced Heat Transfer Performance in Shell and Tube Heat Exchangers: A CFD ...
Advancements in CFD Analysis of Shell and Tube Heat Exchangers with Nanofluid...
Breast Cancer Detection using Computer Vision
Auto-Charging E-Vehicle with its battery Management.
Analysis of high energy charge particle in the Heliosphere
A Novel System for Recommending Agricultural Crops Using Machine Learning App...
Auto-Charging E-Vehicle with its battery Management.
Analysis of high energy charge particle in the Heliosphere
Wireless Arduino Control via Mobile: Eliminating the Need for a Dedicated Wir...

Recently uploaded (20)

PDF
PPT on Performance Review to get promotions
PDF
keyrequirementskkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkk
PPTX
MCN 401 KTU-2019-PPE KITS-MODULE 2.pptx
PDF
PRIZ Academy - 9 Windows Thinking Where to Invest Today to Win Tomorrow.pdf
PDF
Mohammad Mahdi Farshadian CV - Prospective PhD Student 2026
PPT
CRASH COURSE IN ALTERNATIVE PLUMBING CLASS
PDF
Mitigating Risks through Effective Management for Enhancing Organizational Pe...
PDF
Operating System & Kernel Study Guide-1 - converted.pdf
PDF
TFEC-4-2020-Design-Guide-for-Timber-Roof-Trusses.pdf
PPTX
KTU 2019 -S7-MCN 401 MODULE 2-VINAY.pptx
PDF
SM_6th-Sem__Cse_Internet-of-Things.pdf IOT
PDF
Model Code of Practice - Construction Work - 21102022 .pdf
DOCX
ASol_English-Language-Literature-Set-1-27-02-2023-converted.docx
PPTX
CARTOGRAPHY AND GEOINFORMATION VISUALIZATION chapter1 NPTE (2).pptx
PPTX
Recipes for Real Time Voice AI WebRTC, SLMs and Open Source Software.pptx
PPTX
Lecture Notes Electrical Wiring System Components
PPTX
CYBER-CRIMES AND SECURITY A guide to understanding
PDF
BMEC211 - INTRODUCTION TO MECHATRONICS-1.pdf
PDF
Embodied AI: Ushering in the Next Era of Intelligent Systems
PPTX
Internet of Things (IOT) - A guide to understanding
PPT on Performance Review to get promotions
keyrequirementskkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkk
MCN 401 KTU-2019-PPE KITS-MODULE 2.pptx
PRIZ Academy - 9 Windows Thinking Where to Invest Today to Win Tomorrow.pdf
Mohammad Mahdi Farshadian CV - Prospective PhD Student 2026
CRASH COURSE IN ALTERNATIVE PLUMBING CLASS
Mitigating Risks through Effective Management for Enhancing Organizational Pe...
Operating System & Kernel Study Guide-1 - converted.pdf
TFEC-4-2020-Design-Guide-for-Timber-Roof-Trusses.pdf
KTU 2019 -S7-MCN 401 MODULE 2-VINAY.pptx
SM_6th-Sem__Cse_Internet-of-Things.pdf IOT
Model Code of Practice - Construction Work - 21102022 .pdf
ASol_English-Language-Literature-Set-1-27-02-2023-converted.docx
CARTOGRAPHY AND GEOINFORMATION VISUALIZATION chapter1 NPTE (2).pptx
Recipes for Real Time Voice AI WebRTC, SLMs and Open Source Software.pptx
Lecture Notes Electrical Wiring System Components
CYBER-CRIMES AND SECURITY A guide to understanding
BMEC211 - INTRODUCTION TO MECHATRONICS-1.pdf
Embodied AI: Ushering in the Next Era of Intelligent Systems
Internet of Things (IOT) - A guide to understanding

IRJET- Seismic Behavior of RC Flat Slab with and without Shear Wall Technique by using Response Spectrum Analysis

  • 1. International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056 Volume: 06 Issue: 06 | June 2019 www.irjet.net p-ISSN: 2395-0072 © 2019, IRJET | Impact Factor value: 7.211 | ISO 9001:2008 Certified Journal | Page 3604 Seismic Behavior of RC Flat Slab with and without Shear Wall Technique by using Response Spectrum Analysis Shivaraju G D1, Usha S2, Kumbar Bhanu Prakash3 1Assistant Professor, Department of Civil Engineering, SSIT 2Assistant Professor, Department of Civil Engineering, BRCE 3Former Assistant Professor, Department of Civil Engineering, MVJCE ----------------------------------------------------------------------***--------------------------------------------------------------------- Abstract - Earthquake resistant structures are structures designed to withstand earthquakes. According to building codes, earthquake resistant structures are intended to withstand the largest earthquake of a certain probabilitythat is likely to occur at their location. This means the loss of life should be minimized by preventing collapse of the buildings for rare earthquakes while the loss of functionality should be limited for more frequent ones. In this paper, the dynamic response of RC flat slab with bare frame and flat slab with shear wall at different location is compared with static response of the structure. Five models are considered for the analysis which includes Equivalent Static Force Method and Response Spectrum Analysis. From Equivalent static force method base shear, maximum storey drift, displacement results are obtained and from response spectrum analysis acceleration results are obtained. For all the cases zone-5, soil type-2 as per IS 1893-2002(part-1) isconsideredandanalysed using ETABS, a commercially available finite elementanalysis software package. Key words : earthquake, equivalent static force method, modal analysis, displacement, acceleration. 1. INTRODUCTION Earthquake resistant design of RC buildings is a continuing area of research since the earthquake engineering has started not only in India but in other developed countries also. The buildings still damage due to one or the other reason during earthquakes. In spite of all the weaknesses in the structure, either code imperfections or error in analysis and design, the structural configuration system has played a vital role in disaster. Reinforced Concrete Flat Slabs are one of the most popular floor systems used in residentialbuildings,carparking and manyotherstructures.Theyrepresentelegantandeasy-to- construct floor systems. Flat slabs are favoured by both architects and clients because of their aesthetic appeal and economic advantage. A flatslab floor system is oftenthechoice when it comes to heavier loads such as multi-storey car parking, libraries and multi-storey buildings where larger spans are also required. Flat slab building structures are significantlymoreflexiblethantraditionalconcreteframe/wall or frame structures, thus becoming more vulnerable to second order p-effects under seismic excitations. Therefore, the characteristics of the seismic behaviour of flat slab buildings suggest that additional measures for guiding the conception and design of these structures in seismic regions are needed. Reinforced Concrete(RC)buildingsoftenhaveverticalSlab-like RC walls called Shear Walls or structural walls in addition to slabs, beams and columns. These RC wallsarereferredasshear walls because they resist a high proportion of the shear due to the lateral loads. However, failures of RC walls are not necessarily dominated by shear deformations. Shear walls define as vertically oriented wide beamsthatcarryearthquake loads to the foundation. It can also be defined as a slender vertical cantilever resisting the lateral load with or without frames. In this paper, the dynamic responseofRCflatslabwithbare frame and flat slab with shear wall at different location is compared with static response of the structure is studied. Five models are considered for the analysis which includes Equivalent Static Force Method and Response Spectrum Analysis. From Equivalent static force method base shear, maximum storey drift, displacement results are obtained and from response spectrum analysis acceleration results are obtained. For all the cases zone-5, soil type-2 as per IS 1893- 2002(part-1) is considered and analysed using ETABS, a commercially available finite element analysis software package. 2. EQUIVALENT STATIC FORCE METHOD The seismic force effect on the structure can be translated to equivalent lateral forceat the base of the structure andthen this force will be distributed to the different stories and then to the vertical structural elements (frames and/ or shear walls) The static lateral force procedure may be used for the following structures: a. All structures, regular or irregular, in Seismic Zone 1 and in Seismic Zone 2. b. Regular structures under 240 feet (73,152 mm) in height. c. Irregular structures not more than five stories or 65 feet (19,812 mm) in height. d. Structures having a flexible upper portion supported on a rigid lower portion where both portions of the structure considered separately can be classified as being regular, the average story stiffness of the lower
  • 2. International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056 Volume: 06 Issue: 06 | June 2019 www.irjet.net p-ISSN: 2395-0072 © 2019, IRJET | Impact Factor value: 7.211 | ISO 9001:2008 Certified Journal | Page 3605 portion is at least 10 times the average story stiffness of the upper portion and the period of the entire structure is not greater than 1.1 times the period of the upper portion considered as a separate structure fixed at the base. However, for simple regular structures, analysis by equivalent linear static methods is often sufficient. This is permitted in most codes of practice for regular, low- to medium-rise buildings. It begins with an estimation of base shear load and its distribution on each story calculated by using formulas given in the code. Equivalentstaticanalysiscan therefore work well for low to medium-rise buildings without significant coupled lateral-torsional modes, in which only the first mode in each direction is considered. Tall buildings (over, say, 75 m), where second and higher modes can be important, or buildings with torsional effects, are much less suitable for the method, and require more complex methods to be used in these circumstances (Earthquake Design Practice For Buildings, E. Booth). Regular buildings up to around 15 storeys in height can usually be designed using equivalent static analysis; tall buildings or those with significant irregularities in elevation (sudden changes in mass or stiffness with height) or plan (separation between the centres of stiffness and mass at any level) require modal response spectrum analysis. Non-linear static or dynamic analysis (time history analysis) is becoming more common in design practice, and has for many years been mandatory in Japan for buildings taller than 60m. 3. RESPONSE SPECTRUM ANALYSIS In order to perform the seismic analysis and design of a structure to be built at a particular location, the actual time history record is required. However, it is not possible to have such records at each and every location. Further, the seismic analysis of structures cannotbecarriedoutsimplybasedonthe peak value of the ground acceleration as the response of the structure depend upon the frequencycontentofgroundmotion and its own dynamic properties. To overcome the above difficulties, earthquake response spectrum is the most popular tool in the seismic analysis of structures. There are computational advantages in using the response spectrum methodof seismic analysis for prediction of displacementsand member forces in structural systems. The method involves the calculation of only the maximum values of the displacements and member forces in each mode of vibration using smooth design spectra that are the average of several earthquake motions. 4. DESCRIPTION AND MODELLING OF BUILDING A 3D RC frames with 5 bay by 4 bay and 7(G+6) storey of dimension 25mx16mx23.5m, has been taken for seismic analysis. Five building models are considered for comparison: Model-1: Bare Frame with Flat Slab (BFFS) Model-2: Exterior Shear Wall with Flat Slab (E-SWFS) Model-3: L-Shaped Shear Wall with Flat Slab (L-SWFS) Model-4: Rectangular Shear Wall with Flat Slab (R-SWFS) Model-5: Lift core Shear Wall with Flat Slab (LC-SWFS) 5. LOAD CONSIDERATION The following loading standards are considered on the models during analysis A. Gravity and Lateral loads The RC frames comprises of columns, beams and flat slabs. Analysis of the frames is done using ETABS 9.7.1 software. The structural systems are subjected to 3 types of Primary Load Cases as per provisions of Indian Standard Code of Practice for Structural safety of Buildings, loading standards IS 875-1987 (Part I and II) and IS 1893 2002(Part I) they are: i. Dead Load case (Vertical or Gravity load), denoted as “DL” ii. Live Load case (Vertical or Gravity load), denoted as “LL” iii. Floor Finish case(VerticalorGravityload),denotedas “FF” iv. Seismic Load in X-direction (Lateral or Earthquake load), denoted as “Ex” v. Seismic Load in Y-direction (Lateral or Earthquake load), denoted as “Ey” B. Gravity Loads Gravity loads on the structure include the self-weight of beams, columns, flat slabs. The self-weight of beams and columns (frame members) and flat slabs (area sections) is automatically considered by the program itself. i. Dead Load (DL) The dead load isconsideredasperIS875-1987(PartI-Dead loads), “Code of Practice for Design Loads (Other than Earthquake) for Buildings and Structures”.  Unit weight of Reinforced Concrete = 25 kN/m3  Floor finishes = 2 kN/m2 ii. Imposed/Live Load (LL) The imposed load is considered as perIS 875-1987 (Part II- Imposed loads), “Code of Practice for DesignLoads(Otherthan Earthquake) for Buildings and Structures”.
  • 3. International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056 Volume: 06 Issue: 06 | June 2019 www.irjet.net p-ISSN: 2395-0072 © 2019, IRJET | Impact Factor value: 7.211 | ISO 9001:2008 Certified Journal | Page 3606  Imposed load on slab = 4 kN/m2  Imposed load on roof = 4 kN/m2 C. Lateral Loads i. Equivalent static lateral force method The earthquake load is considered as per the IS 1893- 2002(Part 1). The factors considered are Zone factor (z) = 0.36 Soil type = medium (Type-2) Importance factor (I) = 1.0 Response reduction factor (R) =3.0 Time period, For bare frame Ta = 0.075* h 0.75 Ta = 0.075* (22) 0.75 = 0.76 sec For shear wall Ta = (0.09* h)/(sqrt of D) Where D = base dimension in ‘m’ h = height of the building above the ground level in ‘m’ For D=25m in X-direction Ta = (0.09* 22)/ (sqrt of 25) = 0.396 sec For D=16m in Y-direction Ta = (0.09* 22)/ (sqrt of 16) = 0.495 sec ii. Response Spectrum Method The earthquake load is considered as per the IS 1893- 2002(Part 1). The factors considered are Soil Condition: Medium soil Damping: 5% TABLE-1: SEISMIC ZONES AS PER IS 1893(PART 1):2002 Seismic Zone II III IV V Seismic Intensity Low Moderate Severe Very Severe Zone Factor (Z) 0.10 0.16 0.24 0.36 6. DETAILS OF RC FRAME FIG -1: BUILDING PLAN-BARE FRAME FIG -2: ELEVATION- FLAT SLAB WITH BARE FRAME FIG-3: 3D VIEW- FLAT SLAB WITH BARE FRAME
  • 4. International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056 Volume: 06 Issue: 06 | June 2019 www.irjet.net p-ISSN: 2395-0072 © 2019, IRJET | Impact Factor value: 7.211 | ISO 9001:2008 Certified Journal | Page 3607 A. Building Data i. Grid System-Grid Dimensions (Plan) Number of bays = 5 bay by 4 bay Number of bays in X-direction = 5 bay Number of bays in Y-direction = 4 bay ii. Story Height Number of Storeys =7 Storey (G +6) Depth of foundation =1.5 m Bottom storey =4.0 m Other storeys =3.0 m iii. Structural Elements Dimension Beam size =0.2 m x 0.6 m Column size =0.6 m x 0.6 m Flat Slab thickness =0.20 m Drop thickness =0.350 m B. Material properties i. Concrete (IS456:2000) Grade of Concrete: M25 and M30 M25 for beams and Flat slabs M30 for columns Compressive strength of concrete, fck=25000 kN/m2 and 30000 kN/m2 Density of Concrete (weight per unit volume) =25 kN/m3 Modulus of Elasticity of concrete, Ef= (5000√fck) = 22.36X106 kN/m2 and 27.38 X106 kN/m2 Poisson’s ratio of concrete=0.2 ii.Steel (IS456:2000) Grade of Steel: Fe 415 Yield Strength of Steel, Fy= 415000 kN/m2 C. ETABS Models of Structural Systems Different types of frames considered for this analysis are as follows: Model-1: Bare Frame with Flat Slab (BFFS) Model-2: Exterior Shear Wall with Flat Slab (E-SWFS) Model-3: L-Shaped Shear Wall with Flat Slab (L-SWFS) Model-4: Rectangular Shear Wall with Flat Slab (R-SWFS) Model-5: Lift core Shear Wall with Flat Slab (LC-SWFS) FIG-4: PLAN- FLAT SLAB WITH L- SHAPED SHEAR WALL FIG-5: ELEVATION- FLAT SLAB WITH L-SHAPED SHEAR WALL FIG-6: 3D VIEW- FLAT SLAB WITH L-SHAPED SHEAR WALL
  • 5. International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056 Volume: 06 Issue: 06 | June 2019 www.irjet.net p-ISSN: 2395-0072 © 2019, IRJET | Impact Factor value: 7.211 | ISO 9001:2008 Certified Journal | Page 3608 FIG-7: PLAN - FLAT SLAB WITH EXTERIOR - SHEAR WALL FIG-8: PLAN - FLAT SLAB WITH RECTANGULAR- SHEAR WALL FIG-9: PLAN- FLAT SLAB WITH LIFT CORE- SHEAR WALL 7. RESULTS AND DISCUSSIONS The analysis is carried out to compare the response of RC flat slab with bare frame and flat slab with shear wall with different location. Total five models are considered for the linear static and dynamic analysis which includes Equivalent Static Force Method and Response Spectrum Analysis. From Equivalent Static Force Method base shear, maximum storey drift and displacement results are obtained for zone-5, soil type-2 as per IS 1893-2002(part-1). From Response Spectrum Analysis acceleration results are obtained. A. Storey and Base Shear Storey and Base Shear (kN) in X Direction No. of Storeys Model 1 Model 2 Model 3 Model 4 Model 5 Storey 6 826.49 1516.11 1515.46 1511.57 1792.21 Storey 5 1513.58 3203.75 2948.86 2994.38 3248.64 Storey 4 2014.29 4448.27 3999.87 4083.17 4309.66 Storey 3 2358.04 5317.30 4727.82 4838.84 5038.63 Storey 2 2574.27 5878.46 5192.07 5322.30 5496.96 Storey 1 2692.39 6199.37 5451.97 5594.44 5747.35 Ground Floor 2743.25 6348.70 5583.76 5737.12 5859.55 TABLE -2: COMPARISON OF STOREY AND BASE SHEAR ALONG X DIRECTION FOR DIFFERENT MODELS FIG-10: COMPARISON OF STOREY AND BASE SHEAR ALONG X DIRECTION FOR DIFFERENT MODELS From Fig. 10, it is observed that, the decrease in storey shear in bare frame (model- 1) is nearly 57%, 51%, 53% and 54% at ground floor (base level) comparedtomodel-2, model- 3, model-4 and model-5 in equivalent static lateral force method for zone-5, medium soil in X-X direction. It is observed that, there is a decrease in storey shear which is nearly69% to 78% in storey-6 compared to ground floor for all models (i.e. model-1 to model-5) and the storey shear goes on increases from storey-6 to ground floor in X-X direction in Equivalent static force method for all models (i.e. model-1 to model-5). TABLE-3: COMPARISON OF STOREY AND BASE SHEAR ALONG Y DIRECTION FOR DIFFERENT MODELS Storey and Base Shear (kN) in Y Direction No. of Storeys Model 1 Model 2 Model 3 Model 4 Model 5 Storey 6 782.47 1516.11 1432.93 1511.57 1792.21 Storey 5 1432.96 3203.75 2788.27 2994.38 3248.64 Storey 4 1907.00 4448.27 3782.03 4083.17 4309.66 Storey 3 2232.44 5317.30 4470.34 4838.84 5038.63 Storey 2 2437.15 5878.46 4909.31 5322.30 5496.96 Storey 1 2548.99 6199.37 5155.06 5594.44 5747.35 Ground Floor 2597.13 6348.70 5265.20 5717.57 5859.55
  • 6. International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056 Volume: 06 Issue: 06 | June 2019 www.irjet.net p-ISSN: 2395-0072 © 2019, IRJET | Impact Factor value: 7.211 | ISO 9001:2008 Certified Journal | Page 3609 FIG-11: COMPARISON OF STOREY AND BASE SHEAR ALONG Y DIRECTION FOR DIFFERENT MODELS From Fig. 11, it is observed that, the decrease in storey shear in bare frame (model-1) is nearly 59%, 51%, 55% and 56% at ground floor (base level) comparedtomodel-2, model- 3, model-4 and model-5 in equivalent static lateral force method for zone-5, medium soil in Y-Y direction. It is observed that, there was a decrease in storey shear which is nearly70% to 80% in storey-6 compared to ground floor for all models (i.e. model-1 to model-5) and the storey shear goes on increases from storey-6 to ground floor in Y-Y direction in Equivalent static force method for all models (i.e. model-1 to model-5). B. Storey and Base Displacements Storey and Base Displacement (mm) in X Direction No. of Storeys Model 1 Model 2 Model 3 Model 4 Model 5 Storey 6 35.89 1.19 17.76 4.95 2.78 Storey 5 33.52 1.09 15.05 4.26 2.45 Storey 4 29.96 0.95 12.21 3.51 2.07 Storey 3 25.31 0.79 9.37 2.74 1.67 Storey 2 19.87 0.62 6.62 1.99 1.26 Storey 1 13.94 0.44 4.13 1.30 0.86 Ground Floor 7.83 0.27 2.06 0.70 0.50 TABLE-4: COMPARISON OF STOREY AND BASE DISPLACEMENT ALONG X DIRECTION FOR DIFFERENT MODELS FIG-12: COMPARISON OF STOREY AND BASE DISPLACEMENT ALONG X DIRECTION FOR DIFFERENT MODELS From Fig. 12, it is observed that, there is an increase in displacement which is nearly 78% in storey-6 compared to ground floor and the displacement goes on decreases from storey-6 to ground floor in X-X direction in Equivalent static force method. This shows the displacementvalueis morein top floor compared to bottom floor because stiffnessparticipation factor is more in ground floor compared to top floor in X-X direction. It is observed that, there is a increase in displacement which is nearly 75% to 85% in storey-6 compared to ground floor for all models (i.e. model-1 to model-5) and the displacement goes on decreases from storey-6 to ground floor in X-X direction in Equivalent static force method for all models (i.e. model-1 to model-5). Storey and Base Displacement (mm) in Y Direction No. of Storeys Model 1 Model 2 Model 3 Model 4 Model 5 Storey 6 38.49 2.18 24.26 18.93 6.41 Storey 5 35.76 1.97 20.63 16.09 2.45 Storey 4 31.79 1.71 16.82 13.11 2.07 Storey 3 26.68 1.41 12.95 10.09 1.67 Storey 2 20.73 1.09 9.18 7.17 1.26 Storey 1 14.30 0.77 5.73 4.49 0.86 Ground Floor 7.79 0.46 2.84 2.26 0.50 TABLE-5:COMPARISON OF STOREY AND BASE DISPLACEMENT ALONG Y DIRECTION FOR DIFFERENT MODELS FIG-13: COMPARISON OF STOREY AND BASE DISPLACEMENT ALONG Y DIRECTION FOR DIFFERENT MODELS From Fig. 13, it is observed that, there is an increase in displacement which is nearly 80% in storey-6 compared to ground floor and the displacement goes on decreases from storey-6 to ground floor in Y-Y direction in Equivalent static force method. This shows the displacementvalueis morein top floor compared to bottom floor because stiffness participation factor is more in ground floor compared to top floor in Y-Y direction.
  • 7. International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056 Volume: 06 Issue: 06 | June 2019 www.irjet.net p-ISSN: 2395-0072 © 2019, IRJET | Impact Factor value: 7.211 | ISO 9001:2008 Certified Journal | Page 3610 It is observed that, there is an increase in displacement which is nearly 79% to 92% in storey-6 compared to ground floor for all models (i.e. model-1 to model-5) and the displacement goes on decreases from storey-6 to ground floor in Y-Y direction in Equivalent static force method for all models (i.e. model-1 to model-5). C. Acceleration Acceleration (m/s2) in X Direction No. of Storeys Model 1 Model 2 Model 3 Model 4 Model 5 Storey 6 1.4117 2.4036 3.0290 2.8409 2.6354 Storey 5 1.1784 2.1916 2.4063 2.3684 2.2862 Storey 4 1.0627 1.9319 1.9772 1.9523 1.9434 Storey 3 0.9979 1.6638 1.7289 1.6437 1.6466 Storey 2 0.9637 1.3954 1.5426 1.3993 1.3789 Storey 1 0.8843 1.0988 1.2897 1.1403 1.1150 Ground Floor 0.7006 0.7435 0.9084 0.7956 0.7888 TABLE-6:COMPARISON OF ACCELERATION ALONG X DIRECTION FOR DIFFERENT MODELS FIG-14: COMPARISON OF ACCELERATION ALONG X DIRECTION FOR DIFFERENT MODELS From Fig 14, it is observed that, there is an increase in acceleration which is nearly 51% in storey-6 compared to ground floor and the acceleration goes on decreases from storey-6 to ground floor in X-X direction both in Equivalent static force and response spectrum .This shows the acceleration value is more in top floor compared to bottom floor because mass participation factorismore ingroundfloor compared to top floor both in X-X direction. It is observed that, there is an increase in acceleration which is nearly 55% to 85% in storey-6 compared to ground floor for all models (i.e. model-1 to model-5) and the d acceleration goes on decreases from storey-6 to ground floor in X-X direction both in Equivalent static force and response spectrum method for all models(i.e. model-1 to model-5). Acceleration (m/s2) in Y Direction No. of Storeys Model 1 Model 2 Model 3 Model 4 Model 5 Storey 6 1.3917 2.4920 2.8635 3.0816 2.7172 Storey 5 1.1326 2.2332 2.2712 2.408 2.3106 Storey 4 1.0209 1.9426 1.8817 1.9822 1.9508 Storey 3 0.9697 1.6669 1.6545 1.7318 1.6771 Storey 2 0.9504 1.4056 1.4769 1.5396 1.4548 Storey 1 0.8796 1.1185 1.2368 1.2942 1.2135 Ground Floor 0.6967 0.7666 0.8759 0.9179 0.8748 TABLE-7:COMPARISON OF ACCELERATION ALONG Y DIRECTION FOR DIFFERENT MODELS FIG-15: COMPARISON OF ACCELERATION ALONG Y DIRECTION FOR DIFFERENT MODELS From Fig 15, it is observed that, there is an increase in acceleration which is nearly 50% in storey-6 compared to ground floor and the acceleration goes on decreases from storey-6 to ground floor in Y-Y direction both in Equivalent static force and response spectrum .This shows the acceleration value is more in top floor compared to bottom floor because mass participation factorismore ingroundfloor compared to top floor both in Y-Y direction. It is observed that, there is an increase in acceleration which is nearly 50% to 70% in storey-6 compared to ground floor for all models (i.e. model-1 to model-5) and the d acceleration goes on decreases from storey-6 to ground floor in Y-Y direction both in Equivalent static force and response spectrum method for all models(i.e. model-1 to model-5). 8. CONCLUSIONS This paper presents the summary of the study, for RC Flat slab building for bare and shear wall with different location. The effect of seismic load has been studied for the five types of building with bare and shear wall with different location. On the basis of the results following conclusionshavebeendrawn.
  • 8. International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056 Volume: 06 Issue: 06 | June 2019 www.irjet.net p-ISSN: 2395-0072 © 2019, IRJET | Impact Factor value: 7.211 | ISO 9001:2008 Certified Journal | Page 3611 1. For all the structure, base shear is maximum at the base level (ground floor). Base shear of flat slab R.C.C building with bare frame is less than the flat slab building with shear wall for different models or location because of mass participation factor are more in shearwall buildingcompared with that of flat slab with bare frame. 2. For all the structure, displacement increases as the height increases. Displacement of flat slab R.C.C building with bare frame is more than the flat slab building with shear wall for different models or location because of stiffness participation factor is more in shear wall building compared with that of flat slab with bare frame. Displacement value for model-2 (Exterior shear wall) is less compared with those other models (i.e. model-1, model-3, model-4 and model-5). Exterior shear wall structure gives better performance and resists lateral displacement for seismic loads. 3. For flat slab building with bare frame, response acceleration decreases with increase in the height of building, however, for flat slab with shear wall; this change is not significant because in both structures fewer members are stiffened. Flat slab with bare frame is having less acceleration value compared with that of flat slab with shear wall for different models (i.e. model-2 to model-5). REFERENCES [1]. Pan A and MoehleJ. P, “LateralDisplacement Ductility of RC Flat Plates”. ACI Structural Journal, 86:3, 1989, pp. 250- 258. [2]. ACI-ASCE Committee 352, “Recommendations for Design of Slab-Column Connections in Monolithic Reinforced Concrete Structures”. ACI Structural Journal, 85:6, 1988, pp. 675-696. [3]. Erberik M.A and Elnashai A.S, “Seismic Vulnerability of Flat-Slab Structures”. Technical Report Mid-America Earthquake Center DS-9 Project (Risk Assessment Modeling), Civil and Environmental Engineering Department, University of Illinois at Urbana-Champaign, USA, 2003, 178 pages. [4]. Megally S and Ghali A, “Design Considerations for Slab-Column Connections in Seismic Zones”. ACI Structural Journal, 91:3, 1994, pp. 303-314. [5]. Penelis G.G and Kappos A. J, “Earthquake Resistant Concrete Structures”, E & FN Spon, London, UK, 1997. [6]. Sobhy B.M, “A Comparative Study for Three- DimensionalModelingandDesign-OrientedSeismicAnalysisof Mid-rise Flat Slab Buildings”. M.Sc. Thesis, Structural Engineering Department, Cairo University, Egypt, 1997. [7]. Joshi D. S, Nene R. L, Muley M. D, Suresh Salgaonkar, “Design of Reinforced Concrete Structure for Earthquake Resistance”, Indian Society of Structural Engineers, pp.32-37. [8]. Park R., “Capacity Design of Ductile RC Building Structures for Earthquake Resistance”, Journal of the Structural Engineer, Volume 70, No. 16, August 1 1992, pp. 279-289. [9]. Sezen H., Whittaker A.S, Elwood and Mosalam K.M, “Performance of Reinforced Concrete Buildings during the August 17, 1999 Kocaeli, Turkey Earthquake, and Seismic Design and Construction Practice in Turkey”, Journal of Engineering Structures, Volume 25, 2003, pp. 103-114.