Let us start initially with a clear commitment:
the IT system ("unearthed system") is a type of system infrequently used com-
pared to the TN or TT system ("earthed system") – but it would often be the
better alternative.
So why is the worse alternative accepted in prac-
tice? The answer is probably: habit, convenience,
ignorance. Many electrical planners are unfamiliar
with the IT system. It is barely touched upon in uni-
versities and training centres. The earthed system
has therefore become increasingly widespread.
The IT system is used infrequently and then above
all only where its advantages are essential, e.g. in
operating theatres and intensive care stations, or in
railway signalling systems. Why? Because the issue
here is lives. Because we are talking about human
lives. But shouldn’t it always be a concern in our
power supply systems?
Let us take a look at the advantages and disad-
vantages of the IT system:
FIRST ADVANTAGE: inherently safe
– small difference, big impact
The IT system primarily differs from the TN or TT
system in the electrical connection between earth
and the star point on the transformer that supplies
the system. This connection is present on earthed
systems, on unearthed systems it is left out. As an
alternative to the supply transformer, an IT system
can also comprise another source of power, for
Why the IT system is often the best choice
for power supply systems of all types
SECOND ADVANTAGE:
fault localisation
It is possible to locate insulation faults during
operation or in de-energised condition using
so-called insulation fault location systems (IFLS).
Permanently installed devices and mobile devices
are available for this purpose. Fault location is in
principle also possible in earthed systems using
residual current monitoring (RCM) technology.
However, with the restriction that this technology
only works in energised systems and, unlike in
the IT system, remains restricted to asymmetric
insulation faults.
THIRD ADVANTAGE:
no undesirable service interruptions
As stated above, the IT system is inherently safe.
This situation means, almost as a side effect, that
in the event of an insulation fault – even if there is a
dead earth fault – shutdown is not necessary. This
is also the reason why IT systems are stipulated,
e.g., in intensive care units. In the event of an insula-
tion fault, the supply to life-supporting equipment is
maintained. The IT system is in general, excellently
suited to all applications in which shutdowns are
undesirable, would have serious consequences or
would cause high costs – in the process industry,
in computer centres, in automation and, in prin-
ciple, everywhere. Control circuits of all types are
particularly important. Control errors and failures
in control circuits – for example in a substation
or in a nuclear power station – can have serious
consequences. Based on the information provided
by the insulation monitoring device it is possible to
plan long-term servicing and maintenance work in
the IT system and avoid unplanned service calls to
rectify malfunctions.
FOURTH ADVANTAGE:
early detection of deteriorations
A further key advantage is that deteriorations in the
level of insulation can be detected immediately. In
an earthed system fault currents can be resolved in
instance, a battery. In the unearthed system all-pole
protection of all active conductors is necessary. The
same applies to the N conductor, if installed. Since
in a single-phase system none of the two conduc-
tors are earthed, there will be two live conductors
instead of a classical “Phase and neutral”.
What is then the big difference in the impact if there
is only such a small difference in the implementa-
tion? If an uninsulated live conductor or a conduc-
tive enclosure is touched on a live load, NOTHING
happens with an intact unearthed system. Why?
Because a current can only flow in a circuit and the
circuit has not been closed as the star point of the
transformer has not been earthed. It is like a bird on
a high voltage overhead power line, you are safe.
What is the situation on the earthed system? In this
case a closed circuit is set-up in advance and, to
a certain degree, is just waiting for the fault. If in
this case a person touches a live conductor or a
live conductive casing, a fault current immediately
flows through the person due to the low impedance
connection to the supply transformer. This situation
would be dangerous without functional fast switch-
off protection equipment. This circuit is protected
via fuses and residual current devices (also called
RCDs) such that, in the event of a fault, shutdown
occurs quickly enough so the person is not seri-
ously harmed. To make sure that this protection
also functions, the protection equipment must be
regularly checked. For instance, the functionality of
RCDs in electrical installations must be tested every
six months – also in private households. But how
often is this check actually made?
The IT system offers inherent protection against
touch voltages. The only exception here are AC sys-
tems with very high system leakage capacitances
and asymmetric loads. Possible measures in these
cases are, firstly, division into smaller subsystems
and, secondly, the measurement of the capaci-
tance and the calculation of the maximum current
through the body in the event of a fault, which is
possible using the new insulation monitoring device
ISOMETER®
iso685. It goes without saying that
insulation faults must be rectified promptly to keep
the system safe, even in the IT system.
the single-digit milliamp range using sophisticated
residual current monitoring (RCM) technology –
but no further. This situation means detection of
the deterioration of the insulation below 40 kΩ at a
mains voltage of 400 V and a resolution of 10 mA,
if it were possible to select only the ohmic portion
of the residual current. This is a significant improve-
ment compared to an unearthed system not being
monitored that unexpectedly shuts down. In the IT
system an insulation value of 40 kΩ corresponds
to the recommended primary response value. It is
possible to measure in the megaohm range and
above in the IT system – which signifies a factor
of at least 1,000 compared to the earthed system.
Therefore, deteriorations in the insulation can be
measured and rectified very early.
FIFTH ADVANTAGE:
detection of symmetrical faults
In an IT system it is possible to detect symmetrical
faults using an actively measuring insulation moni-
toring device in accordance with IEC 61557-8.
Symmetrical faults are deteriorations in the insula-
tion of a similar order of magnitude on all phase
conductors. Such faults are not unusual. For exam-
ple, the insulation figures in photovoltaic installa-
tions often deteriorate to a similar degree on the
positive and negative side.
SIXTH ADVANTAGE:
measurements in DC systems
RCDs for pure DC systems such as battery systems
are not currently available. Possible options are
either devices for residual current monitoring (RCM)
with a DC supply voltage or implementation as an
IT system with insulation monitoring. In DC systems
the ISOMETER®
iso685 also offers the advantage
that it indicates whether the fault is on the positive
or negative side.
SEVENTH ADVANTAGE:
measurement in mixed AC systems
with DC components
If there are battery systems, inverters, switch mode
power supplies etc. in the AC system, DC fault
currents are possible. The widespread RCDs of
type A for pure AC systems are unsuitable here. In
the earthed system it is only possible to use RCDs
of type B or it must be ensured by other means that
the system is shut down on the occurrence of DC
currents above 6 mA. An appropriate alternative is to
operate the installation as an unearthed system and
to monitor it using an insulation monitoring device.
EIGHTH ADVANTAGE:
offline monitoring
As an insulation monitoring device in accordance
with IEC 61557-8 measures actively in the IT system,
it can also monitor completely de-energised IT or TN
systems. This aspect is important, for example, for
railway points heating, fire extinguishing pumps on
ships, redundant cooling systems in nuclear power
stations. In this way it is also possible to detect an
insulation fault on a heater for railway points in sum-
mer so it can be repaired in good time. Otherwise,
the fault would only be found on switching on in the
winter – in the form of the immediate failure of the
installation exactly when it is needed.
NINTH ADVANTAGE: closing the gap
between the periodic tests
The insulation monitoring device stipulated for
the IT system continuously monitors the insulation
value. Conversely, during the periodic tests (key-
word BGV A3 test) only the instantaneous state of
the insulation is measured. This state can deterio-
rate dramatically immediately after the test and
remain unnoticed for a long time. Continuous moni-
toring by means of the additional usage of residual
current monitoring systems (RCM technology) is
also possible in the earthed system.
ISOMETER® iso685
via switch mode power supplies, the washing
machine contains an inverter and frequency con-
verters are used in large numbers for motors in
industry. A powerful insulation monitoring device
in the IT system has no problem with these issues
and correctly measures the insulation value for
the entire system. The IT system is particularly
suitable for usage with inverters, as in the event
of a serious insulation fault in the link circuit on
large inverter drives in an IT system, damage to the
inductive elements or supplying generators and
transformers due to DC currents and the related
saturation effects in iron cores cannot occur. The
ISOMETER®
iso685 was developed for monitoring
systems with frequency converters and makes it
possible to logically link system parameters to shut
down drives automatically in a critical system state.
Differentiation between faults in the link circuit and
on the motor side in inverter drives is possible in
the iso685 without additional expense or other
equipment.
THIRTEENTH ADVANTAGE:
no stray currents
Stray currents often cause problems in earthed
systems. These are currents that do not flow via the
L, N and PE conductor, but find other paths. They
cause corrosion and pitting on pipes, lightning pro-
tection systems, ball bearings, foundation earths
and other conductive components. They can also
result in the destruction of screens on signal cables
and even fire; as a consequence magnetic field
interference can occur that causes problems in IT
and communication systems. As the return path
to the transformer's star point is not closed in the
unearthed system, stray currents cannot propagate
in unearthed systems.
TENTH ADVANTAGE:
prevention of fire
Insulation faults in electrical installations are the
most common cause of fire. The probability of fire in
the IT system is much lower. Firstly, insulation faults
can be detected and rectified at an early stage in
their evolution. Secondly, as there is no low imped-
ance return path, a current large enough to cause
a fire does not flow in the event of an insulation
fault. The restriction to systems that do not have
an excessively system leakage capacitance also
applies here.
ELEVENTH ADVANTAGE:
long-term view
The new ISOMETERs®
iso685 and iso1685 are
able to record a full set of system parameters with
date and time information over many years. In con-
junction with other recorded system information,
this aspect permits event-based fault analysis and
makes it easier to find and rectify faults that occur
sporadically; it also improves the information avail-
able for making decisions on future investments.
The evaluation can be undertaken in the device
itself or via Ethernet.
TWELFTH ADVANTAGE:
safe handling of non-linear loads,
in particular inverters
These days systems contain ever fewer linear
(ohmic) loads. The incandescent lamp has been
replaced with energy-saving lamps or LEDs, com-
puters and television are connected to the system
ISOMETER® iso1685
FOURTEENTH ADVANTAGE:
more stable in the event of transients
In IEC 62109-1:2010 the possibility of reducing
the overvoltage category from CAT IV to CAT III
by means of isolation using isolating transform-
ers, optocouplers or similar electrical isolation is
described because transients do not cause such
high currents as in earthed systems. The practical
consequence is that components in the electrical
loads in the IT system are subjected less to voltage
spikes and as result have a longer service life.
Now let us look at the disadvantages of the IT
system:
FIRST DISADVANTAGE:
IT systems should not be too large
Very large IT systems can become confusing and
have an undesirably high system leakage capaci-
tance. It is therefore recommended to divide very
large IT systems into separate units using isolating
transformers, which can cause additional costs and
power losses that, however, overall are mostly negli-
gible. The division into electrically isolated subsys-
tems also has advantages, such as the filtering effect
in relation to interference or the possibility to specifi-
cally adjust the voltages to the loads supplied. What
constitutes a large system must be evaluated in the
specific case and depends on the system param-
eters. For instance, the world's largest PV fields can
be monitored entirely by individual ISOMETERs®
of
type isoPV. Which means that a single ISOMETER®
does not miss a faulty connector, a damaged cable
or a damaged PV module, despite an installation the
size of ten football pitches or more.
SECOND DISADVANTAGE:
voltage increase in the event of
insulation faults
In an IT system with insulation faults on one con-
ductor, the line-to-line voltages on the other con-
ductors increase in relation to the earth potential. In
the event of a dead earth fault on a conductor in the
230 V system, the voltages on the other conductors
increase in relation to the earth potential to approx.
400 V. System components on which the potential
in relation to earth is an issue, in particular Y capaci-
tors and overvoltage limiters, should therefore be
suitable for the maximum rated voltage. Voltage
increase can be avoided when the secondary side of
the transformer is connected in Delta mode.
ISOMETER® isoPV
Coupling device
AGH-PV-3
CONCLUSION:
The IT system has many advantages over earthed
systems and is suitable not only for the high
requirements in operating theatres or in nuclear
power stations, but practically everywhere. In
many cases these days this system is not con-
sidered at all, even though it would be the better
choice. The latest generation of insulation moni-
toring devices also offers many economical and
technical advantages that benefit the operator.
Sometimes the costs for an insulation monitoring
device are used as an argument against an IT
system, however, the opposite is the case: in view
of the advantages listed above and their econom-
ical effects, usage in the commercial sector is
always worthwhile!
Dr. Dirk Pieler
Former CEO of Bender GmbH & Co. KG, Grünberg

More Related Content

PDF
Electrical-Safety-Productoverview_PROSP_en
PPT
Solar Power Fencing solutions from Blaze Automation
PPT
Fence presentation
PDF
IRJET - Digital Differential Protection of Power Transformer using MATLAB
PDF
Sequoia wind power
PDF
Solar Power Fencing
PDF
Presentation o surge protection devices
PDF
monkey menace solution , freedom from monkey problms
Electrical-Safety-Productoverview_PROSP_en
Solar Power Fencing solutions from Blaze Automation
Fence presentation
IRJET - Digital Differential Protection of Power Transformer using MATLAB
Sequoia wind power
Solar Power Fencing
Presentation o surge protection devices
monkey menace solution , freedom from monkey problms

What's hot (19)

PPTX
Syngenta solar power fencing by blaze automation
PPTX
Circuit breaker Maintenance By Mobile Agent Software Technology
PDF
Wind Energy
PPT
Ppt for solar fencing
DOCX
Abraham CV 03.06.2015
PDF
Tacstickmanual
PPT
Advanced Network Solutions for Electric Power Application
PDF
Switchgear and protection.
PPT
9900 Presentation
PDF
Industrial Surge Protection: Why Use Mersen Surge Protection Devices?
PPTX
Adaptive relaying
PPTX
Introducing BriteSpot
PDF
Technical guide-for-electromagnetic-disturbance-protection
PPT
Fully Integrated Switch-Mode Power Regulators
PDF
Cylinder Sensor Brochure
PDF
Security electric fence introduction
PDF
Security electric fence introduction
PDF
International Journal of Engineering Research and Development
Syngenta solar power fencing by blaze automation
Circuit breaker Maintenance By Mobile Agent Software Technology
Wind Energy
Ppt for solar fencing
Abraham CV 03.06.2015
Tacstickmanual
Advanced Network Solutions for Electric Power Application
Switchgear and protection.
9900 Presentation
Industrial Surge Protection: Why Use Mersen Surge Protection Devices?
Adaptive relaying
Introducing BriteSpot
Technical guide-for-electromagnetic-disturbance-protection
Fully Integrated Switch-Mode Power Regulators
Cylinder Sensor Brochure
Security electric fence introduction
Security electric fence introduction
International Journal of Engineering Research and Development
Ad

Similar to IT (Floating) System (20)

PPSX
Residual current monitorning (rcm) prevent electrical fire & hazards
PDF
IRJET- Fault Detection, Classification and Location using GPS System
PDF
IRJET- Embedded System based Multi-Source Leakage Current Protection for Low ...
PDF
Underground Cable Fault Detection Using IOT
PDF
ISLANDING DETECTION TECHNIQUE FOR DISTRIBUTED GENERATION SYSTEM
PDF
Ground fault protection
PDF
Ground fault protection
PPTX
wireless fault protection and detection for dc microgrid
PDF
MS4000 Snapshot
PDF
Neutral grounding resistor
PDF
Islanding Detection and Controlled Islanding in Emerging Power Systems Key Is...
PDF
151 south africa cap bank-protection-baker-duly-2008
PDF
G42022933
PDF
IRJET- Cable Fault Detection using IoT
PPTX
GIS substation Information (Detailed Report)
PPTX
Earthing Syatem
PDF
WP1 UPS Topologies
PDF
EarthSense Data Sheet
PDF
A Passive Islanding Detection Method for Neutral point clamped Multilevel Inv...
PDF
Integrated earthing systems
Residual current monitorning (rcm) prevent electrical fire & hazards
IRJET- Fault Detection, Classification and Location using GPS System
IRJET- Embedded System based Multi-Source Leakage Current Protection for Low ...
Underground Cable Fault Detection Using IOT
ISLANDING DETECTION TECHNIQUE FOR DISTRIBUTED GENERATION SYSTEM
Ground fault protection
Ground fault protection
wireless fault protection and detection for dc microgrid
MS4000 Snapshot
Neutral grounding resistor
Islanding Detection and Controlled Islanding in Emerging Power Systems Key Is...
151 south africa cap bank-protection-baker-duly-2008
G42022933
IRJET- Cable Fault Detection using IoT
GIS substation Information (Detailed Report)
Earthing Syatem
WP1 UPS Topologies
EarthSense Data Sheet
A Passive Islanding Detection Method for Neutral point clamped Multilevel Inv...
Integrated earthing systems
Ad

Recently uploaded (20)

PPTX
additive manufacturing of ss316l using mig welding
PPTX
Welding lecture in detail for understanding
PPT
Mechanical Engineering MATERIALS Selection
DOCX
573137875-Attendance-Management-System-original
PPTX
Construction Project Organization Group 2.pptx
PDF
Enhancing Cyber Defense Against Zero-Day Attacks using Ensemble Neural Networks
PPTX
Foundation to blockchain - A guide to Blockchain Tech
PPTX
web development for engineering and engineering
PDF
Embodied AI: Ushering in the Next Era of Intelligent Systems
PDF
TFEC-4-2020-Design-Guide-for-Timber-Roof-Trusses.pdf
PPT
Project quality management in manufacturing
PPTX
UNIT 4 Total Quality Management .pptx
PDF
composite construction of structures.pdf
PDF
keyrequirementskkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkk
PPTX
bas. eng. economics group 4 presentation 1.pptx
PPTX
CH1 Production IntroductoryConcepts.pptx
PPTX
CYBER-CRIMES AND SECURITY A guide to understanding
PPTX
OOP with Java - Java Introduction (Basics)
PDF
Mitigating Risks through Effective Management for Enhancing Organizational Pe...
PPTX
Engineering Ethics, Safety and Environment [Autosaved] (1).pptx
additive manufacturing of ss316l using mig welding
Welding lecture in detail for understanding
Mechanical Engineering MATERIALS Selection
573137875-Attendance-Management-System-original
Construction Project Organization Group 2.pptx
Enhancing Cyber Defense Against Zero-Day Attacks using Ensemble Neural Networks
Foundation to blockchain - A guide to Blockchain Tech
web development for engineering and engineering
Embodied AI: Ushering in the Next Era of Intelligent Systems
TFEC-4-2020-Design-Guide-for-Timber-Roof-Trusses.pdf
Project quality management in manufacturing
UNIT 4 Total Quality Management .pptx
composite construction of structures.pdf
keyrequirementskkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkk
bas. eng. economics group 4 presentation 1.pptx
CH1 Production IntroductoryConcepts.pptx
CYBER-CRIMES AND SECURITY A guide to understanding
OOP with Java - Java Introduction (Basics)
Mitigating Risks through Effective Management for Enhancing Organizational Pe...
Engineering Ethics, Safety and Environment [Autosaved] (1).pptx

IT (Floating) System

  • 1. Let us start initially with a clear commitment: the IT system ("unearthed system") is a type of system infrequently used com- pared to the TN or TT system ("earthed system") – but it would often be the better alternative. So why is the worse alternative accepted in prac- tice? The answer is probably: habit, convenience, ignorance. Many electrical planners are unfamiliar with the IT system. It is barely touched upon in uni- versities and training centres. The earthed system has therefore become increasingly widespread. The IT system is used infrequently and then above all only where its advantages are essential, e.g. in operating theatres and intensive care stations, or in railway signalling systems. Why? Because the issue here is lives. Because we are talking about human lives. But shouldn’t it always be a concern in our power supply systems? Let us take a look at the advantages and disad- vantages of the IT system: FIRST ADVANTAGE: inherently safe – small difference, big impact The IT system primarily differs from the TN or TT system in the electrical connection between earth and the star point on the transformer that supplies the system. This connection is present on earthed systems, on unearthed systems it is left out. As an alternative to the supply transformer, an IT system can also comprise another source of power, for Why the IT system is often the best choice for power supply systems of all types
  • 2. SECOND ADVANTAGE: fault localisation It is possible to locate insulation faults during operation or in de-energised condition using so-called insulation fault location systems (IFLS). Permanently installed devices and mobile devices are available for this purpose. Fault location is in principle also possible in earthed systems using residual current monitoring (RCM) technology. However, with the restriction that this technology only works in energised systems and, unlike in the IT system, remains restricted to asymmetric insulation faults. THIRD ADVANTAGE: no undesirable service interruptions As stated above, the IT system is inherently safe. This situation means, almost as a side effect, that in the event of an insulation fault – even if there is a dead earth fault – shutdown is not necessary. This is also the reason why IT systems are stipulated, e.g., in intensive care units. In the event of an insula- tion fault, the supply to life-supporting equipment is maintained. The IT system is in general, excellently suited to all applications in which shutdowns are undesirable, would have serious consequences or would cause high costs – in the process industry, in computer centres, in automation and, in prin- ciple, everywhere. Control circuits of all types are particularly important. Control errors and failures in control circuits – for example in a substation or in a nuclear power station – can have serious consequences. Based on the information provided by the insulation monitoring device it is possible to plan long-term servicing and maintenance work in the IT system and avoid unplanned service calls to rectify malfunctions. FOURTH ADVANTAGE: early detection of deteriorations A further key advantage is that deteriorations in the level of insulation can be detected immediately. In an earthed system fault currents can be resolved in instance, a battery. In the unearthed system all-pole protection of all active conductors is necessary. The same applies to the N conductor, if installed. Since in a single-phase system none of the two conduc- tors are earthed, there will be two live conductors instead of a classical “Phase and neutral”. What is then the big difference in the impact if there is only such a small difference in the implementa- tion? If an uninsulated live conductor or a conduc- tive enclosure is touched on a live load, NOTHING happens with an intact unearthed system. Why? Because a current can only flow in a circuit and the circuit has not been closed as the star point of the transformer has not been earthed. It is like a bird on a high voltage overhead power line, you are safe. What is the situation on the earthed system? In this case a closed circuit is set-up in advance and, to a certain degree, is just waiting for the fault. If in this case a person touches a live conductor or a live conductive casing, a fault current immediately flows through the person due to the low impedance connection to the supply transformer. This situation would be dangerous without functional fast switch- off protection equipment. This circuit is protected via fuses and residual current devices (also called RCDs) such that, in the event of a fault, shutdown occurs quickly enough so the person is not seri- ously harmed. To make sure that this protection also functions, the protection equipment must be regularly checked. For instance, the functionality of RCDs in electrical installations must be tested every six months – also in private households. But how often is this check actually made? The IT system offers inherent protection against touch voltages. The only exception here are AC sys- tems with very high system leakage capacitances and asymmetric loads. Possible measures in these cases are, firstly, division into smaller subsystems and, secondly, the measurement of the capaci- tance and the calculation of the maximum current through the body in the event of a fault, which is possible using the new insulation monitoring device ISOMETER® iso685. It goes without saying that insulation faults must be rectified promptly to keep the system safe, even in the IT system.
  • 3. the single-digit milliamp range using sophisticated residual current monitoring (RCM) technology – but no further. This situation means detection of the deterioration of the insulation below 40 kΩ at a mains voltage of 400 V and a resolution of 10 mA, if it were possible to select only the ohmic portion of the residual current. This is a significant improve- ment compared to an unearthed system not being monitored that unexpectedly shuts down. In the IT system an insulation value of 40 kΩ corresponds to the recommended primary response value. It is possible to measure in the megaohm range and above in the IT system – which signifies a factor of at least 1,000 compared to the earthed system. Therefore, deteriorations in the insulation can be measured and rectified very early. FIFTH ADVANTAGE: detection of symmetrical faults In an IT system it is possible to detect symmetrical faults using an actively measuring insulation moni- toring device in accordance with IEC 61557-8. Symmetrical faults are deteriorations in the insula- tion of a similar order of magnitude on all phase conductors. Such faults are not unusual. For exam- ple, the insulation figures in photovoltaic installa- tions often deteriorate to a similar degree on the positive and negative side. SIXTH ADVANTAGE: measurements in DC systems RCDs for pure DC systems such as battery systems are not currently available. Possible options are either devices for residual current monitoring (RCM) with a DC supply voltage or implementation as an IT system with insulation monitoring. In DC systems the ISOMETER® iso685 also offers the advantage that it indicates whether the fault is on the positive or negative side. SEVENTH ADVANTAGE: measurement in mixed AC systems with DC components If there are battery systems, inverters, switch mode power supplies etc. in the AC system, DC fault currents are possible. The widespread RCDs of type A for pure AC systems are unsuitable here. In the earthed system it is only possible to use RCDs of type B or it must be ensured by other means that the system is shut down on the occurrence of DC currents above 6 mA. An appropriate alternative is to operate the installation as an unearthed system and to monitor it using an insulation monitoring device. EIGHTH ADVANTAGE: offline monitoring As an insulation monitoring device in accordance with IEC 61557-8 measures actively in the IT system, it can also monitor completely de-energised IT or TN systems. This aspect is important, for example, for railway points heating, fire extinguishing pumps on ships, redundant cooling systems in nuclear power stations. In this way it is also possible to detect an insulation fault on a heater for railway points in sum- mer so it can be repaired in good time. Otherwise, the fault would only be found on switching on in the winter – in the form of the immediate failure of the installation exactly when it is needed. NINTH ADVANTAGE: closing the gap between the periodic tests The insulation monitoring device stipulated for the IT system continuously monitors the insulation value. Conversely, during the periodic tests (key- word BGV A3 test) only the instantaneous state of the insulation is measured. This state can deterio- rate dramatically immediately after the test and remain unnoticed for a long time. Continuous moni- toring by means of the additional usage of residual current monitoring systems (RCM technology) is also possible in the earthed system. ISOMETER® iso685
  • 4. via switch mode power supplies, the washing machine contains an inverter and frequency con- verters are used in large numbers for motors in industry. A powerful insulation monitoring device in the IT system has no problem with these issues and correctly measures the insulation value for the entire system. The IT system is particularly suitable for usage with inverters, as in the event of a serious insulation fault in the link circuit on large inverter drives in an IT system, damage to the inductive elements or supplying generators and transformers due to DC currents and the related saturation effects in iron cores cannot occur. The ISOMETER® iso685 was developed for monitoring systems with frequency converters and makes it possible to logically link system parameters to shut down drives automatically in a critical system state. Differentiation between faults in the link circuit and on the motor side in inverter drives is possible in the iso685 without additional expense or other equipment. THIRTEENTH ADVANTAGE: no stray currents Stray currents often cause problems in earthed systems. These are currents that do not flow via the L, N and PE conductor, but find other paths. They cause corrosion and pitting on pipes, lightning pro- tection systems, ball bearings, foundation earths and other conductive components. They can also result in the destruction of screens on signal cables and even fire; as a consequence magnetic field interference can occur that causes problems in IT and communication systems. As the return path to the transformer's star point is not closed in the unearthed system, stray currents cannot propagate in unearthed systems. TENTH ADVANTAGE: prevention of fire Insulation faults in electrical installations are the most common cause of fire. The probability of fire in the IT system is much lower. Firstly, insulation faults can be detected and rectified at an early stage in their evolution. Secondly, as there is no low imped- ance return path, a current large enough to cause a fire does not flow in the event of an insulation fault. The restriction to systems that do not have an excessively system leakage capacitance also applies here. ELEVENTH ADVANTAGE: long-term view The new ISOMETERs® iso685 and iso1685 are able to record a full set of system parameters with date and time information over many years. In con- junction with other recorded system information, this aspect permits event-based fault analysis and makes it easier to find and rectify faults that occur sporadically; it also improves the information avail- able for making decisions on future investments. The evaluation can be undertaken in the device itself or via Ethernet. TWELFTH ADVANTAGE: safe handling of non-linear loads, in particular inverters These days systems contain ever fewer linear (ohmic) loads. The incandescent lamp has been replaced with energy-saving lamps or LEDs, com- puters and television are connected to the system ISOMETER® iso1685
  • 5. FOURTEENTH ADVANTAGE: more stable in the event of transients In IEC 62109-1:2010 the possibility of reducing the overvoltage category from CAT IV to CAT III by means of isolation using isolating transform- ers, optocouplers or similar electrical isolation is described because transients do not cause such high currents as in earthed systems. The practical consequence is that components in the electrical loads in the IT system are subjected less to voltage spikes and as result have a longer service life. Now let us look at the disadvantages of the IT system: FIRST DISADVANTAGE: IT systems should not be too large Very large IT systems can become confusing and have an undesirably high system leakage capaci- tance. It is therefore recommended to divide very large IT systems into separate units using isolating transformers, which can cause additional costs and power losses that, however, overall are mostly negli- gible. The division into electrically isolated subsys- tems also has advantages, such as the filtering effect in relation to interference or the possibility to specifi- cally adjust the voltages to the loads supplied. What constitutes a large system must be evaluated in the specific case and depends on the system param- eters. For instance, the world's largest PV fields can be monitored entirely by individual ISOMETERs® of type isoPV. Which means that a single ISOMETER® does not miss a faulty connector, a damaged cable or a damaged PV module, despite an installation the size of ten football pitches or more. SECOND DISADVANTAGE: voltage increase in the event of insulation faults In an IT system with insulation faults on one con- ductor, the line-to-line voltages on the other con- ductors increase in relation to the earth potential. In the event of a dead earth fault on a conductor in the 230 V system, the voltages on the other conductors increase in relation to the earth potential to approx. 400 V. System components on which the potential in relation to earth is an issue, in particular Y capaci- tors and overvoltage limiters, should therefore be suitable for the maximum rated voltage. Voltage increase can be avoided when the secondary side of the transformer is connected in Delta mode. ISOMETER® isoPV Coupling device AGH-PV-3 CONCLUSION: The IT system has many advantages over earthed systems and is suitable not only for the high requirements in operating theatres or in nuclear power stations, but practically everywhere. In many cases these days this system is not con- sidered at all, even though it would be the better choice. The latest generation of insulation moni- toring devices also offers many economical and technical advantages that benefit the operator. Sometimes the costs for an insulation monitoring device are used as an argument against an IT system, however, the opposite is the case: in view of the advantages listed above and their econom- ical effects, usage in the commercial sector is always worthwhile! Dr. Dirk Pieler Former CEO of Bender GmbH & Co. KG, Grünberg