3. Transmission Fault Analysis
The cause of electric power system faults is
insulation breakdown/compromise.
This breakdown can be due to a variety of
different factors:
– Lightning ionizing air,
– Wires blowing together in the wind,
– Animals or plants coming in contact with the wires,
– Salt spray or pollution on insulators.
3
4. Transmission Fault Types
There are two main types of faults:
– symmetric faults: system remains balanced; these
faults are relatively rare, but are the easiest to
analyze so we’ll consider them first.
– unsymmetric faults: system is no longer balanced;
very common, but more difficult to analyze
(considered in EE 368L).
The most common type of fault on a three
phase system by far is the single line-to-ground
(SLG), followed by the line-to-line faults (LL),
double line-to-ground (DLG) faults, and balanced
three phase faults.
4
5. Lightning Strike Event Sequence
1. Lighting hits line, setting up an ionized path to ground
30 million lightning strikes per year in US!
a single typical stroke might have 25,000 amps, with a rise
time of 10 s, dissipated in 200 s.
multiple strokes can occur in a single flash, causing the
lightning to appear to flicker, with the total event lasting
up to a second.
2. Conduction path is maintained by ionized air after
lightning stroke energy has dissipated, resulting in
high fault currents (often > 25,000 amps!)
5
6. Lightning Strike Sequence, cont’d
3. Within one to two cycles (16 ms) relays at both ends of
line detect high currents, signaling circuit breakers to
open the line:
nearby locations see decreased voltages
4. Circuit breakers open to de-energize line in an
additional one to two cycles:
breaking tens of thousands of amps of fault current is no
small feat!
with line removed voltages usually return to near normal.
5. Circuit breakers may reclose after several seconds,
trying to restore faulted line to service.
6
7. Fault Analysis
Fault currents cause equipment damage due to
both thermal and mechanical processes.
Goal of fault analysis is to determine the
magnitudes of the currents present during the
fault:
– need to determine the maximum current to ensure
devices can survive the fault,
– need to determine the maximum current the circuit
breakers (CBs) need to interrupt to correctly size the
CBs.
7
8. RL Circuit Analysis
To understand fault analysis we need to
review the behavior of an RL circuit
( )
2 cos( )
v t
V t
(Note text uses sinusoidal voltage instead of cos!)
Before the switch is closed, i(t) = 0.
When the switch is closed at t=0 the current will
have two components: 1) a steady-state value
2) a transient value.
R L
8
9. RL Circuit Analysis, cont’d
2 2 2 2
1
1. Steady-state current component (from standard
phasor analysis)
Steady-state phasor current magnitude is ,
where ( )
and current phasor angle is , tan ( / )
Corresponding in
ac
Z Z
V
I
Z
Z R L R X
L R
ac
stantaneous current is:
2 cos( )
( ) Z
V t
i t
Z
9
10. RL Circuit Analysis, cont’d
1
1
ac dc 1
1
2. Exponentially decaying dc current component
( )
where is the time constant,
The value of is determined from the initial
conditions:
2
(0) 0 ( ) ( ) cos( )
2
t
T
dc
t
T
Z
i t C e
L
T T
R
C
V
i i t i t t C e
Z
V
C
Z
cos( ) which depends on
Z
10
12. RL Circuit Analysis, cont’d
dc
Hence ( ) is a sinusoidal superimposed on a decaying
dc current. The magnitude of (0) depends on when
the switch is closed. For fault analysis we're just
concerned with the worst case.
Highest DC c
i t
i
Z 1
2
urrent occurs for: = ,
( ) ( ) ( )
2 2
( ) cos( )
2
( cos( ) )
ac dc
t
T
t
T
V
C
Z
i t i t i t
V V
i t t e
Z Z
V
t e
Z
12
13. RMS for Fault Current
The interrupting capability of a circuit breaker is
specified in terms of the RMS current it can interrupt.
2
The function ( ) ( cos( ) ) is
not periodic, so we can't formally define an RMS value
t
T
V
i t t e
Z
.
However, if then we can approximate the current
as a sinusoid plus a time-invarying dc offset.
The RMS value of such a current is equal to the
square root of the sum of the squares of the
indivi
T t
dual RMS values of the two current components.
13
14. RMS for Fault Current
2 2
RMS
2
2 2
I ,
2
where , 2 ,
2
This function has a maximum value of 3 .
Therefore the worst case effect of the dc
component is included simply by
mu
ac dc
t t
T T
ac dc ac
t
T
ac ac
ac
I I
V V
I I e I e
Z Z
I I e
I
ltiplying the ac fault currents by 3.
14
15. Generator Modeling During Faults
During a fault the only devices that can contribute fault current
are those with energy storage.
Thus the models of generators (and other rotating machines) are
very important since they contribute the bulk of the fault current.
Generators can be approximated as a constant voltage behind a
time-varying reactance:
'
a
E
15
16. Generator Modeling, cont’d
"
d
'
d
d
The time varying reactance is typically approximated
using three different values, each valid for a different
time period:
X direct-axis subtransient reactance
X direct-axis transient reactance
X dire
ct-axis synchronous reactance
Can then estimate currents using circuit theory:
For example, could calculate steady-state current
that would occur after a three-phase short-circuit
if no circuit breakers interrupt current. 16
17. Generator Modeling, cont’d
'
"
'
'
ac
" '
"
For a balanced three-phase fault on the generator
terminal the ac fault current is (see page 362)
1 1 1
( ) 2 sin( )
1 1
where
direct-axis su
d
d
t
T
d d
d
a t
T
d d
d
e
X X
X
i t E t
e
X X
T
'
btransient time constant ( 0.035sec)
direct-axis transient time constant ( 1sec)
d
T
17
18. Generator Modeling, cont'd
'
"
'
'
ac
" '
'
DC "
The phasor current is then
1 1 1
1 1
The maximum DC offset is
2
( )
where is the armature time constant ( 0.2 seconds)
d
d
A
t
T
d d
d
a t
T
d d
t
T
a
d
A
e
X X
X
I E
e
X X
E
I t e
X
T
18
21. Generator Short Circuit Example
A 500 MVA, 20 kV, 3 is operated with an
internal voltage of 1.05 pu. Assume a solid 3
fault occurs on the generator's terminal and that
the circuit breaker operates after three cycles.
Determine the fault current. Assume
" '
" '
0.15, 0.24, 1.1 (all per unit)
0.035 seconds, 2.0 seconds
0.2 seconds
d d d
d d
A
X X X
T T
T
21
22. Generator S.C. Example, cont'd
2.0
ac
0.035
ac
6
base ac
3
0.2
DC
Substituting in the values
1 1 1
1.1 0.24 1.1
( ) 1.05
1 1
0.15 0.24
1.05
(0) 7 p.u.
0.15
500 10
14,433 A (0) 101,000 A
3 20 10
(0) 101 kA 2 143 k
t
t
t
e
I t
e
I
I I
I e
RMS
A (0) 175 kA
I
22
23. Generator S.C. Example, cont'd
0.05
2.0
ac 0.05
0.035
ac
0.05
0.2
DC
RMS
Evaluating at t = 0.05 seconds for breaker opening
1 1 1
1.1 0.24 1.1
(0.05) 1.05
1 1
0.15 0.24
(0.05) 70.8 kA
(0.05) 143 kA 111 k A
(0.05
e
I
e
I
I e
I
2 2
) 70.8 111 132 kA
23
24. Network Fault Analysis Simplifications
To simplify analysis of fault currents in networks
we'll make several simplifications:
1. Transmission lines are represented by their series
reactance
2. Transformers are represented by their leakage reactances
3. Synchronous machines are modeled as a constant voltage
behind direct-axis subtransient reactance
4. Induction motors are ignored or treated as synchronous
machines
5. Other (nonspinning) loads are ignored
24
25. Network Fault Example
For the following network assume a fault on the
terminal of the generator; all data is per unit
except for the transmission line reactance
2
19.5
Convert to per unit: 0.1 per unit
138
100
line
X
generator has 1.05
terminal voltage &
supplies 100 MVA
with 0.95 lag pf
25
26. Network Fault Example, cont'd
Faulted network per unit diagram
*
'
To determine the fault current we need to first estimate
the internal voltages for the generator and motor
For the generator 1.05, 1.0 18.2
1.0 18.2
0.952 18.2 1.103 7.1
1.05
T G
Gen a
V S
I E
26
27. Network Fault Example, cont'd
The motor's terminal voltage is then
1.05 0-(0.9044 - 0.2973) 0.3 1.00 15.8
The motor's internal voltage is
1.00 15.8 (0.9044 - 0.2973) 0.2
1.008 26.6
We can then solve as a linear circuit:
1
f
j j
j j
I
.103 7.1 1.008 26.6
0.15 0.5
7.353 82.9 2.016 116.6 9.09
j j
j
27
28. Fault Analysis Solution Techniques
Circuit models used during the fault allow the network to be
represented as a linear circuit
There are two main methods for solving for fault currents:
1. Direct method: Use prefault conditions to solve for the internal
machine voltages; then apply fault and solve directly.
2. Superposition: Fault is represented by two opposing
voltage sources; solve system by superposition:
– first voltage just represents the prefault operating point
– second system only has a single voltage source.
28
29. Superposition Approach
Faulted Condition
Exact Equivalent to Faulted Condition
Fault is represented
by two equal and
opposite voltage
sources, each with
a magnitude equal
to the pre-fault voltage
29
30. Superposition Approach, cont’d
Since this is now a linear network, the faulted voltages
and currents are just the sum of the pre-fault conditions
[the (1) component] and the conditions with just a single
voltage source at the fault location [the (2) component]
Pre-fault (1) component equal to the pre-fault
power flow solution
Obvious the
pre-fault
“fault current”
is zero!
30
31. Superposition Approach, cont’d
Fault (1) component due to a single voltage source
at the fault location, with a magnitude equal to the
negative of the pre-fault voltage at the fault location.
(1) (2) (1) (2)
(1) (2) (2)
0
g
g g m m m
f f f f
I I I I I I
I I I I
31
32. Two Bus Superposition Solution
f
(1) (1)
(2) f
(2) f
(2)
Before the fault we had E 1.05 0 ,
0.952 18.2 and 0.952 18.2
Solving for the (2) network we get
E 1.05 0
7
j0.15 j0.15
E 1.05 0
2.1
j0.5 j0.5
7 2.1 9.1
0.952
g m
g
m
f
g
I I
I j
I j
I j j j
I
18.2 7 7.35 82.9
j
This matches
what we
calculated
earlier
32
33. Extension to Larger Systems
bus
bus
The superposition approach can be easily extended
to larger systems. Using the we have
For the second (2) system there is only one voltage
source so is all zeros except at the fault loca
Y
Y V I
I tion
0
0
f
I
I
However to use this
approach we need to
first determine If
33
34. Determination of Fault Current
bus
1
bus bus
(2)
1
(2)
11 1 2
(2)
1 1
(2)
(1)
f
Define the bus impedance matrix as
0
Then
0
For a fault a bus i we get -I
bus
n
f
n nn n
n
ii f i
V
Z Z V
I
Z Z V
V
Z V V
Z
Z Y V Z I
34
35. Determination of Fault Current
(1)
(1) (2) (1)
Hence
Where
driving point impedance
( ) transfer point imepdance
Voltages during the fault are also found by superposition
are prefault values
i
f
ii
ii
ij
i i i i
V
I
Z
Z
Z i j
V V V V
35