SlideShare a Scribd company logo
UNIT II SWITCHING TRANSIENTS
Over voltages due to switching transients -
resistance switching and the equivalent circuit for
interrupting the resistor current - load switching and
equivalent circuit - waveforms for transient voltage
across the load and the switch - normal and abnormal
switching transients. Current suppression - current
chopping – effect ive equivalent circuit. Capacitance
switching - effect of source regulation - capacitance
switching with a restrike, with multiple restrikes.
Illustration for multiple restriking transients - ferro
resonance.
Over voltages due to switching transients - resistance switching and the equivalent circuit for interrupting the resistor current
Over voltages due to switching transients - resistance switching and the equivalent circuit for interrupting the resistor current
• A transient occurs in the power system when the network
changes from one steady state into another.
• The majority of power system transients is, however, the
result of a switching action. Load break switches and
disconnectors switch off and switch on parts of the network
under load and no-load conditions.
• Fuses and circuit breakers interrupt higher currents and
clear short-circuit currents flowing in faulted parts of the
system.
• The time period when transient voltage and current
oscillations occur is in the range of microseconds to
milliseconds.
INTRODUCTION
OVERVOLTAGE
• An overvoltage is an increase in the r.m.s. ac
voltage greater than 110 % at the power
frequency for a duration longer than 1 min.
• It is a result of load switching.
Eg : Switching OFF a Large load
Energizing a capacitor bank
• Switchings in a power system occur
frequently.
• A variety of switchings are performed for
routine operations or automatically by control
and protection systems.
• Typical switchings are as follows:
– Lines (transmission or distribution)
– Cables
– Shunt/series capacitors
– Shunt reactors
– Transformers
– Generators/motors
OVER VOLTAGES
• The causes of power system over voltages are
numerous and the waveforms are complex.
• It is customary to classify the transients on
the basis of frequency content of the
waveforms.
• In this sense, the following three broad
categories are defined:
–Power frequency overvoltages
–Switching overvoltages
–Lightning overvoltages
RESISTANCE SWITCHING
OBJECTIVES
i) To reduce switching surges and over voltages
ii) For potential control access multi-breakers
per phase in the high voltage breakers
iii) To reduce natural frequencies effects and
breaker recovery voltage
RESISTANCE SWITCHING
How does Resistance Switching
Work
• Let us consider a circuit and connect a shunt
resistance R across the contacts of the breaker as
shown . Suppose a fault occurs on the line. Because
of the occurrence of fault, the contacts of breaker
will open and an arc will stuck between the
contacts.
• Since the contacts of breaker are shunted by resistance R, therefore a
part of arc current will flow through this resistance R. Due to this the
magnitude of arc current will reduce which in turn will result in increase
in the rate of de-ionization of arc path. In this way, the arc resistance
increases. This increased arc resistance leads to further increases in the
current through the shunt resistance R.
• Thus again, the arc current will reduce and hence the arc resistance
increases. This cumulative process will continue till the magnitude of
arc current becomes so low that it is not able to maintain the arc. Thus
the arc extinguishes and the current is interrupted by the breaker.
• Resistance Switching also reduces the oscillatory growth of Re-striking
Voltage. The natural frequency of the circuit shown above is given by
fn = (1/2π)√(1/LC – 1/4R2
C2
)
• The main role of shunt resistance R is to limit the growth of re-strike
voltage and cause it to grow exponentially up to recovery voltage. If the
value of R is so selected that the circuit becomes critically damped then
re-strike voltage rises exponentially till recovery voltage is reached.
Equivalent circuit of resistance switching problem.
Over voltages due to switching transients - resistance switching and the equivalent circuit for interrupting the resistor current
NEED FOR RESISTANCE SWITCHING
• The shunt resistors connected across circuit
breaker have two functions:
i) To distribute the transient recovery voltage
more uniformly across the several breaks.
ii) To reduce the severity of transient recovery
voltage at the time of interruption by
introducing damping into oscillation.
• Thus the advantages of resistance switching are
as follows:
• It reduces the rate of rise of re-striking voltage
and the peak value of re-striking voltage.
• Resistance Switching helps to reduce the
voltage transient surge during current chopping
and capacitive current breaking.
ANALYSIS OF RESISTANCE SWITCHING
Over voltages due to switching transients - resistance switching and the equivalent circuit for interrupting the resistor current
Over voltages due to switching transients - resistance switching and the equivalent circuit for interrupting the resistor current
Over voltages due to switching transients - resistance switching and the equivalent circuit for interrupting the resistor current
Over voltages due to switching transients - resistance switching and the equivalent circuit for interrupting the resistor current
Over voltages due to switching transients - resistance switching and the equivalent circuit for interrupting the resistor current
Over voltages due to switching transients - resistance switching and the equivalent circuit for interrupting the resistor current
Over voltages due to switching transients - resistance switching and the equivalent circuit for interrupting the resistor current
Over voltages due to switching transients - resistance switching and the equivalent circuit for interrupting the resistor current
Over voltages due to switching transients - resistance switching and the equivalent circuit for interrupting the resistor current
Over voltages due to switching transients - resistance switching and the equivalent circuit for interrupting the resistor current
Over voltages due to switching transients - resistance switching and the equivalent circuit for interrupting the resistor current
Over voltages due to switching transients - resistance switching and the equivalent circuit for interrupting the resistor current
Normal switching transients are circumstances in
which voltage or current within the normal peak
values Closing switch or circuit in a dominantly
capacitive or inductive network results in inrush
currents which can cause problems for the
protection system.
Abnormal switching transients are circumstances
in which voltage or current are far in excess of twice
in normal peak values. Insulation of high voltage
circuit breakers typically can over voltages up to 2.5
times over its normal voltage.
Over voltages due to switching transients - resistance switching and the equivalent circuit for interrupting the resistor current
Over voltages due to switching transients - resistance switching and the equivalent circuit for interrupting the resistor current
Capacitor Switching
• Capacitor switching is one of the most common
switching events on utility systems.
• Capacitors are used to provide reactive power (in
units of vars) to correct the power factor, which
reduces losses and supports the voltage on the
system.
• They are a very economical and generally trouble-
free means of accomplishing these goals.
• Alternative methods such as the use of rotating
machines and electronic var compensators are
much more costly or have high maintenance costs.
One drawback to the use of capacitors is that they
yield oscillatory transients when switched.
Some capacitors are energized all the time (a fixed
bank), while others are switched according to load
levels.
Various control means, including time,
temperature, voltage, current, and reactive power,
are used to determine when the capacitors are
switched.
It is common for controls to combine two or more
of these functions, such as temperature with
voltage override.
• One of the common symptoms of power quality problems related to
utility capacitor-switching overvoltages is that the problems appear
at nearly the same time each day.
• On distribution feeders with industrial loads, capacitors are
frequently switched by time clock in anticipation of an increase in
load with the beginning of the working day.
• Common problems are adjustable speed-drive trips and
malfunctions of other electronically controlled load equipment that
occur without a noticeable blinking of the lights or impact on other,
more conventional loads.
Restrikes During Capacitor
De-Energizing
 When a grounded capacitor bank is energized using a
mechanical oil filled switch, the switching is most likely to
occur at or near the system voltage peak.
 At this instant, the capacitor voltage is zero while the
system voltage is near maximum.
 The largest potential difference between contacts is 1.0 pu.
 Due to the slow-moving nature of the mechanical switch
and the large potential difference, insulation across the
switch contacts tends to break down giving rise to an
electric arc.
 It allows capacitive current to flow, thereby energizing
the capacitor before the actual switch contacts close or
touch. This phenomenon is known as pre-strike.
It occurs in many types of switches without
closing control.
It is usually considered as a natural behavior
of the switch and should not raise any
concern because capacitor voltage prior to
energizing is negligible.
The resulting peak transient voltage is no
worse than that when the capacitor is
intentionally energized at the system voltage
peak.
 On the other hand, restrikes (or reignitions) during capacitor
deenergizing do rise concerns.
 Restrikes or reignitions occur when arcs between parting
contacts are re-established after initial current extinction
causing unintended re-energizing of the capacitor.
 Because of the trapped charges following the initial extinction,
significant overvoltage well above 2 pu can result.
 It should be noted that a successful capacitor deenergizing
(i.e., no restrike) does not normally yield any transient
overvoltage.
Restrikes can occur multiple times and in
succession over a short time period.
It can also be intermittent over a longer time
span. In either circumstance, a restrike poses
problems to the power system as well as to the
switching device itself.
Capacitance Switching Off
• Disconnect: C /unload Transmission
lines
• Concerns: reignite/restrike in
opening
• Chance low, Cap. Sw. frequent
• Cap fully charged
• Half Cycle VCB=2 Vp
Capacitance Switching off
Discussion Cap. Sw. Off
• In fact Vc>Vsys Ferranti Rise
• Vsource_side decrease to Vsys
• There is a ∆V change (however,exist in weak systems)
• Discon. a C.B. in lower side of step down Transformer
supplying an unloaded cable
• Current in Cap. Sw. is freq. small and it is
possible to disconnect it In first zero
-- with small contact sep., 2 V appear across contacts
--- increased possibility of restrike (small separation)
• Oscillating to new voltage with f0=1/2Π√LC
• I(restrike)=2Vp/√L/C sinω0t
• Transient peak of 3 Vp
Capacitance Switching with a Restrike at
Peak of Voltage
Capacitor Switching …continued
• A 13.8 KV, 5000KVAR, 3ph bank,NGr
• Source Gr, inductance:1 mH
• Restrike at Vp:
1- c=5/(377x13.8 )=69.64
 μF
2- Z=√1000/69.64=3.789Ω
3-Ip=2√2x13.8/(√3x3.789)=5.947 KA
4-f0=603 Hz
Multiple Restrikes During Capacitance Switching
FERRO RESONANCE - DEFINITION
• The term Ferro resonance refers to a special kind of
resonance that involves capacitance and iron-core
inductance. The most common condition in which it
causes disturbances is when the magnetizing
impedance of a transformer is placed in series with a
system capacitor. This happens when there is an
open-phase conductor. Under controlled conditions,
ferro resonance can be exploited for useful purpose
such as in a constant-voltage transformer
RLC SERIES CIRCUIT
Ferro resonance- Occurence
• Nonlinear resonance between unloaded transformer
magnetizing branch and a series capacitor
• May occur when distribution transformers fed from
cables are switched one phase at a time
• Especially a problem on ungrounded star-delta
transformers
• May occur any time an unloaded iron-core coil is in
series with a capacitor
2. Terms and definitions 49
Long-duration overvoltage caused by
ferroresonance of transformer
Ferro resonance is different than resonance
in linear system elements. In linear systems,
resonance results in high sinusoidal voltages
and currents of the resonant frequency.
Ferro resonance can also result in high
voltages and currents, but the resulting
waveforms are usually irregular and chaotic
in shape.
The most common events leading ferro resonance are,
Manual switching of an unloaded, cable-fed, three-
phase transformer where only one phase is closed.
Ferroresonance may be noted when the first phase
is closed upon energization or before the last phase
is opened on de-energization.
Ferroresonant circuits
A
C
B
C
B
A
Possible effects of ferroresonance
• Overvoltage
• Audible noise
• Overheating
• Sustained overvoltage => arrester failure
• Flicker due to erratic voltage
• Subharmonic voltages (e.g., at 1/3 or 1/2 of
normal frequency)
• Chaotic response
Summary
• In Unit 2, we have seen
switching transient- Resistance switching
Load switching
Capacitor switching
Current chopping
Normal and Abnormal switching transient
Current suppression
Ferro resonance

More Related Content

PPT
unit_2.ppt
PPTX
power system transients.pptx
PPTX
Sources of over voltages power quality.pptx
PPTX
protection circuits of scr.pptx
PDF
Design and Mitigation Techniques of MV Capacitor Bank Switching Transients on...
PPTX
Basic Terms of Circuit Breaker
PPT
PDF
IRJET- Generation and Control of Transient Overvoltages in Power System Networks
unit_2.ppt
power system transients.pptx
Sources of over voltages power quality.pptx
protection circuits of scr.pptx
Design and Mitigation Techniques of MV Capacitor Bank Switching Transients on...
Basic Terms of Circuit Breaker
IRJET- Generation and Control of Transient Overvoltages in Power System Networks

Similar to Over voltages due to switching transients - resistance switching and the equivalent circuit for interrupting the resistor current (20)

PPTX
Transient in Power system
PDF
Switchgear Analysis Power system 2 topic
PPTX
Flexible AC Transmission System Overview.pptx
PPT
event looger & Distrubance Recorders.ppt
PPT
basic electrical engineering pdf........
PDF
Chapter 8 (synny katyara-ashfaq hashmani-bs chowdhry)(1)
PPTX
ABB - TRANSFORMERS-PROTECTION-COURSE (2001)
PDF
Resonance of a distribution feeder with a saturable core fault current limiter
PPTX
Power Sytem Protection Unit_5.power point presentation
PDF
Facts unit 2
PPTX
Reactive power consumption in modern power system
PPTX
Circuit Breakers
PDF
Overvoltages 1
PDF
Abb b.g. controlled switching ed4
PPTX
fdocuments.in_presentation-on-substation-220-kv.pptx
PPTX
Turn ON-OFF Methods of SCR.pptx
PDF
6574_ChargingCurrent_DF_20120914_Web2.pdf
PPT
protection of feeders in distribution substation
PPT
Switchyard final
PDF
IRJET- Simulation of Energization and De-Energization of Capacitor Banks and ...
Transient in Power system
Switchgear Analysis Power system 2 topic
Flexible AC Transmission System Overview.pptx
event looger & Distrubance Recorders.ppt
basic electrical engineering pdf........
Chapter 8 (synny katyara-ashfaq hashmani-bs chowdhry)(1)
ABB - TRANSFORMERS-PROTECTION-COURSE (2001)
Resonance of a distribution feeder with a saturable core fault current limiter
Power Sytem Protection Unit_5.power point presentation
Facts unit 2
Reactive power consumption in modern power system
Circuit Breakers
Overvoltages 1
Abb b.g. controlled switching ed4
fdocuments.in_presentation-on-substation-220-kv.pptx
Turn ON-OFF Methods of SCR.pptx
6574_ChargingCurrent_DF_20120914_Web2.pdf
protection of feeders in distribution substation
Switchyard final
IRJET- Simulation of Energization and De-Energization of Capacitor Banks and ...
Ad

More from Karthikkumar Shanmugam (20)

PPTX
Lithium_Ion_Battery_Presentation and working
PPTX
Solar_Central_Receiver_Presentation.pptx
PPTX
Solar_Panel_Working_Presentation and its importance
PPTX
NiMH BatteryPresentation and working principle
PPT
AI-powered algorithms analyze medical images
PPTX
artificial intelleigence battery monitoring
PPTX
disease detection using ai ml for the analysis of early detection
PPT
AI-powered analysis li ion battery performance
PPTX
SINE WAVE INVERTER with New technology.pptx
PPTX
SMART METERING WITH IOT TECHNOLOGY-1.pptx
PDF
An electrical insulator is a materials and
PPT
strain insulator must have considerable mechanical strength as well as the ne...
PPTX
Understand the structure of power system, computation of transmission line pa...
PDF
EEE- BEE601 - TRANSMISSION AND DISTRIBUTION- Dr. V. Jayalakshmi.pdf
PPT
PPTX
unit -III.pptx
PPT
PPT
webinar poster.ppt
PPTX
windturbinepower-160919122215-converted.pptx
PPT
Disaster management.ppt
Lithium_Ion_Battery_Presentation and working
Solar_Central_Receiver_Presentation.pptx
Solar_Panel_Working_Presentation and its importance
NiMH BatteryPresentation and working principle
AI-powered algorithms analyze medical images
artificial intelleigence battery monitoring
disease detection using ai ml for the analysis of early detection
AI-powered analysis li ion battery performance
SINE WAVE INVERTER with New technology.pptx
SMART METERING WITH IOT TECHNOLOGY-1.pptx
An electrical insulator is a materials and
strain insulator must have considerable mechanical strength as well as the ne...
Understand the structure of power system, computation of transmission line pa...
EEE- BEE601 - TRANSMISSION AND DISTRIBUTION- Dr. V. Jayalakshmi.pdf
unit -III.pptx
webinar poster.ppt
windturbinepower-160919122215-converted.pptx
Disaster management.ppt
Ad

Recently uploaded (20)

PDF
Mitigating Risks through Effective Management for Enhancing Organizational Pe...
PPTX
UNIT-1 - COAL BASED THERMAL POWER PLANTS
PPTX
CARTOGRAPHY AND GEOINFORMATION VISUALIZATION chapter1 NPTE (2).pptx
PDF
keyrequirementskkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkk
PPTX
Foundation to blockchain - A guide to Blockchain Tech
PPTX
additive manufacturing of ss316l using mig welding
PPT
Total quality management ppt for engineering students
PDF
Enhancing Cyber Defense Against Zero-Day Attacks using Ensemble Neural Networks
DOCX
ASol_English-Language-Literature-Set-1-27-02-2023-converted.docx
PPTX
UNIT 4 Total Quality Management .pptx
PDF
Embodied AI: Ushering in the Next Era of Intelligent Systems
PPTX
Safety Seminar civil to be ensured for safe working.
PPT
introduction to datamining and warehousing
PDF
737-MAX_SRG.pdf student reference guides
PPTX
CYBER-CRIMES AND SECURITY A guide to understanding
PPTX
Artificial Intelligence
PPTX
FINAL REVIEW FOR COPD DIANOSIS FOR PULMONARY DISEASE.pptx
PDF
BMEC211 - INTRODUCTION TO MECHATRONICS-1.pdf
PPTX
Engineering Ethics, Safety and Environment [Autosaved] (1).pptx
PDF
A SYSTEMATIC REVIEW OF APPLICATIONS IN FRAUD DETECTION
Mitigating Risks through Effective Management for Enhancing Organizational Pe...
UNIT-1 - COAL BASED THERMAL POWER PLANTS
CARTOGRAPHY AND GEOINFORMATION VISUALIZATION chapter1 NPTE (2).pptx
keyrequirementskkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkkk
Foundation to blockchain - A guide to Blockchain Tech
additive manufacturing of ss316l using mig welding
Total quality management ppt for engineering students
Enhancing Cyber Defense Against Zero-Day Attacks using Ensemble Neural Networks
ASol_English-Language-Literature-Set-1-27-02-2023-converted.docx
UNIT 4 Total Quality Management .pptx
Embodied AI: Ushering in the Next Era of Intelligent Systems
Safety Seminar civil to be ensured for safe working.
introduction to datamining and warehousing
737-MAX_SRG.pdf student reference guides
CYBER-CRIMES AND SECURITY A guide to understanding
Artificial Intelligence
FINAL REVIEW FOR COPD DIANOSIS FOR PULMONARY DISEASE.pptx
BMEC211 - INTRODUCTION TO MECHATRONICS-1.pdf
Engineering Ethics, Safety and Environment [Autosaved] (1).pptx
A SYSTEMATIC REVIEW OF APPLICATIONS IN FRAUD DETECTION

Over voltages due to switching transients - resistance switching and the equivalent circuit for interrupting the resistor current

  • 1. UNIT II SWITCHING TRANSIENTS Over voltages due to switching transients - resistance switching and the equivalent circuit for interrupting the resistor current - load switching and equivalent circuit - waveforms for transient voltage across the load and the switch - normal and abnormal switching transients. Current suppression - current chopping – effect ive equivalent circuit. Capacitance switching - effect of source regulation - capacitance switching with a restrike, with multiple restrikes. Illustration for multiple restriking transients - ferro resonance.
  • 4. • A transient occurs in the power system when the network changes from one steady state into another. • The majority of power system transients is, however, the result of a switching action. Load break switches and disconnectors switch off and switch on parts of the network under load and no-load conditions. • Fuses and circuit breakers interrupt higher currents and clear short-circuit currents flowing in faulted parts of the system. • The time period when transient voltage and current oscillations occur is in the range of microseconds to milliseconds. INTRODUCTION
  • 5. OVERVOLTAGE • An overvoltage is an increase in the r.m.s. ac voltage greater than 110 % at the power frequency for a duration longer than 1 min. • It is a result of load switching. Eg : Switching OFF a Large load Energizing a capacitor bank
  • 6. • Switchings in a power system occur frequently. • A variety of switchings are performed for routine operations or automatically by control and protection systems. • Typical switchings are as follows: – Lines (transmission or distribution) – Cables – Shunt/series capacitors – Shunt reactors – Transformers – Generators/motors
  • 7. OVER VOLTAGES • The causes of power system over voltages are numerous and the waveforms are complex. • It is customary to classify the transients on the basis of frequency content of the waveforms. • In this sense, the following three broad categories are defined: –Power frequency overvoltages –Switching overvoltages –Lightning overvoltages
  • 9. OBJECTIVES i) To reduce switching surges and over voltages ii) For potential control access multi-breakers per phase in the high voltage breakers iii) To reduce natural frequencies effects and breaker recovery voltage
  • 11. How does Resistance Switching Work • Let us consider a circuit and connect a shunt resistance R across the contacts of the breaker as shown . Suppose a fault occurs on the line. Because of the occurrence of fault, the contacts of breaker will open and an arc will stuck between the contacts.
  • 12. • Since the contacts of breaker are shunted by resistance R, therefore a part of arc current will flow through this resistance R. Due to this the magnitude of arc current will reduce which in turn will result in increase in the rate of de-ionization of arc path. In this way, the arc resistance increases. This increased arc resistance leads to further increases in the current through the shunt resistance R. • Thus again, the arc current will reduce and hence the arc resistance increases. This cumulative process will continue till the magnitude of arc current becomes so low that it is not able to maintain the arc. Thus the arc extinguishes and the current is interrupted by the breaker. • Resistance Switching also reduces the oscillatory growth of Re-striking Voltage. The natural frequency of the circuit shown above is given by fn = (1/2π)√(1/LC – 1/4R2 C2 ) • The main role of shunt resistance R is to limit the growth of re-strike voltage and cause it to grow exponentially up to recovery voltage. If the value of R is so selected that the circuit becomes critically damped then re-strike voltage rises exponentially till recovery voltage is reached.
  • 13. Equivalent circuit of resistance switching problem.
  • 15. NEED FOR RESISTANCE SWITCHING • The shunt resistors connected across circuit breaker have two functions: i) To distribute the transient recovery voltage more uniformly across the several breaks. ii) To reduce the severity of transient recovery voltage at the time of interruption by introducing damping into oscillation.
  • 16. • Thus the advantages of resistance switching are as follows: • It reduces the rate of rise of re-striking voltage and the peak value of re-striking voltage. • Resistance Switching helps to reduce the voltage transient surge during current chopping and capacitive current breaking.
  • 30. Normal switching transients are circumstances in which voltage or current within the normal peak values Closing switch or circuit in a dominantly capacitive or inductive network results in inrush currents which can cause problems for the protection system. Abnormal switching transients are circumstances in which voltage or current are far in excess of twice in normal peak values. Insulation of high voltage circuit breakers typically can over voltages up to 2.5 times over its normal voltage.
  • 33. Capacitor Switching • Capacitor switching is one of the most common switching events on utility systems. • Capacitors are used to provide reactive power (in units of vars) to correct the power factor, which reduces losses and supports the voltage on the system. • They are a very economical and generally trouble- free means of accomplishing these goals. • Alternative methods such as the use of rotating machines and electronic var compensators are much more costly or have high maintenance costs.
  • 34. One drawback to the use of capacitors is that they yield oscillatory transients when switched. Some capacitors are energized all the time (a fixed bank), while others are switched according to load levels. Various control means, including time, temperature, voltage, current, and reactive power, are used to determine when the capacitors are switched. It is common for controls to combine two or more of these functions, such as temperature with voltage override.
  • 35. • One of the common symptoms of power quality problems related to utility capacitor-switching overvoltages is that the problems appear at nearly the same time each day. • On distribution feeders with industrial loads, capacitors are frequently switched by time clock in anticipation of an increase in load with the beginning of the working day. • Common problems are adjustable speed-drive trips and malfunctions of other electronically controlled load equipment that occur without a noticeable blinking of the lights or impact on other, more conventional loads.
  • 36. Restrikes During Capacitor De-Energizing  When a grounded capacitor bank is energized using a mechanical oil filled switch, the switching is most likely to occur at or near the system voltage peak.  At this instant, the capacitor voltage is zero while the system voltage is near maximum.  The largest potential difference between contacts is 1.0 pu.  Due to the slow-moving nature of the mechanical switch and the large potential difference, insulation across the switch contacts tends to break down giving rise to an electric arc.  It allows capacitive current to flow, thereby energizing the capacitor before the actual switch contacts close or touch. This phenomenon is known as pre-strike.
  • 37. It occurs in many types of switches without closing control. It is usually considered as a natural behavior of the switch and should not raise any concern because capacitor voltage prior to energizing is negligible. The resulting peak transient voltage is no worse than that when the capacitor is intentionally energized at the system voltage peak.
  • 38.  On the other hand, restrikes (or reignitions) during capacitor deenergizing do rise concerns.  Restrikes or reignitions occur when arcs between parting contacts are re-established after initial current extinction causing unintended re-energizing of the capacitor.  Because of the trapped charges following the initial extinction, significant overvoltage well above 2 pu can result.  It should be noted that a successful capacitor deenergizing (i.e., no restrike) does not normally yield any transient overvoltage.
  • 39. Restrikes can occur multiple times and in succession over a short time period. It can also be intermittent over a longer time span. In either circumstance, a restrike poses problems to the power system as well as to the switching device itself.
  • 40. Capacitance Switching Off • Disconnect: C /unload Transmission lines • Concerns: reignite/restrike in opening • Chance low, Cap. Sw. frequent • Cap fully charged • Half Cycle VCB=2 Vp
  • 42. Discussion Cap. Sw. Off • In fact Vc>Vsys Ferranti Rise • Vsource_side decrease to Vsys • There is a ∆V change (however,exist in weak systems) • Discon. a C.B. in lower side of step down Transformer supplying an unloaded cable • Current in Cap. Sw. is freq. small and it is possible to disconnect it In first zero -- with small contact sep., 2 V appear across contacts --- increased possibility of restrike (small separation) • Oscillating to new voltage with f0=1/2Π√LC • I(restrike)=2Vp/√L/C sinω0t • Transient peak of 3 Vp
  • 43. Capacitance Switching with a Restrike at Peak of Voltage
  • 44. Capacitor Switching …continued • A 13.8 KV, 5000KVAR, 3ph bank,NGr • Source Gr, inductance:1 mH • Restrike at Vp: 1- c=5/(377x13.8 )=69.64  μF 2- Z=√1000/69.64=3.789Ω 3-Ip=2√2x13.8/(√3x3.789)=5.947 KA 4-f0=603 Hz
  • 45. Multiple Restrikes During Capacitance Switching
  • 46. FERRO RESONANCE - DEFINITION • The term Ferro resonance refers to a special kind of resonance that involves capacitance and iron-core inductance. The most common condition in which it causes disturbances is when the magnetizing impedance of a transformer is placed in series with a system capacitor. This happens when there is an open-phase conductor. Under controlled conditions, ferro resonance can be exploited for useful purpose such as in a constant-voltage transformer
  • 48. Ferro resonance- Occurence • Nonlinear resonance between unloaded transformer magnetizing branch and a series capacitor • May occur when distribution transformers fed from cables are switched one phase at a time • Especially a problem on ungrounded star-delta transformers • May occur any time an unloaded iron-core coil is in series with a capacitor
  • 49. 2. Terms and definitions 49 Long-duration overvoltage caused by ferroresonance of transformer
  • 50. Ferro resonance is different than resonance in linear system elements. In linear systems, resonance results in high sinusoidal voltages and currents of the resonant frequency. Ferro resonance can also result in high voltages and currents, but the resulting waveforms are usually irregular and chaotic in shape.
  • 51. The most common events leading ferro resonance are, Manual switching of an unloaded, cable-fed, three- phase transformer where only one phase is closed. Ferroresonance may be noted when the first phase is closed upon energization or before the last phase is opened on de-energization.
  • 53. Possible effects of ferroresonance • Overvoltage • Audible noise • Overheating • Sustained overvoltage => arrester failure • Flicker due to erratic voltage • Subharmonic voltages (e.g., at 1/3 or 1/2 of normal frequency) • Chaotic response
  • 54. Summary • In Unit 2, we have seen switching transient- Resistance switching Load switching Capacitor switching Current chopping Normal and Abnormal switching transient Current suppression Ferro resonance