SlideShare a Scribd company logo
protection of feeders in distribution substation
DISTRIBUTION PROTECTION
R.Panneer Selvam B,E.,M.I.E.,
Former Superintending Engineer
Protection and Communication
CHENNAI
There are three aspects of a power system
These aspects are as follows:
A. Normal operation
B. Prevention of electrical failure.
C. Mitigation of the effects of electrical failure.
Normal Operation


The term normal operation assumes no failures of equipment, no mistakes of
personnel, nor Acts of God. It involves the minimum requirements for supplying
the existing load and a certain amount of anticipated future load.
A. Choice between hydro, steam, or other sources of power.
B. Location of generating stations.
C. Transmission of power to the load.
D. Study of the load characteristics and planning for its future growth.
E. Metering
F. Voltage and frequency regulation.
G. System operation.
E. Normal maintenance
Outages


Electrical equipment failures would cause intolerable outages.



There must be additional provisions to minimize damage to
equipment and interruptions to the service when failures occur.



Two recourses are open:
(1) to incorporate features of design aimed at preventing
failures, and
(2) to include provisions for mitigating the effects of failure
when it occurs
Prevention of Electrical Failure


The type of electrical failure that causes greatest concern is the short
circuit, or “fault” as it is usually called, but there are other abnormal
operating conditions peculiar to certain elements of the system that
also require attention. Some of the features of design and operation
aimed at preventing electrical failure are:
A. Provision of adequate insulation.
B. Coordination of insulation strength with the capabilities of lightning arresters.
C. Use of overhead ground wires and low tower-footing resistance.
D. Design for mechanical strength to reduce exposure, and to minimize the likelihood
of failure causable by animals, birds, insects, dirt, etc.
E. Proper operation and maintenance practices .
Design And Operation For Mitigating The
Effects Of Failure


Some of the features of design and operation for mitigating the effects of failure are:
A. Features that mitigate the immediate effects of an electrical failure.
1. Design to limit the magnitude of short-circuit current.1
a. By avoiding too large concentrations of generating capacity.
b. By using current-limiting impedance.
2. Design to withstand mechanical stresses and heating owing to short-circuit currents.
3. Time-delay under-voltage devices on circuit breakers to prevent dropping loads
during momentary voltage dips.
4. Ground-fault neutralizers (Petersen coils).
B. Features for promptly disconnecting the faulty element.
1. Protective relaying.
2. Circuit breakers with sufficient interrupting capacity.
3. Fuses.
C. Features that mitigate the loss of the faulty element.
1. Alternate circuits.
2. Reserve generator and transformer capacity.
3. Automatic reclosing.
Protective Relaying






Thus, protective relaying is one of several features of system design
concerned with minimizing damage to equipment and interruptions to
service when electrical failures occur.
When we say that relays “protect,” we mean that, together with other
equipment, the relays help to minimize damage and improve service.
Therefore, the capabilities and the application requirements of
protective-relaying equipments should be considered
concurrently with the other features.
Protection Technology
 The

last thirty years have seen enormous
changes in relay technology.
 The electromechanical relay in all of its
different forms has been replaced
successively by static, digital and numerical
relays
ELECTROMECHANICAL RELAYS




The mechanical force is generated through current
flow in one or more windings on a magnetic core or
cores, hence the term electromechanical relay
The principle advantage of such relays is that
–
–

they provide galvanic isolation between the inputs and
outputs in a simple, cheap and reliable form
therefore for simple on/off switching functions where the
output contacts have to carry substantial currents, they are
still used.
Philosophy of over Current Protection
 Over

current protection is directed entirely to
the clearance of faults, although with the
settings usually adopted some measure of
overload protection may be obtained.
Attracted Armature Relays




These generally
consist of an ironcored electromagnet that attracts a
hinged armature when
energized.
A restoring force is
provided by means of
a spring or gravity so
that the armature will
return to its original
position when the
electromagnet is deenergized.
Typical attracted armature relays





The contacts can be
made quite robust and
hence able to make,
carry and break
relatively large
currents under quite
onerous conditions
(highly inductive
circuits).
This is still a significant
advantage of this type
of relay that ensures
its continued use.
protection of feeders in distribution substation
The basic connections of a protective relay
Torque production in an induction
relay.
Shaded-pole structure

.

Watthour-meter
structure.
Induction Cup Unit
• These two structures
are shown in Fig
• They most closely
resemble an induction
motor, except that the
rotor iron is stationary,
• Only the rotorconductor portion
being free to rotate.
Induction-Cup and Double-Induction-Loop
Structures
Double-induction-loop structure. Single-induction-loop structure.
The data required for a relay
setting study
i. A single-line diagram of the power system involved, showing the
type and rating of the protection devices and their associated
current transformers
ii. The impedances in ohms, per cent or per unit, of all power
transformers, rotating machine and feeder circuits
iii. The maximum and minimum values of short circuit currents
that are expected to flow through each protection device
iv. The maximum load current through protection devices
v. The starting current requirements of motors and the starting and
locked rotor/stalling times of induction motors
vi. The transformer inrush, thermal withstand and damage
characteristics
vii. Decrement curves showing the rate of decay of the fault current
supplied by the generators
viii.Performance curves of the current transformers.
Over current Protection
for Phase and Earth Faults
protection of feeders in distribution substation
protection of feeders in distribution substation
PRINCIPLES OF
TIME/CURRENT GRADING
protection of feeders in distribution substation
Fault withstand levels

• The typical duration of external short circuits that a transformer
can sustain without damage if the current is limited only by the
self-reactance is shown in Table
• Maximum mechanical stress on windings occurs during the first
cycle of the fault.
• Avoidance of damage is a matter of transformer design.
Over current and Earth Fault Relay
•
•
•

•

Starting current
103 - 110% of current setting.
Closing current
130% of current setting.
Resetting current
The maximum current up to which
the disc will completely reset is 90%
of current setting.
Time settings
0 - 3s at 10 times current setting.
0 - 1.3s at 10 times current setting.

•

•

Resetting time
With the time multiplier set at 1.0 the
resetting times of the above are 9s and 4s
respectively.
Overshoot
On removal of a current equal to 20 times
current setting the overshoot times of the
above are 0.065s and 0.04s respectively.
protection of feeders in distribution substation
protection of feeders in distribution substation
Inverse-time curves.
protection of feeders in distribution substation
protection of feeders in distribution substation
Inverse-time curves.
protection of feeders in distribution substation
protection of feeders in distribution substation
Operating characteristic of over current relays


:-



characteristic




RI curves

operating time
1
t =  x K

- 0.236/ I







Normal inverse



0.14
t =  x K
0.02

I

very inverse

13.5
t =  x K
I–1

Extremely inverse

80
t =  x K
I2 -1










–1

Long time stand by earth fault



120
t =  x K
I-1



Logarithmic inverse



where t = relay operating time
K = scale constant or TMS according to curve
I = multiple of set current Is or PSM = Fault current / CT ratio x PSM




t = 5.8 - 1.35 log n (I / I n)
protection of feeders in distribution substation
protection of feeders in distribution substation
protection of feeders in distribution substation
protection of feeders in distribution substation
Grading Margin
 The time interval that must be allowed between the
operation of two adjacent relays in order to achieve
correct discrimination between them is called the
grading margin.
 The grading margin depends on a number of factors:
i. the fault current interrupting time of the circuit
breaker
ii. relay timing errors
iii. the overshoot time of the relay
iv. CT errors
v. final margin on completion of operation
Grading Margin


At one time 0.5s was a normal grading
margin. With faster modern circuit
breakers and a lower relay overshoot time,
0.4s is reasonable, while under the best
conditions even lower intervals may be
practical.
protection of feeders in distribution substation
protection of feeders in distribution substation
protection of feeders in distribution substation
protection of feeders in distribution substation
protection of feeders in distribution substation
protection of feeders in distribution substation

More Related Content

PPT
Per unit system
PPTX
power system transients.pptx
PPTX
Insulation coordination.
PPTX
electrical machines
PPTX
PPT Fault Analysis
PDF
Application of Capacitors to Distribution System and Voltage Regulation
PPTX
PPTX
Hydrothermal scheduling
Per unit system
power system transients.pptx
Insulation coordination.
electrical machines
PPT Fault Analysis
Application of Capacitors to Distribution System and Voltage Regulation
Hydrothermal scheduling

What's hot (20)

PPTX
Symmetrical and un-symmetrical fault
PPTX
power system protection
PPT
Functions and performance requirements of excitation systems
PPTX
Voltage source Converters as a building block of HVDC and FACTS
PDF
Power system protection topic 1
PDF
Power system analysis material -Mathankumar.s VMKVEC
PPT
Measurement of high_voltage_and_high_currentunit_iv_full_version
PPTX
industrial training on 132 kv substation
PPTX
Bundle conductors in transmission line
PPTX
Heating cooling & ventilation: Methods of cooling & ventilation
PDF
Synchronous generator
PPTX
Overcurrent Protection
PDF
17648889-Introduction-to-Power-System-Protection-Relays.pdf
PPTX
AC Voltage Controller.pptx
PPT
PPTX
Streamer Theory of Breakdown in Gases.pptx
PPTX
Power system analysis (III-EEE)
PDF
Electromagnetic Protection (PART I)
PPTX
Introduction to HVDC
PPTX
Single area load frequency control by using pi,fuzzy logic control1
Symmetrical and un-symmetrical fault
power system protection
Functions and performance requirements of excitation systems
Voltage source Converters as a building block of HVDC and FACTS
Power system protection topic 1
Power system analysis material -Mathankumar.s VMKVEC
Measurement of high_voltage_and_high_currentunit_iv_full_version
industrial training on 132 kv substation
Bundle conductors in transmission line
Heating cooling & ventilation: Methods of cooling & ventilation
Synchronous generator
Overcurrent Protection
17648889-Introduction-to-Power-System-Protection-Relays.pdf
AC Voltage Controller.pptx
Streamer Theory of Breakdown in Gases.pptx
Power system analysis (III-EEE)
Electromagnetic Protection (PART I)
Introduction to HVDC
Single area load frequency control by using pi,fuzzy logic control1
Ad

Viewers also liked (20)

PDF
Er rahul sharma feeder protection
PPTX
FEEDER PROTECTION RELAY
PPTX
Feeder Protection Relays
PPT
protection of transmission lines[distance relay protection scheme]
PPTX
Relay and switchgear protection
PPTX
Surge current protection using superconductor ppt
PPT
POWER SYSTEM PROTECTION
PDF
distance relay
PDF
Transformer Protection using PLC
PDF
OLTC Function Selection, Operation
PPT
Practical Arc Flash Protection for Electrical Safety Professionals
PPTX
RADIAL FEEDER PROTECTION PANEL DEVELOPMENT
PPT
Roll Pass Design strategy
PDF
Best transformer-test-procedures-en
PPTX
Equipments in switchyard and its protection
PPTX
Distance Relay:->Mho relay
PDF
Cogeneration and On-Site Utility (PPA): Definition and Benefits
PPTX
open circuit and short circuit test on transformer
PPTX
ضبط الجودة فى الموقع
PPT
Lightning arresters
Er rahul sharma feeder protection
FEEDER PROTECTION RELAY
Feeder Protection Relays
protection of transmission lines[distance relay protection scheme]
Relay and switchgear protection
Surge current protection using superconductor ppt
POWER SYSTEM PROTECTION
distance relay
Transformer Protection using PLC
OLTC Function Selection, Operation
Practical Arc Flash Protection for Electrical Safety Professionals
RADIAL FEEDER PROTECTION PANEL DEVELOPMENT
Roll Pass Design strategy
Best transformer-test-procedures-en
Equipments in switchyard and its protection
Distance Relay:->Mho relay
Cogeneration and On-Site Utility (PPA): Definition and Benefits
open circuit and short circuit test on transformer
ضبط الجودة فى الموقع
Lightning arresters
Ad

Similar to protection of feeders in distribution substation (20)

PPTX
FEEDER AND BUS BAR PROTECTION
DOCX
Electrical System Design Initial
PPTX
Substation_equipment_ (1).pptx
PPTX
Power System Protection Technique: A Review
PDF
Power Electronics 2 mark Questions
PPTX
Current and Voltage Transformers _23_10_2021.pptx
PPTX
Measurement and Relay Indications download.pptx
PPTX
Measurement and Relay Indications.pptx
PPTX
PROTECTIVE_RELAYS_Fjkknniinpnl.pptx1.pptx
PPTX
L1 General Introductionbbbbbbbbbb-1.pptx
PPT
Power System Protection luctures 1 _1.ppt
PDF
lecture1423723756.pdf
PPTX
Relays and its types - complete guide
PPTX
Electrical Protection Schemes in detail
PPTX
Generator and Transformer Protection (PART 2)
PPTX
PROTECTIO N AND SWITCHGEAR ANNA UNIVERSITY EEE
PPT
LECT_1_E_1435_POWER_SYSTEM_PROTECTION.ppt
PPTX
“STUDY OF THE PROTECTIVE EQUIPMENTS OF A SUBSTATION AND POWER FACTOR IMPROVEM...
PDF
Azizan_2020_IOP_Conf._Ser.__Mater._Sci._Eng._767_012004.pdf
PDF
IRJET- Study Over Current Relay (MCGG53) Response using Matlab Model
FEEDER AND BUS BAR PROTECTION
Electrical System Design Initial
Substation_equipment_ (1).pptx
Power System Protection Technique: A Review
Power Electronics 2 mark Questions
Current and Voltage Transformers _23_10_2021.pptx
Measurement and Relay Indications download.pptx
Measurement and Relay Indications.pptx
PROTECTIVE_RELAYS_Fjkknniinpnl.pptx1.pptx
L1 General Introductionbbbbbbbbbb-1.pptx
Power System Protection luctures 1 _1.ppt
lecture1423723756.pdf
Relays and its types - complete guide
Electrical Protection Schemes in detail
Generator and Transformer Protection (PART 2)
PROTECTIO N AND SWITCHGEAR ANNA UNIVERSITY EEE
LECT_1_E_1435_POWER_SYSTEM_PROTECTION.ppt
“STUDY OF THE PROTECTIVE EQUIPMENTS OF A SUBSTATION AND POWER FACTOR IMPROVEM...
Azizan_2020_IOP_Conf._Ser.__Mater._Sci._Eng._767_012004.pdf
IRJET- Study Over Current Relay (MCGG53) Response using Matlab Model

Recently uploaded (20)

PDF
cuic standard and advanced reporting.pdf
PDF
Unlocking AI with Model Context Protocol (MCP)
PPTX
Big Data Technologies - Introduction.pptx
PDF
NewMind AI Weekly Chronicles - August'25 Week I
PDF
Network Security Unit 5.pdf for BCA BBA.
PDF
The Rise and Fall of 3GPP – Time for a Sabbatical?
PDF
Bridging biosciences and deep learning for revolutionary discoveries: a compr...
PDF
Machine learning based COVID-19 study performance prediction
PDF
KodekX | Application Modernization Development
PDF
CIFDAQ's Market Insight: SEC Turns Pro Crypto
PPTX
Cloud computing and distributed systems.
PDF
TokAI - TikTok AI Agent : The First AI Application That Analyzes 10,000+ Vira...
PDF
Encapsulation theory and applications.pdf
PDF
NewMind AI Monthly Chronicles - July 2025
PPTX
VMware vSphere Foundation How to Sell Presentation-Ver1.4-2-14-2024.pptx
PDF
Build a system with the filesystem maintained by OSTree @ COSCUP 2025
PDF
Shreyas Phanse Resume: Experienced Backend Engineer | Java • Spring Boot • Ka...
PDF
Agricultural_Statistics_at_a_Glance_2022_0.pdf
PDF
Blue Purple Modern Animated Computer Science Presentation.pdf.pdf
PDF
Per capita expenditure prediction using model stacking based on satellite ima...
cuic standard and advanced reporting.pdf
Unlocking AI with Model Context Protocol (MCP)
Big Data Technologies - Introduction.pptx
NewMind AI Weekly Chronicles - August'25 Week I
Network Security Unit 5.pdf for BCA BBA.
The Rise and Fall of 3GPP – Time for a Sabbatical?
Bridging biosciences and deep learning for revolutionary discoveries: a compr...
Machine learning based COVID-19 study performance prediction
KodekX | Application Modernization Development
CIFDAQ's Market Insight: SEC Turns Pro Crypto
Cloud computing and distributed systems.
TokAI - TikTok AI Agent : The First AI Application That Analyzes 10,000+ Vira...
Encapsulation theory and applications.pdf
NewMind AI Monthly Chronicles - July 2025
VMware vSphere Foundation How to Sell Presentation-Ver1.4-2-14-2024.pptx
Build a system with the filesystem maintained by OSTree @ COSCUP 2025
Shreyas Phanse Resume: Experienced Backend Engineer | Java • Spring Boot • Ka...
Agricultural_Statistics_at_a_Glance_2022_0.pdf
Blue Purple Modern Animated Computer Science Presentation.pdf.pdf
Per capita expenditure prediction using model stacking based on satellite ima...

protection of feeders in distribution substation

  • 2. DISTRIBUTION PROTECTION R.Panneer Selvam B,E.,M.I.E., Former Superintending Engineer Protection and Communication CHENNAI
  • 3. There are three aspects of a power system These aspects are as follows: A. Normal operation B. Prevention of electrical failure. C. Mitigation of the effects of electrical failure.
  • 4. Normal Operation  The term normal operation assumes no failures of equipment, no mistakes of personnel, nor Acts of God. It involves the minimum requirements for supplying the existing load and a certain amount of anticipated future load. A. Choice between hydro, steam, or other sources of power. B. Location of generating stations. C. Transmission of power to the load. D. Study of the load characteristics and planning for its future growth. E. Metering F. Voltage and frequency regulation. G. System operation. E. Normal maintenance
  • 5. Outages  Electrical equipment failures would cause intolerable outages.  There must be additional provisions to minimize damage to equipment and interruptions to the service when failures occur.  Two recourses are open: (1) to incorporate features of design aimed at preventing failures, and (2) to include provisions for mitigating the effects of failure when it occurs
  • 6. Prevention of Electrical Failure  The type of electrical failure that causes greatest concern is the short circuit, or “fault” as it is usually called, but there are other abnormal operating conditions peculiar to certain elements of the system that also require attention. Some of the features of design and operation aimed at preventing electrical failure are: A. Provision of adequate insulation. B. Coordination of insulation strength with the capabilities of lightning arresters. C. Use of overhead ground wires and low tower-footing resistance. D. Design for mechanical strength to reduce exposure, and to minimize the likelihood of failure causable by animals, birds, insects, dirt, etc. E. Proper operation and maintenance practices .
  • 7. Design And Operation For Mitigating The Effects Of Failure  Some of the features of design and operation for mitigating the effects of failure are: A. Features that mitigate the immediate effects of an electrical failure. 1. Design to limit the magnitude of short-circuit current.1 a. By avoiding too large concentrations of generating capacity. b. By using current-limiting impedance. 2. Design to withstand mechanical stresses and heating owing to short-circuit currents. 3. Time-delay under-voltage devices on circuit breakers to prevent dropping loads during momentary voltage dips. 4. Ground-fault neutralizers (Petersen coils). B. Features for promptly disconnecting the faulty element. 1. Protective relaying. 2. Circuit breakers with sufficient interrupting capacity. 3. Fuses. C. Features that mitigate the loss of the faulty element. 1. Alternate circuits. 2. Reserve generator and transformer capacity. 3. Automatic reclosing.
  • 8. Protective Relaying    Thus, protective relaying is one of several features of system design concerned with minimizing damage to equipment and interruptions to service when electrical failures occur. When we say that relays “protect,” we mean that, together with other equipment, the relays help to minimize damage and improve service. Therefore, the capabilities and the application requirements of protective-relaying equipments should be considered concurrently with the other features.
  • 9. Protection Technology  The last thirty years have seen enormous changes in relay technology.  The electromechanical relay in all of its different forms has been replaced successively by static, digital and numerical relays
  • 10. ELECTROMECHANICAL RELAYS   The mechanical force is generated through current flow in one or more windings on a magnetic core or cores, hence the term electromechanical relay The principle advantage of such relays is that – – they provide galvanic isolation between the inputs and outputs in a simple, cheap and reliable form therefore for simple on/off switching functions where the output contacts have to carry substantial currents, they are still used.
  • 11. Philosophy of over Current Protection  Over current protection is directed entirely to the clearance of faults, although with the settings usually adopted some measure of overload protection may be obtained.
  • 12. Attracted Armature Relays   These generally consist of an ironcored electromagnet that attracts a hinged armature when energized. A restoring force is provided by means of a spring or gravity so that the armature will return to its original position when the electromagnet is deenergized.
  • 13. Typical attracted armature relays   The contacts can be made quite robust and hence able to make, carry and break relatively large currents under quite onerous conditions (highly inductive circuits). This is still a significant advantage of this type of relay that ensures its continued use.
  • 15. The basic connections of a protective relay
  • 16. Torque production in an induction relay.
  • 18. Induction Cup Unit • These two structures are shown in Fig • They most closely resemble an induction motor, except that the rotor iron is stationary, • Only the rotorconductor portion being free to rotate.
  • 20. The data required for a relay setting study i. A single-line diagram of the power system involved, showing the type and rating of the protection devices and their associated current transformers ii. The impedances in ohms, per cent or per unit, of all power transformers, rotating machine and feeder circuits iii. The maximum and minimum values of short circuit currents that are expected to flow through each protection device iv. The maximum load current through protection devices v. The starting current requirements of motors and the starting and locked rotor/stalling times of induction motors vi. The transformer inrush, thermal withstand and damage characteristics vii. Decrement curves showing the rate of decay of the fault current supplied by the generators viii.Performance curves of the current transformers.
  • 21. Over current Protection for Phase and Earth Faults
  • 26. Fault withstand levels • The typical duration of external short circuits that a transformer can sustain without damage if the current is limited only by the self-reactance is shown in Table • Maximum mechanical stress on windings occurs during the first cycle of the fault. • Avoidance of damage is a matter of transformer design.
  • 27. Over current and Earth Fault Relay • • • • Starting current 103 - 110% of current setting. Closing current 130% of current setting. Resetting current The maximum current up to which the disc will completely reset is 90% of current setting. Time settings 0 - 3s at 10 times current setting. 0 - 1.3s at 10 times current setting. • • Resetting time With the time multiplier set at 1.0 the resetting times of the above are 9s and 4s respectively. Overshoot On removal of a current equal to 20 times current setting the overshoot times of the above are 0.065s and 0.04s respectively.
  • 36. Operating characteristic of over current relays  :-  characteristic   RI curves operating time 1 t =  x K - 0.236/ I     Normal inverse  0.14 t =  x K 0.02 I very inverse 13.5 t =  x K I–1 Extremely inverse 80 t =  x K I2 -1         –1 Long time stand by earth fault  120 t =  x K I-1  Logarithmic inverse  where t = relay operating time K = scale constant or TMS according to curve I = multiple of set current Is or PSM = Fault current / CT ratio x PSM   t = 5.8 - 1.35 log n (I / I n)
  • 41. Grading Margin  The time interval that must be allowed between the operation of two adjacent relays in order to achieve correct discrimination between them is called the grading margin.  The grading margin depends on a number of factors: i. the fault current interrupting time of the circuit breaker ii. relay timing errors iii. the overshoot time of the relay iv. CT errors v. final margin on completion of operation
  • 42. Grading Margin  At one time 0.5s was a normal grading margin. With faster modern circuit breakers and a lower relay overshoot time, 0.4s is reasonable, while under the best conditions even lower intervals may be practical.