This document summarizes an investigation into overvoltages caused by ferroresonance in a distribution system consisting of open-delta single-phase voltage transformers. Simulation and experimentation were used to study the phenomenon. Simulation accurately replicated overvoltages observed in experiments of up to 3 per unit. Additional damping resistors were proposed and simulation was used to determine optimal resistor values to mitigate the ferroresonance. Bifurcation diagrams created from simulation results were useful for investigating the ferroresonance behavior under different conditions and determining mitigation techniques.